AN INTERCONNECTION OF A PHOTOVOLTAIC GENERATOR (PVG) With THE POWER UTILITES GRID : Study Cases Dr. Maamar Taleb Electrical and Electronics Engineering Department University of Bahrain Energy Economy & Energy Management Forum (EEEMF2015) for MENA & Fourth Renewable Energy National Dialogue - Amman – Jordan May 18-20, 2015

Upload: basil-stone

Post on 12-Jan-2016

217 views

Category:

Documents


1 download

TRANSCRIPT

Page 1: AN INTERCONNECTION OF A PHOTOVOLTAIC GENERATOR (PVG) With THE POWER UTILITES GRID: Study Cases Dr. Maamar Taleb Electrical and Electronics Engineering

AN INTERCONNECTION OF A PHOTOVOLTAIC GENERATOR (PVG)

With THE POWER UTILITES GRID :Study Cases

Dr. Maamar Taleb Electrical and Electronics Engineering Department

University of Bahrain

Energy Economy & Energy Management Forum (EEEMF2015) for MENA & Fourth Renewable Energy National Dialogue -

Amman – JordanMay 18-20, 2015

Page 2: AN INTERCONNECTION OF A PHOTOVOLTAIC GENERATOR (PVG) With THE POWER UTILITES GRID: Study Cases Dr. Maamar Taleb Electrical and Electronics Engineering

Agenda

• Motivation and Rationale• Conventional Way of Interconnection• Proposed Idea of Interconnection• PV Panels Characteristics• Control Strategy• Experimental Setup• Performance• Conclusions

Page 3: AN INTERCONNECTION OF A PHOTOVOLTAIC GENERATOR (PVG) With THE POWER UTILITES GRID: Study Cases Dr. Maamar Taleb Electrical and Electronics Engineering

MOTIVATION AND RATIONALEGlobal Primary Energy Demand

0

500

1000

1500

2000

2500

3000

3500

4000

Coal Oil Gas Nuclear Biomass Other renewables

20052050

Fuente: IEA Energy Technology Perspectives 2008BLUE Map scenary: reducción global emisiones de CO2 en un 50% en 2050/2005

Prim

ary

ener

gysu

pply

(Mto

e)

Prim

ary

ener

gysu

pply

(Mto

e)

X6

Prim

ary

ener

gysu

pply

(Mto

e)

X3

X6

X3

Page 4: AN INTERCONNECTION OF A PHOTOVOLTAIC GENERATOR (PVG) With THE POWER UTILITES GRID: Study Cases Dr. Maamar Taleb Electrical and Electronics Engineering

• US … 20% Wind by 2030 (1 % now)• EU … 20% Renewable Energy by 2020• China … 30 GW Wind by 2020• India … 12 GW Wind by 2012

Page 5: AN INTERCONNECTION OF A PHOTOVOLTAIC GENERATOR (PVG) With THE POWER UTILITES GRID: Study Cases Dr. Maamar Taleb Electrical and Electronics Engineering

Europe´s commitment in the promotion of renewables: Directive 20/20

Page 6: AN INTERCONNECTION OF A PHOTOVOLTAIC GENERATOR (PVG) With THE POWER UTILITES GRID: Study Cases Dr. Maamar Taleb Electrical and Electronics Engineering
Page 7: AN INTERCONNECTION OF A PHOTOVOLTAIC GENERATOR (PVG) With THE POWER UTILITES GRID: Study Cases Dr. Maamar Taleb Electrical and Electronics Engineering
Page 8: AN INTERCONNECTION OF A PHOTOVOLTAIC GENERATOR (PVG) With THE POWER UTILITES GRID: Study Cases Dr. Maamar Taleb Electrical and Electronics Engineering
Page 9: AN INTERCONNECTION OF A PHOTOVOLTAIC GENERATOR (PVG) With THE POWER UTILITES GRID: Study Cases Dr. Maamar Taleb Electrical and Electronics Engineering
Page 10: AN INTERCONNECTION OF A PHOTOVOLTAIC GENERATOR (PVG) With THE POWER UTILITES GRID: Study Cases Dr. Maamar Taleb Electrical and Electronics Engineering

Conventional Way of Interconnectioncontinued

Page 11: AN INTERCONNECTION OF A PHOTOVOLTAIC GENERATOR (PVG) With THE POWER UTILITES GRID: Study Cases Dr. Maamar Taleb Electrical and Electronics Engineering

Initiative of Interconnection

0 0.005 0.01 0.015 0.02 0.025 0.03 0.035 0.04

-200

0

200

Vs

and

Vlo

ad

0 0.005 0.01 0.015 0.02 0.025 0.03 0.035 0.040

0.5

1

Pul

ses

0 0.005 0.01 0.015 0.02 0.025 0.03 0.035 0.040

0.2

0.4

Iload

0 0.005 0.01 0.015 0.02 0.025 0.03 0.035 0.04

-200

0

200

Vs

and

Vlo

ad

0 0.005 0.01 0.015 0.02 0.025 0.03 0.035 0.040

0.5

1

Pul

ses

0 0.005 0.01 0.015 0.02 0.025 0.03 0.035 0.040

5

10

15

Iload

)cos(1 KVLoad

030 090

Page 12: AN INTERCONNECTION OF A PHOTOVOLTAIC GENERATOR (PVG) With THE POWER UTILITES GRID: Study Cases Dr. Maamar Taleb Electrical and Electronics Engineering

Proposed Way of Interconnection

_

+

PVG

Sm

oo

thin

g

Co

il

AC Main SupplyBridge Rectifier

AC

load

Rectifier

Firing angle Controller

DC

Vo

ltage S

ou

rce

Firing Pulses (900 ££1800)

Page 13: AN INTERCONNECTION OF A PHOTOVOLTAIC GENERATOR (PVG) With THE POWER UTILITES GRID: Study Cases Dr. Maamar Taleb Electrical and Electronics Engineering

PV PanelsPhoto

Page 14: AN INTERCONNECTION OF A PHOTOVOLTAIC GENERATOR (PVG) With THE POWER UTILITES GRID: Study Cases Dr. Maamar Taleb Electrical and Electronics Engineering

PV PanelsCircuit and Mathematical Model

gg

gg

CVBVA

VVocI

2

)(

gg

ggggg

CVBVA

VVocVIVP

2

)(

Page 15: AN INTERCONNECTION OF A PHOTOVOLTAIC GENERATOR (PVG) With THE POWER UTILITES GRID: Study Cases Dr. Maamar Taleb Electrical and Electronics Engineering

PV MODEL PARAMETERS DETERMINATION

RL1= 23.8

RL2=13.5

RL3=4.3

Page 16: AN INTERCONNECTION OF A PHOTOVOLTAIC GENERATOR (PVG) With THE POWER UTILITES GRID: Study Cases Dr. Maamar Taleb Electrical and Electronics Engineering

PV MODELParameters Determination

121

11

)(

mm

mm

CVBVA

VVocI

222

22

)(

mm

mm

CVBVA

VVocI

323

33

)(

mm

mm

CVBVA

VVocI

424

44

)(

mm

mm

CVBVA

VVocI

Page 17: AN INTERCONNECTION OF A PHOTOVOLTAIC GENERATOR (PVG) With THE POWER UTILITES GRID: Study Cases Dr. Maamar Taleb Electrical and Electronics Engineering

PV Panels Characteristics

0 5 10 15 20 25 30 35 400

1

2

3

4

5

Vg (Volt)

Ig (

A)

0 5 10 15 20 25 30 35 400

50

100

Vg (Volt)

Pg

(W)

(a)

11:00 am

1:00 pm

9:00 am

3:00 pm

11:00 am

3:00 pm1:00 pm

9:00 am

Page 18: AN INTERCONNECTION OF A PHOTOVOLTAIC GENERATOR (PVG) With THE POWER UTILITES GRID: Study Cases Dr. Maamar Taleb Electrical and Electronics Engineering

Firing Angle ControllerBlock Diagram

Firing Pulses

Maximum Power Tracker

Pulses Generator

Desired Firing Angle

900 1800

Insolation Level

DC Side PowerPCC Voltage

Corresponding Maximum PVG

Power+

-

Measured PVG Power

Out = k if error > Out= 0 if - Error Out = - k if error < -

errorout

Output Conditionner Integrator & Limiter

Gain_____

S

Firing angle

1800

900

(a)

(b)

(c)

Synchronized Sawtooth Generator

Converter Of angle to Voltage Level

Fir in

g an

gle

AC M

ain

Volta

ge

Comparator

Firing Pulses

IInsolation

LevelPg,max

PPVG

Page 19: AN INTERCONNECTION OF A PHOTOVOLTAIC GENERATOR (PVG) With THE POWER UTILITES GRID: Study Cases Dr. Maamar Taleb Electrical and Electronics Engineering

Experimental Setup

Page 20: AN INTERCONNECTION OF A PHOTOVOLTAIC GENERATOR (PVG) With THE POWER UTILITES GRID: Study Cases Dr. Maamar Taleb Electrical and Electronics Engineering

Performance(before Interconnection of PV Panels)

Page 21: AN INTERCONNECTION OF A PHOTOVOLTAIC GENERATOR (PVG) With THE POWER UTILITES GRID: Study Cases Dr. Maamar Taleb Electrical and Electronics Engineering

Performance(after Interconnection of PV Panels)

Page 22: AN INTERCONNECTION OF A PHOTOVOLTAIC GENERATOR (PVG) With THE POWER UTILITES GRID: Study Cases Dr. Maamar Taleb Electrical and Electronics Engineering

Limitations & Drawbacks(Of Current Experimental Setup)

• Equipment Ratings

• Low Power Factor

• Harmonics Generation

Page 23: AN INTERCONNECTION OF A PHOTOVOLTAIC GENERATOR (PVG) With THE POWER UTILITES GRID: Study Cases Dr. Maamar Taleb Electrical and Electronics Engineering

Harmonics Generation Solution

AC Main Supply

(i.e Power Grid)

Controlled Bridge Converter

Ps P W-

+

PW

Ph

Wind Driven DC Machine

Active Power Filter

is

ih

iw

Controlled Bridge Converter

Ppvg-

+

Ppvg

PhotoVoltaic Generator (i.e Solar

Pannels)

ipvg

Page 24: AN INTERCONNECTION OF A PHOTOVOLTAIC GENERATOR (PVG) With THE POWER UTILITES GRID: Study Cases Dr. Maamar Taleb Electrical and Electronics Engineering

0.64 0.66 0.68 0.7

-2000

200

Vs (V

)

0.64 0.66 0.68 0.7-20

0

20Is

(A)

0.64 0.66 0.68 0.7-2

0

2

Iline

1 (A

)

0.64 0.66 0.68 0.7-10

010

Iline

2 (A

)

0.64 0.66 0.68 0.7-10

010

Iline

(A)

0.64 0.66 0.68 0.7-10

010

Ih &

Ihre

f (A)

time (s)

0.93 0.94 0.95 0.96

-2000

200

Vs (V

)

0.93 0.94 0.95 0.96-20

0

20

Is (A

)

0.93 0.94 0.95 0.96-2

0

2

Iline

1 (A

)0.93 0.94 0.95 0.96

-100

10

Iline

2 (A

)

0.93 0.94 0.95 0.96-10

010

Iline

(A)

0.93 0.94 0.95 0.96-10

010

Ih &

Ihre

f (A)

time (s)

1.16 1.18 1.2

-2000

200

Vs (V

)

1.16 1.18 1.2-20

0

20

Is (A

)

1.16 1.18 1.2-2

0

2

Iline

1 (A

)

1.16 1.18 1.2-10

010

Iline

2 (A

)

1.16 1.18 1.2-10

010

Iline

(A)

1.16 1.18 1.2-10

010

Ih &

Ihre

f (A)

time (s)

(b)

(c)

(d)

(e)

(f)

(a)

Harmonics Generation SolutionContinued

Page 25: AN INTERCONNECTION OF A PHOTOVOLTAIC GENERATOR (PVG) With THE POWER UTILITES GRID: Study Cases Dr. Maamar Taleb Electrical and Electronics Engineering

Conclusions

• Interconnecting PVG source to a main AC supply was investigated.

- The interconnection was done using a bridge rectifier. The bridge rectifier was operated in an “inverter mode of operation”.

• Quite encouraging results were reached when taken under a

random insolation level. For an almost 130 W power required by an ac load connected at the ac side of the bridge, the PVG source contributed nearly 69.23 % of such power while the main ac supply supplied the rest 33.77 % of power to the AC load.