MOTOR CURRENT SIGNATURE ANALYSIS
FOR
DIAGNOSIS OF FAULTS IN INDUCTION MOTOR DRIVES
Prof Bill Thomson
Director and Consultant
EM Diagnostics Ltd
EM Diagnostics Ltd 20 Greystone Road, Alford, Aberdeenshire, AB33 8TY, Scotland, UK
Tel : +44 (0) 19755 62446 Fax : +44 (0) 19755 62628
e-mail : [email protected] web site : www.mcsainterpreter.com
William T. Thomson EM Diagnostics Ltd 2001 - unauthorised copying, reproduction or amendment of all or part prohibited.
mailto:[email protected]://www.mcsainterpreter.com/http://www.mcsainterpreter.com/mailto:[email protected] -
7/28/2019 Anlise de corrente
2/20
2
MCSA : MOTOR CURRENT SIGNATURE ANALYSIS
INDUCTION MOTOR DRIVES
DIAGNOSE PROBLEMS PRIOR TO MOTORDRIVE FAILURE
BROKEN ROTOR BARS ABNORMAL AIRGAP ECCENTRICITY
SHORTED TURNS IN LV STATORS
ABNORMAL ROTOR DYNAMICS
PUMP WEAR MISALIGNMENT
William T. Thomson EM Diagnostics Ltd 2001 - unauthorised copying, reproduction or
amendment of all or part prohibited
-
7/28/2019 Anlise de corrente
3/20
3
INDUCTION MOTOR DRIVE SYSTEMS
WHY SO IMPORTANT?
USA 800,000 MW GENERATING CAPACITY
40-50% CONSUMED BY INDUCTION MOTORS
320,000MW PLANT SYSTEMS
328 MILLION HORSEPOWER
-
7/28/2019 Anlise de corrente
4/20
4
Power
Utilities
Oil & Gas
Chemical
Refineries
Pulp &
Paper
Mining
Shipping
MOD
Transport
Nuclear
WindPower
DuPont
Kodak
Ford
Uptime of
Induction Motor
Drive Systems
-
7/28/2019 Anlise de corrente
5/20
5
8 CW Induction
Motor Drives
8 PA Induction
Motor Drives8 ID Induction
Motor Drives
26 Mill Motors
Induction Motor
Drives
8Coal Conveyor
Induction Motor
Drives
8 FD Induction
Motor Drives
8 Compressor
Induction Motor
Drives
Numerous
other
InductionMotor Drives
2000 MW Coal
Fired
Power Station
-
7/28/2019 Anlise de corrente
6/20
6
3 PHASE, SCIM, 6.6kV,
2800kW/3753H.P., 2-POLE,
3570r.p.m., 60Hz,
(Full-load slip = 0.00833 or
0.833%)
William T. Thomson EM Diagnostics Ltd 2001 - unauthorisedcopying, reproduction or amendment of all or part prohibited
-
7/28/2019 Anlise de corrente
7/20
7
MOTOR CURRENT SIGNATURE ANALYSIS
CONDITION MONITORING TECHNIQUE
INSURANCE POLICY
TO PREVENT FAILURES
REDUCE DOWNTIME AND REPAIR COSTS
PREVENT LOST PRODUCTION
INCREASE RELIABILITY - PRODUCT DELIVERY
-
7/28/2019 Anlise de corrente
8/20
8
MCSA
MCSA : On-Line Monitoring and Analysis of Current to Assess
the Condition of an Induction Motor Drive System
-
7/28/2019 Anlise de corrente
9/20
9
APPLICATION OF CURRENT TRANSFORMER CT
-
7/28/2019 Anlise de corrente
10/20
10
MCSA Instrumentation
-
7/28/2019 Anlise de corrente
11/20
11
Time Domain signals and Current Spectra
-
7/28/2019 Anlise de corrente
12/20
12
CURRENT SIGNATURE DUE TO BROKEN BARS
LOWER
SIDEBAND
f1 =SUPPLY FREQUENCY (60 Hz)
Hz
dB
UPPER
SIDEBAND
-
7/28/2019 Anlise de corrente
13/20
13
SIGNATURE PATTERN DUE TO BROKEN BARS
TWICE SLIP FREQUENCY SIDEBANDS : 2sf1
fsb = f12sf1
-2sf1 +2sf1
f1dB
Hz
IDEALISED
Current Spectrum Due to
Broken Rotor Bars
-
7/28/2019 Anlise de corrente
14/20
14
MCSA ON GM3802A (January, 2002)
3-PH, HV, SCIM, 4155HP/3.1MW, 11kV, 2974r.p.m., 195A 50 Hz
BROKEN ROTOR BARLIFTED OUT OF THE SLOT
N=46 dB
William T. Thomson EM Diagnostics Ltd 2001 - unauthorised copying,
reproduction or amendment of all or part prohibited
-
7/28/2019 Anlise de corrente
15/20
15
3-PH, HV, SCIM, 4155HP/3.1MW, 11kV, 2974r.p.m., 195A
BROKEN ROTOR BARLIFTED IN THE SLOT
SECONDARY DAMAGE TO HV STATOR
William T. Thomson EM Diagnostics Ltd 2001 - unauthorised copying, reproduction or amendment of all or partprohibited
-
7/28/2019 Anlise de corrente
16/20
16
3-PH, HV, SCIM, 4155HP/3.1MW, 11kV, 2974r.p.m., 195A
BROKEN ROTOR BARLIFTED IN THE SLOT
SECONDARY DAMAGE TO HV STATOR
OFFSHORE OIL PRODUCTION PLATFORM
TOTAL REPAIR COSTS : $270,000.00
(Removal, transport, repair & re-installation costs)
THE BOSS IS NOT HAPPY
PREVENT THIS HAPPENING AGAIN
YOUR JOB IS ON THE LINE
-
7/28/2019 Anlise de corrente
17/20
17
Case History : Large Sea Water Injection Pump
3-Phase SCIM, 6600V, 60Hz, 3.6MW/4285h.p.,376A,3580r.p.m., Star connected
Full-load slip? s=(Ns-Nr)/Ns = 0.0055(0.55%)
Sidebands = 2*0.0055*60 = 0.67 Hz (at full load)
or
Pole Pass Sidebands = 2 *(60 - 59.667) = 0.67 Hz
-
7/28/2019 Anlise de corrente
18/20
18
1985 : 20 BARS BROKEN OUT OF 46
-
7/28/2019 Anlise de corrente
19/20
19
INDUCTION MOTORGEARBOX COMPRESSOR
3phase, 415 V, 134 kW/180 H.P., 210 A, 1485 r.p.m., 50 Hz R = 58
1982 150 A
-
7/28/2019 Anlise de corrente
20/20
20
DIE CAST ROTOR FAULTY END RING
INSPECTION FOLLOWING ON-LINE MCSA
William T. Thomson EM Diagnostics Ltd 2001 - unauthorised copying, reproduction or amendment of all or part prohibited