ansi z358.1-2014 emergency equipment minimum ......ansi z358.1-2014 emergency equipment minimum...

2
Combination unit components shall be capable of operating simultaneously and shall be positioned so that components may be used simultaneously by the same user. (Sec. 7.4.4) 16 Emergency equipment shall be activated weekly. (Sec. 4.6.2) All emergency equipment shall be inspected annually to assure conformance with ANSI Z358.1. (Sec. 4.6.5, 5.5.2, 6.5.2, 7.5.2, 8.2.4.2) 15 All employees subject to exposure to hazardous material should be instructed in use of emergency equipment. (Sec. 4.6.4, 5.5.4, 6.5.4, 7.5.4, 8.2.4.4) 14 Safety Station shall be located on the same level as the hazard and the path of travel shall be free of obstructions. (Sec. 4.5.2, 5.4.2, 6.4.2, 7.4.2) 13 Safety station shall be accessible within 10 seconds of hazard (Sec. 4.5.2, 5.4.2, 6.4.2, 7.4.2) 12 Deliver tepid flushing fluid. A suitable temperature range is 60˚F to 100˚F. (Sec. 4.5.6, 5.4.6, 6.4.6, 7.4.2, 8.2.3.4) 11 10 Emergency equipment location shall be identified with a highly visible sign. Area around equipment shall be well lit. (Sec. 4.5.3, 5.4.3, 6.4.3, 7.4.3, 8.2.3.2) 10 9 Drench hose shall deliver a controlled flow of flushing fluid at a velocity low enough to be non-injurious. (Sec. 8.2.1) 9 8 Valve shall be designed so that the flushing fluid flow remains on without the use of the operator’s hands. The valve shall be simple to operate and go from “off” to “on” in one second or less. (Sec. 5.2, 6.2) 8 7 Eye/Face wash equipment shall deliver minimum of 3 gallons per minute of water for 15 minutes. (Sec. 6.1.6) Eyewash shall deliver minimum of 0.4 gallons per minute for 15 minutes. (Sec. 5.1.6) 7 6 Eyewash and eye/face flushing fluid flow pattern shall not be less than 33 inches and no greater than 53 inches from the surface the user is standing on. (Sec. 5.4.4, 6.4.4) 6 5 Outlets shall be protected from airborn contaminants. (Sec. 5.1.3, 6.1.3) 5 4 Shall provide a means of controlled flow to both eyes. (Sec. 5.1.3, 6.1.3) 4 3 Valve shall be designed so that the flushing fluid flow remains on without the use of the operator’s hands. The valve shall be simple to operate and go from “off” to “on” in one second or less. (Sec. 4.2) 3 2 Shower shall deliver minimum of 20 gallons per minute (Sec. 4.1.2) and provide a column of water 20 inches wide at 60 inches above the surface floor of user. (Sec. 4.1.4) 2 1 Showerhead shall be 82 to 96 inches above surface floor of user. (Sec. 4.1.3) 1 ANSI Z358.1-2014 EMERGENCY EQUIPMENT MINIMUM PERFORMANCE CHECKLIST

Upload: others

Post on 07-Jun-2021

36 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: ANSI Z358.1-2014 EMERGENCY EQUIPMENT MINIMUM ......ANSI Z358.1-2014 EMERGENCY EQUIPMENT MINIMUM PERFORMANCE CHECKLIST Sh o wer within 10 seconds of haza r d Designated b y highly visible

Combination unit components shall be capable of operating simultaneously and shall be positioned so that components maybe used simultaneously by the same user. (Sec. 7.4.4) 16

Emergency equipment shall be activated weekly. (Sec. 4.6.2) All emergency equipment shall beinspected annually to assure conformance with ANSI Z358.1. (Sec. 4.6.5, 5.5.2, 6.5.2, 7.5.2, 8.2.4.2) 15

All employees subject to exposure to hazardous material should be instructed in use ofemergency equipment. (Sec. 4.6.4, 5.5.4, 6.5.4, 7.5.4, 8.2.4.4) 14

Safety Station shall be located on the same level as the hazardand the path of travel shall be free of obstructions. (Sec. 4.5.2, 5.4.2, 6.4.2, 7.4.2) 13

Safety station shall be accessible within 10 seconds ofhazard (Sec. 4.5.2, 5.4.2, 6.4.2, 7.4.2) 12

Deliver tepid flushing fluid. A suitable temperature range is 60˚F to 100˚F. (Sec. 4.5.6, 5.4.6, 6.4.6, 7.4.2, 8.2.3.4) 11

10

Emergency equipment location shall be identified with a highly visible sign. Area around equipment shall be well lit. (Sec. 4.5.3, 5.4.3, 6.4.3, 7.4.3, 8.2.3.2) 10

9

Drench hose shall deliver a controlled flow of flushing fluid at avelocity low enough to be non-injurious. (Sec. 8.2.1) 9

8

Valve shall be designed so that the flushing fluid flow remains on without the use of the operator’s hands. The valve shall be simple to operate and go from “off” to “on” in one second or less. (Sec. 5.2, 6.2)

8

7

Eye/Face wash equipment shall deliver minimum of 3 gallons per minute of water for 15 minutes.(Sec. 6.1.6) Eyewash shall deliver minimum of 0.4 gallons per minute for 15 minutes. (Sec. 5.1.6) 7

6

Eyewash and eye/face flushing fluid flow pattern shall not be less than 33 inchesand no greater than 53 inches from the surface the user is standing on. (Sec. 5.4.4, 6.4.4) 6

5

Outlets shall be protected from airborn contaminants. (Sec. 5.1.3, 6.1.3) 5

4

Shall provide a means of controlled flow to both eyes. (Sec. 5.1.3, 6.1.3) 4

3

Valve shall be designed so that the flushing fluidflow remains on without the use of the operator’shands. The valve shall be simple to operate and gofrom “off” to “on” in one second or less. (Sec. 4.2)

3

2

Shower shall deliver minimum of 20 gallons per minute (Sec. 4.1.2) andprovide a column of water 20 inches wide at 60 inches abovethe surface floor of user. (Sec. 4.1.4)

2

1

Showerhead shall be 82 to 96 inches above surface floor of user. (Sec. 4.1.3) 1

ANSI Z358.1-2014 EMERGENCY EQUIPMENTMINIMUM PERFORMANCE CHECKLIST

Page 2: ANSI Z358.1-2014 EMERGENCY EQUIPMENT MINIMUM ......ANSI Z358.1-2014 EMERGENCY EQUIPMENT MINIMUM PERFORMANCE CHECKLIST Sh o wer within 10 seconds of haza r d Designated b y highly visible

Shower within 10 seconds of hazard

Designated by highly visible signage and well lit

Station on the same level as hazard; no obstructions

Valve goes from off to

on in seconds; simple valves

Valves remain open (hands free operation)

Eyewash outlets protected from contaminants

Minimum eye wash flow (.4gpm eyewash - 3

gpm eye/facewash)

Eye/face wash provides controlled flow to both eyes

Flushing fluid lines up with eyes at a point no more than 8” above nozzle

s

There is a barrier w

ithin 6” of eye/face wash

Proper heights for eye/face wash flow (33” to

53” above floor)

Shower must deliver a minimum 20gpm flow

Proper height for shower head (82” to

96” above floor)

Shower flow pattern (minimum of 20” w

idth @ 60” above floor)

Barrier w

ithin 16” radius of center point of shower

Combo shower - eye/face wash simultaneous use - fl

ow requirements

Combo shower - eye/face wash simultaneous use - p

ositioning

Flushing fluid must be tepid 60˚F -100˚F

Loca

tion

Emer

genc

y Eq

uipm

ent F

ield

Sur

vey

Wor

kshe

et(E

mer

genc

y Sh

ower

s, E

yew

ashe

s, C

ombi

natio

n Un

its, e

tc.)

Com

men

tsM

odel

#

Prep

ared

by:

____

____

____

____

____

____

____

____

____

____

Date

:___

____

____

____

____

____

Com

pany

: ___

____

____

____

____

____

____

_

Loca

tion:

____

____

____

____

____

____

____

_

Addr

ess:

___

____

____

____

____

____

____

__

____

____

____

____

____

____

____

____

____

Phon

e: _

____

____

____

____

____

____

____

_

Emai

l: __

____

____

____

____

____

____

____

_

____

____

____

____

____

_of_

____

____

____

____

____

__ L100

1289

5-23

-18