All aspects of the electrical work required to complete the project represented in this document shall comply with the manufacturer's recomendations/specifications and all codes, The electrical contractor shall seal all penetrations resulting from the electrical scope of work. 3. 4. 2. Electrical Notes: All signage shall be provided as required by the NEC 2008 ed. 5. 1. statutes, and standards adopted by the State and Local Authority Having Jurisdiction. An AC disconnect, at the electrical service entrance, is exempted from requirement by law, for Tier 1 renewable Energy Systems, per Florida Administration Code 25-6.065(6)(a). Auxilliary disconnects are a utility Co. option. If required by the utility Co., the utility Co. shall bear the additional expense incurred, as stipulated by the Florida Administration Code. A8 B7 + - + - + - + - + - + - + - + - + - + - w/#10 USE-2 (typ) + - + - + - + - + - + - + - + - + - + - + - + - + - + - + - + - Kyocera 210 W Kyocera 210 W Kyocera 210 W Kyocera 210 W Kyocera 210 W Kyocera 210 W Kyocera 210 W Kyocera 210 W Kyocera 210 W Kyocera 210 W Kyocera 210 W Kyocera 210 W Kyocera 210 W Kyocera 210 W Kyocera 210 W Kyocera 210 W Kyocera 210 W Kyocera 210 W Kyocera 210 W Kyocera 210 W Kyocera 210 W Kyocera 210 W Kyocera 210 W Kyocera 210 W Kyocera 210 W Kyocera 210 W + - L1 L2 N GND SMA SB5000US A1 A2 A3 A4 A5 A6 A7 B1 B2 B3 B4 B5 B6 B8 A9 A10 A11 A12 A13 B9 B10 B11 B12 B13 Existing 100 Amp 120/240 v 25 N GND Type 4 MC cable 4 #10 THWN-2 & #10 eg in 1/2 Emt Roof mounted J-Box w/#10 USE-2 (typ) Type 4 MC cable 15 Amp Fuses All raceways, conductors and J-Boxes shall be located under the proposed PV panels/rack.` Raceway from roof mounted J-Box shall exit through the bottom of the J-Box, penetrate the roof and be routed, within the building, to the proposed inverter. 6. The proposed 2 pole backfeed circuit breaker shall be located as required by NEC 690.64.(B)(7). 7. Busby 5KW PROPERTY LINE 1 STORY MET HANGAR PZ1 - INSTALLATION AREA SHEET NO: PUBLISHED: SHEET NAME: DRAWN: THIS IS A SINGLE SHEET PLAN CHECKED: SB AG 0041_Busby_PortStLucie_FL.dwg COPY RIGHT & INTELLECTUAL PROPERTY NOTICE THIS PLAN SET IS COPY RIGHT PROTECTED AND CONTAINS INTELLECTUAL PROPERTY WHICH BELONGS TO ALLEN GEZELMAN PE. ACCESS IS GIVEN TO THE INFORMATION HEREON SOLELY FOR THE PURPOSE OF COMPLETION OF THE PROJECT FOR WHICH IT IS INTENDED. NO OTHER USE MAY BE MADE OF THE INFORMATION, DRAWINGS, OR IDEAS HEREON WITHOUT THE EXPRESS , WRITTEN, PERMISSION OF ALLEN GEZELMAN PE 11/5/2009 8:51:58 PM 08 SCALE: 1" = 40' ELECTRICAL SYSTEM NOTES 05 SCALE: N.T.S. PV WIRING / SCHEMATIC 02 SCALE: N.T.S. AERIAL PHOTOGRAPH- SITE PLAN 03 SCALE: N.T.S. PHOTO FROM WEST SIDE 01 SCALE: N.T.S. INSTALLATION NOTES 04 SCALE: 1/8" = 1'-0" MOUNTING SYSTEM- HDG UNISTRUT 07 SCALE: NTS SAMPLE INSTALLATION PHOTO 06 http://www.kyocerasolar.com/pdf/specsheets/KYOCERA-KD210GX-LPU.pdf KYOCERA PV- MODULES - 210 W 09 SCALE: 1/16" = 1'-0" EQUIPMENT LAYOUT ENLARGED VIEWING & HYPERLINKS: PRINT VERSION OF THIS PLAN PROVIDES MINIMUM INFORMATION NEEDED BY USERS. ELECTRONIC VERSION (EV) PROVIDES MAGNIFIED VIEWING UP TO 6400%. EV ALSO PROVIDES HYPERLINK ACCESS TO OEM MANUALS AND ABUNDANT OTHER SUPPLEMENTARY INFORMATION.EV MAY BE ACCESSED AT: WWW.GEZELMANPE.COM/PV/ 0041_Busby_PortStLucie_FL.dwg ENLARGED VIEWING & HYPERLINKS: PRINT VERSION OF THIS PLAN PROVIDES MINIMUM INFORMATION NEEDED BY USERS. ELECTRONIC VERSION (EV) PROVIDES MAGNIFIED VIEWING UP TO 6400%. EV ALSO PROVIDES HYPERLINK ACCESS TO OEM MANUALS AND ABUNDANT OTHER SUPPLEMENTARY INFORMATION.EV MAY BE ACCESSED AT: WWW.GEZELMANPE.COM/PV/ 0041_Busby_PortStLucie_FL.dwg BUSBY PV INSTALLATION NOTES: THE DETAILS SPECIFIED ON THIS “PAPER” PLAN ARE CONSIDERED TO BE THE MINIMUM NEEDED BY AHJ (AUTHORITY HAVING JURISDICTION) AND INSTALLERS. USERS ARE ENCOURAGED TO ACCESS EV (ELECTRONIC VERSION) OF THIS PLAN WWW.GEZELMANPE.COM/PV/0041_BUSBY_PORTSTLUCIE_FL.PDF . ACTIVE HYPERLINKS ON EV PROVIDE EASY ACCESS TO SUPPLEMENTAL INFORMATION. EV ALSO ALLOWS VIEWER TO STUDY THE PLAN AND OEM DETAILS AT MAGNIFICATIONS OF VIEWER CHOICE UP TO 6400%. IF A CONFLICT SHOULD OCCUR BETWEEN A DRAWING AND/OR SPECIFICATION HEREON AND AN OEM DETAIL, OEM SHALL PREVAIL. THIS PLAN GIVES SITE-SPECIFIC INSTALLATION DETAILS FOR A PHOTO VOLTAIC (SOLAR ELECTRIC) SYSTEM TO BE INSTALLED AT THE ABOVE LOCATION. THE SOLAR MODULES SHALL BE THE NUMBER, MAKE AND MODEL LISTED IN FIGURE 05. THE HOLD DOWN ANCHORS SHALL BE 1/2- INCH DIAMETER, CORROSION RESISTANT STEEL BOLTS THRU PURLINS INTO CORROSION RESISTANT UNISTRUT P5500T RACK AS SHOWN IN ACCOMPANYING DRAWINGS. THE PV MODULES SHALL BE INSTALLED IN THE NUMBER OF PARALLEL STRINGS AND NUMBER OF SERIES PV MODULES IN EACH STRING AS DEPICTED IN FIGURE 05. THE PV MODULES SHALL VERTICAL - “PORTRAIT” ORIENTATION. WIRING SHALL BE AS SHOWN IN FIGURE 05. ALL CONTRACTOR AC & DC WIRING SHALL USE MINIMUM 10 AWG COPPER OEM WIRING AND HARNESSES, REGARDLESS OF WIRE SIZE, ARE ACCEPTABLE WHEN APPLIED TO THE OEM USE INTENDED, SUCH AS PV-MODULE TO PV-MODULE CONNECTIONS. PV-MODULES PRODUCE ELECTRICITY WHEN EXPOSED TO SUNLIGHT. KEEP COVERED WITH OPAQUE MATERIAL UNTIL ALL WIRING IS COMPLETED. TWISTED (WIRE NUT) CONNECTIONS ARE NOT PERMITTED FOR DC WIRING. USE OEM PLUG CONNECTOR HARNESS BETWEEN PV MODULES. MAKE SOLID MECHANICAL CONNECTIONS TO ENSURE ELECTRICAL CONDUCTIVITY BETWEEN ALL PV MODULE ENCLOSURES AND FRAMING MEMBERS WITH NO ELECTRICALLY ISOLATED COMPONENTS, USE #10 AWG BARE COPPER WITH SCREWED CONNECTIONS FOR BONDING JUMPERS AS NEEDED. OEM APPROVED BONDING/GROUNDING DEVICES ARE AN ACCEPTABLE SUBSTITUTE WHEN INSTALLED PER OEM INSTRUCTIONS. DO NOT LEAVE LOOSE, UNSECURED WIRES/HARNESS BETWEEN PV-MODULES, TIE TO THE MOUNTING RAILS WITH UV RESISTANT ZIP TIES, APPROVED WIRE CLIPS OR WIRING TROUGH IN NEAT, PROFESSIONAL MANNER. USE APPROVED MEANS AND METHODS PER NEC CURRENT IN THE JURISDICTION (AND ANY APPLICABLE STATE/LOCAL AHJ AMENDMENTS THERETO). ADHERE TO ALL APPLICABLE BUILDING CODE REQUIREMENTS. ADHERE TO MEANS & METHODS OF NRCA ROOFING & WATERPROOFING MANUAL TO ENSURE NO ROOF LEAKS AT TIME OF INSTALLATION AND AS THE SYSTEM “AGES”. THIS PLAN AND ITS USE ARE SUBJECT TO THE PROVISIONS OF EJCDC C-700 (ENGINEERS JOINT CONSTRUCTION DOCUMENTS COMMITTEE - STANDARD GENERAL CONDITIONS OF THE CONSTRUCTION CONTRACT) . EJCDC C-700 MAY BE REVIEWED AT THE FOLLOWING HYPERLINK: HTTP://WWW.DOUGLASAZ.GOV/PUBLICWORKS/DOCUMENTS/RFP/SEWER_REHAB_PHASE_I/00700%20-%20EJCDC.PDF 10 SCALE: N.T.S. REQ. SAFETY SIGNAGE REFER TO 2007 FLORIDA ELECTRICAL CODE FOR REQUIRED SIGNAGE OF WHICH THESE ARE EXAMPLES BUZBY 5.0 KW PV SYSTEM NOTES & CALCULATIONS MODULES: KYOCERA KD210GX-LPU , 210 WATTS X 26 MODULES MODULE PERFORMANCE CHARACTERISTICS (STC): MAX. POWER WP = 210 W MAX. POWER VOLTAGEVMPP = 26.6 V MAX. POWER CURRENT IMPP = 7.90 AMPS OPEN CIRCUIT VOLTAGE VOC = 32.2 V SHORT CIRCUIT CURRENT ISC = 8.58 AMPS MAX. SYSTEM VOLTAGE = 600 V SERIES FUSE = 15 AMPS VOC TC = -.12 V/C° ISC TC = 5.15 X 10¯ ³AMPS/C° MAX. FUSE = 15 AMPS ** ALL MEASUREMENTS ARE AT STANDARD TEST CONDITIONS OF 1000 WATTS/M2 IRRADIANCE AT 25 DEGREES C ** INVERTERS: SB5000US MAX INPUT VOLTAGE = 600 VDC OPERATING RANGE = 250 - 600 VDC PV START VOLTAGE = 300 VDC STRING INFORMATION STRINGS TOTAL; 2 STRINGS, EACH WITH 13 MODULES CONNECTED IN SERIES. VOC= 13 MODULES IN SERIES AT 32.2 VOC = 13 X 32.2V = 418.6 VDC VMP= 13 MODULES IN SERIES AT 26.6 VMP = 13X 26.6= 345.8 VDC ISC= 8.58 AMPS X 2 SOURCE CIRCUITS (A & B) = 17.16 AMPS IMP= 7.90 AMPS X 2 SOURCE CIRCUITS = 15.8 AMPS POWER = 26 MODULES AT 210 WATTS = 5460 WATTS MAXIMUM VOLTAGE: TEMPERATURE CORRECTION FOR CRYSTALLINE MODULES LOWEST RECORDED TEMPERATURE FOR PORT ST LUCIE PER WEATHER.COM 30 DEGREES F. PER NEC 2008-T690.7 MAX SYSTEM VOLTAGE CORRECTION FACTOR OF 1.12 13 PANELS IN SERIES VOC = 418.6 VDC 1.12 X 418.6 = 468.83 VDC 468.83 VDC < 600 VDC MAX ALLOWED, PASSED. MAXIMUM CURRENT: OVER IRRADIATION: EACH STRING HAS AN ISC OF 8.58 AMPS 125% CORRECTION PER NEC 690.8(A)(1)= 8.58 X 1.25=10.725 AMPS AMPACITY/CONTINUOUS CURRENT: NEC 690.8(B)(1) 10.725 X 1.25 = 13.41 AMPS NEC TABLE 310.15(B)(2)(A), 4 WIRES CURRENT CARRYING WIRES IN CONDUIT DE-RATING TO 80% VOLTAGE DROP FOR FARTHEST 11 MODULE STRING TO INVERTER: % VD = 2 (70FT) 1.29OHMS (13.41 AMPS) 100% / ((1000FT) 345.8 VDC) %VD = .7 % CONDUCTOR AMPACITY #10 THWN-2: NEC TABLE 310.16 W/CORRECTION FACTOR @ 41 - 45 DEG. C AND TABLE 310.15(B) (2) (A) 20 W/4 COND. 40 AMPS X .87 X .8 = 27.84 AMPS REVISIONS: FSEC CERTIFICATION#: KC09-NT90-0240 PV MODULE KD210GX-LPU HTTP://WWW.FSEC.UCF.EDU/EN/INDUSTRY/TESTING/PVMODULES/CERTIFIED_MODULES/DETAIL_KYOCERA.HTM INSTALLATION LOCATION SOUTH ROOF INSTALLATION LOCATION STRUCTURAL: GRAVITY LOAD FROM SOLAR EQUIPMENT LESS THAN 5_PSF WIND ENGINEERING: 130-MPH WIND ZONE, EXPOSURE CATEGORY C, BUILDING IMPORTANCE CATEGORY II WIND FORCES: +/- pz1_24.9, pz2_39.9, pz3_57.3 ASCE 7 PRESSURE ZONE DIAGRAM (PAGE 5 AT 1ST LINK) AND UNIRAC DETAILS MAY BE VIEWED AT THE FOLLOWING HYPERLINKS: http://www.unirac.com/pdf/ii227.pdf http://www.unirac.com/pdf/ii206.pdf I CERTIFY THAT THE FRAMING OF THIS STRUCTURE WILL SAFELY ACCOMMODATE CALCULATED WIND UPLIFT AND LATERAL FORCES AND EQUIPMENT DEAD LOADS. THIS IS ATTESTED TO BY MY SIGNATURE AND SEAL ON THIS DRAWING AT THE UPPER RIGHT. ELECTRICAL SPECIFICATIONS: CONFORMS TO THE REQUIREMENTS OF THE 2008 NATIONAL ELECTRICAL CODE THE BELOW ELECTRICAL SCHEMATIC DRAWING IS A TYPICAL REPRESENTATION, CERTAIN DETAILS OF THIS PROJECT MAY DIFFER, REFER TO OEM LITERATURE WHICH SHALL PREVAIL: APPLICABLE CODE: FLORIDA BUILDING CODE 2007 W/09 SUPP FLORIDA ELEC. 2007 CODE W/09 SUPP DESIGNED PER: ASCE 7-05 NEC 2008 THIS PLAN IS VOID WITHOUT MY SIGNATURE & RAISED SEAL. THIS PLAN MAY NOT BE PLACED ON FILE FOR PULLING MULTIPLE PERMITS. EACH PERMIT PULLED REQUIRES ITS OWN RAISED SEAL COPY OF THIS PLAN. ALLEN GEZELMAN 16502 HANNA RD. LUTZ, FLORIDA 33549 PH. 813 650 7246 FX. 866 397 9050 Allen@Gezelman PE.COM www.GezelmanPE.com I CERTIFY THAT THIS DESIGN & SPECIFICATIONS MEET THE REQUIREMENTS OF THE CURRENT FLORIDA BUILDING CODE AND NATIONAL ELECTRICAL CODE. ELECTRICAL ENGINEERING CONSULTANT: BRUCE A. TOZIER, P.E. LIC # 67336 TOZIER ENGINEERING, INC. 209 S. GLEN ARVEN AVE. TEMPLE TERRACE, FL 33617 OFF. (813) 988-3578 CELL (813) 951-4727 FAX (813) 988-3578 SCALE: 1-1/2" = 1'-0" HOLD DOWN DETAIL OWNER: JAMES D BUSBY II KRISTINA A BUSBY 18701 KITTY HAWK CT, PORT ST LUCIE FL 34987 LEGAL DESCRIPTION: PARCEL ID: 3215-801-0045-000-5 AERO ACRES BLK 2 LOT 16 (1.223 AC) (OR 1376-2722: 1617-2904) WIND LOAD: DESIGNED FOR ____ MPH 130 WIND EXPOSURE: CATEGORY _ C COMPLIANCE: IEEE-929, IEE-1547, UL 1741, UL 1998 MINIMUM AC & DC WIRING SIZE #10 AWG COPPER (OEM WIRING & HARNESS EXCLUDED) SMA AMERICA, SB5000US (240V), 5000 WATT GRID TIED PV INVERTER SPECIFICATIONS: WWW.SOLARELECTRICSUPPLY.COM/PDF/SUNNY%20BOY/SB5000US-7000US.PDF SCALE: NTS EXISTING ROOF/RAMING OWNER/CONTRACTOR JAMES D BUSBY 18701 KITTY HAWK CT PORT ST LUCIE FL 34987 NOTE: INVERTER TO BE LOCATED ADJACENT TO 100 AMP PANEL INSIDE HANGAR. PENETRATE THE ROOF AT THE J-BOX AS SHOWN IN THE PHOTO AND RUN CONDUIT ON THE UNDERSIDE OF THE ROOF SCALE: NTS UNISTRUT P5500 T SCALE: 3/4" = 1'-0" UNISTRUT LAYOUT DETAIL SEE DETAIL SCALE: 6" = 1'-0" HOLD DOWN DETAIL

Upload: buidung

Post on 29-Aug-2018

214 views

Category:

Documents


0 download

TRANSCRIPT

All aspects of the electrical work required to complete the

project represented in this document shall comply with the

manufacturer's recomendations/specifications and all codes,

The electrical contractor shall seal all penetrations resulting

from the electrical scope of work.

3.

4.

2.

Electrical Notes:

All signage shall be provided as required by the NEC 2008 ed.

5.

1.

statutes, and standards adopted by the State and Local

Authority Having Jurisdiction.

An AC disconnect, at the electrical service entrance, is exempted

from requirement by law, for Tier 1 renewable Energy Systems,

per Florida Administration Code 25-6.065(6)(a). Auxilliary

disconnects are a utility Co. option. If required by the utility Co.,

the utility Co. shall bear the additional expense incurred, as

stipulated by the Florida Administration Code.

A8B7

+ - + - + - + - + -+ -

+ - + -

+ - + -

w/#10 USE-2 (typ)

+ - + -+ - + -+ -

+ -+ - + - + - + -

+ - + - + - + -+ - + -

Kyocera 210 W

Kyocera 210 W

Kyocera 210 W

Kyocera 210 W

Kyocera 210 W

Kyocera 210 W

Kyocera 210 W

Kyocera 210 W

Kyocera 210 W

Kyocera 210 W

Kyocera 210 W

Kyocera 210 W

Kyocera 210 W

Kyocera 210 W

Kyocera 210 W

Kyocera 210 W

Kyocera 210 W

Kyocera 210 W

Kyocera 210 W

Kyocera 210 W

Kyocera 210 W

Kyocera 210 W

Kyocera 210 W

Kyocera 210 W

Kyocera 210 W

Kyocera 210 W

+ -

L1 L2 N GND

SMA SB5000US

A1 A2 A3 A4 A5 A6 A7

B1B2B3B4B5B6

B8

A9A10A11A12A13

B9 B10 B11 B12 B13

Existing 100 Amp120/240 v

25

N

GND

Type 4 MC cable

4 #10 THWN-2 &

#10 eg in 1/2 Emt

Roof mounted J-Box

w/#10 USE-2 (typ)

Type 4 MC cable

15 Amp Fuses

All raceways, conductors and J-Boxes shall be located under the

proposed PV panels/rack.`

Raceway from roof mounted J-Box shall exit through the bottom

of the J-Box, penetrate the roof and be routed, within the

building, to the proposed inverter.

6.

The proposed 2 pole backfeed circuit breaker shall be located

as required by NEC 690.64.(B)(7).

7.

Busby 5KW

PROPERTY LINE

1 STORY MET HANGAR

PZ1 - INSTALLATION AREA

SHEET NO:

PUBLISHED:

SHEET NAME:

DRAWN:

THIS IS A SINGLE SHEET PLAN

CHECKED:SB AG

0041_Busby_PortStLucie_FL.dwg

C

OP

Y R

IGH

T &

IN

TE

LLE

CT

UA

L P

RO

PE

RT

Y N

OT

ICE

•T

HIS

PLA

N S

ET

IS

CO

PY

RIG

HT

PR

OT

EC

TE

D A

ND

CO

NT

AIN

S I

NT

ELL

EC

TU

AL

PR

OP

ER

TY

WH

ICH

BE

LON

GS

TO

ALL

EN

GE

ZE

LMA

N P

E.

•A

CC

ES

S I

S G

IVE

N T

O T

HE

IN

FO

RM

AT

ION

HE

RE

ON

SO

LELY

FO

R T

HE

PU

RP

OS

E O

F C

OM

PLE

TIO

N O

F T

HE

PR

OJE

CT

FO

R W

HIC

H I

T I

S I

NT

EN

DE

D.

•N

O O

TH

ER

US

E M

AY

BE

MA

DE

OF

TH

E I

NF

OR

MA

TIO

N,

DR

AW

ING

S,

OR

ID

EA

S H

ER

EO

N W

ITH

OU

T T

HE

EX

PR

ES

S,

WR

ITT

EN,

PE

RM

ISS

ION

OF

ALL

EN

GE

ZE

LMA

N P

E

11/5/2009 8:51:58 PM

08SCALE: 1" = 40'

ELECTRICAL SYSTEM NOTES05

SCALE: N.T.S.

PV WIRING / SCHEMATIC

02SCALE: N.T.S.

AERIAL PHOTOGRAPH- SITE PLAN03

SCALE: N.T.S.

PHOTO FROM WEST SIDE01

SCALE: N.T.S.

INSTALLATION NOTES

04SCALE: 1/8" = 1'-0"

MOUNTING SYSTEM- HDG UNISTRUT

07SCALE: NTS

SAMPLE INSTALLATION PHOTO

06http://www.kyocerasolar.com/pdf/specsheets/KYOCERA-KD210GX-LPU.pdf

KYOCERA PV- MODULES - 210 W

09SCALE: 1/16" = 1'-0"

EQUIPMENT LAYOUT

EN

LAR

GE

D V

IEW

ING

& H

YP

ER

LIN

KS

:P

RIN

T V

ER

SIO

N O

F T

HIS

PLA

N P

RO

VID

ES

MIN

IMU

M I

NF

OR

MA

TIO

N N

EE

DE

D B

Y U

SE

RS

.

ELE

CT

RO

NIC

VE

RS

ION

(E

V)

PR

OV

IDE

S M

AG

NIF

IED

VIE

WIN

G U

P T

O 6

40

0%

. E

V A

LSO

PR

OV

IDE

S H

YP

ER

LIN

K A

CC

ES

S T

O O

EM

MA

NU

ALS

AN

D A

BU

ND

AN

T O

TH

ER

SU

PP

LEM

EN

TA

RY

IN

FO

RM

AT

ION

.EV

MA

Y B

E A

CC

ES

SE

D A

T:

WW

W.G

EZ

ELM

AN

PE

.CO

M/P

V/0

04

1_

Bu

sby_

Po

rtS

tLuci

e_F

L.d

wg

ENLARGED VIEWING & HYPERLINKS:PRINT VERSION OF THIS PLAN PROVIDES MINIMUM INFORMATION NEEDED BY USERS.

ELECTRONIC VERSION (EV) PROVIDES MAGNIFIED VIEWING UP TO 6400%. EV ALSO PROVIDES HYPERLINK ACCESS TO OEM MANUALS ANDABUNDANT OTHER SUPPLEMENTARY INFORMATION.EV MAY BE ACCESSED AT:

WWW.GEZELMANPE.COM/PV/0041_Busby_PortStLucie_FL.dwg

BUSBY PV INSTALLATION NOTES:

THE DETAILS SPECIFIED ON THIS “PAPER” PLAN ARE CONSIDERED TO BE THE MINIMUM NEEDED BY AHJ (AUTHORITY HAVING JURISDICTION) AND INSTALLERS.

USERS ARE ENCOURAGED TO ACCESS EV (ELECTRONIC VERSION) OF THIS PLAN WWW.GEZELMANPE.COM/PV/0041_BUSBY_PORTSTLUCIE_FL.PDF . ACTIVEHYPERLINKS ON EV PROVIDE EASY ACCESS TO SUPPLEMENTAL INFORMATION. EV ALSO ALLOWS VIEWER TO STUDY THE PLAN AND OEM DETAILS AT

MAGNIFICATIONS OF VIEWER CHOICE UP TO 6400%. IF A CONFLICT SHOULD OCCUR BETWEEN A DRAWING AND/OR SPECIFICATION HEREON AND AN OEMDETAIL, OEM SHALL PREVAIL.

THIS PLAN GIVES SITE-SPECIFIC INSTALLATION DETAILS FOR A PHOTO VOLTAIC (SOLAR ELECTRIC) SYSTEM TO BE INSTALLED AT THE ABOVE LOCATION. THE

SOLAR MODULES SHALL BE THE NUMBER, MAKE AND MODEL LISTED IN FIGURE 05. THE HOLD DOWN ANCHORS SHALL BE 1/2- INCH DIAMETER, CORROSIONRESISTANT STEEL BOLTS THRU PURLINS INTO CORROSION RESISTANT UNISTRUT P5500T RACK AS SHOWN IN ACCOMPANYING DRAWINGS.

THE PV MODULES SHALL BE INSTALLED IN THE NUMBER OF PARALLEL STRINGS AND NUMBER OF SERIES PV MODULES IN EACH STRING AS DEPICTED IN FIGURE05. THE PV MODULES SHALL VERTICAL - “PORTRAIT” ORIENTATION.

WIRING SHALL BE AS SHOWN IN FIGURE 05. ALL CONTRACTOR AC & DC WIRING SHALL USE MINIMUM 10 AWG COPPER OEM WIRING AND HARNESSES,REGARDLESS OF WIRE SIZE, ARE ACCEPTABLE WHEN APPLIED TO THE OEM USE INTENDED, SUCH AS PV-MODULE TO PV-MODULE CONNECTIONS.

• PV-MODULES PRODUCE ELECTRICITY WHEN EXPOSED TO SUNLIGHT. KEEP COVERED WITH OPAQUE MATERIAL UNTIL ALL WIRING IS COMPLETED.

• TWISTED (WIRE NUT) CONNECTIONS ARE NOT PERMITTED FOR DC WIRING. USE OEM PLUG CONNECTOR HARNESS BETWEEN PV MODULES.• MAKE SOLID MECHANICAL CONNECTIONS TO ENSURE ELECTRICAL CONDUCTIVITY BETWEEN ALL PV MODULE ENCLOSURES AND FRAMING MEMBERS WITH

NO ELECTRICALLY ISOLATED COMPONENTS, USE #10 AWG BARE COPPER WITH SCREWED CONNECTIONS FOR BONDING JUMPERS AS NEEDED. OEM

APPROVED BONDING/GROUNDING DEVICES ARE AN ACCEPTABLE SUBSTITUTE WHEN INSTALLED PER OEM INSTRUCTIONS.

• DO NOT LEAVE LOOSE, UNSECURED WIRES/HARNESS BETWEEN PV-MODULES, TIE TO THE MOUNTING RAILS WITH UV RESISTANT ZIP TIES, APPROVEDWIRE CLIPS OR WIRING TROUGH IN NEAT, PROFESSIONAL MANNER.

• USE APPROVED MEANS AND METHODS PER NEC CURRENT IN THE JURISDICTION (AND ANY APPLICABLE STATE/LOCAL AHJ AMENDMENTS THERETO).• ADHERE TO ALL APPLICABLE BUILDING CODE REQUIREMENTS.• ADHERE TO MEANS & METHODS OF NRCA ROOFING & WATERPROOFING MANUAL TO ENSURE NO ROOF LEAKS AT TIME OF INSTALLATION AND AS THE

SYSTEM “AGES”.

THIS PLAN AND ITS USE ARE SUBJECT TO THE PROVISIONS OF EJCDC C-700 (ENGINEERS JOINT CONSTRUCTIONDOCUMENTS COMMITTEE - STANDARD GENERAL CONDITIONS OF THE CONSTRUCTION CONTRACT) . EJCDC C-700 MAY BE REVIEWED AT THE FOLLOWING HYPERLINK:

HTTP://WWW.DOUGLASAZ.GOV/PUBLICWORKS/DOCUMENTS/RFP/SEWER_REHAB_PHASE_I/00700%20-%20EJCDC.PDF

10SCALE: N.T.S.

REQ. SAFETY SIGNAGE

REFER TO 2007 FLORIDAELECTRICAL CODE FORREQUIRED SIGNAGE OFWHICH THESE AREEXAMPLES

BUZBY 5.0 KW PV SYSTEM NOTES & CALCULATIONS

MODULES: KYOCERA KD210GX-LPU , 210 WATTS X 26 MODULES

MODULE PERFORMANCE CHARACTERISTICS (STC):

MAX. POWER WP = 210 WMAX. POWER VOLTAGEVMPP = 26.6 VMAX. POWER CURRENT IMPP = 7.90 AMPSOPEN CIRCUIT VOLTAGE VOC = 32.2 VSHORT CIRCUIT CURRENT ISC = 8.58 AMPSMAX. SYSTEM VOLTAGE = 600 VSERIES FUSE = 15 AMPSVOC TC = -.12 V/C°ISC TC = 5.15 X 10¯ ³AMPS/C°MAX. FUSE = 15 AMPS

** ALL MEASUREMENTS ARE AT STANDARD TEST CONDITIONS OF1000 WATTS/M2 IRRADIANCE AT 25 DEGREES C **

INVERTERS: SB5000US

MAX INPUT VOLTAGE = 600 VDCOPERATING RANGE = 250 - 600 VDCPV START VOLTAGE = 300 VDC

STRING INFORMATION

STRINGS TOTAL; 2 STRINGS, EACH WITH 13 MODULES CONNECTEDIN SERIES.VOC= 13 MODULES IN SERIES AT 32.2 VOC = 13 X 32.2V = 418.6VDCVMP= 13 MODULES IN SERIES AT 26.6 VMP = 13X 26.6= 345.8 VDCISC= 8.58 AMPS X 2 SOURCE CIRCUITS (A & B) = 17.16 AMPSIMP= 7.90 AMPS X 2 SOURCE CIRCUITS = 15.8 AMPSPOWER = 26 MODULES AT 210 WATTS = 5460 WATTS

MAXIMUM VOLTAGE:

TEMPERATURE CORRECTION FOR CRYSTALLINE MODULESLOWEST RECORDED TEMPERATURE FOR PORT ST LUCIE PERWEATHER.COM 30 DEGREES F.PER NEC 2008-T690.7 MAX SYSTEM VOLTAGE CORRECTIONFACTOR OF 1.1213 PANELS IN SERIES VOC = 418.6 VDC1.12 X 418.6 = 468.83 VDC 468.83 VDC < 600 VDC MAX ALLOWED, PASSED.

MAXIMUM CURRENT:

OVER IRRADIATION:EACH STRING HAS AN ISC OF 8.58 AMPS125% CORRECTION PER NEC 690.8(A)(1)= 8.58 X 1.25=10.725 AMPS

AMPACITY/CONTINUOUS CURRENT:NEC 690.8(B)(1) 10.725 X 1.25 = 13.41 AMPS

NEC TABLE 310.15(B)(2)(A), 4 WIRES CURRENT CARRYING WIRES INCONDUIT DE-RATING TO 80%

VOLTAGE DROP FOR FARTHEST 11 MODULE STRING TO INVERTER:

% VD = 2 (70FT) 1.29OHMS (13.41 AMPS) 100% / ((1000FT) 345.8VDC)

%VD = .7 %

CONDUCTOR AMPACITY #10 THWN-2:

NEC TABLE 310.16 W/CORRECTION FACTOR @ 41 - 45 DEG. C ANDTABLE 310.15(B) (2) (A) 20 W/4 COND.

40 AMPS X .87 X .8 = 27.84 AMPS

REVISIONS:

FSEC CERTIFICATION#: KC09-NT90-0240

PV MODULE KD210GX-LPU

HTTP://WWW.FSEC.UCF.EDU/EN/INDUSTRY/TESTING/PVMODULES/CERTIFIED_MODULES/DETAIL_KYOCERA.HTM

INSTALLATION LOCATION SOUTH ROOFINSTALLATION LOCATION

STRUCTURAL:• GRAVITY LOAD FROM SOLAR EQUIPMENT LESS THAN 5_PSF• WIND ENGINEERING: 130-MPH WIND ZONE, EXPOSURE CATEGORY C, BUILDING IMPORTANCE CATEGORY II

WIND FORCES: +/- pz1_24.9, pz2_39.9, pz3_57.3

• ASCE 7 PRESSURE ZONE DIAGRAM (PAGE 5 AT 1ST LINK) AND UNIRAC DETAILS MAY BE VIEWED AT THE FOLLOWING HYPERLINKS:

• http://www.unirac.com/pdf/ii227.pdf http://www.unirac.com/pdf/ii206.pdf

I CERTIFY THAT THE FRAMING OF THIS STRUCTURE WILL SAFELY ACCOMMODATE CALCULATED WIND UPLIFT AND LATERAL FORCES AND EQUIPMENT DEAD LOADS. THIS IS ATTESTED TO BY MY SIGNATURE AND SEAL ON THIS DRAWING AT THE UPPER RIGHT.ELECTRICAL SPECIFICATIONS: CONFORMS TO THE REQUIREMENTS OF THE 2008 NATIONAL ELECTRICAL CODETHE BELOW ELECTRICAL SCHEMATIC DRAWING IS A TYPICAL REPRESENTATION, CERTAIN DETAILS OF THIS PROJECT MAY DIFFER,REFER TO OEM LITERATURE WHICH SHALL PREVAIL:

APPLICABLE CODE:FLORIDA BUILDING CODE 2007 W/09 SUPP

FLORIDA ELEC. 2007 CODE W/09 SUPP

DESIGNED PER:ASCE 7-05

NEC 2008

THIS PLAN IS VOID WITHOUT MY SIGNATURE & RAISED SEAL.THIS PLAN MAY NOT BE PLACED ON FILE FOR PULLING MULTIPLE PERMITS.EACH PERMIT PULLED REQUIRES ITS OWN RAISED SEAL COPY OF THIS PLAN.

ALLEN GEZELMAN16502 HANNA RD.LUTZ, FLORIDA 33549

PH. 813 650 7246FX. 866 397 9050Allen@Gezelman PE.COM

www.GezelmanPE.com

I CERTIFY THAT THIS DESIGN &SPECIFICATIONS MEET THEREQUIREMENTS OF THE CURRENTFLORIDA BUILDING CODE ANDNATIONAL ELECTRICAL CODE.

ELECTRICAL ENGINEERINGCONSULTANT:

BRUCE A. TOZIER, P.E.LIC # 67336TOZIER ENGINEERING, INC.209 S. GLEN ARVEN AVE.TEMPLE TERRACE, FL 33617OFF. (813) 988-3578CELL (813) 951-4727FAX (813) 988-3578

SCALE: 1-1/2" = 1'-0"

HOLD DOWN DETAIL

OWNER:

JAMES D BUSBY II KRISTINA A BUSBY

18701 KITTY HAWK CT, PORT ST LUCIE FL 34987

LEGAL DESCRIPTION:

PARCEL ID:3215-801-0045-000-5

AERO ACRES BLK 2 LOT 16

(1.223 AC) (OR 1376-2722: 1617-2904)

WIND LOAD:DESIGNED FOR ____ MPH 130

WIND EXPOSURE:CATEGORY _ C

COMPLIANCE: IEEE-929, IEE-1547, UL 1741, UL 1998

MINIMUM AC & DC WIRING SIZE #10 AWG COPPER

(OEM WIRING & HARNESS EXCLUDED)

SMA AMERICA, SB5000US (240V), 5000 WATT GRID

TIED PV INVERTER

SPECIFICATIONS:WWW.SOLARELECTRICSUPPLY.COM/PDF/SUNNY%20BOY/SB5000US-7000US.PDF

SCALE: NTS

EXISTING ROOF/RAMING

OWNER/CONTRACTOR

JAMES D BUSBY

18701 KITTY HAWK CT

PORT ST LUCIE FL 34987

NOTE:INVERTER TO BE LOCATED ADJACENT TO 100 AMP PANEL INSIDE HANGAR.PENETRATE THE ROOF AT THE J-BOX AS SHOWN IN THE PHOTOAND RUN CONDUIT ON THE UNDERSIDE OF THE ROOF

SCALE: NTS

UNISTRUT P5500 T

SCALE: 3/4" = 1'-0"

UNISTRUT LAYOUT DETAIL

SEE DETAIL

SCALE: 6" = 1'-0"

HOLD DOWN DETAIL

dv8230us
Released

2.001.50

1.00

0.75

1.25

Ø0.50

Ø0.25

1

8" THK FLAT STEEL

HOLES FOR PIVOT BOLT-

USED WHEN ANCHORING

ONLY ONE SOLAR PANEL

SOLAR PANEL EACH SIDE

1

8" THK FLAT STEEL

1

8" THK FLAT STEEL

1

4" INDENTURES FOR PIVOT BOLT-

USED WHEN ANCHORING

ONLY ONE SOLAR PANEL

0.75

1.25

Ø0.50

Ø0.25

1

8" THK FLAT STEEL

3.00

INDENTURES FOR PIVOT BOLT-

USED WHEN ANCHORING

ONLY ONE SOLAR PANEL

3.00

S5CLAMP-SUBSTITUE.DWG

11/4/2009 8:14 PM

02SCALE: 1" = 1"

UPPER PLATE ISOMETRIC01

SCALE: 1" = 1"

UPPER PLATE - TOP

04SCALE: 1" = 1"

LOWER PLATE ISOMETRIC03

SCALE: 1" = 1"

LOWER PLATE - TOP

HOLD DOWN BOLT HERE