application of harmonic filters filter web.pdf · application of harmonic filters ... most circuit...
TRANSCRIPT
1
Application of Harmonic FiltersApplication of Harmonic Filters
JuneJune 20082008
Prepared by B. J. Park
PQ TECH INC.
2
IndexIndex
Design ConsiderationsUnderstanding Capacitors (Construction, Process, Capacitor Types, Tests)Filter ReactorsWhat is K factor?Surge ArrestorsSwitching CapacitorsGrounding versus UngroundingBanks Protections (Various Protection, Setting Philosophy)Harmonic Filter TypesBank DesignSteel Making Plant HarmonicsCase Study for Electrochemical Plant
2
3
Harmonic Filter Design ConsiderationsHarmonic Filter Design Considerations
Various Nonlinear Loads Harmonic Voltage and or Current can cause damage to equipment Voltage Current Distortion Guide Line
Harmonic Filter Locations
300
400 75
125
150 150
23kV
380V Bus 1
380V Bus 2
4
Key Filter Design ConsiderationsKey Filter Design Considerations
Reactive Power RequirementsHarmonic LimitationsBackground HarmonicsHarmonic Filter Conditions (Ratings)System Transient, abnormal conditionsContingency Filter Conditions
3
5
Maximum and Minimum SizeMaximum and Minimum Size
The maximum bank sizea) Change in system voltage upon capacitor bank switching.b) Switchgear continuous current limitations.dV is limited in the range of 2%~3%, determined by load flow
The minimum bank sizea) Capacitor bank unbalance considerationsb) Fuse coordination
6
Construction of Capacitor ElementConstruction of Capacitor Element
ALUMINIUM FOIL5um Edge Fold
Hazed Polypropylene Film 11- 15um
4
7
Air Shower Booth to Access W/RAir Shower Booth to Access W/R
8
RollRoll WindingWinding ProcessProcess
5
9
Extended Foil SolderingExtended Foil Soldering
10
Container TIG WeldingContainer TIG Welding
6
11
Impregnation Impregnation FacilityFacility
12
ImpregnaImpregnanntt, , JarylecJarylec C101C101
Good Good performance performance in hin high temperatureigh temperatureLow Low dissipation factordissipation factorExcellent Excellent absorbing absorbing PDPD--characteristicscharacteristicsThe fluid is non chlorine The fluid is non chlorine biogradablebiogradable and contains no PCBs and contains no PCBs
CH2
CH3
CH2 CH2
CH3
Benzyltoluene 75% Dibenzyltoluene 25%
7
13
Impregnation, Under VacuumImpregnation, Under Vacuum 0.01 torrs0.01 torrs
ImpregnantFilling
Sealing
Drying
0
20
40
60
80
100
0 1 2 3 4
DAYS
TEM
P oC
5
14
RoutinRoutinee Test, Test, IEC 60871IEC 60871
8
15
PD Test in Shield Room @ 2.15*UnPD Test in Shield Room @ 2.15*Un
16
Routine Test, Routine Test, IEC 60871IEC 60871
Each capacitor unit undergoes the following:Leakage test at 60°C for 24 hoursPartial Discharge Test at 2.15 UnHV tests:
AC terminal to terminal at 18kV for 10 secAC terminal to case at 38kV for 10 sec
Capacitance and Dielectric loss angle at UnShort circuit discharge test at 1.7UnInternal discharge resistor test
9
17
All-film -Low dissipation, hazed, high energy density Folded foil – Good performance to the PD and transientsImpregnation - Dribble penetration, extra vacuum levels, long term filling.Container -1.5mm 430 grade stainless steel, can be supplied unpainted. TIG welding
Power Capacitor UnitsPower Capacitor Units
18
Harmonic Filter Harmonic Filter CapacitorCapacitors s
D
Film
FoilExtended Foil
DUE0 =
10
19
Between voltage gradient and failure rate, and assumed life can be described as
Assumed LifeVoltage Gradient
Failure rate
Where:L =Expected lifeN = Number of elementsλ = Failure rate (0.01%/year)Eo= Designed Voltage GradientE = Actual Voltage Gradientα = Constant for Voltage Gradient (α = 6 ~17)
Capacitor Life Expectancy Capacitor Life Expectancy
( )-α
Eo
EλNL ⎥
⎦
⎤⎢⎣
⎡=
20
Many connection, fuses, more hands, degrade insulation, costPossible to continuing service after few fuses brownUnit rating around 10kV
Internally Fused Capacitor UnitInternally Fused Capacitor Unit
11
21
Unit rating 15~25kV
Externally Fused Capacitor UnitExternally Fused Capacitor Unit
22
All strings must be separated / simple process / good joint foil electrodes at dielectric fault
FuselessFuseless Capacitor UnitCapacitor Unit
12
23
Yes, but the is concern the oil contamination
Europe
Less
Lower
No(hazard)
Smaller
6P12S
Higher
Impossible
Fuseless
Yes, but the is concern the oil contamination
Europe / Asia
No
America / Asia
Higher
Higher
yes
Higher
6P 12S
Lower
Easy to find
Externally Fused
Less
Lower
No(hazard)
Smaller
12S 6P
Higher
Impossible
Internally Fused
Connection (example)
Replace cost
Visual check for faulty unit
Protection for terminal to case fault
Popular using Area
Cost of protection
Sensitivity of unbalance
Continuing service of unit at a roll faulty
Delta C by faulty roll
Features & Types
Types of Capacitor UnitTypes of Capacitor Unit
24
Filter Capacitor Specification ExampleFilter Capacitor Specification ExampleRated voltage 9008 [V]Rated current 87.48 [A]Rated output 788 [kVAr]
Type All filmRated capacity 788 [kVAr]Rated capacitance 30.91 [uF]
Rated frequency 50 [Hz]Insulation level 30 [kVrms], 95 [kV BIL]Number of phase Single Phase
Number of bushing 2Dielectric Synthetic polypropylene filmElectrodes Fold/Laser cut aluminum foil Impregnate with Non-PCB dielectric fluid
Protection method Internally fusedPainting color Munsell No. 5Y7 / 1Painting method Vapor cure double layers Epoxy coated
Discharge device Built in resistorsDischarge time / unit <50V within 5 [min]Standards IEC60871-1, 60871-2, 60871-4
Case material Stainless Steel 1.6 [mm]Fixing hanger bracket 2 EA for both sideContinues allowable overvoltage 110 [%] Un
Maximum permissible kVAr 135 [%]Tolerance of capacitance -0 ~ +15 [%] at 25 [Ċ]
13
25
Probability of 2Probability of 2ndnd failure for Each Typesfailure for Each Types
IEEE summer meeting 1997IEEE summer meeting 1997
[1]>[2] 2nd Failure in the Same group
[1]>[11] 2nd Failure in the another group
26
24
26
6.40
6.20
λ for [1]>[11]“Random”
% / year
0.0150.4Fuseless(Internal String)
132kV, 36 MVArY-Y connection5
0.0452.6Fuseless(conventional)
132kV, 36 MVArY-Y connection4
0.0100.26Internally fused 132kV, 36 MVArY-Y connection3
0.0220.57Externally fused 33 kV, 9 MVArY-Y connection2
0.0100.26Internally fused33 kV, 9 MVArY-Y connection1
Δc/c
%/ Year
λ for [1]>[2]“Avalanche”
% / yearCapacitor TypeBankCase
26
Filter ReactorsFilter Reactors
Magnet wire is copper wire which has been coated (or enamelled) with a very thin layer of insulating material
14
27
Filter ReactorsFilter Reactors
28
10.1151.596Σ
0.0160.0000.00525
0.0340.0000.00823
0.0160.0000.00621
0.0440.0000.01119
0.0940.0000.01817
0.0810.0000.01915
0.1060.0010.02513
0.3400.0030.05311
0.1570.0020.0449
0.7900.0160.1277
3.5530.1420.3775
3.8880.4320.6573
1.0001.0001.0001I2 x h2I2Current (Pu)Harmonic
Ex)K factor = 6.34 PEC-R= 8% (Eddy current loss factor) Irms = 0.85 (pu)
2
2h
h
I hK
I= ∑
∑2
11
ECRrms
ECR
PIKP
−+=
+´
What is K factor?What is K factor?
IEEE C57.110IEEE C57.110--19861986
15
29
Typical Air Core Dry Type ReactorTypical Air Core Dry Type Reactor
30
Magnetic ClearanceMagnetic Clearance
16
31
Filter Reactor Specification ExampleFilter Reactor Specification ExampleType Air Core, 6 [%] System Voltage 132 [kV]Rated Frequency 50 [Hz]Rated Inductance 59.0 [mH]Rated Current 262.43 [A]Insulation Level 275 / 650 [kV]Number of Phase Single PhaseTemperature Rise 60.5 [Ċ]Color Munsell No. 5Y7 / 1Standards IEC 289Frame and StructureReactors shall have mechanical and electrical strength and it shall be painted with Munsell No. 5Y7 / 1.Installation OutdoorCooling Air-cooled with natural convectionImpedance calculation of the bankZf for Fundamental Frequency, Xcf = 308.94 Ohm, Xlf = 18.54 Ohm, Zf = 290.4 OhmZ5 for 5th harmonic Frequency, Xc5 = 61.79 Ohm, Xl5 = 92.7 Ohm, Z5 = 30.91 Ohm TestsThe tests are carried out by manufacturer accordance with standard IEC 289.The reports are attached herein.Routine testsMeasurement of winding resistanceMeasurement of impedance at continuous currentSeparate source voltage withstand testInduced over voltage withstand test
Type testsTemperature rise testLightning impulse test
Marking IEC 289.16
32
Surge ArrestorsSurge Arrestors
17
33
To prevent capacitor failures at a breaker restrike or failure.
To limit the risk of repeated breaker restrikes.
To prolong the service life of the capacitors by limiting high overvoltages.
To serve as an ”insurance” against unforeseen resonance conditions which otherwise would lead to capacitor failures.
For overall limitation of transients related to capacitor bank switching which can be transferred further in the system and cause disturbances in sensitive equipment.
For upgrading of capacitors by preventing high overvoltages and/or for increasing the service voltage.
To serve as protection against lightning for capacitor banks connected to lines.
Using Surge ArrestorsUsing Surge Arrestors
34
Arrestor PositioningArrestor Positioning
Continuous operating voltageRated voltageEnergy capability
18
35
Arrestor PositioningArrestor Positioning
ExampleSystem voltage: 36 kVFault clearing time:10 s or lessSystem grounding: UngroundedCapacitor bank connection: Ungrounded wyeRated 3-phase power: 18 MVArDesired protective level : 2,4 p.u.
Summary of required arrester data for connection Phase-ground:Rated voltage: 33 kV or moreProtective level at 3kA: 64,7 kV or less (switching surge)Energy capability for capacitor discharges:2,8 kJ per kV rated voltage or more
Summary of required arrester data for connection Phase-neutral:Rated voltage: 33 kV or moreProtective level at 3kA: 69 kV or less (switching surge)Energy capability for capacitor discharges:3,2 kJ per kV rated voltage or more
36
High duty-cycleMost circuit breakers and protective devices operate a few times in their entire life span.Switch for capacitor bank gets to operate every day, sometimes several operations per day.
Voltage spikeWhen capacitor switches do operate, they generate undesirable voltage surges, which if unmitigated, can cause problems in Power Quality to the users.
Re-strikeCommon concern for older switching technologies.
Switching Capacitor BanksSwitching Capacitor Banks
19
37
Continuous currentungrounded neutral banks – 1.25 times the nominal currentgrounded neutral banks – 1.35 times the nominal currents
Inrush current during energizationNominal system voltageTransient recovery voltage during de-energization
Switches must be capable of withstanding inrush current
Ipk = Peak of Inrush current
Isc = available three phase fault currentI1 = capacitor bank current
141.1 III scpk ⋅=
The Key Considerations for SwitchgearThe Key Considerations for Switchgear
38
Inrush current during back to back switching
Fs = system frequency in HzFt = frequency of transient in kHzLeq = total inductance between two banks in micro-henriesI1, I2 = being switched, already energized banks currents in AVLL = line to line voltage in kV
)()(1747
21
21
IILIIVI
eq
LLpk ⋅
⋅⋅=
)())()((5.9
21
21
IILIIVff
eq
LLst ⋅
+⋅=
The Key Considerations for SwitchgearThe Key Considerations for Switchgear
20
39
Several hundred meters between overhead capacitor banks is usually an adequate separation distance to limit the inrush current to an acceptable level, but configurations where the banks are very close together may require inrush current limiting reactors.
When switching is done at nominal system voltage, the switch recovery voltage reaches 2.0 per unit for a grounded-wye-connected bank and 2.5 per unit for an ungrounded-wyebank.
The Key Considerations for SwitchgearThe Key Considerations for Switchgear
Ec = Peak System Voltage
To = Beginning of Switching Opening
T1 = First Current Zero
T2 = 1/2 Cycle After First Current Zero
T3 = Switch Completely Opened
Switching Recovery Voltage
40
The 6% inductor to the capacitive reactance has been widely usedThe 6% inductor to the capacitive reactance has been widely used , , to reduce the inrush current less than 5 times the nominal curreto reduce the inrush current less than 5 times the nominal currents nts
LCo1
=ω LC ZZ =× 06.0
ωω1,11
=Ω== CC
ZC
)(sin tZVi o
oo ω=
ω
ωω
ω ×=×
= 1.406.01
1o
ωω 06.0,06.0 =Ω== LLZL
The Key Considerations for SwitchgearThe Key Considerations for Switchgear
21
41
ITI CurveITI Curve
42
Synchronous Type Circuit BreakerSynchronous Type Circuit Breaker
P1 : Graphs
0.1825 0.1850 0.1875 0.1900 0.1925 0.1950 0.1975 0.2000 0.2025 0.2050
-200
-150
-100
-50
0
50
100
150
200
y
Ap
A
B
C
Switching Sequence_ Ungrounded Capacitor Banks
22
43
Synchronous Type Circuit BreakerSynchronous Type Circuit Breaker
Case 19
0.160 0.180 0.200 0.220 0.240 0.260 0.280 0.300
-8.0
-6.0
-4.0
-2.0
0.0
2.0
4.0
6.0
8.0
y
step1-Ia step1-Ib step1-Ic
-300
-200
-100
0
100
200
300
y
Ap
Without Series ReactorWithout Series Reactor
44
Synchronous Type Circuit BreakerSynchronous Type Circuit Breaker
With 6% Series ReactorWith 6% Series ReactorCase 19
0.160 0.180 0.200 0.220 0.240 0.260 0.280 0.300
-8.0
-6.0
-4.0
-2.0
0.0
2.0
4.0
6.0
8.0
y
step1-Ia step1-Ib step1-Ic
-300
-200
-100
0
100
200
300
y
Ap
23
45
Conventional Circuit BreakerConventional Circuit Breaker
Case 19
0.160 0.180 0.200 0.220 0.240 0.260 0.280 0.300
-8.0
-6.0
-4.0
-2.0
0.0
2.0
4.0
6.0
8.0
y
step1-Ia step1-Ib step1-Ic
-300
-200
-100
0
100
200
300
y
Ap
kA
kV
Without Series ReactorWithout Series Reactor
1.6 Per unit peak
65 kA peak
46
Conventional Circuit BreakerConventional Circuit Breaker
Case 19
0.160 0.180 0.200 0.220 0.240 0.260 0.280 0.300
-8.0
-6.0
-4.0
-2.0
0.0
2.0
4.0
6.0
8.0
y
step1-Ia step1-Ib step1-Ic
-300
-200
-100
0
100
200
300
y
Ap
With 6% Series ReactorWith 6% Series Reactor
24
47
General Control StrategyGeneral Control Strategy
grounded neutral, the three poles should close in succession with a time separation of 1/6 cycle (3.3 ms at 50 Hz or 2.8 ms at 60 Hz).
ungrounded neutral, two poles should close simultaneously at phase - phase voltage zero, and the last one 1/4 cycle later (5 ms at 50 Hz or 4.2 ms at 60 Hz).
48
The advantages of the grounded wye compared to the ungrounded
Initial cost is lower, the neutral does not needed to full system BIL
Recovery voltages are reduced
Mechanical duties less severe for the structure
Low impedance path to ground for lighting gives self protection from surge
System & cap bank be grounded at 121kV above _ IEEE C37.99-2000
The disadvantages of the grounded wye compared to the ungrounded
Higher inrush current may occur in ground, it is needed NGR
Zero sequence harmonic current may draw to the ground
Usually makes current limiting fuses due to line to ground fault
Grounded Grounded vsvs UngroundedUngrounded
25
49
SR Location and Insulation CostSR Location and Insulation Cost
2nd
0.0928[H]
A_curr
0.21 [ohm]
37.94[uF]
A_c
ap_u
0.01 [ohm]
0.01 [ohm]
0.01 [ohm]
1 [ohm]
A_rr
37.94[uF]
A_ca
p_d
2nd0.0928[H
]
B_curr
0.21 [ohm]
37.94[uF]
e_s
0.01 [ohm]
0.01 [ohm]
0.01 [ohm]
1 [ohm]
B_rr
37.94[uF]
B_ca
p_d
B_r
A_ng
B_n
g
Main : Graphs
0.00 0.10 0.20 0.30 0.40 0.50
0.0
2.5k
5.0k
7.5k
10.0k
12.5k
15.0k
17.5k
20.0k
y
A cap u B r
Main : Graphs
0.00 0.10 0.20 0.30 0.40 0.50
0.0 1.0k2.0k3.0k4.0k5.0k6.0k7.0k8.0k9.0k
10.0k
y
A_cap_d B_cap_d
Main : Graphs
0.00 0.10 0.20 0.30 0.40 0.50
0.0
2.5k
5.0k
7.5k
10.0k
12.5k
15.0k
17.5k
20.0ky
e_s A_cap_u
Reactor Bushing Potential
Capacitor Bushing Potential
Capacitor Bushing Potential
50
Unbalance detection means ;An internal element fails → voltage distribution & current flow change within a bank
Magnitude of changesexternally fused > internally fused
Purpose of the unbalance protection ;alarm or disconnect the entire capacitor bank when more than 10% over voltages across the healthy capacitors
More consideration required for ;Types of unbalance protectionOver currentsOver & under voltage
Protecting the Harmonic Filter BanksProtecting the Harmonic Filter Banks
26
51
Neutral currentNeutral voltage
Current unbalance between neutralsPhase voltage unbalance
Voltage differenceCurrent unbalance in bridge connection
Types of Unbalance ProtectionTypes of Unbalance Protection
52
Sensing Neutral Current & VoltageSensing Neutral Current & Voltage
Neutral Current Neutral Voltage
Star Connection with Neutral Grounded Through a Current Transformer
Star Connection with Voltage Transformer Between Neutral and Ground
27
53
Sensing dV & Current UnbalanceSensing dV & Current Unbalance
Voltage Difference Current Unbalance in Bridge Connection
Star Connection with Grounded Neutral and Voltage Transformers Connected in differential Measurement
Bridge Connection
54
Sensing Unbalance Current & VoltageSensing Unbalance Current & Voltage
Current Unbalance BetweenNeutrals
Phase VoltageUnbalance
Double Star Connection with Ungrounded Neutral
Star Connection with Ungrounded Neutral and Voltage Transformers Connected in an Open Delta
28
55
Summary of Capacitor Protection Methods Reference IEEE C37.99
Various schemes used, suitability depends on banks arrangements
Unbalance sensing with currents or voltage relays
Instantaneous relay action necessary to limit fault damage
Unbalance relayingOver current relayRack faultRack fault
To reduce inrush current required series reactor
Switched or fixed impedance in series with cap. BankInrush currentInrush current
Proper bank design Limit number of cap. Unit
Individual unit fuse Proper bank design
Discharge current from Discharge current from parallel connected unitparallel connected unit
Not suitable for unmanned substation for system over voltages
Visual inspection phase overvoltage relay
Continuous capacitor Continuous capacitor unit over voltageunit over voltage
Coordination provided by manufacture
Individual unit fuses (Expulsion or current limiting)
Over current due to unit Over current due to unit failurefailure
Grounded capacitor banks partially reduce surge voltageSurge arrestersSystem surgeSystem surge
Conventional methods applySupply breaker with OVR Power fusesBus faultBus fault
RemarksRemarksType of Protection Type of Protection Condition Condition
Summary of the Capacitor Banks ProtectionSummary of the Capacitor Banks Protection
56
1.01.0 1010 100100 1,0001,000 10,00010,000
Currents in amperes (Currents in amperes (r.m.sr.m.s.).)
1,0001,000
100100
1010
1.01.0
0.10.1
0.010.01
Time in SecondsTime in Seconds
Low probability Low probability of case ruptureof case rupture
High probability High probability of case ruptureof case rupture
Paper or paper Paper or paper film dielectricfilm dielectric
All film dielectricAll film dielectric
Case Volume 30,000CmCase Volume 30,000Cm33
Typical Case Rupture CurvesTypical Case Rupture Curves
29
57
Meters A, V, Var, MVA, MW, pf, Hz
SCADA - Var and Voltage control
Main BusSub Bus
TCCC
C / T * 3
Ground SW
Arresters
Capacitor S. W
60MVAr Capacitor Bank
4 Levels of Unbalance Protection
4 Levels of Instantaneous OCP
Reactor Over Load TD Protection
Under Currents TD protection
Measurements Last Trip Record
Remote Control for Trip & Closing
Reactors
NeutralResistor
ID for Faulty Phase
PT 3P
In- Sensitivity 0.005A
51Q, 51G, 51N - 3Vo, 3V1, 3V2, 3Io, 3I1, 3I2
Event Waveform Oscillograph
Breaker Failure Detection
Failure Target for Each phase Group
Meters and Indicators for Alarm
Battery Voltage Measurement
1 Serial ports1 Front, 3 rear- integrating
relays to SCADA
An example Protection SchemeAn example Protection Scheme
58
Conventional3CTs2P + 2PBalanced DY665kVAr, 96EAID faulty side, to be checked 48EA for a side
Advanced protection7 CTs (KEPCO)2P+2PBalanced SYDB665kVar, 96EAID the faulty phase,to be checked 32EA for
a phase
Advanced protection6 CTs2P+2PBalanced SYDB665kVar, 96EAID the faulty phase,to be checked 32EA for
a phase
Conventional1 CT2P(L) + 1P(R) Unbalanced DY887kVAr, 77EAFail only, to be checked 77EA for whole bank
Grounded YY (Single Y Double Br)Grounded YY (Single Y Double Br)Grounded YGrounded Y--Y (Double Y)Y (Double Y)
Ungrounded YY (Single Y Double Br) Ungrounded YY (Single Y Double Br) Ungrounded YUngrounded Y--Y (Double Y)Y (Double Y)
NGRNGR
Various ConfigurationsVarious Configurations
30
59
Filter Capacitor BankFilter Capacitor Bank
60
Overview of Capacitor Banks ProtectionOverview of Capacitor Banks Protection
Aim of Unbalance Protection (Alarm, Trip) Isolate faulty capacitor banks To prevent any of healthy units exposed to over than 110% of Un
Inherent unbalance current, Sufficient delay time to override external disturbances.
Overload Protection is to Protect from (Alarm, Trip) Overcurrent, harmonic current, OvervoltageThe trip stage is based on the IEEE Std. C37.99 IEC60871-1 inverse time characteristics
Overcurrent Earth Fault Protection, Should be Consider Switching inrush currentTime delay to clear the fuseSingle phase numerical type, standard inverse time
Overvoltage Protection is to Protect from the System Power Frequency Overvoltage
Undervoltage Protection, to trip the bank loss of system voltage, should be consideredReenergizing capacitor bank with a trapped chargeEnergizing a cap bank without parallel load through a previously unenergized transformerDelay time to override external faults
31
61
List of Relay UsedList of Relay Used
SWITCHSYNCE113ABBF25-POWPoint on Wave device7
KVGC 202ALSTOMF90-AVCAutomatic VoltageController6
KVFG 142AREVAF27=UVUnder-voltage Interlock Relay5
P 922SAREVAF27-UVUnder-voltage protection4
P 922SAREVAF59-OVOver-voltage protection3
SPAJ 160CABBF51 –UB &F49- OL
Capacitor Unbalance&Over-load protection2
P 123AREVAF50/51OCOver-current & EarthFault protection1
TypeManufacturerDesignationFunctionNo.
62
Protection Scheme & Coordination Plot Protection Scheme & Coordination Plot
Protection Scheme for 132kV 60MVAr
32
63
Features of Protection RelayFeatures of Protection Relay
Current Unbalance and OverCurrent Unbalance and Over--load Protection [ABB SPAJ 160C]load Protection [ABB SPAJ 160C]
Current Unbalance Relays (-F51UB)The relay receive the signal through neutral current transformer.Two stages of alarm provided. If any capacitor element fails, the relay shall set to
alarm (Stage 1) at appropriate value and to trip (Stage 2) the capacitor bank if the 110% rated voltage appears on any remaining units in the same unit.
Over-load Relays (-F49OL)Both inverse time current characteristic and definite time characteristic are provided.
Two stages of operation for alarm and tripping are also provided
64
OverOver--current and Earthcurrent and Earth--Fault Protection (F50/51OC) [AREVA P123]Fault Protection (F50/51OC) [AREVA P123]
Over-current Relays (-F50/51)Relays are of the three-single phase numerical type with both definite time and standard inverse time characteristic and with an independent measuring unit for each phase.
Earth fault Relays (-F50N/51N)Relays are single-phase numerical type with both definite time and standard inverse time characteristic and with an independent measuring unit for each phase
Features of Protection RelayFeatures of Protection Relay
33
65
OverOver--voltage and Undervoltage and Under--voltage Protection [AREVA P 922S]voltage Protection [AREVA P 922S]
Over-voltage Relays (-F59OV)Time delay of both inverse time and definite characteristics types are provided. The relay should be provided for tripping off the capacitor bank in case of overvoltage condition occurring in the system such as due to sudden load loss.
Under-voltage Relays (-F27UV)Voltage Input is taken from existing voltage selection scheme / busbar VT. If there is no busbar VT then it is required that the voltage is taken from capacitor side VT, with is supplemented with a blocking logic as below.
The relay should be provided for tripping off the capacitor bank in case of temporary loss voltage such as during the line auto-reclosing, to prevent re-closing of capacitor bank before the capacitor is fully discharged.
Features of Protection RelayFeatures of Protection Relay
66
Setting PhilosophySetting Philosophy
OverOver--current and Earth Fault (current and Earth Fault (--F5l OCEF) [AREVA P123]F5l OCEF) [AREVA P123]
The -F51 OCEF relay shall be set to operate as fast as possible in the occurrences of short circuit in the capacitor bank feeder since down-stream coordination are not required.
Characteristics of the -F51 OCEF relays will be determine from coordination studies. Both definite time (DT) characteristic and IDMT-Extremely Inverse Characteristic are used to protect the bank.
Time over-current relay (510C) - For a shunt capacitor bank, pickup setting 130% (IEEE std37.99-2000; the desirable minimum pickup is 135% of IN for grounded wye banks and 125% of IN for ungrounded banks) of rated current of the capacitor bank is proposed. Selection of time delay characteristic is based on coordination study. Both definite time and inverse time characteristic with time multiplier setting (TMS) higher than their respective overload characteristics is recommended.
Instantaneous over-current relay (50OC) - For shunt capacitor bank, pickup at least 1.15 times peak inrush to override inrush transient. (IEEE std. C37.99-2000 clause 7.2.3)
Time over-current relay (51 EF) - The capacitor bank is not grounded hence sensitive EF should be set to 20% pickup with the same operating time as OC elements to detect and to provide fast clearing for ground faults.
Instantaneous over-current relay (50EF) - Same as 51 OC or defeated if setting range not available.
34
67
Unbalance and Overload (Unbalance and Overload (--F5l UB/F5l UB/--F49OL) [ABB SPAJ160C]F49OL) [ABB SPAJ160C]
F49OL - This is a protection against over-voltages and harmonics current. Capacitor shall be able to carry continuous over-load current of 130% the rated current including due to harmonic and maximum voltage variations. The over-voltage trip start setting should be at 110% of capacitor bank rating, utilizing overload curve (at 1.1 pu). The alarm setting shall be at 110% of overload start setting with a time delay of 60 seconds and trip 115% with time delay 0.2seconds
F5l UB - The time delay of the unbalance relay trip should be minimized to reduce damage from an arcing fault within the bank structure and prevent exposure of the remaining capacitor units to over-voltage conditions beyond their permissible limits.
Setting shall be followed by Annex 4) which is analyzed that the unbalance neutral current, and based on over-voltage limit (per capacitor unit) when the internal fuse has blown up to three elements, the terminal voltage of the faulty unit capacitor is less than 103.1% of Un.Setting shall also be confirmed / compensated with neutral unbalance current after exercitation. (with measurement)
Setting PhilosophySetting Philosophy
68
Setting PhilosophySetting Philosophy
Characteristic of the overload curve is related to over-voltage characteristic of ANSI-1990 and IEC 60871-1. 1997 as tabulated below.
ANSI 1036-19926 cycles0.102.20
ANSI 1036-199215 cycles0.272.00
ANSI 1036-19921.00 s0.901.70
ANSI 1036-199215.0 s13.51.40
ANSI 1036-199260.0 s54.01.30
IEC 60871-1. 1997300 s2701.20
IEC 60871-1. 19971800 s16201.15
Standard durationTime (s)Overload
35
69
Setting PhilosophySetting Philosophy
Under & OverUnder & Over--voltage (voltage (--F27UV/F27UV/--F59OV) [AREVA P922S]F59OV) [AREVA P922S]
F59OV - This protection as backup for the main protection. Inverse characteristic shall be coordinated with the allowable range as tabulated below. Alternatively, a definite time characteristic can be used with pickup at the maximum system voltage limit (+10%). Operating time shall be coordinated wilt the AVR setting.
1min1.30Voltage rise at light load5min1.20
System voltage regulation and fluctuations30min inevery 24h1.15
System voltage regulation and fluctuations8h in every 24h1.10
Highest average value during any period of capacitor service.Continues1.00
Power Frequency
Observation MaximumDuration
Voltage factor ×Un VrmsType
Capacitor allowable over-voltage range is as table 6 from IEC 60871-1. 1997 as follows
70
F27UV - Under voltage protection can be used to trip the capacitor bank and to block CB closing when its residual voltage is still high before being discharged after disconnection. The tripping function may be required if loss of system voltage. VT source should be taken from the busbar voltage selection to avoid blocking during normal closing if VT source from capacitor bank side.
Residual voltage allowable for capacitor discharging is less than 50Vdc from initial voltage of √2 of the rated voltage (Un). For this project, the bank is designed to reduce the residual voltage less then 50Vdc within 5 minutes. The manufacturer should provide discharge time to 50V in the instruction manual or rating plate.
Setting PhilosophySetting Philosophy
36
71
Automatic Voltage Control (Automatic Voltage Control (--F90AVC)F90AVC)
System operations shall advise the bandwidth setting. The setting depends on the local system condition. Typical operating system voltage is between 1.0 to 1.05 p.u. The AVR setting for 132kv system is recommended to regulate the system voltage between the normal operating range. Recommended time delay to be set is 30s.
As per the operating experience we recommend the programmable timer setting, the daily closing time is at 08:00 and opening time is at 23:00, it shall be determined by the system operator.
Setting PhilosophySetting Philosophy
72
Fault Level Calculation ExampleFault Level Calculation Example
37
73
Fault an AMPG Bus Under Peak LoadFault an AMPG Bus Under Peak Load
-79.625832.6TOTAL FAULT CURRENT (AMPS)NA
0.000.0TO SHUNT (AMPS)
999990.0049.35-82.404269.9AMP/OHM213275.00AMPG27588215
999990.0049.35-82.404269.9AMP/OHM113275.00AMPG27588215
5.91780.412.77-80.374319.4AMP/OHM213132.00PMJU13288175
5.91780.412.77-80.374319.4AMP/OHM113132.00PMJU13288175
4.20876.631.12-72.512692.9AMP/OHM213132.00TWSA13288137
4.20876.631.12-72.512692.9AMP/OHM113132.00TWSA13288137
5.91980.412.60-81.821661.4AMP/OHM213132.00KLJTI13288121
5.91980.412.60-81.821661.4AMP/OHM113132.00KLJTI13288121
APP X/RAN(Z+)/Z+/AN(I+)/I+/I/ZCKTAREAX-----------FROM--------------X
THREE PHASE FAULT
AT BUS 88120 AMPG132 132.00 Area 13 (kV L-G) V+: / 0.000/ 0.00THEV. R, X, X/R : POSITIVE 0.00360 0.0168 4.605
PSSE/E SHORT CIRCUIT OUTPUT MON, MAY 16 2005 17:16 HOME BUS is 881202007 PEAK LOAD CASE AMPG 132.00FAULTED BUS IS 88120 (AMPG132 132.00) 0 LEVELS AWAY
50 kA500kV40/50* kA275kV31.5 kA132kV
Short Circuit RatingVoltage Class TNB Planning criteria TNB Planning criteria
74
Construction of the Unit CapacitorConstruction of the Unit CapacitorConstruction of the Unit Capacitor
Rating : 9kV 1P 50Hz 591kvar, 23.18uF, 65.6A Construction : 6Series x 10Para (60 Rolls)
Eco : 13.91uF Discharge Resistor : 375kΩ x 6 series =2.25MΩ
Fuse : 0.4Φ Cupper Wire, Fuse Total length 20mΩ, Fuse operating Length 13.5mΩ
Unit Capacitor
Discharge Discharge ResistorResistor
13.91uF
Unbalance CalculationUnbalance Calculation
38
75
Unbalance current and overvoltage characteristics Unbalance current and overvoltage characteristics
99.612,971103.113,3141372,959357m3
99.812,888101.813,1501222,630214m2
99.912,901100.813,0201102,36993.8m1
100.012,912100.012,9121002,1522.76m0
Sound groupUnit % of Un
Sound groupunit VT-T[Vp]
Faulty Unit% of Un
Faulty unitVT-T[Vp]
Faulty Elementof Un
Faulty ElementGroup [Vp]NCT [Ap]No. of
faults
76
Typical Air Core Dry Type Reactor Typical Air Core Dry Type Reactor
39
77
Allowable Overload Current for ReactorAllowable Overload Current for Reactor
78
Typical Case Rupture Curve for ALL Film CapTypical Case Rupture Curve for ALL Film Cap
Typical case rupture curve for approximately 1800 cubic inchesTypical case rupture curve for approximately 1800 cubic inches-- case volume the dielectric case volume the dielectric material with Polypropylene film (ALL PP) quoted from IEEE Std. material with Polypropylene film (ALL PP) quoted from IEEE Std. 10361036--19921992
S’s typical clearing time of the internal fuse
40
79
Harmonic Filter TypesHarmonic Filter Types
80
Current Transformer2:2A 20VA
R S T
Configurations of Single Line Configurations of Single Line DwgDwg..
9 Series / phase
4 Parallel / phase
9s x 4p x 3 = 108 Cans
41
81
Key Rating FactorsKey Rating Factors
/(1 )c pV V α= −
/L cX Xα =
2( / ) (1/(1 ))L effXc V Q α= × −
/ 3P LV V=
2(1/ )L CX h X= ×
21/ hα =
L CX Xα= ×
(1/(1 ))cphase pV V α= × −/cunit cphaseV V Ns=
/( /(1 ))sr pV V α α= −
Three Phase Three Phase -- Single PhaseSingle Phase
VL Vsr
Vp
Vcphase
/(1 )cap effQ Q α= −
/capunit cap capQ Q N=
sr cap effQ Q - Q=
82
Harmonic Filter designHarmonic Filter design
2LLsys
effeff
kVX =
Q (Mvar)2
2 1C effhX X
h⎛ ⎞
= ⎜ ⎟−⎝ ⎠
2C
LXXh
=
Xeff is the effective reactance of the harmonic filter,Qeff is the effective reactive power (Mvar) of the harmonic filter,VLLsys is the nominal system line-to-line voltage,XC is the capacitive reactance of the harmonic filter capacitor at the fundamental frequency,XL is the inductive reactance of the harmonic filter reactor at the fundamental frequency,h is the harmonic number.
42
83
Numerical ExampleNumerical Example
A 30 MVA industrial load is supplied from a 34.5 kV bus. The three-phase fault level at the bus is 10.0 kA rms symmetrical. The load has a power factor of 0.85. It is desired that the power factor be raised to 0.95.The load is a source of harmonic current. The magnitude of the harmonic current suggests that the capacitor should be designed as a
harmonic filter.
Qeff (in kvar) = (multiplying factor)(load power in kilowatts)
Qeff = (0.291)(30 000 kVA)(.85) = 7420 kvar
84
Numerical ExampleNumerical Example
Because of Phase shift of h component
43
85
Numerical ExampleNumerical Example
86
Numerical ExampleNumerical Example
44
87
Harmonic Current EstimationHarmonic Current Estimation
jXL Rs
-jXC Xs
Ih
88
Configurations of 132kV 60MVAr Configurations of 132kV 60MVAr (Ungrounded Double Y) Side view(Ungrounded Double Y) Side view
45
89
Configurations of 132kV 60MVAr Configurations of 132kV 60MVAr (Ungrounded Double Y) Front view(Ungrounded Double Y) Front view
90
Steel Making Plant HarmonicsSteel Making Plant Harmonics
Changing cycle by cycleInterharmonicsDesign Filter is not traditional
Interharmonics ->torsional and mechanical resonance
46
91
Steel Making Plant HarmonicsSteel Making Plant Harmonics
92
Steel Making FacilitiesSteel Making Facilities
Important Categories
Characteristic harmonicsDerive loads in the rolling mill
Non-characteristic harmonicsThird harmonic componentEven harmonic componentsShorter duration than conventional but important
InterharmonicsFluctuating EAF, CycloconverterShould be capable of measurement
Statistical characteristics of the harmonic levels
47
93
Steel Making FacilitiesSteel Making Facilities
Statistically evaluation for interharmonic12 cycles sample, bin size of 5HzCumulative probability distributionSpecific values can be determined the distortion levels
Vh95%
VTHD95%
Vh99%
VTHD99%
Ih95%
ITDD95%
Ih99%
ITDD99%
The harmonic filters should not magnify interharmonic components, resulting in excessive levels.
94
Steel Making Plant HarmonicsSteel Making Plant Harmonics
Example filter design for arc furnace installations.
48
95
Case Study for Electrochemical PlantCase Study for Electrochemical Plant
System Problems
The utility side transformer has excessive audio frequency noise and overheats.
Voltage THD on the 22 kV system is 7.7%, exceeding limits in IEEE Standard 519.
The rectifiers incur thyristor phase control malfunctions due to voltage sensing errors.Utility and customer capacitor banks incur over currents and excessive noise.
Complaints are generated from adjacent customers due to device malfunctions, and in particular, standstill conditions created at a precision electrical facility
Increasing System Reliability Using Series Tuned Increasing System Reliability Using Series Tuned Harmonic Filter Banks in a Chemical FacilityHarmonic Filter Banks in a Chemical Facility
16th Annual Power Quality Conference
October 25th -27th 2005
Baltimore Convention center
96
Case Study for Electrochemical PlantCase Study for Electrochemical Plant
Utility Data
The normal Utility operating voltage is approximately 154 kV.
The Utility three-phase short circuit MVA is 1,400 MVA, with an X/R ratio of 10.
The 45 MVA supply transformer has a primary delta and secondary ungrounded wye winding arrangement, and a 5% impedance.
The incoming line distance from utility is indeed 0.75 km, composed with single core copper conductor 400 mm2.
22.9kV line has two sets of the capacitor banks 5MVAr, 6% SR
49
97
Case Study for Electrochemical PlantCase Study for Electrochemical Plant
Ratings of Rectifier Converter
No.1 rectifier 5,810kW 3,210kVAr 6-pulse thyristor converter
No.2 rectifier 6,100kW 4,900kVAr 6-pulse thyristor converter
No.3 rectifier 5,810kW 3,210kVAr 6-pulse thyristor converter
No.4 rectifier 2,100kW 820kVAr 6-pulse thyristor converter
98
Case Study for Electrochemical PlantCase Study for Electrochemical PlantPlant System with 6% SL Capacitors
UTIL 1400MVA
D-Y154/22.9kV45/65MVAZ=5%
D-D22.9/6.6kV9MVA, 7%
D-D22.9/3.3kV5MVA, 7%
3.7MW950kVAr
3.7MW950kVAr
300kVA6.3Ohm
5MVAr22.9kV
CU500mm2
500mCU400mm2
750m
PCC
KPC23kVDSN
PKCOM23
300kVA6.3Ohm
5MVAr22.9kV
6% SeriesReactors
22.9kV1400kVAr
22.9kV1500kVAr
22.9kV900kVAr
D-Y22.9/0.22kV7.5MVA, 7.5%
D-Y22.9/0.22kV8.6MVA, 10%
D-Y22.9/0.22kV7.5MVA, 10%
D-Y22.9/0.22kV2.3MVA, 5.5%
5.8MW3.21MVAR
6.1MW4.91MVAR
5.8MW3.21MVAR
2.1MW0.821MVAR
UTIL 1400MVA
D-Y154/22.9kV45/65MVAZ=5%
D-D22.9/6.6kV9MVA, 7%
D-D22.9/3.3kV5MVA, 7%
3.7MW950kVAr
3.7MW950kVAr
300kVA6.3Ohm
5MVAr22.9kV
CU500mm2
500mCU400mm2
750m
PCC
KPC23kVDSN
PKCOM23
300kVA6.3Ohm
5MVAr22.9kV
6% SeriesReactors
22.9kV1400kVAr
22.9kV1500kVAr
22.9kV900kVAr
D-Y22.9/0.22kV7.5MVA, 7.5%
D-Y22.9/0.22kV8.6MVA, 10%
D-Y22.9/0.22kV7.5MVA, 10%
D-Y22.9/0.22kV2.3MVA, 5.5%
5.8MW3.21MVAR
6.1MW4.91MVAR
5.8MW3.21MVAR
2.1MW0.821MVAR
50
99
Case Study for Electrochemical PlantCase Study for Electrochemical Plant
Impedance scan results and Harmonic spectrum
100
Passive FilterPassive Filter
Series Tuned Harmonic FilterHigh voltage Class : 50 < Q < 150Low voltage Class : 10 < Q < 50
LC1
C
L
R
ω
CL
RQ 1=
Cω1
Lω
R
FZ
)(ωFZ
51
101
Passive FilterPassive Filter
Damped High Passive Filter (2nd Order)
LC1
C
L
R
FZ
ω
Cω1
Lω
R
)(ωFZ
bR
bR
CRb
1
102
Without Filter: VTHD = 7.6%
Case Study for Electrochemical PlantCase Study for Electrochemical Plant
Without Filter
52
103
Plant System with Harmonic Filter Banks
Case Study for Electrochemical PlantCase Study for Electrochemical Plant
UTIL 1400MVAD-Y154/22.9kV45/65MVAZ=5%
D-D22.9/6.6kV9MVA, 7%
D-D22.9/3.3kV5MVA, 7%
3.7MW950kVAr
3.7MW950kVAr
300kVA6.3Ohm
5MVAr22.9kV
CU500mm500m
CU400mm750m
PCC
KPC23kV DSN
PKCOM23
300kVA6.3Ohm
5MVAr22.9kV
D-Y22.9/0.22kV7.5MVA, 7.5%
D-Y22.9/0.22kV8.6MVA, 10%
D-Y22.9/0.22kV7.5MVA, 10%
D-Y22.9/0.22kV2.3MVA, 5.5%
5.8MW3.21MVAR
6.1MW4.91MVAR
5.8MW3.21MVAR
2.1MW0.821MVAR 5th_1, 11th_High, 5th HF, 7th HF, 11th HF
60.7 6.05 15.6 15.4 8.2 mH
1006kVAr, 1934kVAr, 3162kVAr, 2028kVAr, 1485kVAr
UTIL 1400MVAD-Y154/22.9kV45/65MVAZ=5%
D-D22.9/6.6kV9MVA, 7%
D-D22.9/3.3kV5MVA, 7%
3.7MW950kVAr
3.7MW950kVAr
300kVA6.3Ohm
5MVAr22.9kV
CU500mm500m
CU400mm750m
PCC
KPC23kV DSN
PKCOM23
300kVA6.3Ohm
5MVAr22.9kV
D-Y22.9/0.22kV7.5MVA, 7.5%
D-Y22.9/0.22kV8.6MVA, 10%
D-Y22.9/0.22kV7.5MVA, 10%
D-Y22.9/0.22kV2.3MVA, 5.5%
5.8MW3.21MVAR
6.1MW4.91MVAR
5.8MW3.21MVAR
2.1MW0.821MVAR 5th_1, 11th_High, 5th HF, 7th HF, 11th HF
60.7 6.05 15.6 15.4 8.2 mH
UTIL 1400MVAD-Y154/22.9kV45/65MVAZ=5%
D-D22.9/6.6kV9MVA, 7%
D-D22.9/3.3kV5MVA, 7%
3.7MW950kVAr
3.7MW950kVAr
300kVA6.3Ohm
5MVAr22.9kV
CU500mm500m
CU400mm750m
PCC
KPC23kV DSN
PKCOM23
300kVA6.3Ohm
5MVAr22.9kV
D-Y22.9/0.22kV7.5MVA, 7.5%
D-Y22.9/0.22kV8.6MVA, 10%
D-Y22.9/0.22kV7.5MVA, 10%
D-Y22.9/0.22kV2.3MVA, 5.5%
5.8MW3.21MVAR
6.1MW4.91MVAR
5.8MW3.21MVAR
2.1MW0.821MVAR 5th_1, 11th_High, 5th HF, 7th HF, 11th HF
60.7 6.05 15.6 15.4 8.2 mH
1006kVAr, 1934kVAr, 3162kVAr, 2028kVAr, 1485kVAr
104
Case Study for Electrochemical PlantCase Study for Electrochemical Plant
Fr. scan results & modeling data TR / Filter
53
105
Name Type Comp IRMS kW Losses kVar Losses VSUM%ADFL-5_1 Notch 59.589 4.134 1058.369 146.4%ADFL-11A 2nd Ord R 2.081 4.807
L 55.943 0.290 82.018C 55.990 110.5%
FL-5 Notch 95.393 1.204 490.719 116.6%FL-7 Notch 65.681 0.473 265.355 114.5%FL-11 Notch 46.222 0.201 94.608 111.9%
Case Study for Electrochemical PlantCase Study for Electrochemical Plant
Filter data for design
106
Case Study for Electrochemical PlantCase Study for Electrochemical Plant
5th, 7th, 11th, 11th Hi-pass filter currents
54
107
Case Study for Electrochemical PlantCase Study for Electrochemical Plant
With Harmonic Filters
108
1.22.3K factor
0.7k0.76kCurrent Peak in Vp
19.1k20.9kVoltage Peak in Vp
471.9523.3Current Average in A
2.967.59~7.7Voltage Distortion %
6.73~7.0414.1~16.6Current Distortion %
0.980.88Power Factor
3,7009,870Power Q in kVAr
18,53018,440Power P in kW
18,90020,900Power S in kVA
Tuned Harmonic Filters6% SR CapacitorsDescription
Case Study for Electrochemical PlantCase Study for Electrochemical Plant
Summary of before and after power characteristics