6
2018 INTERNATIONAL BUILDING CODES W/ LOCAL AMENDMENTS 2018 INTERNATIONAL BUILDING CODE 2017 NATIONAL ELECTRICAL CODE 2018 INTERNATIONAL ENERGY CONSERVATION CODE 2018 INTERNATIONAL EXISTING BUILDING CODE 2018 INTERNATIONAL FUEL GAS CODE 2018 INTERNATIONAL MECHANICAL CODE 2018 INTERNATIONAL PLUMBING CODE 2018 INTERNATIONAL RESIDENTIAL CODE 2018 INTERNATIONAL FIRE CODE 2018 CITY OF TUCSON/PIMA COUNTY OUTDOOR LIGHTING CODE ZONING CODES UNIFIED DEVELOPMENT CODE W/ SUPPORTING DOCUMENTS ADMINISTRATIVE MANUAL TECHNICAL STANDARDS MANUAL SUPPLEMENT NO.1 - 8 applicable codes Project Location I - 10 S Houghton Rd H S. MARK E. E G R A R N Z I O U. A BOLLARD 23459 I S D E T E R A R C C E A. T I T N T A C I F I A D D E N G S T E I R C E T E O. job date revisions 7350 EAST SPEEDWAY 210 TUCSON, ARIZONA 85710 (520) 326-3700 (520) 326-1148 www.swaimaia.com OFFICE FAX ASSOCIATES LTD ARCHITECTS AIA / / 10/15/2019 9:09:21 AM C:\Active Revit Projects\1817.02 Andrada High School Field & Court Lighting_jseymour.rvt g1.0 cover sheet Andrada Polytechnic High School Bond Improvement Projects Field & Court Lighting 12960 S. Houghton Rd, Tucson, AZ 85747 10.15.19 1817.02 15 10 19 Andrada Polytechnic High School CONSTRUCTION DOCUMENTS SWAIM ASSOCIATES LTD. ARCHITECTS AIA architect 7350 E. Speedway 210 Tucson, AZ 85710 (520) 326 - 3700 - fax: (520) 326 - 1148 www.swaimaia.com Phil Swaim, AIA [email protected] ENGINEERED DESIGN GROUP - WEST electrical engineer 954 N. Alvernon Way Tucson, AZ 85711 - 1018 (520) 881 - 8896 - fax: (520) 881 - 5647 www.edg - ce.com Dennis Coon, PE DWC@edg - ce.com sheet index design team VAIL UNIFIED SCHOOL DISTRICT #20 FIELD LIGHTING north 1" = 1'-0" g1.0 1 location map GENERAL g1.0 COVER SHEET g1.1 ABBREVIATIONS AND SYMBOLS ARCHITECTURAL SITE PLAN x1.0 SITE PLAN ELECTRICAL e1.1 FEEDER DIAGRAM & CALCULATIONS e2.0 REFERENCE ELECTRICAL PLAN e2.1 ELECTRICAL LEGEND & REFERENCE PLANS ALT #1 TENNIS COURT LIGHTING add alternates

Upload: others

Post on 31-Jan-2021

4 views

Category:

Documents


0 download

TRANSCRIPT

  • 2018 INTERNATIONAL BUILDING CODES W/ LOCAL AMENDMENTS

    2018 INTERNATIONAL BUILDING CODE2017 NATIONAL ELECTRICAL CODE2018 INTERNATIONAL ENERGY CONSERVATION CODE2018 INTERNATIONAL EXISTING BUILDING CODE2018 INTERNATIONAL FUEL GAS CODE2018 INTERNATIONAL MECHANICAL CODE2018 INTERNATIONAL PLUMBING CODE2018 INTERNATIONAL RESIDENTIAL CODE2018 INTERNATIONAL FIRE CODE2018 CITY OF TUCSON/PIMA COUNTY OUTDOOR LIGHTING CODE

    ZONING CODES

    UNIFIED DEVELOPMENT CODE W/ SUPPORTING DOCUMENTSADMINISTRATIVE MANUAL TECHNICAL STANDARDS MANUALSUPPLEMENT NO.1 - 8

    applicable codes

    Project Location

    I-10

    S Ho

    ughto

    n Rd

    H

    S.

    MARK E.

    EG

    RA

    R

    NZI O U.A

    BOLLARD

    23459

    ISDET ER

    ARC

    CE

    A.

    T

    IT

    N

    TACIFI

    AD

    DENGS

    TE

    I

    R

    CET E

    O.

    job

    date

    revisions

    7350 EAST SPEEDWAY 210TUCSON, ARIZONA 85710

    (520) 326-3700(520) 326-1148

    www.swaimaia.com

    OFFICEFAX

    ASSOCIATES LTDARCHITECTS AIA

    /

    /

    10/1

    5/20

    19 9

    :09:

    21 A

    MC

    :\Act

    ive

    Rev

    it Pr

    ojec

    ts\1

    817.

    02 A

    ndra

    da H

    igh

    Scho

    ol F

    ield

    & C

    ourt

    Ligh

    ting_

    jsey

    mou

    r.rvt

    g1.0

    cove

    r sh

    eet

    Andr

    ada

    Poly

    tech

    nic

    High

    Sch

    ool

    Bond

    Impr

    ovem

    ent P

    roje

    cts

    Fiel

    d &

    Cour

    t Lig

    htin

    g12

    960

    S. H

    ough

    ton

    Rd, T

    ucso

    n, A

    Z 85

    747

    10.15.19

    1817.02

    1510

    19

    Andrada Polytechnic High School

    CONSTRUCTION DOCUMENTS

    SWAIM ASSOCIATES LTD. ARCHITECTS AIA

    architect

    7350 E. Speedway 210Tucson, AZ 85710(520) 326-3700 - fax: (520) 326-1148www.swaimaia.com

    Phil Swaim, AIA [email protected]

    ENGINEERED DESIGN GROUP - WEST

    electrical engineer

    954 N. Alvernon WayTucson, AZ 85711-1018(520) 881-8896 - fax: (520) 881-5647www.edg-ce.com

    Dennis Coon, PE [email protected]

    sheet index

    design team

    VAIL UNIFIED SCHOOL DISTRICT #20

    FIELD LIGHTINGno

    rth1" = 1'-0"g1.0

    1 location map

    GENERALg1.0 COVER SHEETg1.1 ABBREVIATIONS AND SYMBOLS

    ARCHITECTURAL SITE PLANx1.0 SITE PLAN

    ELECTRICALe1.1 FEEDER DIAGRAM & CALCULATIONSe2.0 REFERENCE ELECTRICAL PLANe2.1 ELECTRICAL LEGEND & REFERENCE PLANS

    ALT #1 TENNIS COURT LIGHTING

    add alternates

  • 1a7.1

    N-S section1/8" = 1'-0"

    CLASS129

    A129B

    10'-0"

    11'-3 3/4"LANDING 2

    3

    1a1.0

    A

    5a6.3

    G

    F

    E

    D

    a6.1

    1a9.2

    1a1.0

    1a1.0

    2a7.2

    2a7.2

    2a5.2

    ELEVATION INDICATOR

    PARTITION TYPE

    KEYNOTE

    CEILING HEIGHT

    WINDOW MARK

    DOOR NUMBER

    ROOM NAME / NUMBER

    EXTERIOR ELEVATIONS

    INTERIOR ELEVATIONS

    ENLARGED AREA

    SECTION / DETAIL TAG

    BUILDING SECTION TAG

    DRAWING TITLE

    WALL SECTION TAG

    2

    symbols legend

    H

    S.

    MARK E.

    EG

    RA

    R

    NZI O U.A

    BOLLARD

    23459

    ISDET ER

    ARC

    CE

    A.

    T

    IT

    N

    TACIFI

    AD

    DENGS

    TE

    I

    R

    CET E

    O.

    job

    date

    revisions

    7350 EAST SPEEDWAY 210TUCSON, ARIZONA 85710

    (520) 326-3700(520) 326-1148

    www.swaimaia.com

    OFFICEFAX

    ASSOCIATES LTDARCHITECTS AIA

    /

    /

    10/1

    5/20

    19 9

    :09:

    22 A

    MC

    :\Act

    ive

    Rev

    it Pr

    ojec

    ts\1

    817.

    02 A

    ndra

    da H

    igh

    Scho

    ol F

    ield

    & C

    ourt

    Ligh

    ting_

    jsey

    mou

    r.rvt

    g1.1

    abbr

    evia

    tion

    s an

    dsy

    mbo

    lsAn

    drad

    a Po

    lyte

    chni

    c Hi

    gh S

    choo

    lBo

    nd Im

    prov

    emen

    t Pro

    ject

    sFi

    eld

    & Co

    urt L

    ight

    ing

    1296

    0 S.

    Hou

    ghto

    n Rd

    , Tuc

    son,

    AZ

    8574

    7

    10.15.19

    1817.02

    1510

    19

    general project notesabbreviationsTYP TYPICALUNFIN UNFINISHEDUNO UNLESS NOTED

    OTHERWISEUON UNLESS OTHERWISE

    NOTEDURNL URINALVAC VENTILATION AND AIR

    CONDITIONINGVAR VARIESVCT VINYL COMPOSITION TILEVERT VERTICALVEST VESTIBULEVIF VERIFY IN FIELDVP VISION PANELVR VAPOR RETARDERVT VINYL TILEVWC VINYL WALL COVERINGW WIDE/WESTW/ WITHW/O WITHOUTWC WATER CLOSETWD WOODWIN WINDOWWM WIRE MESHWP WATERPROOF/WATERPRO

    OFINGWPM WATERPROOF MEMBRANEWS WEATHER-STRIPPINGWSCT WAINSCOTWT WEIGHTWV WATER VALVEWWF WELDED WIRE FABRICWWM WELDED WIRE MESH

    OD OUTSIDE DIAMETEROD OVERFLOW DRAINOFCI OWNER FURNISHED,

    CONTRACTOR INSTALLEDOFF OFFICEOFOI OWNER FURNISHED,

    OWNER INSTALLEDOH OVERHEADOPNG OPENINGOPP OPPOSITEORD OVERFLOW ROOF DRAINP PAINTPAV PAVINGPBD PARTICLE BOARDPC PRECASTPDF POWER DRIVEN FASTENERPERF PERFORATEDPERIM PERIMETERPERP PERPENDICULARPI. PLATEPLAM PLASTIC LAMINATEPLAS PLASTERPLBG PLUMBINGPLF POUNDS PER LINEAR FOOTPLYWD PLYWOODPNL PANELPNT PAINT OR PAINTEDPOL POLISHEDPR PAIRPREFAB PREFABRICATEDPROJ PROJECTPSF POUNDS PER SQUARE

    FOOTPT POINTPT PRESSURE TREATEDPTD PAINTEDPTN PARTITIONPVC POLYVINYL CHLORIDEQT QUARRY TILEQTY QUANTITYR RADIUS/RISERRA RETURN AIRRAD RADIUSRB RESILIENT BASERBR RUBBERRCP REFLECTED CEILING PLANRD ROOF DRAINREC RECESSEDRECPT RECEPTACLEREF REFERENCEREFR REFRIGERATORREG REGISTERREINF REINFORCED

    REINFORCINGREINF REINFORCEDREL RELOCATEREM REMOVABLEREOOM RECOMMENDEDREQ REQUIRE/REQUIREDREQD REQUIREDRESIL RESILIENTREV REVISION/REVISEDRM ROOMRO ROUGH OPENINGRTD RATEDRTG RATINGRWL RAIN WATER LEADERS SOUTHSA SUPPLY AIRSAF SELF ADHERED FLASHINGSC SOLID CORESCHED SCHEDULESD STORM DRAINSECT SECTIONSF SQUARE FEET/FOOTSH SPRINKLER HEADSHR SHOWERSHT SHEETSIM SIMILARSM SHEET METALSM SURFACE MOUNTEDSP STANDPIPESPEC SPECIFICATIONSPEC SPECIFIED OR

    SPECIFICATIONSPK SPRINKLER OR SPEAKERSPKR SPEAKERSQ SQUARESS STAINLESS STEELSSK SERVICE SINKSTA STATIONSTC SOUND TRANSMISSION

    COEFFICIENTSTL STEELSTOR STORAGESTRG STRINGERSTRUCT STRUCTURALSTRUCT STRUCTURE OR

    STRUCTURALSUBCAT SUBCATEGORYSUSP SUSPENDEDSYM SYMMETRICALSYS SYSTEMT TREADT&B TOP AND BOTTOMT&G TONGUE AND GROOVETB TOWEL BARTEL TELEPHONE/TELECOMTELE TELEPHONETEMP TEMPERATURETEMP TEMPORARYTHK THICKNESSTHRU THROUGHTKBD TACK BOARDTLT TOILETTMPD TEMPEREDTO TOP OFTOB TOP OF BEAMTOC TOP OF CONCRETETOS TOP OF STEELTS TUBE STEELTV TELEVISION

    EQUIP EQUIPMENTEXH EXHAUSTEXIST EXISTINGEXP EXPANSIONEXT EXTERIORFA FIRE ALARMFB FACE BRICKFD FLOOR DRAINFD FLOOR DRAIN OR FIRE

    DEPARTMENTFDC FIRE DEPARTMENT

    CONNECTIONFE FIRE EXTINGUISHERFEC FIRE EXTINGUISHER

    CABINETFF&E FURNITURE, FIXTURES AND

    EQUIPMENTFFB FLUSH FLOOR BOXFFEL FINISH FLOOR ELEVATIONFH FLAT HEADFHC FIRE HOSE CABINETFIN FINISHFIXT FIXTUREFLASH FLASHINGFLR FLOORFLUOR FLUORESCENTFND FOUNDATIONFO FACE OFFP FIRE PROTECTIONFPG FIREPROOFINGFR FIRE RESISTANTFRC FIBER REINFORCED

    CONCRETEFRT FIRE RETARDANT TREATEDFT FEET/FOOTFTG FOOTINGFURN FURNITUREFURR FURRINGFWC FABRIC WALL COVERINGFWP FABRIC WRAPPED PANELGA GAUGEGALV GALVANIZEDGB GRAB BARGC GENERAL CONTRACT(OR)GEN GENERALGFRC GLASS FIBER REINFORCED

    CONCRETEGL GLASSGLAZ GLAZINGGRAN GRANULARGRD GROUNDGRFG GLASS FIBER REINFORCED

    GYPSUMGSM GALVANIZED SHEET METALGV GAS VALVEGWB GYPSUM WALL BOARDGYP GYPSUMH HIGH/HEIGHTHB HOSE BIBHB HOSE BIBBHC HANDICAPPEDHDWD HARDWOODHDWR HARDWAREHGT HEIGHTHM HOLLOW METALHNDRL HANDRAILHO HOLD OPENHORIZ HORIZONTALHR HOURHRC HOSE REEL CABINETHTG HEATINGHVAC HEATING VENTILATION AND

    AIR CONDITIONINGHW HOT WATERID INSIDE DIAMETERIN INCH/INCHESINCAND INCANDESCENTINCL INCLUDED/INCLUDINGINFO INFORMATIONINSUL INSULATIONINSUL INSULATED OR INSULATIONINT INTERIORINTERM INTERMEDIATEINV INVERTJAN JANITORJC JANITOR'S CLOSETJST JOISTJT JOINTKIT KITCHENKO KNOCK OUTLAM LAMINATELAV LAVATORYLB POUNDSLLH LONG LEG HORIZONTALLLV LONG LEG VERTICALLT LIGHTMAS MASONRYMAX MAXIMUMMECH MECHANICALMED MEDIUMMEMBR MEMBRANEMFR MANUFACTURERMH MAN HOLEMIN MINIMUMMISC MISCELLANEOUSMO MASONRY OPENINGMR MOISTURE RESISTANTMTD MOUNTEDMTG MOUNTINGMTL METALMULL MULLIONN NORTHNA NOT APPLICABLENC NOISE CRITERIANIC NOT IN CONTRACTNO NUMBERNOM NOMINALNONCOMB

    NON COMBUSTIBLE

    NTS NOT TO SCALEOA OUTSIDE AIROC ON CENTER

    & AND@ ATAB ANCHOR BOLTABC AGGREGATE BASE

    COURSEABI ADDITIVE BID ITEMAC AIR CONDITIONINGACC ACCESSIBLEACOUST ACOUSTICALACT ACOUSTIC CEILING TILEAD AREA DRAINADJ ADJUSTABLEAFF ABOVE FINISHED FLOORAFG ABOVE FINISHED GRADEAGGR AGGREGATEALT ALTERNATEALUM ALUMINUMANOD ANODIZEDAP ACCESS PANELAPC ACOUSTICAL PANEL

    CEILINGAPPROX APPROXIMATEARCH ARCHITECTURALASPH ASPHALTATTN ATTENTIONAUTO AUTOMATICAV AUDIOVISUALBD BOARDBET BUILDING ENTRANCE

    TERMINALBFF BELOW FINISHED FLOORBIT BITUMINOUSBL BASELINEBLDG BUILDINGBLK BLOCKBLKG BLOCKINGBM BEAM, BENCHMARKBO BOTTOM OFBOS BOTTOM OF STEELBOT BOTTOMBRG BEARINGBRK BRICKBRKT BRACKETBSMNT BASEMENTBUR BUILT-UP ROOFINGC CONDUITCA COMPRESSED AIRCAB CABINETCAT CATEGORYCB CATCH BASINCB CEMENT BOARDCBU CEMENTITIOUS BACKER

    UNITCC CENTER TO CENTERCCTV CLOSED CIRCUIT

    TELEVISIONCEM CEMENTCER CERAMICCG CORNER GUARDCH CHILLERCI CAST IRONCIP CAST-lN-PLACECJ CONTROL JOINTCL CENTERLINECLG CEILINGCLKG CAULKINGCLR CLEARCNTR COUNTERCO CLEANOUTCOL COLUMNCONC CONCRETECOND CONDITIONCONN CONNECTIONCONST CONSTRUCTIONCONT CONTINUOUSCONTR CONTRACTORCOORD COORDINATECORR CORRIDORCPT CARPETCT CERAMIC TILECTR CENTERCTSK COUNTERSUNKCW COLD WATERD DEEP, DEPTHDBL DOUBLEDEG DEGREEDEMO DEMOLISH OR DEMOLITIONDEMO DEMOLITIONDEPT DEPARTMENTDF DRINKING FOUNTAINDIA DIAMETERDIFF DIFFUSERDIM DIMENSIONDIMS DIMENSIONSDISP DISPENSERDIV DIVISIONDMPF DAMP PROOFINGDN DOWNDO DOOR OPENINGDR DOORDRN DRAINDS DOWNSPOUTDS DOWN SPOUTDTL DETAILDW DISHWASHERDWG DRAWINGDWR DRAWERCMU CONCRETE MASONRY UNITE EASTEA EACHEB EXPANSION BOLTEJ EXPANSION JOINTEL ELEVATIONELEC ELECTRICALELEV ELEVATOREMER EMERGENCYENCL ENCLOSUREENG ENGINEEREP ELECTRICAL PANELEPDM ETHYLENE PROPYLENE

    DIENE M-CLASSEQ EQUAL

    A. THE CONTRACTOR SHALL BE RESPONSIBLE FOR VERIFYING THE EXISTENCE AND LOCATION OF ALL UNDERGROUND OR CONCEALED UTILITIES IN ADVANCE OF ANY CONSTRUCTION. THE CONTRACTOR IS RESPONSIBLE TO HIRE A PRIVATE UTILITY LOCATING SERVICE TO LOCATE ALL UNDERGROUND UTILITIES ON OR NEAR THE PROJECT SITE.

    B. CONTRACTOR SHALL BE RESPONSIBLE FOR VERIFYING ANY OR ALL EXISTING CONDITIONS PRIOR TO THE START OF CONSTRUCTION. ANY UTILITIES FOUND TO BE IN THE WAY OF THE NEW CONSTRUCTION SHALL BE REMOVED, RELOCATED OR REPLACED AS DIRECTED. REFER TO PLUMBING, ELECTRICAL, MECHANICAL AND/OR CIVIL PLANS FOR SPECIFIC REQUIREMENTS.

    C. IT SHALL BE THE CONTRACTORS RESPONSIBILITY TO REMOVE ALL ABANDONED (RETIRED) UTILITIES THAT INTERFERE WITH THE CONSTRUCTION PROJECT. THE CONTRACTORS AND LOCAL UTILITY AND TRAFFIC CREWS SHALL COORDINATE WORK SCHEDULES SO AS TO PREVENT ANY CONFLICTING WORK CONDITIONS.

    D. CONTRACTOR SHALL REPAIR ANY AND ALL UTILITIES DAMAGED DURING THE COURSE OF CONSTRUCTION IN ACCORDANCE WITH LOCAL SPECIFICATIONS, AT NO ADDITIONAL COST.

    E. CONTRACTOR TO NOTIFY "BLUE STAKE" @ 1-800-782-5348, AT LEAST 48-HOURS IN ADVANCE OF ANY EXCAVATION. UTILITY LOCATIONS SHALL BE COORDINATED WITH THE ARCHITECT.

    F. THE CONTRACTOR IS RESPONSIBLE FOR THE REMOVAL AND DISPOSAL OF ANY DEBRIS RESULTING FROM THE DEMOLITION AND CONSTRUCTION. AT NO TIME SHALL ANY OF THIS MATERIAL OBSTRUCT THE NORMAL OPERATION.

    G. CONTRACTOR SHALL BE RESPONSIBLE FOR THE REMOVAL OF ANY OR ALL EXCESS EXCAVATION AND CONSTRUCTION RELATED DEBRIS, AT THE END OF EACH WORK DAY.

    H. THE CONTRACTOR IS ADVISED THAT DAMAGE TO ANY PORTION OF THIS PROJECT'S BUILDING(s) & SURROUNDING AREA AS A RESULT OF THIS PROJECT IS TO BE REPAIRED AT THE CONTRACTOR'S EXPENSE.

    I. IT IS THE CONTRACTOR'S RESPONSIBILITY TO INSPECT THE JOB SITE TO FAMILIARIZE HER/HIM SELF WITH ALL THE EXISTING CONDITIONS THAT COULD AFFECT THE INSTALLATION OF ANY WORK SET FORTH IN THESE PLANS.

    J. THE JOB SITE, AT THE COMPLETION OF CONSTRUCTION, SHALL BE CLEANED OF ANY DEBRIS OR SPOILS RESULTING FROM THE CONSTRUCTION.

    K. THE CONTRACTOR IS RESPONSIBLE TO FIELD VERIFY ALL EXISTING RECORDED DIMENSIONS INDICATED AND ALL EXISTING CONDITIONS THAT IMPACT NEW CONSTRUCTION.

    L. THE CONTRACTOR SHALL ESTABLISH ALL QUANTITIES BASED ON ACTUAL CONDITIONS. THESE DRAWINGS ARE NOT TO BE SCALED.

    M. COMPLY WITH ALL APPLICABLE CODES, RULES AND REGULATIONS. OBTAIN AND PAY FOR ALL PERMITS AND LICENSES REQUIRED.

    N. THE CONTRACTOR SHALL NOTIFY THE ARCHITECT AT LEAST 72 HOURS IN ADVANCE OF ANY CONSTRUCTION THAT REQUIRES SPECIAL/REQUIRED INSPECTION(s).

    O. REFERENCE ALL ARCHITECTURAL & ELECTRICAL SHEETS FOR SCOPE OF WORK & COORDINATION.

    P. ALL MATERIALS REQUIRED SHALL BE OF A GRADE AND QUALITY CONSISTENT WITH THE INTENDED USE AS SPECIFIED & APPROVED BY THE ARCHITECT.

    Q. ALL EQUIPMENT OR MATERIALS NOT SHOWN OR SPECIFIED ON THE PLANS OR IN THE SPECIFICATIONS, BUT ARE REQUIRED TO COMPLETE THE INSTALLATION SHALL BE SUPPLIED BY THE CONTRACTOR AS PART OF THE CONTRACT WORK.

    R. FIRE LANES SHALL BE MAINTAINED IN A CONDITION TO ASSURE ACCESS TO ALL BUILDINGS DURING CONSTRUCTION.

    S. SMOKING, ALL TOBACCO PRODUCTS & ELECTRONIC CIGARETTES ARE PROHIBITED ON THIS SITE.

  • ++

    +

    +

    ++

    +

    +++

    SITERESIDENTPAD 18.0

    D

    A

    1. COORDINATE WITH CIVIL AND STRUCTURAL.

    2. COORDINATE MATERIAL DELIVERIES WITH THE SCHOOL SCHEDULE.

    3. MAINTAIN SITE DRAINAGE.

    4. SCHOOL WILL BE IN SESSION DURING THIS PROJECT.

    general notes

    FUTURE FIELD

    EXISTING FIELD

    ANDRADAPOLYTECHNICHIGH SCHOOL

    PANTANO HIGH SCHOOL

    ANDRADAPOLYTECHNICADDITION

    HO

    UG

    HTO

    N R

    D.

    TENNIS COURTS

    CONTRACTOR ACCESS POINT

    CONTRACTOR YARD AND PROJECT ACCESS1. 5'-0" H CHAINLINK FENCE REQUIRED2. REPAIR TO PREVIOUS CONDITION3. REPAIR CONCRETE CURBS AS NECESSARY

    1

    2

    2 3

    3333

    H

    S.

    MARK E.

    EG

    RA

    R

    NZI O U.A

    BOLLARD

    23459

    ISDET ER

    ARC

    CE

    A.

    T

    IT

    N

    TACIFI

    AD

    DENGS

    TE

    I

    R

    CET E

    O.

    job

    date

    revisions

    7350 EAST SPEEDWAY 210TUCSON, ARIZONA 85710

    (520) 326-3700(520) 326-1148

    www.swaimaia.com

    OFFICEFAX

    ASSOCIATES LTDARCHITECTS AIA

    /

    /

    10/1

    5/20

    19 9

    :09:

    23 A

    MC

    :\Act

    ive

    Rev

    it Pr

    ojec

    ts\1

    817.

    02 A

    ndra

    da H

    igh

    Scho

    ol F

    ield

    & C

    ourt

    Ligh

    ting_

    jsey

    mou

    r.rvt

    x1.0

    site

    pla

    nAn

    drad

    a Po

    lyte

    chni

    c Hi

    gh S

    choo

    lBo

    nd Im

    prov

    emen

    t Pro

    ject

    sFi

    eld

    & Co

    urt L

    ight

    ing

    1296

    0 S.

    Hou

    ghto

    n Rd

    , Tuc

    son,

    AZ

    8574

    7

    10.15.19

    1817.02

    1510

    19

    keynotes1 PAINT NEW WALL MOUNTED CONDUIT TO MATCH WALL.2 REMOVE & REPLACE CONCRETE SIDEWALK, JOINT TO JOINT,

    TO ALLOW INSTALLATION OF NEW CONDUIT.3 AFTER INSTALLATION OF CONDUIT, RAKE OUT AREA.

    SUPPLEMENT DECOMPOSED GRANIT TO MATCH EXISTING.

    nort

    h1" = 60'-0"x1.01 reference site plan

  • keynotes

    fee

    de

    r dia

    gra

    m &

    ca

    lcu

    lati

    ons

    LOAD CALCULATIONS

    (E) PANEL H1A

    (E) TRANSF. T1

    (E) PANEL H2A

    =

    =

    =

    SUB-TOTAL =

    148A

    150A

    470A

    2730A

    ABC∅

    19A

    0A

    63A

    195A

    NEUTRAL

    (E) SERVICE ENTRANCE 'SES' 277/480V-3 -4W∅

    'SES' DEMAND CALC. (SCHOOL)

    2730A x (480V x 1.73) = 2269 KVA

    2269 KVA / 120,453 S.F. = 18.8 VA/SF

    3.0 VA/SF @ 100% x 120,453 SF

    15.8 VA/SF @ 75% x 120,453 SF

    TOTAL DEMAND LOAD

    =

    =

    =

    362 KVA

    1427 KVA

    1789 KVA

    1789 KVA / (480V x 1.73) = 2152 A

    (E) PANEL H3A = 500A 22A

    (E) PANEL H4A = 236A 12A

    (E) PANEL H5A = 211A 11A

    (E) PNL PHA - PANTANO H.S. = 291A 18A

    (E) WASTEWATER PLANT = 41A 0A

    =

    =

    (E) ON-SITE MODULAR HOME = 78 A

    SERVICE TOTAL = 2230 A

    (E) PANEL H6A 381A 26A

    (E) PANEL H7A 86A 11A

    EXISTING 2500A SERVICE IS ADEQUATE.

    TVSS 250 250 250 400 600 600

    400

    SPACE

    (E) SES

    2500A, 277/480V, 65KAIC

    EATON TYPE POW-R-LINE C

    (E) TEP

    REVENUE

    (E)

    TO

    SO

    LAR

    PO

    WER S

    YSTEM

    METER

    100 90

    GB

    N

    W

    (E)

    MO

    D.

    HO

    ME

    (E)

    WASTEW

    ATER

    TREATM

    EN

    T P

    LAN

    T

    200 500

    (E) TO POWER CO. TRANSF.

    PARALLEL 9 SETS OF

    3-#500KCMIL (AL) ØABC &

    1-#350KCMIL (AL) NEUTRAL

    XHHW-2, 4"C.

    (E)

    PAN

    TAN

    O H

    .S.

    CAM

    PU

    S

    (E)

    PAN

    EL 'H

    1A'

    (E)

    TRAN

    SF. 'T

    1'

    (E)

    PAN

    EL 'H

    5A'

    (E)

    PAN

    EL 'H

    4A'

    (E)

    PAN

    EL 'H

    2A'

    (E)

    PAN

    EL 'H

    3A'

    (E)

    PAN

    EL 'H

    7A'

    (E)

    PAN

    EL 'H

    6A'

    =(E) PANEL H8A 112A 13A

    FAULT CURRENT CALCULATIONS

    1+0.255

    1= 0.255, m = = 0.797FAULT #1: f =

    1.73 x 52,400 x 260

    9 x 21395 x 480

    FAULT #1 = 52,400A x 0.80 + (MOTORS = 5,000A) + SOLAR

    POWER SYSTEM BACKFEED 2,500A MAX. = 49,241A

    'SES'

    6

    5

    4

    7

    1+9.159

    1= 9.159, m = = 0.098FAULT #2: f =

    1.73 x 49,241 x 663

    12862 x 480

    FAULT #2 = 49,241A x 0.098 = 4,847A

    'H9A'

    H9A

    NEW EATON TYPE PRL3A

    X X

    X 18KAIC, MINIMUM

    277/480V-3Ø-4W

    200A BREAKER

    21401 28901 28901

    79 KVA 104 AMPS

    18194441

    18194441

    TENNIS COURT POLE LT SOCCER FIELD POLE LT

    (5.25 FLA) "

    "18194441

    "

    "

    "

    "

    "

    " 3

    203 10 8 1

    "

    "

    "

    "

    "

    "

    "

    "

    3 10 8 1

    (12.82 FLA)

    "

    SPACE - - - -

    SPACE - - - -

    SPACE - - - -

    SPACE - - - -- - - ---

    200

    200A

    SPACE

    200A

    SPACE

    (E)

    PRESEN

    TATIO

    N

    HALL P

    AN

    EL H

    8A

    200A/3P

    =NEW PANEL H8A 104A 0A

    job

    date

    revisions

    (520) 326-3700(520) 326-1148

    OFFICEFAX

    1817.02

    10- 0

    3-1

    9

    EDG-WEST, INC.

    Web Site: www.edg-ce.com

    CONSULTING ELECTRICAL ENGINEERS

    schematic feeder wiring diagramn.t.s.

    1e1.1 NOTE: ALL FEEDERS, PANELS & SES ARE EXISTING,

    EXCEPT FOR NEW ATHLETIC FIELD LIGHTING

    ADDITION.

    NEW PULL BOX, REFER TO

    REFERENCE PLAN, SHEET E2.0

    FOR LOCATION.

    PANEL

    'H9A'

    277/480V

    3Ø-4W

    PANEL

    'L9A'

    120/240V

    1Ø-3W

    3-#250KCMIL (AL) ØABC,1-#1 (AL) NEUTRAL & 1-#4(AL) EG, ALL TYPE XHHW-2COMPACT STRANDED,2.5"C.

    FIELD LIGHTING BRANCHCIRCUITS, SEE SCHEDULE

    GB

    N

    9

    87

    2

    115KVA

    FIELD

    LIGHTING

    CONTROL

    AND

    MONITORING

    CABINET

    (2) #6 CU(1) #10 CU GND3/4" C

    1. GROUND BAR BONDED TO BOX.

    2. INSULATED NEUTRAL BAR. DO NOT GROUND THE NEUTRAL

    IN THIS PANEL.

    3. GROUND THE SECONDARY NEUTRAL IN TRANSFORMER PER

    NEC 250.30.

    4. (E) #500 (CU) MAIN BONDING JUMPER.

    5. (E) #3/0 (CU) BOND TO METALLIC PIPING.

    6. (E) #3/0 (CU) BOND TO METAL BLDG. FRAME.

    7. (E) #4 (CU) UFER GROUND.

    8. #2 (CU) GROUND TO BUILDING STEEL FRAME.

    9. #2 (CU) BOND TO METALLIC PIPING.

    10. NEW TRANSFORMER T-8 SHALL BE 480V DELTA TO

    208Y/120V, 3Ø-4W, K-4 RATED, (CU) OR (AL) WINDINGS,

    NEMA 1 ENCLOSED 150 DEGREE C TEMP RISE, DOE 2016

    RATED. KVA RATING AS NOTED., MIN. 3%Z.

    TO FIELD LIGHTING. REFERTO SHEET E2.0 FOR POLELOCATIONS AND FEEDER

    INFORMATION

    ADD NEW EATON

    65KAIC BREAKER IN

    EXISTING SERVICE

    ENTRANCE FEEDER

    SECTION.

    "

    TENNIS COURT POLE LT

    (5.25 FLA) "

    "

    "

    "

    "

    "

    "

    " 3

    203 10 8 1

    "

    18194441

    18194441

    18194441

    -4441

    -4441

    -4441

    -4441

    -4441

    -4441

    SPACE - - - -

    SPACE - - - -

    SPACE - - - -

    SPACE

    3

    20

    SOCCER FIELD POLE LT

    (12.82 FLA)

    "3

    20

    SOCCER FIELD POLE LT

    (12.82 FLA)

    "3

    20

    SOCCER FIELD POLE LT

    (12.82 FLA)

    "3

    20

    --

    --

    --

    --

    --

    --

    -7500

    -7500

    SPACE - - - -

    SPACE - - - -

    SPACE - - - -

    SPACE - - - -

    SPACE - - - -

    SPACE - - - -

    SPACE - - - -

    SPACE - - - -

    - - - -

    - - - -

    SPACE

    SPACE

    - - - -

    - - - -

    - - - -

    SPACE

    SPACE

    SPACE

    "

    "

    "

    "

    "

    "

    "

    "

    3 10 8 1

    "

    "

    "

    "

    "

    "

    "

    "

    3 10 8 1

    "

    "

    "

    "

    "

    "

    "

    "

    3 10 8 1

    PANEL L9A

    (15KVA ESTIMATED LOAD)" " " "

    2 6 10

    7

    INDICATES CONTINUOUS DUTY LOAD AT 125% DEMAND

    TOTAL VOLT-AMPS

    41

    37

    39

    35

    27

    31

    33

    29

    25

    21

    23

    19

    15

    17

    9

    11

    13

    40

    42

    38

    36

    34

    20

    32

    28

    30

    26

    22

    24

    14

    16

    18

    8

    10

    12

    FLUSH

    PANEL

    CIRCUIT DESCRIPTION

    TYPE

    SURFACE

    NO.BRKR

    3

    1

    5

    CIRCUIT

    ΦA

    CIRCUIT DESCRIPTION

    SHORT CIRCUIT RATING:

    BRKR

    CIRCUIT

    VOLTAGE

    BUS

    NO.

    4

    2

    6

    ΦB ΦC MAINNEMA 1 NEMA 3R

    FULLY RATED SERIES RATED

    NEUTRAL = 0A

    7

    INDICATES CONTINUOUS DUTY LOAD AT 125% DEMAND

    TOTAL VOLT-AMPS

    27

    29

    25

    21

    23

    19

    15

    17

    9

    11

    13

    20

    28

    30

    26

    22

    24

    14

    16

    18

    8

    10

    12

    FLUSH

    PANEL

    CIRCUIT DESCRIPTION

    TYPE

    SURFACE

    NO.BRKR

    3

    1

    5

    CIRCUIT

    ΦA

    CIRCUIT DESCRIPTION

    SHORT CIRCUIT RATING:

    BRKR

    CIRCUIT

    VOLTAGE

    BUS

    NO.

    4

    2

    6

    ΦB MAINNEMA 1 NEMA 3R

    FULLY RATED SERIES RATEDL8A

    NEW SQUARE D 15KVA MINI-POWER ZONE

    X X

    X

    60A

    SECONDARY: 120/240V-1 -3W∅

    PRIMARY: 480V-1∅

    SEC: 60A M.B.PRI: 60A M.B.

    14KAIC, SEE BELOW

    2 3/412 12 REC-TENNIS COURT

    2 3/412 12 REC-TENNIS COURT

    120

    120

    2

    80BACK-FED MAIN BREAKER

    120

    120

    120

    120

    SPARE

    SPARE

    SPARE

    SPARE

    SPACESPACE

    SPACE

    SPACE

    SPACE

    SPACE

    SPACESPACE

    SPACESPACE

    SPACESPACE

    SPACESPACE

    SPACESPACE

    SPACESPACE

    SPACESPACE

    SPACESPACE

    -1000

    1000

    7500 7500

    15 KVA 63 AMPS

    MAX POSSIBLE LOADING INCLUDING FUTURE

    AIC RATING IS THE HIGH VOLTAGE (480V) BREAKER SHORT CIRCUIT RATING. THE MINI POWER CENTER IS RATED BY THE MANUFACTURERTO USE 10KAIC RATED 120/240V BRANCH CIRCUIT BREAKERS. (FAULT ON L.V. SIDE IS LIMITED BY TRANSFORMER IMPEDANCE.)

    PANEL HAS INTEGRAL 15KVA TRANSFORMER

    2

    60

  • (E) SERVICE ENTRANCE 'SES'

    T2

    T1

    S2

    S4

    S3

    34

    3

    3

    5

    FUTURE RESTROOM BUILDING

    PB

    6

    4

    6

    NEW PANEL 'H9A'

    NEW PANEL L9A'

    FIELD LIGHTING CONTROL

    AND MONITORING CABINET

    L9A-2

    L9A-4

    2 1

    S1 S1

    S2

    H9A-1,3,5

    H9A-1,3,5

    H9A-7,9,11

    H9A-7,9,11 H9A-2,4,6

    H9A-8,10,12

    H9A-14,16,18

    H9A-20,22,24

    WP WP

    WP WP

    7

    7

    no

    rth

    refe

    ren

    ce

    ele

    ctr

    ica

    l pla

    n

    job

    date

    revisions

    (520) 326-3700(520) 326-1148

    OFFICEFAX

    1817.02

    10- 0

    3-1

    9

    EDG-WEST, INC.

    Web Site: www.edg-ce.com

    CONSULTING ELECTRICAL ENGINEERS

    A. COORDINATE WITH OWNER SO THAT WORK CAN BE SCHEDULED NOT TO

    INTERRUPT OPERATIONS, NORMAL ACTIVITIES, BUILDING ACCESS, ACCESS

    TO DIFFERENT AREAS.

    B. COORDINATE THE EXACT LOCATION OF EXISTING UTILITIES AND

    EQUIPMENT PRIOR TO COMMENCEMENT OF WORK.

    C. MAINTAIN ELECTRICAL CONTINUITY OF EXISTING SYSTEMS.

    keynotes

    1. ROUTE FEEDERS FROM TOP OF SERVICE ENTRANCE ENCLOSURE,

    TIGHT TO BOTTOM OF STRUCTURE, TO EXTERIOR WALL.

    2. CONTINUE CONDUIT FROM EXTERIOR WALL PENETRATION, DOWN

    WALL, AND ROUTE UNDERGROUND TO NEW ELECTRICAL PANEL.

    3. PROVIDE (3)#10, (1)#8 GROUND IN 1"CONDUIT.

    4. (6)#10, (1)#8 GROUND IN 1.25" CONDUIT.

    5. PROVIDE (2) SEPARATE CONDUIT RUNS OF

    (6)#10, (1)#8 GROUND IN 1.25"CONDUIT.

    6. PROVIDE (3)#10, (1)#8 GROUND IN 1"CONDUIT.

    7. MOUNT ON WEATHERPROOF UNISTRUT WITH VANDAL RESISTANT

    HARDWARE.

    general notes

    1e2.0

    reference electrical plan1" = 30'-0"

  • ele

    ctr

    ica

    l le

    gend &

    refe

    ren

    ce

    pla

    ns

    job

    date

    revisions

    (520) 326-3700(520) 326-1148

    OFFICEFAX

    1817.02

    10- 0

    3-1

    9

    EDG-WEST, INC.

    Web Site: www.edg-ce.com

    CONSULTING ELECTRICAL ENGINEERS

    ELECTRICAL SYMBOLS

    SERVICE, ETC. TO AND CONNECT AS SHOWN AND/OR AS REQUIRED.

    MAGNETIC STARTER CONTROLS MOUNTED IN SECTION (SIZE AS NOTED).

    MAGNETIC STARTER CONTROLS ETC. FURNISHED WITH EQUIPMENT, CONNECT

    SPECIAL OUTLET - PROVIDE OUTLET, ASSEMBLE AND MAKE ALL EQUIPMENT

    FUSTAT HOLDER WITH FUSTAT, ADAPTER AND SWITCH OR RECEPTACLE

    DUPLEX CONVENIENCE RECEPTACLE - GROUND FAULT CIRCUIT INTERRUPTING.

    DUPLEX CONVENIENCE RECEPTACLE MOUNTED UNDER COMMON COVER

    TOGGLE SWITCHES - SINGLE POLE, DOUBLE POLE, 3-WAY AND 4-WAY.

    LIGHT FIXTURE OUTLET - CEILING (LETTER INDICATES FIXTURE TYPE).

    CONNECTIONS AS REQUIRED.

    STUB-OUT CONDUIT TO LOCATION AS INDICATED. (IF NOT INDICATED STUB

    TELEPHONE TERMINAL BOARD. 4' X 4' (OR SIZE AS NOTED) 3/4-INCH

    FURNISHED BY OTHERS, ELECTRICAL CONTRACTOR TO INSTALL AND PROVIDE

    T

    WP WEATHERPROOF. (NEMA 3R)

    BC BARE COPPER.

    UG UNDERGROUND.

    CWR CONTROL WIRING AS REQUIRED.

    NL NIGHT LIGHT.

    EDF ELECTRIC DRINKING FOUNTAIN.

    RESPECTIVELY. WHEN NO TICK MARKS SHOWN PROVIDE TWO

    CIRCUIT RUN IN OR UNDER FLOOR.

    AS REQUIRED.

    MAGNETIC STARTER AS NOTED.

    DISCONNECT SWITCH, FUSED (PLAN).

    DISCONNECT SWITCH, NON-FUSED (PLAN).

    CEILING MOUNTED EXHAUST FAN.

    WALL MOUNTED EXHAUST FAN.

    THERMOSTAT OUTLET.

    AS REQUIRED TO MAKE EQUIPMENT CONNECTION.

    FLOOR TELEPHONE OUTLET.

    TELEPHONE/DATA OUTLET ROUGH-IN, SINGLE GANG OUTLET AT RECEPTACLE

    FLOOR DUPLEX RECEPTACLE.

    DUPLEX CONVENIENCE RECEPTACLE WITH ISOLATED GROUND.

    DUPLEX CONVENIENCE RECEPTACLE FLUSH CEILING MOUNTED.

    MANUAL MOTOR STARTER WITH MOTOR RUNNING OVERLOAD PROTECTION

    DUPLEX CONVENIENCE RECEPTACLE.

    DUPLEX CONVENIENCE RECEPTACLE WITH ONE HALF SWITCHED.

    QUADRAPLEX RECEPTACLE. (2-GANG BOX WITH 2 DUPLEX RECEPTACLES.)

    MULTI-OUTLET ASSEMBLY (WIREMOLD PLUGMOLD 2100, U.N.O.).

    LIGHT TRACK AND FIXTURE (LETTERS INDICATE FIXTURE TYPES).

    STRIP LIGHT FIXTURE (LETTER INDICATES FIXTURE TYPE).

    TOGGLE SWITCH WITH PILOT LIGHT (LIGHT INDICATING ON).

    JUNCTION BOX.

    LIGHT FIXTURE OUTLET - WALL (LETTER INDICATES FIXTURE TYPE).

    LENSED LIGHT FIXTURE (LETTER INDICATES FIXTURE TYPE).

    CIRCUIT RUN IN CEILING OR WALL.

    CIRCUIT RUN TO PANEL, OR AS NOTED.

    GROUND EXTEND AND CONNECT TO APPROVED GROUND.

    TO ABOVE ACCESSIBLE CEILING INSIDE BUILDING OR UNDERGROUND IF

    DISCONNECT SWITCH-NON FUSED (SCHEMATIC).

    MOTOR OUTLET CONNECT AS REQUIRED.

    DENOTES NEUTRAL, CIRCUIT, OR SWITCHED OR TRAVELER CONDUCTORS,

    PANEL.

    NOT IN CONTRACT.

    NOT TO SCALE.

    UNLESS NOTED OTHERWISE.

    DISCONNECT SWITCH-FUSED (SCHEMATIC).

    TTB

    NIC

    NTS

    FBO

    UNO

    A

    B

    A

    AA

    A

    J

    P

    M

    2 3 4

    GFI

    J PM

    F

    F

    A

    J

    EXISTING(E) or EXIST

    EQUIPMENT GROUNDEG

    ISOLATED GROUND PER NEC 250.146 (D).IG

    CONDUCTORS. CONTRACTOR IS RESPONSIBLE TO PROVIDE CORRECT

    HEIGHT, STUB-OUT 3/4-INCH CONDUIT TO ABV. CLG., U.N.O.

    -SINGLE POLE, 2-POLE.

    TELEPHONE OUTLET ROUGH-IN, SINGLE GANG OUTLET AT RECEPTACLE HEIGHT,

    U.N.O. STUB-OUT 3/4-INCH CONDUIT TO ABV. CLG., U.N.O. 'W' DENOTES W

    OUTSIDE OF BUILDING.)

    WITH ADJACENT DEVICE.

    A-C PLYWOOD WITH #6 BC GROUND TO MAIN ELECTRIC GROUND ELECTRODE.

    TELEVISION OUTLET, SINGLE GANG AT RECEPTACLE HEIGHT, STUB-OUT

    3/4-INCH CONDUIT TO ABV. CLG., U.N.O.

    GROUNDGND

    OR EXIT SIGN (CEILING MOUNT OR WALL MOUNT).XX

    DOUBLE-GANG BOX MOUNTED AT RECEPTACLE HEIGHT, STUB-OUT3/4-INCH CONDUIT TO ABV. CLG., OUTLETS AND WIRING BY OTHERS.

    2M

    OR

    DIAGONAL LINE INDICATES DEVICE IS MOUNTED AT ABOVE COUNTER HEIGHT.

    DN DOWN

    QUANTITY OF CONDUCTORS IN EACH CIRCUIT RUN.

    PROVIDE INSULATED/ISOLATED GROUND CONDUCTOR IN CIRCUIT PER

    NEC 250.146 (D).

    'WALL' TELEPHONE OUTLET +53" AFF.

    1817.02 Andrada High School Field & Court Lighting 10.15.19.pdfSheetsg1.0 - cover sheetg1.1 - abbreviations and symbolsx1.0 - site plan

    Electrical.pdfe2.1.pdfe2.0.pdfe1.1.pdf