Universal Stopper InstallSTI-13000 & STI-14000 Series
Rely on STI®
SpecificationsPolycarbonate Enclosure· Flammability - flush and surface mount models (Fig. 2, 3 & 4): UL 94 V-2, enclosed flush and enclosed back box models (Fig. 5 & 6): UL 94 5VA· Cover wall thickness 0.125 inches
Dry Contact Relay· 30 VAC/VDC, 1A
Temperature Range· Electronics operating range: -40° to 120°F (-40° to 49°C) Below -4°F (-20°C), a remote power source is recommended· Polycarbonate rated: -40° to 284°F (-40° to 140°C)
Installation Notes· When used outdoors, the manual station must also be rated for outdoor use.· UL Listing does not permit external power source or connection of horn relay contacts to fire alarm or life safety devices.· When properly installed, the operation of this cover will not interfere with the function of your life safety system.· Horn operation and performance must be tested annually. Battery replacement is recommended annually dependent on usage and
battery expiration date.· Ensure the service pin is properly inserted in the service pin receptor to silence horn while performing installation or servicing horn.· If mounting to an uneven surface, a backplate (STI-1314) is recommended to help ensure proper sealing to mounting surface. · The backplate may be drilled if wire access or screw mounting holes are needed.
ApprovalsIt has been tested and approved or listed by:· UL, CUL Listed - S2466· UL Certified to meet ADA· NEMA Type 3RX models with enclosed flush mount and enclosed back box options
Polycarbonate Cleaning InstructionsRinse with water to remove abrasive dust and dirt. Wash with soap or mild detergent, using a soft cloth. Rinse once more then dry with a soft cloth or chamois. Exercise caution when using water inside enclosure. Make sure unit is completely dry inside before reassembling. To remove grease or wet paint from exterior of cover, rub gently with a soft cloth thoroughly wetted with Naptha. Then wash and rinse. Do not use razor blades.
4.08 in.(104mm)
5.42 in.(138mm)
4.96 in.(126mm)
4.31 in.(110mm)
3.25 in.(83mm)
2.54 in.(84mm)
2.66 in.(68mm)
2.0 in.(51mm)
1.5 in.(38mm)
1.0 in.(25mm)
FLUSH END VIEW
.67 in.(17mm)
5.95 in.(151mm)WITHOUT HORN
5.28 in.(134mm)WITH HORN
.42 in.(11mm)
5.42 in.(138mm)WITH HORN
6.36 in.(162mm)WITHOUT HORN
FLUSH SIDE VIEW
LIFT HERE
TEXT HERE
5.950 in.(151.13mm)
6.798 in.(172.68mm)
5.7 in.(144.78mm)
3.83 in.(97.28mm)
4.08 in.(103.63mm)
4.898 in.(124.42mm)
5.699 in.(144.75mm)
LIFT HERE
TEXT HERE
5.950 in.(151.13mm)
6.798 in.(172.68mm)
5.7 in.(144.78mm)
3.83 in.(97.28mm)
4.08 in.(103.63mm)
4.898 in.(124.42mm)
5.699 in.(144.75mm)
LOCKINGTAB
LIFT HERE
TEXT HERE
5.95 in.(151mm)
6.80 in.(172mm)5.7 in.
(144mm)
3.83 in.(97mm)
4.08 in.(103mm)
4.90 in.(124mm)
5.70 in.(144mm)
LOCKING TAB
Fig. 1 - Dimensions Center pull station to the Universal Stopper with the help of dimensions shown in Fig. 1.
Open cover, use frame or optional backplate to mark mounting holes.
NOTE: Be sure the entire cover travel will not interfere with operation of the pull station or other safety system equipment when installed.
Horn (battery included) current draw dBA @ 9VDC STI-13*20 & STI-13*30 models 9vdc 12vdc 24vdc 1 ft. 3 ft. 10 ft. Low volume 36 mA 42 mA 22 mA 98 87 75 High volume 155 mA 146 mA 95 mA 108 93 82 Standby current 0.03 mA 0.64 mA 1.9 mA - - - current draw dBA @ 3VDC STI-14*20 & STI-14*30 models 3vdc 12vdc 24vdc 1 ft. 3 ft. 10 ft. Low volume 60 mA 46 mA 25 mA 84 74 62 High volume 140 mA 87 mA 45 mA 95 85 76 Standby current 0.04 mA 0.10 mA 0.014 mA - - -
See website for accessories
Fig. 2 - Flush Mounting Option - Models 130** & 140**
Fig. 4 - Surface Mounting Option - Models 132** & 142**
DRILL 3/16 DIA. HOLES 1-1/4 in. DEEP WHENUSING ANCHORS
DRILL 7/64 DIA. HOLES 1-1/4 in. DEEP WHENANCHORS ARE NOT USED
LOCKING TAB DRILL 1/8 in. HOLE WHILE COVER IS CLOSED. INSERT THE BREAKAWAY SEAL (KIT-65) COMPLETELY INTO THE LOCKING TAB.*NOT FOR USE ON FIRE OR EMERGENCY SIGNAL APPLICATIONS.
#6 x 1-1/4 in. SCREW(4) PROVIDED
STI-1314 OPTIONAL BACKPLATE -RECOMMENDED WHEN MOUNTING TO UNEVEN SURFACE
#6 x 1-1/4 in. SCREW(4) PROVIDED
1/2 in. & 3/4 in. CONDUITWEATHER GASKET
STI-1314 OPTIONAL BACKPLATE -RECOMMENDED WHEN MOUNTING TO UNEVEN SURFACE
DRILL 3/16 DIA. HOLES1-1/4 in. DEEP WHENUSING ANCHORS
DRILL 7/64 DIA. HOLES1-1/4 in. DEEP WHENANCHORS ARE NOT USED
LOCKING TAB DRILL 1/8 in. HOLE WHILE COVER IS CLOSED. INSERT THE BREAKAWAY SEAL (KIT-65) COMPLETELY INTO THE LOCKING TAB.*NOT USED ON FIRE OR EMERGENCY SIGNAL APPLICATIONS.
STI-1401 GASKET
LOCKING TAB DRILL 1/8 in. HOLE WHILE COVER IS CLOSED.INSERT THE BREAKAWAY SEAL (KIT-65)COMPLETELY INTO THE LOCKING TAB.*NOT USED ON FIRE OR EMERGENCY SIGNAL APPLICATIONS.
DRILL 3/16 DIA. HOLES1-1/4 in. DEEP WHEN USING ANCHORS
DRILL 7/64 DIA. HOLES1-1/4 in. DEEP WHEN ANCHORS ARE NOT USED
#6 x 1-1/4 in. SCREW(4) PROVIDED
IP67 GROMMET FOR REMOTE CABLE OPTIONDRILL 5/8 in. (16mm)
(INCLUDED WITH REMOTE OPTION)DRILL POINT CENTER LOCATED ON
BACK SIDE OF MOUNTING PLATE
DRILL 3/16 DIA. HOLES 1-1/4 in. DEEP WHEN USING ANCHORS
DRILL 7/64 DIA. HOLES 1-1/4 in. DEEP WHEN ANCHORS ARE NOT USED
#6 x 1-1/4 in. SCREW(4) PROVIDED
#6 - 32 x 1/2 in. PHIL. PANHEAD SCREW(2) PROVIDED SEALED MOUNTING PLATE (SHOWN)
LOCATE GROMET AS NEEDEDDRILL 5/8 in (16mm) HOLEINSERT GROMET AS SHOWN
FEED WIRES THROUGH GROMET(INCLUDED WITH SEALED MOUNTING PLATE)
3/4 in. NPT PLUG (1) PROVIDEDUSE A FLAT HEAD SCREWDRIVER OR COIN TO REMOVE.APPLY THREAD SEALANT. SCREW NPT BACK INTO BACK BOX
LOCKING TAB DRILL 1/8 in. HOLE WHILE COVER IS CLOSED. INSERT THE BREAKAWAY SEAL (KIT-65)COMPLETELY INTO THE LOCKING TAB.*NOT FOR USE ON FIRE OR EMERGENCY SIGNAL APPLICATION.
#6 O-RING USE TO SEALBACK BOX MOUNTING HOLES
(4) PROVIDED
IP67
A
5 CONDUCTORWIRE HARNESS
SERVICE PIN (1) PROVIDED
ROTATE BOTTOM END OFBATTERY UPWARD FOR REMOVAL
HILOW FACTORY DEFAULT HIGH
VOLUME SWITCH
#6 - 32 x 1/2 in. PHIL. FLATHEAD SCREW(6) PROVIDED
#4 HI-LO SCREW(2) PROVIDED
WHEN REPLACING COVERMAKE SURE COVER IS UNDERHORN CASE TAB AND ROTATECOVER CLOSED. INSERT HI-LOSCREWS AND TIGHTEN.
HORN COVER
REMOVE BOTH HI-LOSCREWS AND ROTATE COVER OPEN AS SHOWN.
HORN CASE SERVICE PINRECEPTOR
ENCLOSEDFLUSH MOUNT
COVER ASSEMBLY
#6 1-1/4 in. SCREW(4) PROVIDED
STI-1401 GASKET
EXISTING ULTYPE 3R RATEDIN-WALL ELECTRICAL BOX
DRILL 3/16 DIA. HOLES1 1/4 in. DEEP WHEN USING ANCHORS
DRILL 7/64 DIA. HOLES1 1/4 in. DEEP WHEN ANCHORS ARE NOT USED
PLASTIC WALL ANCHOR(4) PROVIDED
LOCKING TABDRILL 1/8 in. HOLE WHILE COVER IS CLOSED. INSERT THEBREAKWAY SEAL (KIT-65) COMPLETELY INTO THE LOCKING TAB.*NOT FOR USE ON FIRE OR EMERGENCY SIGNAL APPLICATIONS.
CONDUIT INSERT(2) PROVIDED
PLASTIC WALL ANCHOR(4) PROVIDED
#8x10 WALL ANCHOR(4) PROVIDED
INSERT(2) PROVIDED
#8x10 WALL ANCHOR(4) PROVIDED
PLASTIC WALL ANCHOR(4) PROVIDED
Fit appropriate conduit weather gasket to conduit. Then fit gasket to insert or directly to the housing knock-out. For additional seal reliability a bead of silicone may be applied to conduit fitting.
Fig. 3 - Flush Mount with add-on Spacer - Models 131** & 141**
BREAK OFF ALL (4) OF THE CONDUIT WINDOWS AND TABSTHEN TRIM SHARP EDGES BEFORE INSTALLATION
STI-1331 SPACER
CONDUIT INSERT(2) PROVIDED
INSERT(2) PROVIDED
#6 x 2-1/2 in. SCREW(4) PROVIDED
GASKET CAN BE CUT TOINSTALL BEHIND CONDUIT
G01307 SPACER/WALL GASKET**Models may contain form-in-place gasket on spacer and 1/8” diameter gaskets for conduit areas.
STI-1314 OPTIONAL BACKPLATE -RECOMMENDED WHENMOUNTING TO UNEVEN SURFACE
BREAK OFF ALL (4)OF THE CONDUITWINDOWS AND
TABS THEN TRIMSHARP EDGES
BEFORE INSTALLATION
LOCKING TABDRILL 1/8 in. HOLE WHILE COVER IS CLOSED. INSERT THEBREAKWAY SEAL (KIT-65) COMPLETELY INTO THE LOCKING TAB.*NOT FOR USE ON FIRE OR EMERGENCY SIGNAL APPLICATIONS.
LOCKING TABDRILL 1/8 in. HOLE WHILE COVER IS CLOSED. INSERT THEBREAKWAY SEAL (KIT-65) COMPLETELY INTO THE LOCKING TAB.*NOT FOR USE ON FIRE OR EMERGENCY SIGNAL APPLICATIONS.
INSERT(2) PROVIDED
CONDUIT INSERT(2) PROVIDED
1/2 in. and 3/4 in.CONDUIT WEATHER GASKET
(2) PROVIDED
PLASTIC WALL ANCHOR(4) PROVIDED
GASKET CAN BE CUT TOINSTALL BEHIND CONDUIT
#6 x 1-1/4 in. SCREW(4) PROVIDED
DRILL 3/16 DIA. HOLES1-1/4 in. DEEP WHENUSING ANCHORSDRILL 7/64 DIA. HOLES1-1/4 in. DEEP WHENANCHORS ARE NOT USED
PLASTIC WALL ANCHOR(4) PROVIDED
DRILL 3/16 DIA. HOLES1-1/4 in. DEEP WHENUSING ANCHORSDRILL 7/64 DIA. HOLES1-1/4 in. DEEP WHENANCHORS ARE NOT USED
1/2 in. and3/4 in. CONDUITWEATHER GASKET(2) PROVIDEDG01331
SPACER/WALL GASKET
BREAK OFF ALL (4) OF THE CONDUIT WINDOWS AND TABSTHEN TRIM SHARP EDGES BEFORE INSTALLATION
STI-1331 SPACER
CONDUIT INSERT(2) PROVIDED
INSERT(2) PROVIDED
#6 x 2-1/2 in. SCREW(4) PROVIDED
GASKET CAN BE CUT TOINSTALL BEHIND CONDUIT
G01307 SPACER/WALL GASKET**Models may contain form-in-place gasket on spacer and 1/8” diameter gaskets for conduit areas.
STI-1314 OPTIONAL BACKPLATE -RECOMMENDED WHENMOUNTING TO UNEVEN SURFACE
BREAK OFF ALL (4)OF THE CONDUITWINDOWS AND
TABS THEN TRIMSHARP EDGES
BEFORE INSTALLATION
LOCKING TABDRILL 1/8 in. HOLE WHILE COVER IS CLOSED. INSERT THEBREAKWAY SEAL (KIT-65) COMPLETELY INTO THE LOCKING TAB.*NOT FOR USE ON FIRE OR EMERGENCY SIGNAL APPLICATIONS.
LOCKING TABDRILL 1/8 in. HOLE WHILE COVER IS CLOSED. INSERT THEBREAKWAY SEAL (KIT-65) COMPLETELY INTO THE LOCKING TAB.*NOT FOR USE ON FIRE OR EMERGENCY SIGNAL APPLICATIONS.
INSERT(2) PROVIDED
CONDUIT INSERT(2) PROVIDED
1/2 in. and 3/4 in.CONDUIT WEATHER GASKET
(2) PROVIDED
PLASTIC WALL ANCHOR(4) PROVIDED
GASKET CAN BE CUT TOINSTALL BEHIND CONDUIT
#6 x 1-1/4 in. SCREW(4) PROVIDED
DRILL 3/16 DIA. HOLES1-1/4 in. DEEP WHENUSING ANCHORSDRILL 7/64 DIA. HOLES1-1/4 in. DEEP WHENANCHORS ARE NOT USED
PLASTIC WALL ANCHOR(4) PROVIDED
DRILL 3/16 DIA. HOLES1-1/4 in. DEEP WHENUSING ANCHORSDRILL 7/64 DIA. HOLES1-1/4 in. DEEP WHENANCHORS ARE NOT USED
1/2 in. and3/4 in. CONDUITWEATHER GASKET(2) PROVIDEDG01331
SPACER/WALL GASKET
Fig. 6 - Enclosed Back Box Mounting Option - Models 134**, 135**, 138**, 139**, 144**, 145**, 148** & 149** NEMA TYPE 3RX
DRILL 3/16 DIA. HOLES 1-1/4 in. DEEP WHENUSING ANCHORS
DRILL 7/64 DIA. HOLES 1-1/4 in. DEEP WHENANCHORS ARE NOT USED
LOCKING TAB DRILL 1/8 in. HOLE WHILE COVER IS CLOSED. INSERT THE BREAKAWAY SEAL (KIT-65) COMPLETELY INTO THE LOCKING TAB.*NOT FOR USE ON FIRE OR EMERGENCY SIGNAL APPLICATIONS.
#6 x 1-1/4 in. SCREW(4) PROVIDED
STI-1314 OPTIONAL BACKPLATE -RECOMMENDED WHEN MOUNTING TO UNEVEN SURFACE
#6 x 1-1/4 in. SCREW(4) PROVIDED
1/2 in. & 3/4 in. CONDUITWEATHER GASKET
STI-1314 OPTIONAL BACKPLATE -RECOMMENDED WHEN MOUNTING TO UNEVEN SURFACE
DRILL 3/16 DIA. HOLES1-1/4 in. DEEP WHENUSING ANCHORS
DRILL 7/64 DIA. HOLES1-1/4 in. DEEP WHENANCHORS ARE NOT USED
LOCKING TAB DRILL 1/8 in. HOLE WHILE COVER IS CLOSED. INSERT THE BREAKAWAY SEAL (KIT-65) COMPLETELY INTO THE LOCKING TAB.*NOT USED ON FIRE OR EMERGENCY SIGNAL APPLICATIONS.
STI-1401 GASKET
LOCKING TAB DRILL 1/8 in. HOLE WHILE COVER IS CLOSED.INSERT THE BREAKAWAY SEAL (KIT-65)COMPLETELY INTO THE LOCKING TAB.*NOT USED ON FIRE OR EMERGENCY SIGNAL APPLICATIONS.
DRILL 3/16 DIA. HOLES1-1/4 in. DEEP WHEN USING ANCHORS
DRILL 7/64 DIA. HOLES1-1/4 in. DEEP WHEN ANCHORS ARE NOT USED
#6 x 1-1/4 in. SCREW(4) PROVIDED
IP67 GROMMET FOR REMOTE CABLE OPTIONDRILL 5/8 in. (16mm)
(INCLUDED WITH REMOTE OPTION)DRILL POINT CENTER LOCATED ON
BACK SIDE OF MOUNTING PLATE
DRILL 3/16 DIA. HOLES 1-1/4 in. DEEP WHEN USING ANCHORS
DRILL 7/64 DIA. HOLES 1-1/4 in. DEEP WHEN ANCHORS ARE NOT USED
#6 x 1-1/4 in. SCREW(4) PROVIDED
#6 - 32 x 1/2 in. PHIL. PANHEAD SCREW(2) PROVIDED SEALED MOUNTING PLATE (SHOWN)
LOCATE GROMET AS NEEDEDDRILL 5/8 in (16mm) HOLEINSERT GROMET AS SHOWN
FEED WIRES THROUGH GROMET(INCLUDED WITH SEALED MOUNTING PLATE)
3/4 in. NPT PLUG (1) PROVIDEDUSE A FLAT HEAD SCREWDRIVER OR COIN TO REMOVE.APPLY THREAD SEALANT. SCREW NPT BACK INTO BACK BOX
LOCKING TAB DRILL 1/8 in. HOLE WHILE COVER IS CLOSED. INSERT THE BREAKAWAY SEAL (KIT-65)COMPLETELY INTO THE LOCKING TAB.*NOT FOR USE ON FIRE OR EMERGENCY SIGNAL APPLICATION.
#6 O-RING USE TO SEALBACK BOX MOUNTING HOLES
(4) PROVIDED
IP67
A
5 CONDUCTORWIRE HARNESS
SERVICE PIN (1) PROVIDED
ROTATE BOTTOM END OFBATTERY UPWARD FOR REMOVAL
HILOW FACTORY DEFAULT HIGH
VOLUME SWITCH
#6 - 32 x 1/2 in. PHIL. FLATHEAD SCREW(6) PROVIDED
#4 HI-LO SCREW(2) PROVIDED
WHEN REPLACING COVERMAKE SURE COVER IS UNDERHORN CASE TAB AND ROTATECOVER CLOSED. INSERT HI-LOSCREWS AND TIGHTEN.
HORN COVER
REMOVE BOTH HI-LOSCREWS AND ROTATE COVER OPEN AS SHOWN.
HORN CASE SERVICE PINRECEPTOR
ENCLOSEDFLUSH MOUNT
COVER ASSEMBLY
#6 1-1/4 in. SCREW(4) PROVIDED
STI-1401 GASKET
EXISTING ULTYPE 3R RATEDIN-WALL ELECTRICAL BOX
DRILL 3/16 DIA. HOLES1 1/4 in. DEEP WHEN USING ANCHORS
DRILL 7/64 DIA. HOLES1 1/4 in. DEEP WHEN ANCHORS ARE NOT USED
PLASTIC WALL ANCHOR(4) PROVIDED
LOCKING TABDRILL 1/8 in. HOLE WHILE COVER IS CLOSED. INSERT THEBREAKWAY SEAL (KIT-65) COMPLETELY INTO THE LOCKING TAB.*NOT FOR USE ON FIRE OR EMERGENCY SIGNAL APPLICATIONS.
CONDUIT INSERT(2) PROVIDED
PLASTIC WALL ANCHOR(4) PROVIDED
#8x10 WALL ANCHOR(4) PROVIDED
INSERT(2) PROVIDED
#8x10 WALL ANCHOR(4) PROVIDED
PLASTIC WALL ANCHOR(4) PROVIDED
DRILL 3/16 DIA. HOLES 1-1/4 in. DEEP WHENUSING ANCHORS
DRILL 7/64 DIA. HOLES 1-1/4 in. DEEP WHENANCHORS ARE NOT USED
LOCKING TAB DRILL 1/8 in. HOLE WHILE COVER IS CLOSED. INSERT THE BREAKAWAY SEAL (KIT-65) COMPLETELY INTO THE LOCKING TAB.*NOT FOR USE ON FIRE OR EMERGENCY SIGNAL APPLICATIONS.
#6 x 1-1/4 in. SCREW(4) PROVIDED
STI-1314 OPTIONAL BACKPLATE -RECOMMENDED WHEN MOUNTING TO UNEVEN SURFACE
#6 x 1-1/4 in. SCREW(4) PROVIDED
1/2 in. & 3/4 in. CONDUITWEATHER GASKET
STI-1314 OPTIONAL BACKPLATE -RECOMMENDED WHEN MOUNTING TO UNEVEN SURFACE
DRILL 3/16 DIA. HOLES1-1/4 in. DEEP WHENUSING ANCHORS
DRILL 7/64 DIA. HOLES1-1/4 in. DEEP WHENANCHORS ARE NOT USED
LOCKING TAB DRILL 1/8 in. HOLE WHILE COVER IS CLOSED. INSERT THE BREAKAWAY SEAL (KIT-65) COMPLETELY INTO THE LOCKING TAB.*NOT USED ON FIRE OR EMERGENCY SIGNAL APPLICATIONS.
STI-1401 GASKET
LOCKING TAB DRILL 1/8 in. HOLE WHILE COVER IS CLOSED.INSERT THE BREAKAWAY SEAL (KIT-65)COMPLETELY INTO THE LOCKING TAB.*NOT USED ON FIRE OR EMERGENCY SIGNAL APPLICATIONS.
DRILL 3/16 DIA. HOLES1-1/4 in. DEEP WHEN USING ANCHORS
DRILL 7/64 DIA. HOLES1-1/4 in. DEEP WHEN ANCHORS ARE NOT USED
#6 x 1-1/4 in. SCREW(4) PROVIDED
IP67 GROMMET FOR REMOTE CABLE OPTIONDRILL 5/8 in. (16mm)
(INCLUDED WITH REMOTE OPTION)DRILL POINT CENTER LOCATED ON
BACK SIDE OF MOUNTING PLATE
DRILL 3/16 DIA. HOLES 1-1/4 in. DEEP WHEN USING ANCHORS
DRILL 7/64 DIA. HOLES 1-1/4 in. DEEP WHEN ANCHORS ARE NOT USED
#6 x 1-1/4 in. SCREW(4) PROVIDED
#6 - 32 x 1/2 in. PHIL. PANHEAD SCREW(2) PROVIDED SEALED MOUNTING PLATE (SHOWN)
LOCATE GROMET AS NEEDEDDRILL 5/8 in (16mm) HOLEINSERT GROMET AS SHOWN
FEED WIRES THROUGH GROMET(INCLUDED WITH SEALED MOUNTING PLATE)
3/4 in. NPT PLUG (1) PROVIDEDUSE A FLAT HEAD SCREWDRIVER OR COIN TO REMOVE.APPLY THREAD SEALANT. SCREW NPT BACK INTO BACK BOX
LOCKING TAB DRILL 1/8 in. HOLE WHILE COVER IS CLOSED. INSERT THE BREAKAWAY SEAL (KIT-65)COMPLETELY INTO THE LOCKING TAB.*NOT FOR USE ON FIRE OR EMERGENCY SIGNAL APPLICATION.
#6 O-RING USE TO SEALBACK BOX MOUNTING HOLES
(4) PROVIDED
IP67
A
5 CONDUCTORWIRE HARNESS
SERVICE PIN (1) PROVIDED
ROTATE BOTTOM END OFBATTERY UPWARD FOR REMOVAL
HILOW FACTORY DEFAULT HIGH
VOLUME SWITCH
#6 - 32 x 1/2 in. PHIL. FLATHEAD SCREW(6) PROVIDED
#4 HI-LO SCREW(2) PROVIDED
WHEN REPLACING COVERMAKE SURE COVER IS UNDERHORN CASE TAB AND ROTATECOVER CLOSED. INSERT HI-LOSCREWS AND TIGHTEN.
HORN COVER
REMOVE BOTH HI-LOSCREWS AND ROTATE COVER OPEN AS SHOWN.
HORN CASE SERVICE PINRECEPTOR
ENCLOSEDFLUSH MOUNT
COVER ASSEMBLY
#6 1-1/4 in. SCREW(4) PROVIDED
STI-1401 GASKET
EXISTING ULTYPE 3R RATEDIN-WALL ELECTRICAL BOX
DRILL 3/16 DIA. HOLES1 1/4 in. DEEP WHEN USING ANCHORS
DRILL 7/64 DIA. HOLES1 1/4 in. DEEP WHEN ANCHORS ARE NOT USED
PLASTIC WALL ANCHOR(4) PROVIDED
LOCKING TABDRILL 1/8 in. HOLE WHILE COVER IS CLOSED. INSERT THEBREAKWAY SEAL (KIT-65) COMPLETELY INTO THE LOCKING TAB.*NOT FOR USE ON FIRE OR EMERGENCY SIGNAL APPLICATIONS.
CONDUIT INSERT(2) PROVIDED
PLASTIC WALL ANCHOR(4) PROVIDED
#8x10 WALL ANCHOR(4) PROVIDED
INSERT(2) PROVIDED
#8x10 WALL ANCHOR(4) PROVIDED
PLASTIC WALL ANCHOR(4) PROVIDED
Fig. 5 - Enclosed Flush Mounting Option - Models 133** & 143** NEMA TYPE 3RX
STI-134** STI-144**
STI-135** STI-145**
STI-136** STI-146**
STI-137** STI-147**
STI-138** STI-148**
STI-139** STI-149**
STI-13A** STI-14A**
STI-13B** STI-14B**
Back BoxConduit Thread
3/4 NPT
20mm
3/4 NPT
20mm
Electrical BoxType
North America
European
European
North America
Models
DRILL 3/16 DIA. HOLES 1-1/4 in. DEEP WHENUSING ANCHORS
DRILL 7/64 DIA. HOLES 1-1/4 in. DEEP WHENANCHORS ARE NOT USED
LOCKING TAB DRILL 1/8 in. HOLE WHILE COVER IS CLOSED. INSERT THE BREAKAWAY SEAL (KIT-65) COMPLETELY INTO THE LOCKING TAB.*NOT FOR USE ON FIRE OR EMERGENCY SIGNAL APPLICATIONS.
#6 x 1-1/4 in. SCREW(4) PROVIDED
STI-1314 OPTIONAL BACKPLATE -RECOMMENDED WHEN MOUNTING TO UNEVEN SURFACE
#6 x 1-1/4 in. SCREW(4) PROVIDED
1/2 in. & 3/4 in. CONDUITWEATHER GASKET
STI-1314 OPTIONAL BACKPLATE -RECOMMENDED WHEN MOUNTING TO UNEVEN SURFACE
DRILL 3/16 DIA. HOLES1-1/4 in. DEEP WHENUSING ANCHORS
DRILL 7/64 DIA. HOLES1-1/4 in. DEEP WHENANCHORS ARE NOT USED
LOCKING TAB DRILL 1/8 in. HOLE WHILE COVER IS CLOSED. INSERT THE BREAKAWAY SEAL (KIT-65) COMPLETELY INTO THE LOCKING TAB.*NOT USED ON FIRE OR EMERGENCY SIGNAL APPLICATIONS.
STI-1401 GASKET
LOCKING TAB DRILL 1/8 in. HOLE WHILE COVER IS CLOSED.INSERT THE BREAKAWAY SEAL (KIT-65)COMPLETELY INTO THE LOCKING TAB.*NOT USED ON FIRE OR EMERGENCY SIGNAL APPLICATIONS.
DRILL 3/16 DIA. HOLES1-1/4 in. DEEP WHEN USING ANCHORS
DRILL 7/64 DIA. HOLES1-1/4 in. DEEP WHEN ANCHORS ARE NOT USED
#6 x 1-1/4 in. SCREW(4) PROVIDED
IP67 GROMMET FOR REMOTE CABLE OPTIONDRILL 5/8 in. (16mm)
(INCLUDED WITH REMOTE OPTION)DRILL POINT CENTER LOCATED ON
BACK SIDE OF MOUNTING PLATE
DRILL 3/16 DIA. HOLES 1-1/4 in. DEEP WHEN USING ANCHORS
DRILL 7/64 DIA. HOLES 1-1/4 in. DEEP WHEN ANCHORS ARE NOT USED
#6 x 1-1/4 in. SCREW(4) PROVIDED
#6 - 32 x 1/2 in. PHIL. PANHEAD SCREW(2) PROVIDED SEALED MOUNTING PLATE (SHOWN)
LOCATE GROMET AS NEEDEDDRILL 5/8 in (16mm) HOLEINSERT GROMET AS SHOWN
FEED WIRES THROUGH GROMET(INCLUDED WITH SEALED MOUNTING PLATE)
3/4 in. NPT PLUG (1) PROVIDEDUSE A FLAT HEAD SCREWDRIVER OR COIN TO REMOVE.APPLY THREAD SEALANT. SCREW NPT BACK INTO BACK BOX
LOCKING TAB DRILL 1/8 in. HOLE WHILE COVER IS CLOSED. INSERT THE BREAKAWAY SEAL (KIT-65)COMPLETELY INTO THE LOCKING TAB.*NOT FOR USE ON FIRE OR EMERGENCY SIGNAL APPLICATION.
#6 O-RING USE TO SEALBACK BOX MOUNTING HOLES
(4) PROVIDED
IP67
A
5 CONDUCTORWIRE HARNESS
SERVICE PIN (1) PROVIDED
ROTATE BOTTOM END OFBATTERY UPWARD FOR REMOVAL
HILOW FACTORY DEFAULT HIGH
VOLUME SWITCH
#6 - 32 x 1/2 in. PHIL. FLATHEAD SCREW(6) PROVIDED
#4 HI-LO SCREW(2) PROVIDED
WHEN REPLACING COVERMAKE SURE COVER IS UNDERHORN CASE TAB AND ROTATECOVER CLOSED. INSERT HI-LOSCREWS AND TIGHTEN.
HORN COVER
REMOVE BOTH HI-LOSCREWS AND ROTATE COVER OPEN AS SHOWN.
HORN CASE SERVICE PINRECEPTOR
ENCLOSEDFLUSH MOUNT
COVER ASSEMBLY
#6 1-1/4 in. SCREW(4) PROVIDED
STI-1401 GASKET
EXISTING ULTYPE 3R RATEDIN-WALL ELECTRICAL BOX
DRILL 3/16 DIA. HOLES1 1/4 in. DEEP WHEN USING ANCHORS
DRILL 7/64 DIA. HOLES1 1/4 in. DEEP WHEN ANCHORS ARE NOT USED
PLASTIC WALL ANCHOR(4) PROVIDED
LOCKING TABDRILL 1/8 in. HOLE WHILE COVER IS CLOSED. INSERT THEBREAKWAY SEAL (KIT-65) COMPLETELY INTO THE LOCKING TAB.*NOT FOR USE ON FIRE OR EMERGENCY SIGNAL APPLICATIONS.
CONDUIT INSERT(2) PROVIDED
PLASTIC WALL ANCHOR(4) PROVIDED
#8x10 WALL ANCHOR(4) PROVIDED
INSERT(2) PROVIDED
#8x10 WALL ANCHOR(4) PROVIDED
PLASTIC WALL ANCHOR(4) PROVIDED
Fig. 7 - Horn Option Models STI-13x20 & STI-13x30 - Wiring Details - Remote Power/Relay Options*9V battery acts as a backup power when using remote power
Remove service pin and horn should sound. Close covers and horn should silence. When performing annual battery test/replacement or when servicing alarm system, insert service pin to prevent horn from sounding. Remember to remove to return to normal operation.
DRILL 3/16 DIA. HOLES 1-1/4 in. DEEP WHENUSING ANCHORS
DRILL 7/64 DIA. HOLES 1-1/4 in. DEEP WHENANCHORS ARE NOT USED
LOCKING TAB DRILL 1/8 in. HOLE WHILE COVER IS CLOSED. INSERT THE BREAKAWAY SEAL (KIT-65) COMPLETELY INTO THE LOCKING TAB.*NOT FOR USE ON FIRE OR EMERGENCY SIGNAL APPLICATIONS.
#6 x 1-1/4 in. SCREW(4) PROVIDED
STI-1314 OPTIONAL BACKPLATE -RECOMMENDED WHEN MOUNTING TO UNEVEN SURFACE
#6 x 1-1/4 in. SCREW(4) PROVIDED
1/2 in. & 3/4 in. CONDUITWEATHER GASKET
STI-1314 OPTIONAL BACKPLATE -RECOMMENDED WHEN MOUNTING TO UNEVEN SURFACE
DRILL 3/16 DIA. HOLES1-1/4 in. DEEP WHENUSING ANCHORS
DRILL 7/64 DIA. HOLES1-1/4 in. DEEP WHENANCHORS ARE NOT USED
LOCKING TAB DRILL 1/8 in. HOLE WHILE COVER IS CLOSED. INSERT THE BREAKAWAY SEAL (KIT-65) COMPLETELY INTO THE LOCKING TAB.*NOT USED ON FIRE OR EMERGENCY SIGNAL APPLICATIONS.
STI-1401 GASKET
LOCKING TAB DRILL 1/8 in. HOLE WHILE COVER IS CLOSED.INSERT THE BREAKAWAY SEAL (KIT-65)COMPLETELY INTO THE LOCKING TAB.*NOT USED ON FIRE OR EMERGENCY SIGNAL APPLICATIONS.
DRILL 3/16 DIA. HOLES1-1/4 in. DEEP WHEN USING ANCHORS
DRILL 7/64 DIA. HOLES1-1/4 in. DEEP WHEN ANCHORS ARE NOT USED
#6 x 1-1/4 in. SCREW(4) PROVIDED
IP67 GROMMET FOR REMOTE CABLE OPTIONDRILL 5/8 in. (16mm)
(INCLUDED WITH REMOTE OPTION)DRILL POINT CENTER LOCATED ON
BACK SIDE OF MOUNTING PLATE
DRILL 3/16 DIA. HOLES 1-1/4 in. DEEP WHEN USING ANCHORS
DRILL 7/64 DIA. HOLES 1-1/4 in. DEEP WHEN ANCHORS ARE NOT USED
#6 x 1-1/4 in. SCREW(4) PROVIDED
#6 - 32 x 1/2 in. PHIL. PANHEAD SCREW(2) PROVIDED SEALED MOUNTING PLATE (SHOWN)
LOCATE GROMET AS NEEDEDDRILL 5/8 in (16mm) HOLEINSERT GROMET AS SHOWN
FEED WIRES THROUGH GROMET(INCLUDED WITH SEALED MOUNTING PLATE)
3/4 in. NPT PLUG (1) PROVIDEDUSE A FLAT HEAD SCREWDRIVER OR COIN TO REMOVE.APPLY THREAD SEALANT. SCREW NPT BACK INTO BACK BOX
LOCKING TAB DRILL 1/8 in. HOLE WHILE COVER IS CLOSED. INSERT THE BREAKAWAY SEAL (KIT-65)COMPLETELY INTO THE LOCKING TAB.*NOT FOR USE ON FIRE OR EMERGENCY SIGNAL APPLICATION.
#6 O-RING USE TO SEALBACK BOX MOUNTING HOLES
(4) PROVIDED
IP67
A
5 CONDUCTORWIRE HARNESS
SERVICE PIN (1) PROVIDED
ROTATE BOTTOM END OFBATTERY UPWARD FOR REMOVAL
HILOW FACTORY DEFAULT HIGH
VOLUME SWITCH
#6 - 32 x 1/2 in. PHIL. FLATHEAD SCREW(6) PROVIDED
#4 HI-LO SCREW(2) PROVIDED
WHEN REPLACING COVERMAKE SURE COVER IS UNDERHORN CASE TAB AND ROTATECOVER CLOSED. INSERT HI-LOSCREWS AND TIGHTEN.
HORN COVER
REMOVE BOTH HI-LOSCREWS AND ROTATE COVER OPEN AS SHOWN.
HORN CASE SERVICE PINRECEPTOR
ENCLOSEDFLUSH MOUNT
COVER ASSEMBLY
#6 1-1/4 in. SCREW(4) PROVIDED
STI-1401 GASKET
EXISTING ULTYPE 3R RATEDIN-WALL ELECTRICAL BOX
DRILL 3/16 DIA. HOLES1 1/4 in. DEEP WHEN USING ANCHORS
DRILL 7/64 DIA. HOLES1 1/4 in. DEEP WHEN ANCHORS ARE NOT USED
PLASTIC WALL ANCHOR(4) PROVIDED
LOCKING TABDRILL 1/8 in. HOLE WHILE COVER IS CLOSED. INSERT THEBREAKWAY SEAL (KIT-65) COMPLETELY INTO THE LOCKING TAB.*NOT FOR USE ON FIRE OR EMERGENCY SIGNAL APPLICATIONS.
CONDUIT INSERT(2) PROVIDED
PLASTIC WALL ANCHOR(4) PROVIDED
#8x10 WALL ANCHOR(4) PROVIDED
INSERT(2) PROVIDED
#8x10 WALL ANCHOR(4) PROVIDED
PLASTIC WALL ANCHOR(4) PROVIDED
Wire Description Red 12VDC - 24VDCBlack 12VDC - 24VDCBlue CommonGreen NC - Norm ClosedYellow NO - Norm Open
Horn Activation
2306 Airport Rd • Waterford, MI 48327, USAPhone: 248-673-9898 • Fax: 248-673-1246
info@sti-usa.com • www.sti-usa.com
Taylor House • 34 Sherwood Road • BromsgroveWorcestershire • B60 3DR • England • Tel: +44 (0)1527 520 999
Fax: +44 (0)1527 501 999 • info@sti-emea.com • www.sti-emea.comSubject to changewithout notice.Printed in USA
Univ Stopper ISFeb2019
Important Notice (when used on fire systems) The Universal Stopper is intended to be used in areas where the incidence of false fire alarms from manual pull stations is high or has proven to be a serious problem. Any disadvantage of this device is more than balanced when one considers the consequences of false fire alarms, especially if fire service personnel and equipment are responding to a false fire alarm when they are needed for a real fire somewhere else. Add to this, the disruption to the facility when false alarms occur. If you have, or may have, a problem with false fire alarms or physical/weather damage to your fire alarm activation devices, the Universal Stopper could prove invaluable.
Avis important (en cas d’utilisation sur les réseaux d’incendie) Le Universal Stopper est destiné à être utilisé dans les zones où l’occurrence de fausses alertes d’incendie issues d’avertisseurs d’incendie manuels est élevée ou présente un problème grave. Un quelconque inconvénient de ce dispositif est vite contrecarré par les conséquences des fausses alertes d’incendie, surtout lorsque le personnel et l’équipement des services d’incendie réagissent à une fausse alerte d’incendie alors que leur intervention ailleurs sur un vrai incendie s’avère nécessaire en même temps.À cela s’ajoute l’agitation éprouvée dans l’établissement au moment du déclenchement d’une fausse alerte. Si vous rencontrez, ou risquez de rencontrer, un problème avec les fausses alertes d’incendie ou avec l’éventuel endommagement par effet climatique ou physique de vos dispositifs de déclenchement des alertes d’incendie, le Universal Stopper pourra alors se révéler d’une valeur inestimable.
WarrantyThree year guarantee against breakage of polycarbonate in normal use (one year on electro mechanical and electronic components). Electronic warranty form at www.sti-usa.com/wc14.
WARNING: This product can expose you to chemicals including Dichloromethane, which is known to the State of California to cause cancer, and Bisphenol A (BPA), which is known to the State of California to cause birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov.
#4 HI-LO SCREW(2) PROVIDED
SERVICE PIN (1) PROVIDEDSERVICE PIN RECEPTOR
HORN COVER
TO REMOVE SOUNDER ASSEMBLY,REMOVE 2 HI-LO, ROTATE THE REAR OFTHE SOUNDER ASSEMBLY OFF THEFRONT TAB OF THE MESSAGE HOOD.
TO INSTALL SOUNDER ASSEMBLY,REVERSE THE REMOVAL PROCESS.
OPTIONAL REMOTE WIRE HARNESS
A
CR123A
5 CONDUCTOR WIRE HARNESS(REFER TO WIRING INSTRUCTIONS ON FIG. 7)
VIEW A
VOLUME JUMPER
FACTORY DEFAULT HIGH
FLASHING LED’sDO NOT TOUCH
WHEN REPLACINGCOVER MAKE SURECOVER IS UNDERHORN CASE TABAND ROTATE COVERCLOSED. INSERTHI-LO SCREWSAND TIGHTEN
VIEW A
VOLUME JUMPERHI OR LOW
(DEFAULT HI)
A
+
-
VOLUME JUMPERHI OR LOW
(DEFAULT HI)
CR123A
5 CONDUCTOR WIRE HARNESS(REFER TO WIRING
INSTRUCTIONS ON FIG. 7)
VIEW A
LED LIGHTS
Fig. 8 - Horn Option Models STI-14x20 & STI-14x30 - Wiring Details - Remove Power/Relay Options*CR123A battery acts as a backup power when using remote power
TO REPLACE BATTERY REMOVE BOTH HI-LO SCREWS AND ROTATE COVER
OPEN AS SHOWN
See FIG. 7 for wire description and activation instructions.
#4 HI-LO SCREW(2) PROVIDED
SERVICE PIN (1) PROVIDEDSERVICE PIN RECEPTOR
HORN COVER
TO REMOVE SOUNDER ASSEMBLY,REMOVE 2 HI-LO, ROTATE THE REAR OFTHE SOUNDER ASSEMBLY OFF THEFRONT TAB OF THE MESSAGE HOOD.
TO INSTALL SOUNDER ASSEMBLY,REVERSE THE REMOVAL PROCESS.
OPTIONAL REMOTE WIRE HARNESS
A
CR123A
5 CONDUCTOR WIRE HARNESS(REFER TO WIRING INSTRUCTIONS ON FIG. 7)
VIEW A
VOLUME JUMPER
FACTORY DEFAULT HIGH
FLASHING LED’sDO NOT TOUCH
WHEN REPLACINGCOVER MAKE SURECOVER IS UNDERHORN CASE TABAND ROTATE COVERCLOSED. INSERTHI-LO SCREWSAND TIGHTEN
VIEW A
VOLUME JUMPERHI OR LOW
(DEFAULT HI)
A
+
-
VOLUME JUMPERHI OR LOW
(DEFAULT HI)
CR123A
5 CONDUCTOR WIRE HARNESS(REFER TO WIRING
INSTRUCTIONS ON FIG. 7)
VIEW A
LED LIGHTS
2306 Airport Road • Waterford, Michigan 48327-1209Phone: 248-673-9898 • Fax: 248-673-1246Toll Free: 800-888-4784 • E-mail: info@sti-usa.comWeb: www.sti-usa.com
Taylor House • 34 Sherwood Road • BromsgroveWorcestershire • B60 3DR • England Tel: +44 (0)1527 520 999 • Fax: +44 (0)1527 501 999 E-mail: info@sti-emea.com • Web: www.sti-emea.com
*SS2xx4 and LT1-UL NOTES: For access control installations, power for the LT-1UL Timer must be supplied by a power source listed to UL294. When used for access control, this device shall be used as part of an access controlled egress door system. It is up to the local AHJ to allow use of this device in place of an automatic sensor. For higher security installations, lower time limits should be used. For SS2xx4 and LT1-UL the enclosed timer is to be used and installed per the enclosed LT-1UL installation sheet. *SS2xx4 and LT1-UL maximum rating 30 VDC 3A.
REMARQUES POUR *SS2xx4 et LT1-UL: Pour les installations de contrôle d’accès, l’alimentation de la minuterie LT-1UL doit être fournie par une source homologuée UL294. Lorsque cet appareil est utilisé aux fins de contrôle d’accès, il doit faire partie d’un système de porte de sortie à accès contrôlé. Il incombe donc à l’AHJ local d’autoriser l’utilisation de cet appareil au lieu d’un capteur automatique. Pour les installations de sécurité plus renforcée, des délais inférieurs doivent être utilisés. Pour les modèles SS2xx4 et LT1-UL, la minuterie intégrée doit être installée et utilisée suivant la fiche d’installation LT-1UL fournie. La cote maximale des modèles *SS2xx 4 et LT1-UL est de 30 VCC 3A.
WARNING: This product can expose you to chemicals including Bisphenol A, which is known to the State of California to cause reproductive harm and Dichloromethane, which is known to the State of California to cause cancer. For more information go to www.P65Warnings.ca.gov.
Three year warranty or a one year limited warranty (from date of purchase) on most products. See website for details. Electronic warranty form at www.sti-usa.com/wc14.
1027IS OCT2018
INSTALLATION OF SS2xx0, SS2xx1, SS2xx3, SS2xx4 SERIES STOPPER® STATIONAll specifications and information shown were current as of publication, and are subject to change without notice.
“A” - Contact DepthSS2xy0* 2.16”SS2xy1 2.04”SS2xy3* 2.13”SS2xy4 2.04”
* If extra depth needed in electrical box order KIT-102722-color.
NC
NO1
23
4
STRIP 1/4 in. OF WIRE INSULATIONINSERT IN TERMINAL (AS SHOWN) THENUSING A PHILLIPS SCREWDRIVER TURNCLOCKWISE UNTIL TIGHT.
SEPARATION OF TERMINAL ASSEMBLY.FROM BUTTON ASSEMBLY IS AS FOLLOWS:GRASP TERMINAL HOUSING AND USING THUMBAPPLY PRESSURE DOWNWARD, REMOVE TERMINAL.
REMOVAL OF TERMINAL BLOCKFROM TERMINAL HOUSING: INSERTSMALL SCREWDRIVER (AS SHOWN)AND PRY UPWARD, REMOVE TERMINAL.
TERMINAL BLOCKRELEASE LEVERMUST FACE UPWARDAS SHOWN FOR SWITCHTO FUNCTION CORRECTLY.
ELECTRICAL TERMINAL BLOCKUP TO 3 TERMINALS MAY BE USED
INSERT NOTCH, AS SHOWNTHEN ROTATE UPWARD
TERMINAL BLOCKKIT-E10196 NO (1) PROVIDEDKIT-E10198 NC (1) PROVIDED
SEE VIEW IN DIRECTION OF ARROWFOR CONTACT INDENTIFIER LOCATIONSUP TO (3) TERMINALS MAY BE USED FOR EACHSTATION ASSEMBLY.
OUTGOING
INCOMING
SCREWS #6-32 x 1OUTLET BOX (2) PROVIDED.
SCREWS #6-32 x 1.50 WHENUSING KIT-102722-COLOR SPACER
(SEE REVERSE SIDE).#10-32 x 3/8 in. GROUND SCREW
(1) PROVIDED
BUTTON LOCK NUT
BACKPLATE
A
EXISTING STANDARDSINGLE GANGBOX
HOUSING INDEXING SLOTS
BACKPLATE ASSEMBLY(SEE REVERSE SIDE)
5/8” SPACERKIT-102722-B (BLUE)
KIT-102722-G (GREEN)KIT-102722-R (RED)
KIT-102722-W (WHITE)KIT-102722-Y (YELLOW)
M10274-W OCTAGON SHELLRED, GREEN, YELLOW, WHITE AND BLUE
E10105 MOMENTARY BUTTON (#4)* KIT-H18062 KEYS(2) PROVIDED
M10271 STATION HOUSINGRED, GREEN, YELLOW,
WHITE AND BLUE
E10100 PUSH/TURNRESET BUTTON (#1)
KEY BUTTON (#3)KEY REQUIRED TO ACTIVATE - INACTIVATE MODE KEY CAN BE REMOVED
#8-32 x 3/8 in. BUTTON HEADSCREW (1) PROVIDED
KIT-H19030 KEYS(2) PROVIDED
E10102 KEY RESET SWITCH
OCTAGON KEY RESET BUTTON (#0)RED, GREEN, YELLOW, WHITEAND BLUE
M02050
PUSH
PUSH
HERE
MESSAGEAREA
NOTE: TO PROVIDE ADEQUATECLEARANCE FOR INSTALLATION,
MAY REQUIRE: KIT-102722 5/8” SPACER
PRODUCT DIMENSIONS
3.25 in.(82mm)
4.87 in.(124mm)
1.62 in.(41mm) 2.25 in.
(57mm)
“A”
UL294 Performance Levels: Line Security: IAttack: I
Endurance: IVStandby Power: I
2306 Airport Road • Waterford, Michigan 48327-1209Phone: 248-673-9898 • Fax: 248-673-1246Toll Free: 800-888-4784 • E-mail: info@sti-usa.comWeb: www.sti-usa.com
Taylor House • 34 Sherwood Road • BromsgroveWorcestershire • B60 3DR • England Tel: +44 (0)1527 520 999 • Fax: +44 (0)1527 501 999 E-mail: info@sti-emea.com • Web: www.sti-emea.com
1027IS OCT2018
INSTALLATION OF SS2xx0, SS2xx1, SS2xx3, SS2xx4 SERIES STOPPER® STATIONAll specifications and information shown were current as of publication, and are subject to change without notice.
ALL TERMINALS ACCEPT TWO 12 TO 18 (AWG)
VOLTAGERATED AVERAGE CURRENT
250 VDC 1 AMP
600 VAC 3 AMP
NOTE: SS-2XX4/LT CONTACTS ON FORM C TIMER RATED: 120 VAC, 3A 28 VDC, 3A
NC
NO1
23
4
STRIP 1/4 in. OF WIRE INSULATIONINSERT IN TERMINAL (AS SHOWN) THENUSING A PHILLIPS SCREWDRIVER TURNCLOCKWISE UNTIL TIGHT.
SEPARATION OF TERMINAL ASSEMBLY.FROM BUTTON ASSEMBLY IS AS FOLLOWS:GRASP TERMINAL HOUSING AND USING THUMBAPPLY PRESSURE DOWNWARD, REMOVE TERMINAL.
REMOVAL OF TERMINAL BLOCKFROM TERMINAL HOUSING: INSERTSMALL SCREWDRIVER (AS SHOWN)AND PRY UPWARD, REMOVE TERMINAL.
TERMINAL BLOCKRELEASE LEVERMUST FACE UPWARDAS SHOWN FOR SWITCHTO FUNCTION CORRECTLY.
ELECTRICAL TERMINAL BLOCKUP TO 3 TERMINALS MAY BE USED
INSERT NOTCH, AS SHOWNTHEN ROTATE UPWARD
TERMINAL BLOCKKIT-E10196 NO (1) PROVIDEDKIT-E10198 NC (1) PROVIDED
SEE VIEW IN DIRECTION OF ARROWFOR CONTACT INDENTIFIER LOCATIONSUP TO (3) TERMINALS MAY BE USED FOR EACHSTATION ASSEMBLY.
OUTGOING
INCOMING
SCREWS #6-32 x 1OUTLET BOX (2) PROVIDED.
SCREWS #6-32 x 1.50 WHENUSING KIT-102722-COLOR SPACER
(SEE REVERSE SIDE).#10-32 x 3/8 in. GROUND SCREW
(1) PROVIDED
BUTTON LOCK NUT
BACKPLATE
A
EXISTING STANDARDSINGLE GANGBOX
HOUSING INDEXING SLOTS
BACKPLATE ASSEMBLY(SEE REVERSE SIDE)
5/8” SPACERKIT-102722-B (BLUE)
KIT-102722-G (GREEN)KIT-102722-R (RED)
KIT-102722-W (WHITE)KIT-102722-Y (YELLOW)
M10274-W OCTAGON SHELLRED, GREEN, YELLOW, WHITE AND BLUE
E10105 MOMENTARY BUTTON (#4)* KIT-H18062 KEYS(2) PROVIDED
M10271 STATION HOUSINGRED, GREEN, YELLOW,
WHITE AND BLUE
E10100 PUSH/TURNRESET BUTTON (#1)
KEY BUTTON (#3)KEY REQUIRED TO ACTIVATE - INACTIVATE MODE KEY CAN BE REMOVED
#8-32 x 3/8 in. BUTTON HEADSCREW (1) PROVIDED
KIT-H19030 KEYS(2) PROVIDED
E10102 KEY RESET SWITCH
OCTAGON KEY RESET BUTTON (#0)RED, GREEN, YELLOW, WHITEAND BLUE
M02050
PUSH
PUSH
HERE
MESSAGEAREA
NOTE: TO PROVIDE ADEQUATECLEARANCE FOR INSTALLATION,
MAY REQUIRE: KIT-102722 5/8” SPACER
PRODUCT DIMENSIONS
3.25 in.(82mm)
4.87 in.(124mm)
1.62 in.(41mm) 2.25 in.
(57mm)
“A”
NC
NO1
23
4
STRIP 1/4 in. OF WIRE INSULATIONINSERT IN TERMINAL (AS SHOWN) THENUSING A PHILLIPS SCREWDRIVER TURNCLOCKWISE UNTIL TIGHT.
SEPARATION OF TERMINAL ASSEMBLY.FROM BUTTON ASSEMBLY IS AS FOLLOWS:GRASP TERMINAL HOUSING AND USING THUMBAPPLY PRESSURE DOWNWARD, REMOVE TERMINAL.
REMOVAL OF TERMINAL BLOCKFROM TERMINAL HOUSING: INSERTSMALL SCREWDRIVER (AS SHOWN)AND PRY UPWARD, REMOVE TERMINAL.
TERMINAL BLOCKRELEASE LEVERMUST FACE UPWARDAS SHOWN FOR SWITCHTO FUNCTION CORRECTLY.
ELECTRICAL TERMINAL BLOCKUP TO 3 TERMINALS MAY BE USED
INSERT NOTCH, AS SHOWNTHEN ROTATE UPWARD
TERMINAL BLOCKKIT-E10196 NO (1) PROVIDEDKIT-E10198 NC (1) PROVIDED
SEE VIEW IN DIRECTION OF ARROWFOR CONTACT INDENTIFIER LOCATIONSUP TO (3) TERMINALS MAY BE USED FOR EACHSTATION ASSEMBLY.
OUTGOING
INCOMING
SCREWS #6-32 x 1OUTLET BOX (2) PROVIDED.
SCREWS #6-32 x 1.50 WHENUSING KIT-102722-COLOR SPACER
(SEE REVERSE SIDE).#10-32 x 3/8 in. GROUND SCREW
(1) PROVIDED
BUTTON LOCK NUT
BACKPLATE
A
EXISTING STANDARDSINGLE GANGBOX
HOUSING INDEXING SLOTS
BACKPLATE ASSEMBLY(SEE REVERSE SIDE)
5/8” SPACERKIT-102722-B (BLUE)
KIT-102722-G (GREEN)KIT-102722-R (RED)
KIT-102722-W (WHITE)KIT-102722-Y (YELLOW)
M10274-W OCTAGON SHELLRED, GREEN, YELLOW, WHITE AND BLUE
E10105 MOMENTARY BUTTON (#4)* KIT-H18062 KEYS(2) PROVIDED
M10271 STATION HOUSINGRED, GREEN, YELLOW,
WHITE AND BLUE
E10100 PUSH/TURNRESET BUTTON (#1)
KEY BUTTON (#3)KEY REQUIRED TO ACTIVATE - INACTIVATE MODE KEY CAN BE REMOVED
#8-32 x 3/8 in. BUTTON HEADSCREW (1) PROVIDED
KIT-H19030 KEYS(2) PROVIDED
E10102 KEY RESET SWITCH
OCTAGON KEY RESET BUTTON (#0)RED, GREEN, YELLOW, WHITEAND BLUE
M02050
PUSH
PUSH
HERE
MESSAGEAREA
NOTE: TO PROVIDE ADEQUATECLEARANCE FOR INSTALLATION,
MAY REQUIRE: KIT-102722 5/8” SPACER
PRODUCT DIMENSIONS
3.25 in.(82mm)
4.87 in.(124mm)
1.62 in.(41mm) 2.25 in.
(57mm)
“A”