ANALYSIS OF THE COMBUSTION FUMES AND GASES RELEASED DURING THE BURNING OF SOME C-SI PV MODULES Claudio Liciotti 1 , Piergiacomo Cancelliere 2 , Michele Cardinali 1 , Vincenzo Puccia 3 , 1 Brandoni Solare S.p.A., 2 Italian National Fire Services, Active Fire Protection Department 3 Italian National Fire Services, Padova Fire Services 29th European Photovoltaic Solar Energy Conference RAI Congress & Exhibition Centre, Amsterdam, The Netherlands September 23 rd , 2014

Upload: claudio-liciotti

Post on 04-Jul-2015

155 views

Category:

Environment


2 download

DESCRIPTION

Along with the strong growth of PV installations, also the number of fires involving PV systems has grown. The fire risk analysis due to PV systems has been taken into strong consideration. About that, 3 were the most considered issues: 1) PV modules and components fire behavior; 2) causes of fire ignition related to PV components; 3) risk of electrocution in firefighting activities in proximity to photovoltaic generators. To protect the firefighter and to respect the environment, the type of fumes and gases that are released into the environment during a fire of a PV system should also be considered. This paper shows the analysis of the fumes and gases released during the burning and pyrolysis of some c-Si PV modules.

TRANSCRIPT

Page 1: ANALYSIS OF THE COMBUSTION FUMES AND GASES RELEASED DURING THE BURNING OF SOME C-SI PV MODULES

ANALYSIS OF THE COMBUSTION FUMES AND GASES RELEASED DURING THE BURNING OF

SOME C-SI PV MODULES

Claudio Liciotti1, Piergiacomo Cancelliere 2, Michele Cardinali1, Vincenzo Puccia3,

1 Brandoni Solare S.p.A.,

2 Italian National Fire Services, Active Fire Protection Department

3 Italian National Fire Services, Padova Fire Services

29th European Photovoltaic Solar Energy Conference

RAI Congress & Exhibition Centre, Amsterdam, The Netherlands

September 23rd , 2014

Page 2: ANALYSIS OF THE COMBUSTION FUMES AND GASES RELEASED DURING THE BURNING OF SOME C-SI PV MODULES

Outline

• About Us• Introduction and motivation• Aim of the work• Analysis of combustion fumes - Cone Calorimeter coupled

to FTIR- Samples- Setup- Results

• Analysis of pyrolysis fumes – TGA coupled to FTIR- Samples- Setup- Results

• Conclusion• Acknowledgement

Page 3: ANALYSIS OF THE COMBUSTION FUMES AND GASES RELEASED DURING THE BURNING OF SOME C-SI PV MODULES

About Us

• Brandoni Solare S.p.A. is an Italian PV moduleproducer.

• Founded in 2007.• Current capacity 55MW/yr.• Focuses on PV modules design and production

(customized solutions).• R&D focus is on BIPV and PV module reliability.

Page 4: ANALYSIS OF THE COMBUSTION FUMES AND GASES RELEASED DURING THE BURNING OF SOME C-SI PV MODULES

Introduction and motivation

• Mechanical resistance and stability• Safety in case of fire• Hygiene, health and the environment• Safety in use• Protection against noise• Energy economy and heat retention

Residential Segment BIPV

Special requirements

DRAFT prEN 50583

Page 5: ANALYSIS OF THE COMBUSTION FUMES AND GASES RELEASED DURING THE BURNING OF SOME C-SI PV MODULES

Introduction and motivation

• Factors required for fire hazard assessment [1]

• PV modules are installed on the roof (outside thebuilding)

• During a PV system burning, the fire exposesfirefighters and other rescue personnel not only tothermal and to electrocution hazards, but also to thefumes.

[1] Anna A. Stec and T. Richard Hull, “Assessment of the fire toxicity of building insulation materials”, Energy and Buildings, 43 (2-3), pp. 498-506 (2011).

Fire Safety

Hazard

Structuralintegrity

Fire growrate

Firetoxicity Smoke

Risk

Materialignitability

IgnitionSources

Page 6: ANALYSIS OF THE COMBUSTION FUMES AND GASES RELEASED DURING THE BURNING OF SOME C-SI PV MODULES

Aim of the work

• The c-Si PV modules contain large amount of plasticmaterials that could also produce dangerous combustionproducts.

• Modules with different kind of raw materials wereanalyzed in:

- Cone Calorimeter coupled to FTIR; the aimof this test is analyze the fumes and gasesreleased during the combustion of c-Si PVmodules.- TGA coupled to FTIR to analyze the fumesand gases released during the pyrolysis of c-SiPV modules.

Page 7: ANALYSIS OF THE COMBUSTION FUMES AND GASES RELEASED DURING THE BURNING OF SOME C-SI PV MODULES

Analysis of combustion fumes - Cone Calorimeter coupled to FTIR - Samples• Samples for Cone Calorimeter coupled to FTIR

- Sample 1: EVA- Sample 2: TPO- Sample 3: EVA + PET/PET/Primer backsheet- Sample 4: EVA + PVF/PET/PVF backsheet- Sample 5: EVA +PA/PET/PA backsheet

• Samples dimensions 100 mm x 100 mm

• The plastic materials are laminated on a 4 mm glass

Page 8: ANALYSIS OF THE COMBUSTION FUMES AND GASES RELEASED DURING THE BURNING OF SOME C-SI PV MODULES

Analysis of combustion fumes - Cone Calorimeter coupled to FTIR - Setup

• Cone Calorimeter NoselabASTM E 1354/ ISO 5660.

• System well ventilated• Specimen combustion• Radiator pre-set 50 kW/m2

Page 9: ANALYSIS OF THE COMBUSTION FUMES AND GASES RELEASED DURING THE BURNING OF SOME C-SI PV MODULES

Analysis of combustion fumes - Cone Calorimeter coupled to FTIR - Setup

• The fumes are extracted from exhaust duct extraction bya probe

• The combustion fumes were analysed with FTIR (PerkinElmer Spectrum One).

Page 10: ANALYSIS OF THE COMBUSTION FUMES AND GASES RELEASED DURING THE BURNING OF SOME C-SI PV MODULES

Analysis of combustion fumes - Cone Calorimeter coupled to FTIR - Results• Sample 1 (EVA) – FTIR analysis

Page 11: ANALYSIS OF THE COMBUSTION FUMES AND GASES RELEASED DURING THE BURNING OF SOME C-SI PV MODULES

Analysis of combustion fumes - Cone Calorimeter coupled to FTIR - Results• Sample 2 (TPO) – FTIR analysis

Page 12: ANALYSIS OF THE COMBUSTION FUMES AND GASES RELEASED DURING THE BURNING OF SOME C-SI PV MODULES

Analysis of combustion fumes - Cone Calorimeter coupled to FTIR - Results• Sample 3 (EVA + PET/PET/Primer) – FTIR analysis

Page 13: ANALYSIS OF THE COMBUSTION FUMES AND GASES RELEASED DURING THE BURNING OF SOME C-SI PV MODULES

Analysis of combustion fumes - Cone Calorimeter coupled to FTIR - Results• Sample 4 (EVA + PVF/PET/PVF ) – FTIR analysis

Page 14: ANALYSIS OF THE COMBUSTION FUMES AND GASES RELEASED DURING THE BURNING OF SOME C-SI PV MODULES

Analysis of combustion fumes - Cone Calorimeter coupled to FTIR - Results• Sample 5 (EVA +PA/PET/PA) – FTIR analysis

Page 15: ANALYSIS OF THE COMBUSTION FUMES AND GASES RELEASED DURING THE BURNING OF SOME C-SI PV MODULES

Analysis of Pyrolysis fumes – TGA coupled to FTIR - Samples

• Samples for TGA coupled to FTIR- Sample 1: EVA- Sample 2: TPO- Sample 3: EVA + PET/PET/Primer backsheet- Sample 6: TPO+ PET/PET/Primer backsheet

• The sample was cut into small pieces, transferred into analumina crucible (Al2O3 - 85 μL) and placed into the TGA.

• Sample holder: standard sample carrier.

• Sample mass: 4-6 mg.

Page 16: ANALYSIS OF THE COMBUSTION FUMES AND GASES RELEASED DURING THE BURNING OF SOME C-SI PV MODULES

Analysis of Pyrolysis fumes – TGA coupled to FTIR - Setup

• TGA NETZSCH TG 209 F1 Libra® simultaneously coupledto the Agilent 7890A Gas chromatograph and theAgilent 5975 MSD („mass selective detector“) andcoupled to the BRUKER Optics FTIR TENSOR.

• Measure: Temperature-dependent mass change (TG),rate of mass change (DTG) and the Gram Schmidt, 3Dplot of all detected IR spectra.

Page 17: ANALYSIS OF THE COMBUSTION FUMES AND GASES RELEASED DURING THE BURNING OF SOME C-SI PV MODULES

Analysis of Pyrolysis fumes – TGA coupled to FTIR - Results

• Temperature-dependent mass change (TG), rate of masschange (DTG) and the Gram Schmidt curve of Sample 3(EVA + PET/PET/Primer)

Page 18: ANALYSIS OF THE COMBUSTION FUMES AND GASES RELEASED DURING THE BURNING OF SOME C-SI PV MODULES

Analysis of Pyrolysis fumes – TGA coupled to FTIR - Results

• Temperature-dependent mass change (TG), rate of masschange (DTG) and the Gram Schmidt curve of Sample 6(TPO+ PET/PET/Primer)

Page 19: ANALYSIS OF THE COMBUSTION FUMES AND GASES RELEASED DURING THE BURNING OF SOME C-SI PV MODULES

Analysis of Pyrolysis fumes – TGA coupled to FTIR - Results

• 3D plot of all detected IR spectra of Sample 1 (EVA)and Sample 3 (EVA + PET/PET/Primer) heated to1000 °C

Sample 1 Sample 3

Page 20: ANALYSIS OF THE COMBUSTION FUMES AND GASES RELEASED DURING THE BURNING OF SOME C-SI PV MODULES

Analysis of Pyrolysis fumes – TGA coupled to FTIR - Results

• 3D plot of all detected IR spectra of Sample 2 (TPO)and Sample 6 (TPO+ PET/PET/Primer) heated to1000 °C

Sample 2 Sample 6

Page 21: ANALYSIS OF THE COMBUSTION FUMES AND GASES RELEASED DURING THE BURNING OF SOME C-SI PV MODULES

Analysis of Pyrolysis fumes – TGA coupled to FTIR - Results

• Spectra comparison: Sample 1 - EVA (orange) andSample 3 - EVA + PET/PET/Primer (light blue) at370°C compared with the database spectrum of aceticacid (blue).

Sample 1

Sample 3

acetic acid

Page 22: ANALYSIS OF THE COMBUSTION FUMES AND GASES RELEASED DURING THE BURNING OF SOME C-SI PV MODULES

Analysis of Pyrolysis fumes – TGA coupled to FTIR - Results

• Spectra comparison: Sample 1 - EVA (green) at 170 °Ccompared with the database spectrum of dimethyl butane(blue).

Sample 1

dimethyl butane

Page 23: ANALYSIS OF THE COMBUSTION FUMES AND GASES RELEASED DURING THE BURNING OF SOME C-SI PV MODULES

Analysis of Pyrolysis fumes – TGA coupled to FTIR - Results

• Spectra comparison: Sample 1 - EVA (light green)Sample 2 - TPO (blue) and Sample 3 - EVA +PET/PET/Primer (black) at 480 °C compared with thedatabase spectrum of C25H52 (pink).

Sample 2 Sample 1 Sample 3

C25H52

Page 24: ANALYSIS OF THE COMBUSTION FUMES AND GASES RELEASED DURING THE BURNING OF SOME C-SI PV MODULES

Analysis of Pyrolysis fumes – TGA coupled to FTIR - Results

• Spectra comparison: Sample 3 - EVA +PET/PET/Primer (red) and Sample 6 – TPO +PET/PET/Primer (orange) at 820 °C compared with thedatabase spectrum of carbon dioxide (blue).

Sample 6

Sample 3

CO2

Page 25: ANALYSIS OF THE COMBUSTION FUMES AND GASES RELEASED DURING THE BURNING OF SOME C-SI PV MODULES

Conclusion

• The use of FTIR applied to the cone calorimeter allow toidentify only the outlet gasses produced by thecombustion as carbon monoxide (CO), and carbon dioxide(C02).

• FTIR applied to the cone calorimeter is not usefully tomake an analytical analysis of the materialsdecomposition

• The coupling of FTIR with TGA give a wide and usefulinformation about the degradation of the material duringthe pyrolysis. With this method is possible to identify thegasses produced at different temperature during thepyrolysis process.

Page 26: ANALYSIS OF THE COMBUSTION FUMES AND GASES RELEASED DURING THE BURNING OF SOME C-SI PV MODULES

Conclusion

• The polymers included in the PV modules have directeffect on combustion products toxicity.

• In case of an outbreak of a fire in a PV system, theVolatile Organic Compounds (VOCs) and carbon oxides(CO) released require, obviously, the breathingapparatus to be used by the rescue team memberswhile they are doing firefighting and rescue operations.

Page 27: ANALYSIS OF THE COMBUSTION FUMES AND GASES RELEASED DURING THE BURNING OF SOME C-SI PV MODULES

Acknowledgement

• The authors wish to thank Dr. Eng. Giovanni Longobardofor his help in setting up the PV module specimens andthe reaction to fire test rig.

• The authors wish also to thank the ThermoanalyticalSection of the NETZSCH Applications Laboratory for theirsupport in the test analysis.

Page 28: ANALYSIS OF THE COMBUSTION FUMES AND GASES RELEASED DURING THE BURNING OF SOME C-SI PV MODULES

Thank you for your attention

Brandoni Solare S.p.a.

Via O.Pigini, 860022 Castelfidardo (AN)

ITALY

@mail: [email protected]