What's Next for RTU2020 & Experion SCADA
Paul Vellacott
3 © 2015 Honeywell International All Rights Reserved
Honeywell Solution Offering
End to End Solution
Experion PKS
Integrated with..
RTU2020Ready-To-Use
RTU2020
Process Controller,
I/O & EFM
Instruments, Camera, Radio,
FDAP….
4 © 2015 Honeywell International All Rights Reserved
Perfect Vision, 20/20 Vision with RTU2020
75º70º
Honeywell RTU2020 Process Controller
5 © 2015 Honeywell International All Rights Reserved
The Physical Detail...
1 2
3
4
5
7DIN Rail Mount
Honeywell RTU2020 Process Controller
R1101. 24 Vdc Power Input
2. RS485 Ports x 2
3. RS232 Ports x 2
4. Ethernet Ports x 2
5. Onboard I/O (qty 28)
6. SD Card Slot
7. Status LEDs
8. Expansion I/O
Connector
9. Control Processor Module
9
6
8
6 © 2015 Honeywell International All Rights Reserved
RTU2020 I/O Modules
Mixed I/O, 28 channels
Mixed I/O, 28 channels
Mixed I/O, 28 channels
R110
7 © 2015 Honeywell International All Rights Reserved
Using Expansion I/O Modules
1. Controller
2. I/O module
3. Right end plate
4. Left end plate
1 2
3
4 3
CAT 5
24Vdc
R110
8 © 2015 Honeywell International All Rights Reserved
Configuring Expansion I/O R110
IOMsBound variable:
complex data type
9 © 2015 Honeywell International All Rights Reserved
Perfect, 20/20 Vision with RTU2020
75º70º
Harsh Environment Specifications
10 © 2015 Honeywell International All Rights Reserved
Harsh Environment Specifications
•-40ºC to 75ºC -40 to 167ºF
•Conformal Coating – G3
•Hazardous Locations‒FM/CSA Class I Div 2
‒ATEX Zone 2
‒ IECEx Zone 275º
70º
R110
11 © 2015 Honeywell International All Rights Reserved
Perfect, 20/20 Vision with RTU2020
HART enabled I/O Channels
12 © 2015 Honeywell International All Rights Reserved
28 Channels of Mixed I/O per Module
Onboard with Controller or as Expansion I/O
CPM IOM
R110
14 © 2015 Honeywell International All Rights Reserved
All Onboard: No Special Modules or Extra Hardware
FDM
Experion
HA
RT
IP
HART
AI
AO
CMD48CMD03
SV Logic
Common
Alarm
PID
RTU2020 and HART
15 © 2015 Honeywell International All Rights Reserved
Perfect, 20/20 Vision with RTU2020
Efficient Wiring and Configuration
16 © 2015 Honeywell International All Rights Reserved
To change an RTU on-site
• Reduce exposure in hazardous environments
• Reduce production downtime
After
5 min
Before
45 min
Less Errors – Saves Time
Efficient Field Wiring & Cabinet Assembly
17 © 2015 Honeywell International All Rights Reserved
Efficient Configuration with RTU Builder
• IEC 61131-3 Programming‒ Ladder Program
‒ Function block program
‒ Structured text
‒ Instruction List
‒ Sequential Function Chart
• Intuitive Work Flows
• Online Diagnostics
• Datalog Upload
• Firmware Upgrades‒ over slow networks
R110
19 © 2015 Honeywell International All Rights Reserved
Intuitive RTU Builder R110
Task DrivenIntuitive
User Interface
Multi versionFirmwareSupport
20 © 2015 Honeywell International All Rights Reserved
Bulk Datalog Upload
Scripted bulk recovery of datalogs
R110
Alternative to DNP3 based history recovery
Remote recovery of
data
For use in external systems
21 © 2015 Honeywell International All Rights Reserved
Perfect, 20/20 Vision with RTU2020
Modern Processor
22 © 2015 Honeywell International All Rights Reserved
Modern Processor
Future Proof for Advanced Features
667 MHz Dual Core ARM® Cortex™-A9
Ready for ‒ Wireless I/O
‒ Redundant Controller
Other popular RTUs:
‒ 32 MHz Single core
‒ 256 MHz Single core
‒ 33 MHz Single core
‒ 150 MHz Single core
24 © 2015 Honeywell International All Rights Reserved
Use Wireless I/O
Reduce Capital Cost - Increase Safety - Reduce Site Time
R120
Expensive Duct Worklaid at site
Cabling at Risk
… Expensive
… Difficult
… At risk of damage
… On pre-built skids
separate to controller
… where ‘wiring’ is
25 © 2015 Honeywell International All Rights Reserved
RTU2020 Wireless I/O
Less Hardware‒ No extra modules
‒ Less spares
‒ More reliable
Single Configuration Tool ‒ Hardwired & wireless I/O
‒ No address mapping
‒ Firmware management
‒ Remote configuration &
management
Integrated - No Specialised Modules
… On board
R120
26 © 2015 Honeywell International All Rights Reserved
Configuring Wireless I/O
Configure & Commission in 1 tool
R120
29 © 2015 Honeywell International All Rights Reserved
RTU2020 Redundant Process Controller
The Physical Detail...
1. 24 Vdc Power Input x 2
2. RS485 Ports x 2
3. RS232 Ports x 2
4. Ethernet Ports 2 / CPM
6. SD Card Slot
7. Status LEDs
8. Expansion I/O
Connector
9. Control Processor Module x 2
1
3
4
9
7DIN Rail Mount
94
1
8
66
2
R120
30 © 2015 Honeywell International All Rights Reserved
RTU2020 Redundant Process Controller
500 I/O Channels across 30 I/O Modules
Mixed I/O, 28 channels
Mixed I/O, 28 channels
R120
31 © 2015 Honeywell International All Rights Reserved
Multi Well PadsOne controller with many wells
…better availability
…more uptime
… less eggs in one basket
… when you require
Pipeline Compressor Station
High availability required
Pipeline Pump StationHigh availability required
R120Use a Redundant Controller
32 © 2015 Honeywell International All Rights Reserved
Controller Redundancy Methods
Redundancy Simplified
Oth
er
RT
Us
I/O Rack
Switch
PanelCP
U1
CP
U2
PS
PS
Co
mP
S
Switch
Switch
RT
U2020
R120
• CPU Rack
‒ 2 x CPU
‒ 2 x Power supply
‒ 1 x CPM Red Chassis
‒ 1 x Switch Panel
‒ 2 x Switch cable
• I/O Rack
‒ 1 x CPU
‒ 1 x Power supply
‒ 1 x IO Chassis
‒ I/O Modules as required
• Others
‒ 2 x Switches
‒ Network cables
• 1 x Redundant Controller
• Expansion I/O Modules as
required
• 1 x right end plate
33 © 2015 Honeywell International All Rights Reserved
Configuring Redundant Controller
No Complicated Programming
R120
Select Controller Type:
Non-Redundant
Or
Redundant
34 © 2015 Honeywell International All Rights Reserved
Perfect, 20/20 Vision with RTU2020
Flow Calculations
35 © 2015 Honeywell International All Rights Reserved
Gas & Liquid Flow Calculations
Now verified to AER Directive 17
Standards Library Description
AGA
AGA 3 Orifice Meter
AGA 5 Volume to Energy Calculation
AGA 7 Turbine Meter
AGA 9 Ultrasonic Meter
AGA 8 Gas Compressibility
AGA 11 Coriolis Metering
API
API 11.1 Volume Correction Factors
API 11.2.2/M Compressibility Factors
API 11.2.4 Temperature Correction
API 11.2.5 Correction Factor for pressure
ISO
ISO 6976Natural gas: calorific value, density,
relative density and Wobbe Index
ISO 5167Pressure differential devices such
as orifice plates and venturisR110
36 © 2015 Honeywell International All Rights Reserved
Gas Meter Run
API 21.1 Compliant
R110
• RTU Builder 5 step ‘wizard’‒ Orifice
‒ Turbine
‒ Ultrasonic
‒ Coriolis
• 4 meter runs per RTU
38 © 2015 Honeywell International All Rights Reserved
Meter Run Data via Enron Modbus
All API 21.1 Compliant
Meter Data Collection StatusIn Station
EFM
RepositorySCADA
Interface
Experion
Server
Monitoring
& Control
RTU2020
EFM
Experion
StationGas
Management
R430
39 © 2015 Honeywell International All Rights Reserved
HMI Design Alarm Management Distributed System Architecture
Virtualization Solutions Radically Simplified Configuration Superior Operator Experience
Experion SCADA
40 © 2015 Honeywell International All Rights Reserved
EFM Protocols with EFM Export Option
• EFM Protocols‒ Enron Modbus
‒ Flow-X EFM
‒ Bristol Babcock EFM
‒ Omni
‒ Emerson ROC
‒ ABB TotalFlow
• Export to:‒ FlowCal (CFX files) or
‒ CSV file
• Support for Gas & Liquids EFMs‒ Gas: API 21.1
‒ Liquids: API 21.2
One System to Collect All Data
SCADA
Interface
Experion
Server
Monitoring
& Control
Electronic Flow Meter
Experion
StationGas
Management
EFM Repository
•Transaction records
•Audit Events
•Configuration
CFX / CSV
export
Transaction record collection integratedinto polling engine
41 © 2015 Honeywell International All Rights Reserved
• Multiple people working on the same
server at the same time
• Up to 12 concurrent Users
• A ‘LEAP’ enabler
• Management of Change‒ Logging and reporting of SCADA point
changes
Supports API 1168: Recommended Practice for Pipeline Control Room Management
Quick Builder Concurrent Users
42 © 2015 Honeywell International All Rights Reserved
• For custom displays‒ HMI Web Display Builder
‒ New display repository
Version control
Check in, check out
• Supports API 1168:
Recommended Practice for
Pipeline Control Room
Management
Inbuilt Management of Change of the HMI
Display Builder MOC
43 © 2015 Honeywell International All Rights Reserved
User Defined Parameters
New types:“Scanned – Analog”“Scanned – Status”
Config for this parameter
Use case: Motor Status
Use case: Flag arrays
Use case: PLC PID Loop
44 © 2015 Honeywell International All Rights Reserved
PLC Configuration Options such as PID Tuning
User defined
scanned
parameters on an
Analog point
Example Use Case: PLC PID Loops
45 © 2015 Honeywell International All Rights Reserved
IEC 61850 SCADA Interface
Experion’s Integrated Electrical Automation Solution
Thursday 09:55 – 10:40 Venecia
46 © 2015 Honeywell International All Rights Reserved
IEC 61850 SCADA Interface, update
• Enhanced Configuration‒ History & Trend config
‒ Import/Export bulk build
‒ IED cloning bulk build
• Alarm and SOE on same
point
• Selective Report Enable
• Field Timestamp on events
• Q3 2015 update:‒ Edition 2 support
‒ Single Line Diagrams from
SCD files
‒ Experion PRP driver
Protectio
n Relay TMUIntelligent
breaker
Clone
R431
47 © 2015 Honeywell International All Rights Reserved
HMI Design Alarm Management Distributed System Architecture
Virtualization Solutions Radically Simplified Configuration Superior Operator Experience
Experion SCADA