Technical Building Systems Security SystemsData Center Planning

Data Center Cooling Technology

SCHNABEL DC Consultants India Sreekumar K M, Consultant 02.09.2010

CII - Energy Efficiency Summit 2010

Technical Building Systems Security SystemsData Center Planning

3

1

3

Introduction

Air Conditioning

44

45

“The Process of Treating Air in an Indoor Environment to Establish and Maintain Required Standards of Temperature, Humidity, Cleanliness and Motion”

Technical Building Systems Security SystemsData Center Planning

3

1

3

Introduction

Environment Criteria – Temperature and Humidity

Parameter2004

Version2008

VersionLow End

Temperature20°C 18°C

44

45

Temperature20°C 18°C

High End Temperature

25°C 27°C

Low End Moisture

40% RH 5.5°C DP

High End Moisture

50% RH60% RH and

15°C DP

Technical Building Systems Security SystemsData Center Planning

3

1

3

Introduction

Environment Criteria – Cleanliness

� Gaseous Contamination - Severity level G1 as per ANSI/ISA – 71.04 – 1985

� Particulate Contamination - Cleanliness level as per ISO14644 Class 8

44

45

- Cleanliness level as per ISO14644 Class 8- Deliquescent Relative Humidity of the Particulate Contaminate Should be

more than 60%- Data Center must be Free of Zinc Whiskers

Technical Building Systems Security SystemsData Center Planning

3

1

3

Classic DC Cooling Methodology

44

45

Technical Building Systems Security SystemsData Center Planning

3

1

3

Optimised DC Cooling Methodology

Isolation of Airstreams

44

45

Chimney Racks

Cold Aisle Containment

Hot Aisle Containment

Technical Building Systems Security SystemsData Center Planning

3

1

3

Optimised DC Cooling Methodology

Moving Cooling Coil Closer to Load

44

45

Over Head Cooling Rear Door Heat ExchangerIn row Cooling

Technical Building Systems Security SystemsData Center Planning

3

1

3

Optimised DC Cooling Methodology

Hybrid

44

45

Close Coupled Racks

In row Cooling withAisle Containment

Supplemental Fans

Technical Building Systems Security SystemsData Center Planning

3

1

3

DC Energy Efficiency

Data Center Efficiency Metrics

� DCiE = IT Equipment Energy / Total Facility Energy

Standard Good Better.5 .7 .9

44

45� PUE = 1/ DCiE = Total Facility Energy / IT Equipment Energy

Standard Good Better2.0 1.4 1.1

.5 .7 .9

Technical Building Systems Security SystemsData Center Planning

3

1

3

DC Energy Efficiency

Climate Zones - ASHRAE Standards 90.1-2007 and 90.2-2007

44

45

Technical Building Systems Security SystemsData Center Planning

3

1

3

DC Energy Efficiency

DCiE by Climate Zone & Data Center Type, ASHRAE TC9.9 Committee

44

45

Technical Building Systems Security SystemsData Center Planning

3

1

3

DC Energy Efficiency

Mechanical System Efficiency Metrics

� PUE Mechanical = Energy Mechanical / Energy IT

� Recommended PUE Mechanical as per Climatic Zone =0.55

44

45

as per Climatic Zone =0.55

� Mechanical System Effectiveness = KWh/yr IT /kWh/yr HVAC

Standard Good Better

0.7 1.4 2.5

Technical Building Systems Security SystemsData Center Planning

3

1

3

DC Energy Efficiency

Social Impact

44

45

Technical Building Systems Security SystemsData Center Planning

3

1

3

Energy Efficiency

CII Initiative

“Energy Efficiency Guidelines and Best Practices in Indian Data Centers”

44

45

Technical Building Systems Security SystemsData Center Planning

3

1

3Thank You

44

45

SCHNABEL DC Consultants India Pvt. Ltd.Bangalore Mumbai