WIND DESIGN MADE SIMPLE ICC TRI-CHAPTER UNIFORM CODE

COMMITTEE

2

2

WIND DESIGN MADE SIMPLE ICC TRI-CHAPTER CODE COMMITTEE

• With special acknowledgement to:

Dr. S. K. Ghosh, PhD

www.skghoshassociates.com

John Henry, PE

www.ICCsafe.org

Jerry J. Barbera, P.E.

www.gostructural.com

&

The SEI Institute of ASCE

http://content.seinstitute.org/

3

3

Overview of the current Wind

design provisions

4

4

1605.3.2 ASD Load Combinations Alternate Basic (UBC 94)

D + L + (Lr or S or R) (Formula 16-16)

D + L + (W) (Formula 16-17)

D + L + W + S/2 (Formula 16-18)

D + L + S + W/2 (Formula 16-19)

D + L + S + E/1.4 (Formula 16-20)

0.9D + E/1.4 (Formula 16-21)

Where wind loads are calculated in accordance with ASCE 7, the

coefficient in the above formulas shall be taken as 1.3. For other

wind loads shall be taken as 1.0.

5

5

ASD Load Combinations Alternate Basic – Allowable Stress Increase

• When using these alternate basic load combinations that

include wind or seismic loads, allowable stresses are

permitted to be increased or load combinations reduced,

where permitted by the material section of this code or

referenced standard.

• For load combinations that include the counteracting effects of

dead and wind loads, only two-thirds of the minimum dead

load likely to be in place during a design wind event shall be

used

6

6

WIND-RESISTANT DESIGN

7

7

Wind Flow Around Building

8

8

External Pressure due to Wind

9

9

Fastest-mile Wind

Instantaneous velocity of wind at a point as a function of time:

10

10

Variation of Wind Velocity with Height for a Steady Wind

11

11

Velocity Pressure-ASCE 6.5.10

• ASCE 7 adds two more factors:– Topographic Factor - Kzt

• Hills and Escarpments• Complex Equations

– Directionality Factor - Kd

• 0.85 for all building structures

IKKKV00256.0q dztz2

12

12

Gust

• Rapid fluctuation of wind

• Ordinary structures are sensitive to peak gusts

of about 1 second duration.

• Use of fastest-mile wind in design inadequate

Gust speed, Vg = Gv V

• Pressure generated by gust, pg = Gp p

p V 2 Gp = Gv2

• Flexible structures more sensitive to gust.

13

13

Basic Wind Equation – 6.5.12.2

• For buildings with External and Internal

Pressure:

qi = Velocity pressure calculated for

internal pressure.

piiGCqqGCp p

14

14

Wind-resistant Design

• Wind Pressures on a Building

15

15

1609.1 General Requirements

• Requires all parts of all buildings and

structures be designed for wind.

• Base method is ASCE 7-05.

• Permits the use of other alternatives

subject to some limitations for low rise

buildings

16

16

1609.1 General Requirements

• Allows SSTD 10-99– SBCCI - Standard for Hurricane Resistant Residential

Construction.

• Allows WFCM– AF&PA - Wood Frame Construction Manual for One and Two

Family Dwellings.

• Restricts use of SSTD 10 & WFCM to Exposure

B & C in areas without topographic effects

17

17

General Requirements

• Minimum Wind Load of 10 psf for MWFRS and

C&C (ASCE 6.1.4)

• Must meet seismic detailing even if wind

loads are greater

18

18

1609.2 & 6.2 Definitions• Important items:

– Simple Diaphragm Building

A building in which both windward and leeward wind

loads are transmitted through floor and roof diaphragms

to the same vertical MWFRS (e.g., no structural

separations)

19

19

Figure 1609 & 6-1 Basic Wind Speeds

• Based on 3 Second Gust Measurement.

• Conversion Table 1609.3.1 for 3 Second

Gust to Fastest Mile wind speed.

20

20

1609.4 & 6.5.6 Exposure Categories

• Exposure A

- No longer used in ASCE 7

• Exposure B:

– Use as the default.

• Exposure C:

– Includes shorelines of hurricane prone regions (no longer

Exposure D).

• Exposure D:

– Now applies only to inland waterways, Great Lakes,

Coastal California, Oregon, Washington, Alaska.

21

21

Enclosure Classifications (6.2)

For the purpose of determining internal

pressure coefficients, all buildings shall be

classified as enclosed, partially enclosed, or

open as defined in 6.2

22

22

Enclosure Classifications (6.2)

• BUILDING, OPEN: A building having each wall at

least 80 percent open. This condition is expressed for

each wall by the equation Ao ≥ 0.8Ag where

• Ao = total area of openings in a wall that receives

positive external pressure, in ft2

• Ag = the gross area of that wall in which Ao is

identified, in ft2

23

23

BUILDING, PARTIALLY ENCLOSEDBUILDING, PARTIALLY ENCLOSED: A building that complies with both of the following

conditions:

1. The total area of openings in a wall that receives positive external pressure exceeds the

sum of the areas of openings in the balance of the building envelope (walls and roof )

by more than 10 percent.

2. The total area of openings in a wall that receives positive external pressure exceeds 4

ft2 (0.37 m2) or 1 percent of the area of that wall, whichever is smaller, and the

percentage of openings in the balance of the building envelope does not exceed 20

percent.

These conditions are expressed by the following equations:

1. Ao > 1.10Aoi

2. Ao > 4 sq ft (0.37 m2) or >0.01Ag, whichever is smaller, and Aoi /Agi ≤ 0.20

where

Ao, Ag are as defined for Open Building

Aoi = the sum of the areas of openings in the building envelop (walls and roof) not

including Ao, in ft2 (m2)

Agi = the sum of the gross surface areas of the building envelope

(walls and roof) not including Ag, in ft2 (m2)

24

24

1609.5 Roof Systems

• All Roof Decks must be designed for wind

loads

• All Roof Coverings must be designed for

wind loads

– Except:

• Wind loads on Rigid Tiles have special loading

provisions in 1609.5.3.

25

25

ASCE 7-05 6.4 - 6.6 Design Procedures

• Choice of 3 Design Procedures

– 6.4 - Method 1 - Simplified Procedure

– 6.5 - Method 2 - Analytical Procedure

– 6.6 - Method 3 - Wind Tunnel Procedure

26

26

Simplified Provisions for Low-Rise Buildings 6.4

• ASCE 7-05 Method 1 provisions

• Allows buildings up to 60 ft

• Applies loads like SBC Simplified Method:

on projected areas

• Restricted to simple diaphragm buildings

27

27

ASCE6.4– Simplified Wind Load Method

• Conditions1. The building is a simple diaphragm building as defined in Section 6.2.

2. The building is a low-rise building as defined in Section 6.2.

3. The building is enclosed as defined in Section 6.2 and conforms to the wind-borne debris

provisions of Section 6.5.9.3.

4. The building is a regular-shaped building or structure as defined in Section 6.2.

5. The building is not classified as a flexible building as defined in Section 6.2.

6. The building does not have response characteristics making it subject to across wind

loading, vortex shedding, instability due to galloping or flutter; and does not have a site

location for which channeling effects or buffeting in the wake of upwind obstructions

warrant special consideration.

7. The building has an approximately symmetrical cross-section in each direction with either a

flat roof or a gable or hip roof with θ ≤ 45◦.

8. The building is exempted from torsional load cases as indicated in Note 5 of Fig. 6-10, or

the torsional load cases defined in Note 5 do not control the design of any of the MWFRSs

of the building.

28

28

Simplified Provisions

• MWFRS (6.4.2.1)Simplified design wind pressures for the MWFRS represent the net pressures (sum of internal and external) to be applied to the horizontal and vertical projections of building surfaces as shown in Figure 6-2. For the horizontal pressures (Zones A, B, C, D), ps is the combination of the windward and leeward pressures.

29

29

Simplified Provisions

• ps = λ Kzt I pS30 (6-1)

• λ = adjustment factor for building height and exposure

• from Fig. 6-2

• Kzt = topographic factor as defined in Section 6.5.7 evaluated

• at mean roof height, h

• I = importance factor as defined in Section 6.2

• pS30 = simplified design wind pressure for Exposure B, at

• h = 30 ft, and for I = 1.0, from Fig. 6-2

30

30

IBC Provisions Figure 6-2 MWFRS

31

31

• Method 2 – Analytical Procedure of Sect. 6.5

This method is applicable to all buildings that satisfy

the two conditions in Sect. 6.5.1

1. The building is regular in shape as defined in ASCE 7-05 Section 6.2

2. The building does not have response characteristics making it subject to across wind loading, vortex shedding, instability due to galloping or flutter; or does not have a site location for which channeling effects or buffeting in the wake of upwind obstructions warrant special consideration

2B

Analytical Procedures – ASCE 7-05

32

32

ASCE 7-05 6.5 Analytical Procedure

• Design Procedure (6.5.3):

1. Wind Speed V (Figure 6-1 map)

2. Wind Directionality Factor Kd (6.5.4.4, Table 6-4)

3. Importance Factor I (6.5.5, Table 6-1 & Table 1-1)

4. For each wind direction:

Exposure Category (6.5.6)

Velocity Pressure Exposure Coefficient

Kz, Kh (6.5.6, Table 6-3)

5. Topographic Factor, Kzt (6.5.7, Figure 6-4)

33

33

ASCE 7-05 6.5 Analytical Procedure

• Design Procedure (6.5.3):

6. Gust Effect Factor G or Gf (6.5.8)

7. Enclosure Classification (6.5.9)

8. Internal Pressure Coefficient GCpi (6.5.11.1, Figure 6-5)

9. External Pressure Coefficients Cp, GCpf (6.5.11.2) or

force coefficients Cf (6.5.11.3)

10. Velocity Pressure qz, qh (6.5.10)

qz = 0.00256 kz kzt kd V2 I Eq. 6-15

34

34

ASCE 7-05 6.5 Analytical Procedure

• Design Procedure (6.5.3)

11. Design wind load p (6.5.12) or F (6.5.13)

MWFRS:

Rigid Buildings of All heights:

p = q GCp - qi(GCpi) Eq. 6-17

Low rise: p = qh [(GCpf) - (GCpi)] Eq. 6-18

35

35

ASCE 7-05 6.5 Analytical Procedure

• Design Pressure – Components & Cladding

(6.5.12.4):

– Low rise and buildings with h 60 ft

p = qh[(GCp) - (GCpi)] Eq. 6-22

– Buildings with h > 60 ft

p = q(GCp) - qi(GCpi) Eq. 6-23

36

36

We need a simpler method

37

37

WIND DESIGN MADE SIMPLE ICC TRI-CHAPTER UNIFORM CODE COMMITTEE

TUCC ALTERNATE WIND DESIGN

PROVISIONS

38

38

WIND DESIGN MADE SIMPLE ICC TRI-CHAPTER CODE COMMITTEE

Alternate 1:

• Allows relatively small and uncomplicated

projects such as residential buildings, store

fronts, etc.. to use the MAXIMUM wind load

values indicated in the following table:

39

39

40

40

41

41

Alternate 1

Table Assumptions:

• Building Size = 50-feet x 100-feet

• Building Shape = Gable end roof

with regular shape

• Basic Wind Speed (3Sec. Gust) = 85 mph.

• Topography factor Kzt = 1.26

• Directionality factor Kd = 0.85

• Gust Effect factor G = 0.85

42

42

WIND DESIGN MADE SIMPLE ICC TRI-CHAPTER UNIFORM CODE COMMITTEE

Alternate 2:

• Allows the use of 2009 IBC’s new section 1609.6 in lieu of

ASCE Method 2 for buildings up to 75 ft in height.

• The new section 1609.6 is the result of two proposals that

were submitted to the ICC Structural Review Committee.

The proposal by the National Council of Structural

Engineers Associations (NCSEA) won the final approval

with some modification.

43

43

1609.6

Quote From The Structural Engineer magazine:

“The original motivation for these proposal was to provide a

simplified way to obtain the wind forces on a structure to

engineers who design for areas of the country where wind forces

do not govern the design of structures other than, perhaps, low-

rise, light-framed buildings.

Typically these structures would be located in areas where

earthquake design controls. However, since we started our efforts,

we have heard from engineers across the country that are eager to

see simplification incorporated into the building code process.”

44

44

2009 IBC ALTERNATE WIND DESIGN PROVISIONS

45

45

2009 IBC ALTERNATE ALL HEIGHTS DESIGN PROVISIONS

• 1609.6.1 Scope. As an alternate to ASCE 7 Section 6.5, the

following provisions are permitted to be used to determine the

wind effects on regularly shaped buildings, or other structures

which meet all of the following conditions:

• 1. The building or other structure is less than 75 feet in height,

with a height to least width ratio of 4 or less.

• 2. The building or other structure is not sensitive to dynamic

effects.

• 3. The building or other structure is not located on a site for

which channeling effects or buffeting in the wake of upwind

obstructions warrant special consideration.

46

46

2009 IBC ALTERNATE ALL HEIGHTS DESIGN PROVISIONS

• Pnet = qs Kz Cnet I Kzt (Equation 16-36)

Where:

Cnet = Net pressure coefficient based on

Kd [(G) (Cp) – (GCpi)], per Table 1609.6.2(2)

qs = Wind velocity pressure in lb/ft2 (N/m2),

Per Table 1609.6.2(1)

47

47

2009 IBC ALTERNATE ALL HEIGHTS DESIGN PROVISIONS

48

48

2009 IBC ALTERNATE ALL HEIGHTS DESIGN PROVISIONS

49

49

2009 IBC ALTERNATE ALL HEIGHTS DESIGN PROVISIONS

• In the meantime the State of California issued

January 1, 2009 amendments to the CBC Volume

II incorporating these provisions. However, the

amendments only apply to certain occupancies:

50

50

2009 IBC ALTERNATE ALL HEIGHTS DESIGN PROVISIONS

• And, the amendments are not technically

effective until August 1, 2009.

51

51

Mechanisms for allowing these alternatives

1. Adopt a local ordinance (complicated &

time consuming)

2. Allow by requiring the submittal of an

Application for Alternate Materials And

Methods of Construction (quick and

streamlined)

52

52

2009 IBC ALTERNATE ALL HEIGHTS DESIGN PROVISIONS

Example 1 for Alternate 2

53

53

54

54

Example 1 for Alternate 2

55

55

Example 1 for Alternate 2

56

56

Example 1 for Alternate 2

57

57

2009 IBC ALTERNATE ALL HEIGHTS DESIGN PROVISIONS

Example 2 for Alternate 2

58

58

Example 2 for Alternate 2

59

59

60

60

61

61

62

62

63

63

64

64