Page 1: Application example APF report templates based on … report templates based on data from the WinCC User Archive PCS 7, Information Server Warranty and liability APF-Berichtsvorlagen

https://support.industry.siemens.com/cs/ww/en/view/64906050

Application example 03/2017

APF report templates based on data from the WinCC User Archive PCS 7, Information Server

Page 2: Application example APF report templates based on … report templates based on data from the WinCC User Archive PCS 7, Information Server Warranty and liability APF-Berichtsvorlagen

Warranty and liability

APF-Berichtsvorlagen auf Datenbasis der WinCC User Archive Entry ID: 64906050, V1.0, 03/2017 2

S

iem

en

s A

G 2

01

7 A

ll ri

gh

ts r

ese

rve

d

Warranty and liability

Note The Application Examples are not binding and do not claim to be complete regarding the circuits shown, equipping and any eventuality. The Application Examples do not represent customer-specific solutions. They are only intended to provide support for typical applications. You are responsible for ensuring that the described products are used correctly. These Application Examples do not relieve you of the responsibility to use safe practices in application, installation, operation and maintenance. When using these Application Examples, you recognize that we cannot be made liable for any damage/claims beyond the liability clause described. We reserve the right to make changes to these Application Examples at any time without prior notice. If there are any deviations between the recommendations provided in these Application Examples and other Siemens publications – e.g. Catalogs – the contents of the other documents have priority.

We do not accept any liability for the information contained in this document. Any claims against us – based on whatever legal reason – resulting from the use of the examples, information, programs, engineering and performance data etc., described in this Application Example shall be excluded. Such an exclusion shall not apply in the case of mandatory liability, e.g. under the German Product Liability Act (“Produkthaftungsgesetz”), in case of intent, gross negligence, or injury of life, body or health, guarantee for the quality of a product, fraudulent concealment of a deficiency or breach of a condition which goes to the root of the contract (“wesentliche Vertragspflichten”). The damages for a breach of a substantial contractual obligation are, however, limited to the foreseeable damage, typical for the type of contract, except in the event of intent or gross negligence or injury to life, body or health. The above provisions do not imply a change of the burden of proof to your detriment.

Any form of duplication or distribution of these Application Examples or excerpts hereof is prohibited without the expressed consent of the Siemens AG.

Security infor-

mation

Siemens provides products and solutions with industrial security functions that support the secure operation of plants, systems, machines and networks.

In order to protect plants, systems, machines and networks against cyber threats, it is necessary to implement – and continuously maintain – a holistic, state-of-the-art industrial security concept. Siemens’ products and solutions only form one element of such a concept.

Customers are responsible for preventing unauthorized access to their plants, systems, machines and networks. Systems, machines and components should be connected to the enterprise network or the Internet only where necessary, only to the extent needed and only with appropriate security measures (e.g. use of firewalls and network segmentation) in place.

Additionally, Siemens’ guidance on appropriate security measures must be taken into account. For more information about industrial security, please visit http://www.siemens.com/industrialsecurity.

Siemens’ products and solutions undergo continuous development to make them even more secure. Siemens strongly recommends applying product updates as soon as available and to always use the latest product versions. Using versions that are obsolete or are no longer supported can increase the risk of cyber threats.

To stay informed about product updates, subscribe to the Siemens Industrial Security RSS Feed under http://www.siemens.com/industrialsecurity.

Page 3: Application example APF report templates based on … report templates based on data from the WinCC User Archive PCS 7, Information Server Warranty and liability APF-Berichtsvorlagen

Table of contents

APF-Berichtsvorlagen auf Datenbasis der WinCC User Archive Entry ID: 64906050, V1.0, 03/2017 3

S

iem

en

s A

G 2

01

7 A

ll ri

gh

ts r

ese

rve

d

Table of contents Warranty and liability ................................................................................................... 2

1 Introduction ........................................................................................................ 4

2 Creating a user-defined report ......................................................................... 5

2.1 Operating principle ............................................................................... 5 2.2 Example data ....................................................................................... 6

3 Sequence ............................................................................................................ 7

3.1 Creating connection to WinCC database ............................................. 7 3.2 Defining the data contents of the report ............................................... 9 3.3 Layout definition ................................................................................. 14 3.4 Uploading the report template ............................................................ 20 3.5 Creating a report ................................................................................ 24

4 Appendix .......................................................................................................... 26

4.1 Service and Support ........................................................................... 26 4.2 Links and Literature ............................................................................ 27 4.3 Documentation of changes................................................................. 27

Page 4: Application example APF report templates based on … report templates based on data from the WinCC User Archive PCS 7, Information Server Warranty and liability APF-Berichtsvorlagen

1 Introduction

APF-Berichtsvorlagen auf Datenbasis der WinCC User Archive Entry ID: 64906050, V1.0, 03/2017 4

S

iem

en

s A

G 2

01

7 A

ll ri

gh

ts r

ese

rve

d

1 Introduction

Advanced Process Functions

The SIMATIC PCS 7 Advanced Process Functions (APF) automates simple batch processes for small and medium-sized automation systems with simple material processing. These are mainly dosing, mixing or stirring systems. The modules for material management, parameter management, task management, and archive management support automation of the production process from the raw materials intake to release for filling and packing.

Reports with APF

The PCS 7 add-on APF does not contain an independent function for generating reports from the WinCC User Archive used. The generation of reports with APF is carried out via the report templates of the information server, which uses the WinCC User Archive as its data base.

Core contents of the Application Example

The following documentation describes how the SIMATIC Information Server can be used to create complex and detailed reports and thus display the data generated by APF in a meaningful and appealing form.

Validity

SIMATIC Information Server 2014

SIMATIC PCS 7 V8.2

Page 5: Application example APF report templates based on … report templates based on data from the WinCC User Archive PCS 7, Information Server Warranty and liability APF-Berichtsvorlagen

2 Creating a user-defined report

APF-Berichtsvorlagen auf Datenbasis der WinCC User Archive Entry ID: 64906050, V1.0, 03/2017 5

S

iem

en

s A

G 2

01

7 A

ll ri

gh

ts r

ese

rve

d

2 Creating a user-defined report

2.1 Operating principle

These five steps must be followed in order to create a user-defined report:

1. Create a (redundant) connection between the information server and the WinCC database (Section 3.1).

2. Create a new report template in the MS Report Builder based on the default template ISBase.rdl and define the data content / SQL queries (Section 3.2).

3. Define the report layout in the MS Report Builder. (Section 3.3).

4. Upload the report template to the information server (Section 3.4).

5. Create a report using the Information Server client (Section 3.5).

Database query prerequisites

To create a consistent report, the following constraints must be observed:

1. The name of the WinCC Runtime database must be called up dynamically during the database query, since the name of the WinCC Runtime database can change, for example, by downloading a project completely or by archiving / retrieving a project in SIMATIC Manager.

2. Implement a handling for server redundancy if the default master is not available or cannot be started.

Page 6: Application example APF report templates based on … report templates based on data from the WinCC User Archive PCS 7, Information Server Warranty and liability APF-Berichtsvorlagen

2 Creating a user-defined report

APF-Berichtsvorlagen auf Datenbasis der WinCC User Archive Entry ID: 64906050, V1.0, 03/2017 6

S

iem

en

s A

G 2

01

7 A

ll ri

gh

ts r

ese

rve

d

2.2 Example data

The following example shows how a pie chart can be created from the data of two WinCC user archives used by APF.

The first WinCC User Archive contains the material management data (FB_MATERIAL_001).

The second WinCC User Archive contains the data for production tracking (FB_ARCHIVING_001).

Page 7: Application example APF report templates based on … report templates based on data from the WinCC User Archive PCS 7, Information Server Warranty and liability APF-Berichtsvorlagen

3 Sequence

APF-Berichtsvorlagen auf Datenbasis der WinCC User Archive Entry ID: 64906050, V1.0, 03/2017 7

S

iem

en

s A

G 2

01

7 A

ll ri

gh

ts r

ese

rve

d

3 Sequence

3.1 Creating connection to WinCC database

In this example, a redundant OS server pair (SV80A and SV80B) is connected to the information server.

1. Start the Information Server client.

2. Go to the “Configuration" view and click on "Reporting".

3. Under "Connect projects", fill in the appropriate fields and then click on the "Select projects” button:

– Server name or IP address: “SV80A” (Default Master/ Single OS Server or OS Single Station)

– Type: “WinCC- / PCS 7 OS”

– SQL instance: “wincc”

Page 8: Application example APF report templates based on … report templates based on data from the WinCC User Archive PCS 7, Information Server Warranty and liability APF-Berichtsvorlagen

3 Sequence

APF-Berichtsvorlagen auf Datenbasis der WinCC User Archive Entry ID: 64906050, V1.0, 03/2017 8

S

iem

en

s A

G 2

01

7 A

ll ri

gh

ts r

ese

rve

d

4. Enter a project name, activate the options box and click on the "OK" button.

Result

An information server connection to the redundant WinCC OS server pair has been successfully created.

Information Server Client (left) SQL Management Studio (right)

The project will be created under the given name “SV80A”.

The name "SV80A" is used for the "project" parameter when the report is created.

In the SQL server instance of the information server, the two linked servers SV80A\wincc and SV80B\wincc are created automatically under "Server Objects -> Linked Servers".

Within the report template, these are referenced as SQL server instances for the data query.

Page 9: Application example APF report templates based on … report templates based on data from the WinCC User Archive PCS 7, Information Server Warranty and liability APF-Berichtsvorlagen

3 Sequence

APF-Berichtsvorlagen auf Datenbasis der WinCC User Archive Entry ID: 64906050, V1.0, 03/2017 9

S

iem

en

s A

G 2

01

7 A

ll ri

gh

ts r

ese

rve

d

3.2 Defining the data contents of the report

This example refers to the two example WinCC User Archives from Section 2.2 "FB_MATERIAL_001" and "FB_ARCHIVING_001" of the APF demo project.

1. Copy the template "ISBase.rdl" from the corresponding folder and open it. (C:\Program Files (x86)\SIEMENS\InformationServer\RDL\ISBase.rdl)

2. Open the report properties via “right-clicking> Report Properties ... "

Page 10: Application example APF report templates based on … report templates based on data from the WinCC User Archive PCS 7, Information Server Warranty and liability APF-Berichtsvorlagen

3 Sequence

APF-Berichtsvorlagen auf Datenbasis der WinCC User Archive Entry ID: 64906050, V1.0, 03/2017 10

S

iem

en

s A

G 2

01

7 A

ll ri

gh

ts r

ese

rve

d

3. Click on “References” and delete the complement: “ ,Version=7.3.0.0, Culture=neutral, PublicKeyToken=10e6533682f60eab”. Confirm by clicking on the "OK” button.

4. To access the data in the WinCC User Archive, right-click “Add Dataset ... "

Note The “Text” query offers the most flexibility.

Page 11: Application example APF report templates based on … report templates based on data from the WinCC User Archive PCS 7, Information Server Warranty and liability APF-Berichtsvorlagen

3 Sequence

APF-Berichtsvorlagen auf Datenbasis der WinCC User Archive Entry ID: 64906050, V1.0, 03/2017 11

S

iem

en

s A

G 2

01

7 A

ll ri

gh

ts r

ese

rve

d

5. The following query includes the determination of the database name as well as the overlapping of the server redundancy and connects NAME and TYPE from "FB_MATERIAL_001" to PV (= process value “production quantity”) from "FB_ARCHIVING_001" (archiving group type "BATCH-related").

Query for redundancy cover and WinCC Runtime database name finding

DECLARE @prefix AS SYSNAME, @retval int

SET @prefix = 'SV80A\WINCC'

SET @retval = 0

BEGIN TRY EXEC @retval = sys.sp_testlinkedserver @prefix END TRY

BEGIN CATCH SET @retval = sign(@@error) END CATCH

IF @retval = 0

SELECT @prefix = '[SV80A\WINCC].' + name + '.dbo.' FROM

[SV80A\WINCC].master.sys.databases WHERE name LIKE 'CC_%R'

IF @retval <> 0 OR @prefix = 'SV80A\WINCC'

SELECT @prefix = '[SV80B\WINCC].' + name + '.dbo.' FROM

[SV80B\WINCC].master.sys.databases WHERE name LIKE 'CC_%R'

Page 12: Application example APF report templates based on … report templates based on data from the WinCC User Archive PCS 7, Information Server Warranty and liability APF-Berichtsvorlagen

3 Sequence

APF-Berichtsvorlagen auf Datenbasis der WinCC User Archive Entry ID: 64906050, V1.0, 03/2017 12

S

iem

en

s A

G 2

01

7 A

ll ri

gh

ts r

ese

rve

d

Query without redundancy cover:

DECLARE @prefix AS SYSNAME

SELECT @prefix = '[SV80A\WINCC].' + name + '.dbo.' FROM

[SV80A\WINCC].master.sys.databases WHERE name LIKE 'CC_%R'

Query for the desired data in the report

EXECUTE

(

‘SELECT

UA#FB_MATERIAL_001.NAME AS ProductName

,UA#FB_ARCHIVING_001.PV AS Quantity

FROM

' + @prefix + 'UA#FB_ARCHIVING_001

INNER JOIN ' + @prefix + 'UA#FB_MATERIAL_001 ON

UA#FB_MATERIAL_001.REC_ID = UA#FB_ARCHIVING_001.MAT_ID

WHERE UA#FB_MATERIAL_001.TYPE = 2'

)

Result

A database query and its content were created.

Page 13: Application example APF report templates based on … report templates based on data from the WinCC User Archive PCS 7, Information Server Warranty and liability APF-Berichtsvorlagen

3 Sequence

APF-Berichtsvorlagen auf Datenbasis der WinCC User Archive Entry ID: 64906050, V1.0, 03/2017 13

S

iem

en

s A

G 2

01

7 A

ll ri

gh

ts r

ese

rve

d

Testing the database query

Before the report is implemented, the query should be pre-tested in the SQL Management Studio (the aggregate (SUM ... GROUP BY) explicitly added in the following query is implicitly executed by the report generator)

Query for the SQL Management Studio as plain text:

-- How to access WinCC user archives on redundant OS servers

-- use cases covered by this approach:

-- while server B is in master mode:

-- - server A is switched off

-- - WinCC project has not been opened on server A

-- - server A is in stand-by mode (data synchronized from server B)

-- use cases NOT covered by this approach:

-- - WinCC project has been opened on server A, but not started yet:

old outdated data will be read out from server A

-- Adaption to other projects: server A name to be adapted 4 times,

server B name to be adapted 2 times (do not add or remove any brackets)

DECLARE @prefix AS SYSNAME, @retval int

-- define server A database instance name as shown in Linked Servers list

(without brackets, to be adapted 1 time)

SET @prefix = 'SV80A\WINCC'

SET @retval = 0

-- check whether server A is available

BEGIN TRY EXEC @retval = sys.sp_testlinkedserver @prefix END TRY

BEGIN CATCH SET @retval = sign(@@error) END CATCH

-- if server A is available:

IF @retval = 0

Page 14: Application example APF report templates based on … report templates based on data from the WinCC User Archive PCS 7, Information Server Warranty and liability APF-Berichtsvorlagen

3 Sequence

APF-Berichtsvorlagen auf Datenbasis der WinCC User Archive Entry ID: 64906050, V1.0, 03/2017 14

S

iem

en

s A

G 2

01

7 A

ll ri

gh

ts r

ese

rve

d

-- define prefix for server A database instance name (including

brackets, to be adapted 2 times!)

SELECT @prefix = '[SV80A\WINCC].' + name + '.dbo.' FROM

[SV80A\WINCC].master.sys.databases WHERE name LIKE 'CC_%R'

-- if server A is not available

-- or CC_%R database has not been found in server A database instance

(without brackets, to be adapted 1 time) in case of WinCC project closed:

IF @retval <> 0 OR @prefix = 'SV80A\WINCC'

-- define prefix for server B database instance name (including

brackets, to be adapted 2 times!)

SELECT @prefix = '[SV80B\WINCC].' + name + '.dbo.' FROM

[SV80B\WINCC].master.sys.databases WHERE name LIKE 'CC_%R'

-- for check in Messages window (e.g. "@prefix =

[SV80A\WINCC].CC_OSS1_16_12_06_08_27_29R.dbo.")

PRINT '@prefix = ' + @prefix

-- define statement, add prefix to each table name

EXECUTE (

‘SELECT

UA#FB_MATERIAL_001.NAME AS ProductName

,SUM(UA#FB_ARCHIVING_001.PV) AS Quantity

FROM

' + @prefix + 'UA#FB_ARCHIVING_001

INNER JOIN ' + @prefix + 'UA#FB_MATERIAL_001 ON

UA#FB_MATERIAL_001.REC_ID = UA#FB_ARCHIVING_001.MAT_ID

WHERE UA#FB_MATERIAL_001.TYPE = 2

GROUP BY UA#FB_MATERIAL_001.NAME'

)

3.3 Layout definition

Use the Chart Wizard to display the data from "DataSet1" as a pie chart.

1. Open the Chart Wizard by selecting "Chart> Chart Wizard ...".

Page 15: Application example APF report templates based on … report templates based on data from the WinCC User Archive PCS 7, Information Server Warranty and liability APF-Berichtsvorlagen

3 Sequence

APF-Berichtsvorlagen auf Datenbasis der WinCC User Archive Entry ID: 64906050, V1.0, 03/2017 15

S

iem

en

s A

G 2

01

7 A

ll ri

gh

ts r

ese

rve

d

2. Select the desired data set and click on the "Next" button.

3. Select "Pie Chart" as chart type and then click on the "Next>" button.

Page 16: Application example APF report templates based on … report templates based on data from the WinCC User Archive PCS 7, Information Server Warranty and liability APF-Berichtsvorlagen

3 Sequence

APF-Berichtsvorlagen auf Datenbasis der WinCC User Archive Entry ID: 64906050, V1.0, 03/2017 16

S

iem

en

s A

G 2

01

7 A

ll ri

gh

ts r

ese

rve

d

4. Select the "ProductName" field as the category and the "Quantity" field for the sum totals, then click on the "Next>" button.

5. Select the desired display style and then click on the “Finish>>" button.

Page 17: Application example APF report templates based on … report templates based on data from the WinCC User Archive PCS 7, Information Server Warranty and liability APF-Berichtsvorlagen

3 Sequence

APF-Berichtsvorlagen auf Datenbasis der WinCC User Archive Entry ID: 64906050, V1.0, 03/2017 17

S

iem

en

s A

G 2

01

7 A

ll ri

gh

ts r

ese

rve

d

6. To display the values in the pie chart, open the context menu by clicking with the right mouse button on the diagram "Add data labels" in the pie chart.

7. Click on the "Run” button.

Page 18: Application example APF report templates based on … report templates based on data from the WinCC User Archive PCS 7, Information Server Warranty and liability APF-Berichtsvorlagen

3 Sequence

APF-Berichtsvorlagen auf Datenbasis der WinCC User Archive Entry ID: 64906050, V1.0, 03/2017 18

S

iem

en

s A

G 2

01

7 A

ll ri

gh

ts r

ese

rve

d

8. Select the project. To create a report, click on the "View Report" button.

Result

A production report has been created with the desired type of data display.

Note The name of the project corresponds to the name of the connection between the WinCC Runtime project and the information server in Section 3.1.

Page 19: Application example APF report templates based on … report templates based on data from the WinCC User Archive PCS 7, Information Server Warranty and liability APF-Berichtsvorlagen

3 Sequence

APF-Berichtsvorlagen auf Datenbasis der WinCC User Archive Entry ID: 64906050, V1.0, 03/2017 19

S

iem

en

s A

G 2

01

7 A

ll ri

gh

ts r

ese

rve

d

Changes to the database query allow you to display other information, such as, for instance, raw material consumption.

Page 20: Application example APF report templates based on … report templates based on data from the WinCC User Archive PCS 7, Information Server Warranty and liability APF-Berichtsvorlagen

3 Sequence

APF-Berichtsvorlagen auf Datenbasis der WinCC User Archive Entry ID: 64906050, V1.0, 03/2017 20

S

iem

en

s A

G 2

01

7 A

ll ri

gh

ts r

ese

rve

d

3.4 Uploading the report template

Name the report template as it is to appear in the information server client.

1. Open the report properties via “right-click> Report Properties”.

2. Go to "Default Values" and click on the "Function" button.

Page 21: Application example APF report templates based on … report templates based on data from the WinCC User Archive PCS 7, Information Server Warranty and liability APF-Berichtsvorlagen

3 Sequence

APF-Berichtsvorlagen auf Datenbasis der WinCC User Archive Entry ID: 64906050, V1.0, 03/2017 21

S

iem

en

s A

G 2

01

7 A

ll ri

gh

ts r

ese

rve

d

3. Replace the expression "ISBase" with a label of your choice (for example, "APF Production Report V1.1") and click on the "OK" button.

4. Save the report as an RDL file.

Page 22: Application example APF report templates based on … report templates based on data from the WinCC User Archive PCS 7, Information Server Warranty and liability APF-Berichtsvorlagen

3 Sequence

APF-Berichtsvorlagen auf Datenbasis der WinCC User Archive Entry ID: 64906050, V1.0, 03/2017 22

S

iem

en

s A

G 2

01

7 A

ll ri

gh

ts r

ese

rve

d

5. Open the Information Server, change to “Administration” and click on “Reporting”.

6. Make a new folder under “Templates”.

7. Click on the created folder and click on the "Upload" button and "Select files ...”.

Page 23: Application example APF report templates based on … report templates based on data from the WinCC User Archive PCS 7, Information Server Warranty and liability APF-Berichtsvorlagen

3 Sequence

APF-Berichtsvorlagen auf Datenbasis der WinCC User Archive Entry ID: 64906050, V1.0, 03/2017 23

S

iem

en

s A

G 2

01

7 A

ll ri

gh

ts r

ese

rve

d

8. Select the report you want to create and click on the “Open” button.

Result

The Report template has been successfully uploaded to the Information Server.

Page 24: Application example APF report templates based on … report templates based on data from the WinCC User Archive PCS 7, Information Server Warranty and liability APF-Berichtsvorlagen

3 Sequence

APF-Berichtsvorlagen auf Datenbasis der WinCC User Archive Entry ID: 64906050, V1.0, 03/2017 24

S

iem

en

s A

G 2

01

7 A

ll ri

gh

ts r

ese

rve

d

3.5 Creating a report

1. Click on "Create report” in the Information Server.

2. Select your project.

Page 25: Application example APF report templates based on … report templates based on data from the WinCC User Archive PCS 7, Information Server Warranty and liability APF-Berichtsvorlagen

3 Sequence

APF-Berichtsvorlagen auf Datenbasis der WinCC User Archive Entry ID: 64906050, V1.0, 03/2017 25

S

iem

en

s A

G 2

01

7 A

ll ri

gh

ts r

ese

rve

d

3. Click on the "Show preview” button. To create a report, click on the “Create Report" button.

Result

A production report has been generated successfully.

Page 26: Application example APF report templates based on … report templates based on data from the WinCC User Archive PCS 7, Information Server Warranty and liability APF-Berichtsvorlagen

4 Appendix

APF-Berichtsvorlagen auf Datenbasis der WinCC User Archive Entry ID: 64906050, V1.0, 03/2017 26

S

iem

en

s A

G 2

01

7 A

ll ri

gh

ts r

ese

rve

d

4 Appendix

4.1 Service and Support

Industry Online Support

Do you have any questions or need assistance?

Siemens Industry Online Support offers round the clock access to our entire service and support know-how and portfolio.

The Industry Online Support is the central address for information about our products, solutions and services.

Product information, manuals, downloads, FAQs and application examples – all information is accessible with just a few mouse clicks at: https://support.industry.siemens.com/ .

Technical Support

The Technical Support of Siemens Industry provides you fast and competent support regarding all technical queries with numerous tailor-made offers – ranging from basic support to individual support contracts.

Please send queries to Technical Support via Web form: www.siemens.en/industry/supportrequest .

Service offer

Our range of services includes, inter alia, the following:

Product trainings

Plant data services

Spare parts services

Repair services

On-site and maintenance services

Retrofitting and modernization services

Service programs and contracts

You can find detailed information on our range of services in the service catalog: https://support.industry.siemens.com/cs/sc

Industry Online Support app

You will receive optimum support wherever you are with the "Siemens Industry Online Support" app. The app is available for Apple iOS, Android and Windows Phone: https://support.industry.siemens.com/cs/ww/en/sc/2067

Page 27: Application example APF report templates based on … report templates based on data from the WinCC User Archive PCS 7, Information Server Warranty and liability APF-Berichtsvorlagen

4 Appendix

APF-Berichtsvorlagen auf Datenbasis der WinCC User Archive Entry ID: 64906050, V1.0, 03/2017 27

S

iem

en

s A

G 2

01

7 A

ll ri

gh

ts r

ese

rve

d

4.2 Links and Literature

Table 4-1

No. Topic

\1\ Siemens Industry Online Support

https://support.industry.siemens.com

\2\ https://support.industry.siemens.com/cs/ww/en/view/64906050

\3\

4.3 Documentation of changes

Table 4-2

Version Date Change