Installation and Service Instructions for Contractors
6720
8198
41 (2
016/0
4) U
S
ANALOGIC 0-10 VDC INPUT DEVICE FOR BUDERUS SSB BOILERS
6720819841 (2016/04) US Analogic Device
2 | Key to symbols and safety instructions
1 Key to symbols and safety instructions . . . . . . . . . . . . . . 21.1 Key to symbols . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
2 Connection to the boiler . . . . . . . . . . . . . . . . . . . . . . . . 3
3 Use of the device for a single boiler application . . . . . . . . . 43.1 Central Heating with Analog Input Control of setpoint . . . .43.2 Central Heating with Analog Input Control of
Modulation Rate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
4 Use of the device for a cascade system . . . . . . . . . . . . . . 6
1 Key to symbols and safety instructions
1 .1 Key to symbolsWarnings
aaWarnings in this document are identified by a warning triangle printed against a grey background.Keywords at the start of a warning indicate the type and seriousness of the ensuing risk if measures to prevent the risk are not taken.
The following keywords are defined and can be used in this document:• DANGER indicates a hazardous situation which, if not avoided, will
result in death or serious injury.• WARNING indicates a hazardous situation which, if not avoided,
could result in death or serious injury.• CAUTION indicates a hazardous situation which, if not avoided,
could result in minor to moderate injury.• NOTICE is used to address practices not related to personal injury.
Important information
amThis symbol indicates important information where there is no risk to people or property.
Contents
Analogic Device 6720819841 (2016/04) US
Connection to the boiler | 3
2 Connection to the boilerIn the following figure is shown an overview of connectors and components.
Fig. 1 Connectors and components diagram
NOTICE: This control may be mounted remotely from the boiler. Please make sure this control is not subjected to high heat, excessive moisture, or dust. All wiring shall be accomplished by a licensed electrician according to Federal, State and/or local codes.
To connect the cables follow these instructions:• Connect the “Analog input” cable to the 0-10 VDC output device considering that the brown cable [brn] is for the positive.• Connect the “Link” cable to the terminal 1-2 of the boiler (“cascade link” connection, see the boiler installation manual for details)
considering that the polarity is NOT important.• Connect the “Supply” cable [Wire per National, Federal, State and/or local codes].
Code Description
J1 Receptacle / Connector with leads
J2 Receptacle [not used]J3 Receptacle [not used]J4 Receptacle [not used]J5 Receptacle [not used]
J5 Receptacle / Connector with leads
J7 Receptacle [not used]J8 Receptacle [not used]J9 Receptacle [not used]K1 RelayK2 RelayK3 RelayK4 RelayC3 CapacitorC4 CapacitorC8 CapacitorC10 CapacitorC22 CapacitorISO1 Opto-isolatorISO2 Opto-isolatorISO3 Opto-isolatorISO4 Opto-isolatorF1 Fuse [3.15 A]S4 SwitchT1 Transformer
Wire color legendblu Bluebrn Brownwh Whiteblk Blackgrn/yel Green / Yellow
+
C8
T1C4J6
K1
J2 J9 J3
F1
J1
C22K2 K4 K3
L N GROUND
J5 J7
S4
IS03 IS04 IS01 IS02
J4
ON - OFFLINK
J82
1
2
8
4
2
3
1
1
4
+
+
C10+
C3
+0-10V
GN
D
grn/yel
wh
blkblu
brn
1 2 3
CASCADELINK
blu
brn
SSB Boiler
SUPPLY 120VAC / 60Hz, 24 hour dedicated circuit.
Analog Input From BMS [Building Management System]
6720819841 (2016/04) US Analogic Device
4 | Use of the device for a single boiler application
3 Use of the device for a single boiler application
3 .1 Central Heating with Analog Input Control of setpointWith this configuration it is possible to manage via a 0-10 VDC analog signal the setpoint of the boiler. The parameters involved are the following:
N . Description Comment1 Central Heating (CH) Mode This parameter must be set to 423 Design Supply Min Limit Min setpoint temperature24 Design Supply Max Limit Max setpoint temperatureTab. 1 Parameters
The functioning of the boiler depending on the voltage output is shown in the following picture:
Fig. 2 Voltage output diagram
• The setpoint of the boiler is linearly controlled into the voltage interval of 1VDC to 9VDC from a minimum value equal to Par. 23 to a maximum value equal to Par. 24.
• For a voltage between 9VDC and 10VDC the setpoint is in any case set to the maximum value.• The boiler starts when the voltage is higher than 1.5VDC and turns off when the voltage is lower than 1VDC.
Fig. 3 Basic interface
Temp
eratu
re
9VDC
0VDC
1.5VDC1VDC
Voltage
Des. Supply Min Limit
Des. Supply Max Limit
10VDC
+0-10V
GN
D
Analog Input From BMS [Building Management System]
S4=ONANALOGIC 0-10 VDC
INPUT DEVICE
J5 S4=ON J4
Boiler 1
Boiler 1
1 2 3
CASCADELINK
Analogic Device 6720819841 (2016/04) US
Use of the device for a single boiler application | 5
3 .2 Central Heating with Analog Input Control of Modulation RateWith this configuration it is possible to manage via a 0-10 VDC analog signal the power of the boiler. The parameters involved are the following:
N . Description Comment1 Central Heating (CH) Mode This parameter must be set to 524 Design Supply Max Limit This parameter sets the setpoint of the boiler92 Fan Speed Maximum This parameter sets the maximum power93 Fan Speed Minimum This parameter sets the minimum powerTab. 2 Parameters
The functioning of the boiler depending on the voltage output is shown in the following picture:
Fig. 4 Voltage output diagram
• The power of the boiler is linearly controlled into the voltage interval of 1VDC to 9VDC from a minimum value defined by the Par. 93 to a maximum value defined by the Par. 92.
• For a voltage between 9VDC and 10VDC the power is in any case set to the maximum value.• The boiler starts when the voltage is higher than 1.5VDC and turns off when the voltage is lower than 1VDC.• The setpoint of the boiler is in any case controlled by the system. The value of the setpoint is defined by the Par. 24. If during the supply
temperature becomes higher than the setpoint the boiler starts to modulate ignoring the power adjustment supplied via the analog control.
Fig. 5 Basic interface
Powe
r
9VDC
0VDC
1.5VDC1VDC
Voltage
Fan Speed Minimum
Fan Speed Maximum
10VDC
+0-10V
GN
D
Analog Input From BMS [Building Management System]
S4=ONANALOGIC 0-10 VDC
INPUT DEVICE
J5 S4=ON J4
Boiler 1
Boiler 1
1 2 3
CASCADELINK
6720819841 (2016/04) US Analogic Device
6 | Use of the device for a cascade system
4 Use of the device for a cascade systemIn a cascade system you can only use the control setpoint via the 0-10 VDC analog device.
The parameters involved are the same illustrated in paragraph “3.1 Central Heating with Analog Input Control of setpoint” for a single boiler:
N . Description Comment1 Central Heating (CH) Mode This parameter must be set to 423 Design Supply Min Limit Min setpoint temperature24 Design Supply Max Limit Max setpoint temperatureTab. 3 Parameters
The functioning of the cascade depending on the voltage output is shown in the following picture:
Fig. 6 Voltage output diagram
• The setpoint of the cascade system is linearly controlled into the voltage interval of 1VDC to 9VDC from a minimum value equal to Par. 23 to a maximum value equal to Par. 24.
• For a voltage between 9VDC and 10VDC the setpoint is in any case set to the maximum value.• The cascade starts when the voltage is higher than 1.5VDC and turns off when the voltage is lower than 1VDC.
Fig. 7 Basic interface
Temp
eratu
re
9VDC
0VDC
1.5VDC1VDC
Voltage
Des. Supply Min Limit
Des. Supply Max Limit
10VDC
+0-10V
GN
D
Analog Input From BMS [Building Management System]
S4=ON
J5 S4=ON J4
Boiler 1
Boiler 1
1 2 3
CASCADELINK
S4=OFFBoiler 2 ÷ Boiler 16
1 2 3
CASCADELINK
Boiler 2
ANALOGIC 0-10 VDC
INPUT DEVICE
Analogic Device 6720819841 (2016/04) US
Key to symbols and safety instructions | 7
6720
8198
41 -
Rev.0
United States and Canada
Bosch Thermotechnology Corp.50 Wentworth AvenueLondonderry, NH 03053Tel. 603-552-1100Fax 603-965-7581www.boschheatingandcooling.comU.S.A.