Heat Pump Water Heater((((Northern Europe))))
Service Manual
GREE ELECTRIC APPLIANCES INC. OF ZHUHAI
CONTENTS RODUCT INTRODUCTION .....................................................................................2
1 MODELS LIST............................................................................................................................. 2 2 NOMENCLATURE...................................................................................................................... 2 3 FUNCTION .................................................................................................................................. 3 4 PRODUCT DATA......................................................................................................................... 4
4.1 Product Data at Rated Condition........................................................................................ 4 4.2 Ambient Temp Range......................................................................................................... 4 4.3 Electrical Data.................................................................................................................... 5
5 PIPING DIAGRAM...................................................................................................................... 6
UNITS CONTROL ......................................................................................................8
1 OPERATION FLOWCHART....................................................................................................... 8 2 MAIN LOGIC............................................................................................................................. 10
2.1 Heating Mode................................................................................................................... 10 2.2 Defrosting Mode .............................................................................................................. 10
3 WIRED CONTROLLER ............................................................................................................ 11 3.1 Dimension ........................................................................................................................ 11 3.2 Function ........................................................................................................................... 11 3.3 Installation........................................................................................................................ 14
4 CONTROL WIRING DESIGN................................................................................................... 16
UNITS INSTALLATION ..........................................................................................18
1 UNITS INSTALL........................................................................................................................ 18 1.1 Installation Positions ........................................................................................................ 18 1.2 Matters need Attention ..................................................................................................... 18 1.3 Dimension Date................................................................................................................ 18 1.4 Installation Clearance Date .............................................................................................. 19
2 ELECTRIC WIRING WORK..................................................................................................... 21 2.1 Wiring Principle ............................................................................................................... 21 2.2 Electric Wiring Design..................................................................................................... 21 2.3 Specification of Power Supply Wire and Air Switch ....................................................... 22
UNITS MAINTENANCE..........................................................................................24
1 ERROR CODE LIST .................................................................................................................. 24 2 FLOW CHART OF TROUBLESHOOTING ............................................................................. 25 3 DISASSEMBLY AND ASSEMBLY PROCEDURE OF MAIN PARTS.................................... 31 4 EXPLODED VIEWS AND PART LIST..................................................................................... 37
4.1 Single Fan ........................................................................................................................ 37 4.2 Double Fan....................................................................................................................... 38
GREE COMMERCIAL AIR CONDITIONERS HEAT PUMP WATER HEATER (NORTHERN EUROPE)
1
PRODUCT
HEAT PUMP WATER HEATER (NORTHERN EUROPE) PRODUCT
2
RODUCT INTRODUCTION
1 MODELS LIST
Model
Refrigerant Model Name
Nominal Capacity
(kW) Power Supply
(V,Ph,Hz) Appearance
KFRS-9/Na-M 9.0
R410A
GRS-S16/Na-M(O) 16
380~415V 3Ph 50Hz
Note:1Ton =12000Btu/h = 3.517kW
2 NOMENCLATURE
K F RS - 9 / Na - M
1 2 3 4 5 6
HEAT PUMP WATER HEATER (NORTHERN EUROPE) PRODUCT
3
NO. Description Options
1 Air Source 2 Split Type F= Split Type, Default= Integral Type 3 Heat Pump Water Heater 4 Heating Capacity 9KW 6 Refrigerant Na=R410A, Default=R22
7 Voltage M=380~415V 3Ph 50Hz
G RS - S 16 / Na - M (0)
1 2 3 4 5 6 7
NO. Description Options 1 GREE 2 Heat Pump Water Heater 3 Static S= Static ,C =Circulating 4 Heating Capacity 16KW 5 Refrigerant Na=R410A, Default=R22
6 Voltage M=380~415V 3Ph 50Hz
7 Outdoor Unit O= Outdoor Unit ,I=Indoor Unit
3 FUNCTION
Function Description
Heating
Memory restart High efficiency and energy saving Environmentally friendly Healthy and comfortable Friendly man-machine interface Easy installation Low noise design Safety and reliability thanks to advance compressor balance control
HEAT PUMP WATER HEATER (NORTHERN EUROPE) PRODUCT
4
4 PRODUCT DATA
4.1 Product Data at Rated Condition
Technical parameters of host unit
Models KFRS-9/Na-M GRS-S16/Na-M(O)
kW 9 16
Btu/h 30708 54592 Nominal Capacity Heating
RT 2.56 4.55
Power Consumption Heating kW 3 5.5
Power Supply 380~415V,3Ph,50Hz
Safeties High/Low pressure switch, compressor thermal
protection, over current protection, lose of phase/anti-phase protection, antifreeze protection,
Type R410A Refrigerant Charge kg 3.3 4.5
Type scroll Compressor NO. 1 1
Heat Exchanger Aluminum fin-copper tube
Liquid mm 1/2" 1/2" Evaporator Connection Pipe Gas mm 3/4" 3/4"
Height mm 840/985 1250/1405 Width mm 1018/1110 1032/1110
Unit/ Packing
Dimension Depth mm 412/450 412/450
Net / Gross Weights kg 90/100 132/145
NOTE:Testing condition of heating :Setting temp of outlet water: 45℃, outdoor ambient temp : DB7℃/WB6
℃.
4.2 Ambient Temp Range
Ambient temp range of unit during operation: -15~28℃.
HEAT PUMP WATER HEATER (NORTHERN EUROPE) PRODUCT
5
4.3 Electrical Data
Fan Motor Compressor
Outdoor Total
Model Rated Power Supply NO.
LRA each (A)
MRC each (A)
NO. MRC (A)
MRC (A)
NRC (A)
KFRS-9/Na-M 1 48 10.8 1 1.5 12.3 8.2
GRS-S16/Na-M(O)
380~415V 3Ph 50Hz 1 74 15.0 2 2 19.5 12.0
Notes: LRA: Locked rotor amps (A) MRC: Maximum running current (A) NRC: Nominal running current (A)
HEAT PUMP WATER HEATER (NORTHERN EUROPE) PRODUCT
6
5 PIPING DIAGRAM
Hot water
City water
Thermal expansion valve
Liquid-gas separator
Low-pressureswitch
Compressor
High-pressure switch
Water tank
Four-way valve
Aluminum fin-copper tube coil
High pressure tank
GREE COMMERCIAL AIR CONDITIONERS HEAT PUMP WATER HEATER (NORTHERN EUROPE)
7
CONTROL
GREE COMMERCIAL AIR CONDITIONERS HEAT PUMP WATER HEATER (NORTHERN EUROPE)
8
UNITS CONTROL
1 OPERATION FLOWCHART
HEAT PUMP WATER HEATER (NORTHERN EUROPE) INSTALLATION
9
HEAT PUMP WATER HEATER (NORTHERN EUROPE) INSTALLATION
10
2 MAIN LOGIC
2.1 Heating Mode
When press ON button, if the temperature of water tank meets the heating running requirements,
it starts the fans of outdoor unit. Then the compressor will run after 15s.
If the temperature of water tank is over the set temperature , the unit will stop, and turn off all
loads .The fans of outdoor unit will stop after 15s.
Turn on
Fan 1
Compressor
Turn off
Four-way Valve
15S
Fan 2 When it is turned off
15S5S
30S
When it is turned off
2.2 Defrosting Mode
The condition of start defrosting mode:
Under heating mode, if the accumulative running time of compressor is over the set interval time
of defrosting(default 45min),and the defrosting temperature is lower than the set starting
temperature(default -4℃) ,the unit will start running defrosting mode, and the 4-way valve will shut
HEAT PUMP WATER HEATER (NORTHERN EUROPE) INSTALLATION
11
off and the outdoor fan will stop after 2s.
The condition of quit defrosting mode:
Under defrosting mode, if the continual defrosting time is over the set continual time of defrosting
(default 8min),and the defrosting temperature is over the set stopping temperature(default 20℃) ,the
unit will restart running heating mode, and the 4-way valve will turn on and the outdoor fan will run.
3 WIRED CONTROLLER
3.1 Dimension
3.2 Function
3.2.1 Operation View
HEAT PUMP WATER HEATER (NORTHERN EUROPE) INSTALLATION
12
OFF
QUIT
ON
CHECK
MODE
NO. Name Function description
1 MODE button This button is available only on heating unit.
2 CHECK button
Press it once under normal state to enter check mode, under check mode, press this button when “17” is displayed can change the value of “17”. Under parameter set mode, press this once can switch the adjusting objection between parameter and value, press this button for long (about 5s) to save and quit this parameter setting.
3 Increasing button To increase present set value or change set/check object.
4 Decreasing button To decrease present set value or change set/check object.
5 QUIT button
Under Set and Check mode, press it once to quit this mode. Under parameter set mode, this set value would not be saved. Press this button for long (about 5s) to set sound, and make sound switches between always on and always off.
6 ON button To turn on the unit; press it once to quit compel operation when the unit is under compel operation.
7 OFF button To turn off the unit; press it once to quit compel operation when the unit is under compel operation.
8 LCD display Display information of the unit.
HEAT PUMP WATER HEATER (NORTHERN EUROPE) INSTALLATION
13
Note:
(1) Turn On, Off Auxiliary Heater: It is only available for heat pump unit. Press CHECK once to enter
Check mode. Press ▲ and ▼ to change check object, press CHECK again till the present check
object becomes “17”, value “17” switches between 01/03 (auxiliary heater on) and 00/02 (auxiliary
heater off). That is 00 Off —>01 On —>00 Off, or 02 Off —>03 On —>02 Off.
(2) Check Parameter: After electrify for 20s, press QUIT then ▲ to enter parameter checking mode.
Under this mode, Auxiliary display area shows the checking object, Main display area displays the
value for the checking object. Press ▲ and ▼ to change the checking object. Press QUIT to quit
from the check mode.
3.2.2 Display View
NO. Name Function description
1 Running mode display : heating mode
2 Temp display It shows temperature value displays at main display area.
3 Auxiliary display area It contains 2 numbers and a comma, for showing temperature and number of parameter at main display area. It only displays when under Check mode and Parameter checking mode.
4 Main display area
It contains a minus, 2 numbers and 1 temperature unit, for displaying value of temperature and parameter (temperature or time value) and error code. When temperature value is displayed, it shows value in algorism and temperature unit; when time is displayed, it shows algorism value but no temperature unit (default unit is min); when it is code, it displays specific error (refer to Malfunction Error List) but no temperature unit.
HEAT PUMP WATER HEATER (NORTHERN EUROPE) INSTALLATION
14
Individual temperature or parameter may exceed 99, then adopt AX for
100~109, bX for 110~119, CX for 120~129, dX for 130~139, EX for
140~149, FX for 150~159, and X stands for a number between 0~9. Under normal state, it shows temperature for back water.
5 Parameter display It means the value shown at present main display area is parameter. It shows only under Parameter Check mode.
6 Defrost display It displays when defrosting, otherwise it doesn’t displays.
7 System ID It displays when system or compressor orders, for showing which system is defrosting.
8 Testing display For testing, it displays under compel operation.
9 Error code display It shows the error code displayed on Main Display Area. It displays when there is error at system or communication.
Caution:
When unit is off, it displays only temperature of water tank. When unit is on, under normal state, if
there is no error, it displays temperature of water tank, if there is error, it displays error code; when
there is no operation after 60s of pressing the button, it quit back to normal state display automatically.
Auto antifreeze operation display (only for heat pump unit)
When auto antifreeze function is started and relevant conditions are satisfied, unit begins auto
antifreeze operation. At this time, LCD main display area displays code d2 (if there is error it displays
error code).
3.3 Installation
First select an installation position. According to the size of the communication line of the wire
controller, leave a recess or a embedded wire hole to bury the communication line.
If the communication line between the wire controller (85×85×20) and the indoor unit is
surface-mounted, use 1# PVC pipe and make matching recess in the wall (refer to Figure 6); If
concealed installation is adopted, 1# PVC pipe can be used (Refer to Figure 7).
No matter if surface mounting or concealed mounting is selected, it is required to drill 2 holes (in
the same level) which distance shall be the same as the distance (60mm) of installation holes in the
bottom plate of the wire controller. Then insert a wood plug into each hole. Fix the bottom plate of the
wire controller to the wall by using the two holes. Plug the communication line onto the control panel.
Lastly install the panel of the wire controller.
HEAT PUMP WATER HEATER (NORTHERN EUROPE) INSTALLATION
15
Caution:
During the installation of the bottom plate of the wire controller, pay attention to the direction of
the bottom plate. The plate’s side with two notches must be at the lower position, and otherwise the
panel of the wire controller cannot be correctly installed.
PVC pi pe
Fig6:Surface Mounting of Cable Fig7:Concealed mounting of Cable
1 32 4
Fig 8 Schematic Diagram of Installation
No. Name
1 Wall Surface
2 Bottom Plate of Wire Controller
3 Screw M4X10
4 Panel of Wire Controller
HEAT PUMP WATER HEATER (NORTHERN EUROPE) INSTALLATION
16
Caution: The communication distance between the main board and the wire controller can be as far as 20m
(The standard distance is 8m).The wire controller shall not be installed in a place where there is water
drop or large amount of water vapor.
4 CONTROL WIRING DESIGN
WIRED CONTROLLER
Manual Unit Controller Outdoor Unit Controller
CN1 CN2
J1 X17
twisted-pair twisted-pair
The controllers of the unit include manual controller, wired controller and outdoor unit controller.
The wired controller communications with manual controller and outdoor unit controller in RS485. The wired controller connects manual controller with 4-line twisted-pair. Similarly, wired controller connects outdoor unit controller with 4-line twisted-pair.
HEAT PUMP WATER HEATER (NORTHERN EUROPE) INSTALLATION
17
INSTALLATION
HEAT PUMP WATER HEATER (NORTHERN EUROPE) INSTALLATION
18
UNITS INSTALLATION
1 UNITS INSTALL
1.1 Installation Positions
For outdoor unit: � The installation is frost-free. � The space around the unit is adequate for servicing. � The space around the unit allows for sufficient air circulation. � There is no danger of fire due to leakage of flammable gas. � All piping lengths and distances have been taken into consideration.
1.2 Matters need Attention
At delivery, the unit should be checked and any damage should be reported immediately to the carrier claims agent.
1.3 Dimension Date
KFRS-9/Na-M
950 340
840
378
412572
HEAT PUMP WATER HEATER (NORTHERN EUROPE) INSTALLATION
19
GRS-S16/Na-M(O)
Unit: mm
1.4 Installation Clearance Date
L3
L2
L4
L1air inlet
air outlet
HEAT PUMP WATER HEATER (NORTHERN EUROPE) INSTALLATION
20
unit:mm
demonstration L1 L2 L3 L4
distance >500 >1000 >500 >500
HEAT PUMP WATER HEATER (NORTHERN EUROPE) MAINTENANCE
21
2 ELECTRIC WIRING WORK
2.1 Wiring Principle
The power cord should firstly connect with dynamic power terminal in electric box and then connect with relevant power terminals of outdoor unit and electric heater. Never mistake the connection to avoid damage to electric elements. If the units is under protection condition. Check out leakage causes to clear the fault and then open the electric box without power supply to reset leakage protector. If leakage protector trips off again, stop the unit and ask professionals for help. Never check or repair it by yourself to avoid safety accident. With green mark is normal , while with red mark
means conglutination between contacts, in which case, it should be replaced after cutting off its power supply.
General principles: � Wires, equipment and connectors supplied for use on the site must be in
compliance with provisions of regulations and engineering requirements.
� Only electricians holding qualification are allowed to perform wire connection
on the site.
� Before connection work is started, the power supply must be shut off.
� Installer shall be responsible for any damage due to incorrect connection of the
external circuit of the unit.
� Caution --- MUST use copper wires. 2.2 Electric Wiring Design
Outdoor Unit Electric Box
L1 L2 L3 N X17XT1
L1 L2 L3 NPE
PE
Intdoor Unit Electric Box CN2XT3
CN1
AP
CN5
4-co
re tw
site
dpa
ir w
ire
AP2
4-co
re tw
site
dpa
ir w
ire
Display Board
L1 L2 L3 N L1 L2 L3
PE
POWER 380-400V 3N Hz
PEElectric heater
XT1 XT2
Water Tank
Water-outlet Temp.Sensor
HEAT PUMP WATER HEATER (NORTHERN EUROPE) MAINTENANCE
22
2.3 Specification of Power Supply Wire and Air Switch
Power cable specifications and air switch types in the following list are recommended for selection.
Unit Model Power supply Air switch capacity
(A)
Min. sectional area of
grounding cable (mm2)
Min. sectional area of power
cable (mm2)
KFRS-9/Na-M 380-415V 3N~ 50Hz
13 1.5 4×1.5
GRS-S16/Na-M(O) 380-415V 3N~ 50Hz
25 2.5 4×2.5
Note: � The power supply wire must be copper core wire, and the working temperature can not be
higher than limited value. � If the length of power supply wire is longer than 15meters, do please increase the section
area to avoid any accident due to over-load. � If the supply cord is damaged, it must be replaced by the manufacturer or its service agent
or a similar qualified person in order to avoid a hazard. � The appliance shall be installed according to national regulations � When installing the connection wiring for manual controller, the wire must be put inside a
separate protective sheath to avoid direct sunshine.
Warning! An all-pole disconnection switch having a contact separation of at least 3mm in all
poles should be connected in fixed wiring.
HEAT PUMP WATER HEATER (NORTHERN EUROPE) MAINTENANCE
23
MAINTENANCE
HEAT PUMP WATER HEATER (NORTHERN EUROPE) MAINTENANCE
24
UNITS MAINTENANCE 1 ERROR CODE LIST
Code Indication Error Name Cause of Error Code Control Description
E1 Comp High-pressure
protection
� Comp High-pressure switch is broken or the wiring is loose.
� The water in the tank is not enough.
� The installation of tank temp sensor is not correct.
� The gas valve and liquid valve are not fully open.
� The thermal expansion valve can not work normally.
Press ON/OFF key to clear
E3 Comp Low- pressure
protection
� Comp Low-pressure switch is broken or the wiring is loose.
� The system has leaked.
� The fans stop running or reverse.
Press ON/OFF key to clear
E4 Comp Discharge temp
protection
� The resistance of temperature sensor is not correct.
� The thermal expansion valve is blocked.
� The system has leaked.
� Mainboard of outdoor unit is damaged.
Press ON/OFF key to clear
E5 Comp overload protection
� AC contactor is damaged.
� The compressor wiring is not correct.
� The voltage is not normal.
� Overcurrent test board is damaged.
� The refrigerant of the system is excessive.
Press ON/OFF key to clear
E8 Fan 1 overload protection
� Mainboard of outdoor unit is damaged.
� The wire connecting the wiring terminals of the mainboard
breaks.
Press ON/OFF key to clear
b8 Fan 2 overload protection
� Mainboard of outdoor unit is damaged.
� The wire connecting the wiring terminals of the mainboard
breaks.
Press ON/OFF key to clear
F3 Defrost temp sensor failure
� The plug on temperature sensor is not correctly connected to the
socket on mainboard.
� The resistance of temperature sensor is not correct.
Auto resume
F5 Discharge temp sensor error
� The plug on temperature sensor is not correctly connected to the
socket on mainboard.
� The resistance of temperature sensor is not correct.
Auto resume
F7 Outdoor ambient temp sensor
failure
� The plug on temperature sensor is not correctly connected to the
socket on mainboard.
� The resistance of temperature sensor is not correct.
Auto resume
EC Communication malfunction
� The communication line of the unit is not connected.
� The communication line is not through.
� The communication line of the unit is not connected correctly.
� The two ends of communication line are not mounted with
magnetic ring.
� The outdoor unit is not electrically powered.
Auto resume
HEAT PUMP WATER HEATER (NORTHERN EUROPE) MAINTENANCE
25
2 FLOW CHART OF TROUBLESHOOTING
(1)Comp High-pressure Protection E1
Comp High-pressure Protection E1
Check if the water in the tank is enough
Check if the installation of tank temp sensor is correct
Check if the thermal expansion valve can work normally
Install rightly the tank temp sensor
NO
YES
NO
YES
NO
YES
NO
Check if the gas valve and liquid valve are fully open
Fill the tank with the water
Fully open the valve
Replace the thermal expansion valve
(2)Comp Low- pressure Protection E3
HEAT PUMP WATER HEATER (NORTHERN EUROPE) MAINTENANCE
26
(3)Comp Discharge Temp Protection E4
HEAT PUMP WATER HEATER (NORTHERN EUROPE) MAINTENANCE
27
(4) Comp Overload Protection E5
HEAT PUMP WATER HEATER (NORTHERN EUROPE) MAINTENANCE
28
(5)Fan 1 Overload Protection E8
(6)Fan 2 Overload Protection b8
HEAT PUMP WATER HEATER (NORTHERN EUROPE) MAINTENANCE
29
(7) Temperature Sensor Error F3, F5, F7
(8) Communication Malfunction EC
HEAT PUMP WATER HEATER (NORTHERN EUROPE) MAINTENANCE
30
Communication Malfunction EC
Check if the communicationline of the unit is connected
Measure if the Communication line is through
Check if the outdoor unitis electrically powered
Replace the communication line
NO
YES
NO
YES
NO
YES
NO
Check if the communication line of the unit is connected correctly
Check the orientationof plug and socket
Check the orientationof plug and socket
Please supply powerto the outdoor unit
HEAT PUMP WATER HEATER (NORTHERN EUROPE) MAINTENANCE
31
3 DISASSEMBLY AND ASSEMBLY PROCEDURE OF MAIN PARTS
Disassembly and Assembly of external casing
Remark:Please first cut off the power and drain let the Freon out of the unit
Operation Procedure Illustration
(1) Remove the front case
1) Remove the panel
·Loosen the two tapping screws fixing
the front grill.
·Pull down and remove the front grill.
(See Fig. 2)
2) Remove the cover.
· Loosen the two tapping screws fixing
the cover. Remove the cover(See Fig.
Fig. 1
Fig. 2
Fig. 3
HEAT PUMP WATER HEATER (NORTHERN EUROPE) MAINTENANCE
32
3)Remove the front plate.
· Loosen the two tapping screws
fixing the front plate. Remove the
front plate.(See Fig. 5)
4)Remove the grill
· Loosen the two tapping screws
fixing the grill. Remove the grill.
(See Fig. 6)
grill
Fig. 4
Fig. 5
Fig. 6
HEAT PUMP WATER HEATER (NORTHERN EUROPE) MAINTENANCE
33
(2) Remove the axial fan
· Loosen the ball nuts fixing the axial
fan and remove the washer.(See Fig.
7)
·Pull outward to remove the impeller.
(See Fig. 7)
(3) Remove the motor
· Loosen the screws fixing the motor
support. Remove the motor support.
(See Fig .8 & Fig.9)
Ball Nut
Fig. 7
Motor support
Fig. 8
Fig. 9
HEAT PUMP WATER HEATER (NORTHERN EUROPE) MAINTENANCE
34
· Loosen the two screws fixing the
motor. Pull backward and remove the
motor.(See Fig .10)
·Loosen the wire of motor, and pull it
through the hole.
(4) Remove the 4-way valve
Remove the 4-way valve
·Loosen the screws fixing the coil of
4-way valve。
·Remove the coil of 4-way valve。
·Welding out the tubes connected to the
4-way valve.
·Remove the 4-way valve.(See Fig.11)
Note:When welding, the valve should
be covered by wet cloth in order
to avoid the high temp. hurt。
Fig. 10
Fig. 11
(5) Remove electric box
· Loosen the screws fixing the box
HEAT PUMP WATER HEATER (NORTHERN EUROPE) MAINTENANCE
35
cover. Remove all pressure
switches and temp. sensor.(See
Fig.12)
(6)Remove compressor and
gas-liquid separator
· Remove the connection wire of
compressor。(See Fig.13)
· welding out the suction pipe and
discharge pipe.(See Fig.13)
·Loosen the bolts fixing the compressor
and Remove the compressor and
gas-liquid separator.
Fig.12
Compressor Gas-liquid separator
Fig.13
(7)Remove gas and liquid
valve
HEAT PUMP WATER HEATER (NORTHERN EUROPE) MAINTENANCE
36
1. Remove gas valve
·Loosen the bolts fixing the gas valve.
·welding out the pipe connected to the gas
valve (See Fig.14).
Note:When welding, the valve should be
covered by wet cloth in order to avoid the
high temp hurt.
2. Remove liquid valve
· Loosen the bolts fixing the liquid
valve.
·welding out the pipe connected to the
liquid valve (See Fig.15).
Note:When welding, the valve should be
covered by wet cloth in order to avoid the
high temp hurt.
Bolts Gas valve
Fig.14
Bolts Liquid valve
Fig.15
HEAT PUMP WATER HEATER (NORTHERN EUROPE) MAINTENANCE
37
4 EXPLODED VIEWS AND PART LIST
4.1 Single Fan
Exploded Views:
No. Name of part Part code Quantity
1 Valve Support Sub-Assy 01715001 1
2 Compressor Support Sub-Assy 01802222 1
3 Chassis Sub-Assy 01282235 1
4 Wooden Package Base 501154042 1
5 Compressor and Fittings 00205208 1
6 Cabinet 01435103 1
7 Front Grill 22265401 1
8 Condenser Inlet Pipe 04655706 1
9 Fan Motor 150154011 1
10 Axial Flow Fan 10335401 1
11 Motor Support Sub-Assy 01705402 1
12 Top Cover 01255402 1
13 Electric Box Sub-Assy 01392129 1
14 Clapboard Assy 01242214 1
15 Condenser Assy 01122216 1
16 4-way Valve Sub-Assy 04142216 1
17 Inhalation Tube Sub-Assy 04672240 1
HEAT PUMP WATER HEATER (NORTHERN EUROPE) MAINTENANCE
38
18 Cut-off Valve Sub-Assy 07332217 1
19 Gas-liquid Separator Assy 07255403 1
20 Bidirection Accumulator 07228741 1
21 Inflate Valve Sub-Assy 07332218 1
22 Rear Grill 01475401 1
23 Front Side Plate Sub-Assy 01312232 1
24 Rear Side Plate Sub-Assy 01305402 1
25 Capacitor CBB61 33010013 1
26 Main Board 30221602 1
27 Terminal Board 42011043 1
28 Terminal Board 42011103 2
29 Capacitor CBB65 3300002232 1
30 Transformer 43110240 1
31 AC Contactor 44010226 1
4.2 Double Fan
Exploded views:
No. Name of part Part code Quantity
1 Rear Side Plate Sub-Assy 01312815P 1
2 Valve Support Sub-Assy 01715001 1
3 4-way Valve Sub-Assy 04142815 1
4 Inflate Valve Sub-Assy 07332818 1
HEAT PUMP WATER HEATER (NORTHERN EUROPE) MAINTENANCE
39
5 Accumulator 07422204 1
6 Chassis Sub-Assy 01192813P 1
7 Liquid Valve Sub-Assy 07302803 1
8 Compressor and Fittings 00205205 1
9 Front Side Plate Sub-Assy 01305430 1
10 Handle 26235253 3
11 Axial Flow Fan 10338731 1
12 Fan Motor 150154513 1
13 Motor Support Sub-Assy 01705471 1
14 Front Grill 22414102 1
15 Cabinet 01435436 1
16 Top Cover 01255262 1
17 Condenser Assy 01122808 1
18 Inhalation Tube Sub-Assy 04672820 1
19 Electric Box Assy 01393734 1
20 Upper Insulation Plate Sub-Assy 01242802 1
21 Gas-liquid Separator Sub-Assy 07225018 1
22 Lower Insulation Plate 01242804 1