Rotronic goes CO2!
CO2Topics:• CO2 in general• CO2 transmitter• CO2 & Temp. transmitter• CO2 special transmitter
CO2 in general
Big topic over the last year, everybody has it.. e.g. Green house effect and environment …
CO2 in general
CO2 in general
Photosynthesis:
Chemical recation CO2 + H2O --> CHO + O2 + H2O
Carbon dioxide, water using light and chlorophyll, oxygen and glucose
CO2 in general
CO2 in general
Indoor air quality in offices leads to high or low levels of gases:
Since CO2 is exhaled by people at predictable levels the content of Carbon Dioxide - CO2 – in air may be a significant indication of air quality.
A measure of CO2 indicates the amount of fresh air supply:15 cfm = 7.0l/s ventilation rate per occupant
corresponds to 1000 ppm CO2
20 cfm = 9.2l/s ventilation rate per occupant corresponds to 800 ppm CO2
Normal CO2 LevelsThe effects of increased CO2 summarized:
• normal outdoor level: 350 - 450 ppm• acceptable levels: < 600 ppm• complaints of stiffness and odors: 600 - 1000 ppm• ASHRAE and OSHA standards: 1000 ppm• general drowsiness: 1000 - 2500 ppm• adverse health effects expected: 2500 - 5000 ppm• maximum allowed concentration within a 8 hour working period:
5000 ppm
CO2 in general
CO2 in general
Extreme and Dangerous CO2 Levels
• slightly intoxicating, breathing and pulse rate increase, nausea: 30,000 ppm
• above plus headaches and sight impairment: 50,000 ppm
• unconscious, further exposure death: 100.000 ppm
Rotronic CO2 transmitter Portfolio
CO2 transmitter
CO2 transmitter for climate control
• EU/US electrical junction box• Selectable with and without display• for fixed installation
“decreasing your energy consumption while creating a healthier indoor air climate”
CO2 transmitter
Specification EU:
• Measurement range : 0…2000 ppm• Method infrared (NDIR) w. Auto calibration • Accuracy : ± 30 ppm• Supply : 24 VDC/AC• Output 1 : 0…10 VDC (CO2)• Output 2: 4…20 mA (CO2)• Operation temperature : 0…50 °C• Dimensions (H x W x D): 100 x 80 x 25 mm
CF3-W-EU
CF3-W-EU-Dips
CO2 transmitter
Specification US:
• Measurement range : 0…2000 ppm• Measurement method:
Infrared (NDIR) w. Auto calibration • Accuracy : ± 30 ppm• Supply : 24 VDC/AC• Output 1 : 0…10 VDC (CO2)• Output 2: 4…20 mA (CO2)• Operation temperature : 0…50 °C• Dimensions (H x W x D): 130 x 85 x 30 mm
CF3-W-US
CF3-W-US-Dips
CO2 transmitter
Specification for duct version:
• Measurement range : 0…2000 ppm• Method infrared (NDIR) w. Auto calibration • Accuracy : ± 30 ppm• Supply : 24 VDC/AC• Output 1 : 0…10 VDC (CO2)• Output 2: 4…20 mA (CO2)• Operation temperature : 0…50 °C
CF3-D
CF3-D-Dips
CO2 & Temperature transmitter
CO2 & temperature transmitter for:
• BMS• Controlling Ventilation, Air flaps &
valves
“decreasing your energy consumption while creating a healthier indoor air climate”
DuctWall
Specification for wall mount:
• Measurement range : 0…2000 ppm• Measurement Temperature: 0.. 50 °C• Method infrared (NDIR) w. Auto calibration • Accuracy : ± 30 ppm• Supply : 24 VDC/AC• Output 1 : 0…10 VDC (CO2)• Output 2: 4…20 mA (CO2)• Operation temperature : 0…50 °C• Dimensions (H x W x D): 120 x 82 x 30 mm
CF5-W
CF5-W-Dips
CO2 & Temperature transmitter
Specification for duct mount:
• Measurement range : 0…2000 ppm• Measurement Temperature: 0.. 50 °C• Method infrared (NDIR) w. auto calibration • Accuracy : ± 30 ppm• Supply : 24 VDC/AC• Output 1 : 0…10 VDC (CO2)• Output 2: 4…20 mA (CO2)• Operation temperature : 0…50 °C• Dimensions (H x W x D): 142 x 84 x 46 mm• Ductprobe: 245 mm
CF5-D
CF5-D-Dips
CO2 & Temperature transmitter
CO2 special transmitter
Special CO2 transmitters:
• „Fresh Air Indication“• Carbon dioxide alarm • Sound & light indication• relays out’s • bigger ranges • for classrooms , offices , controllers
and more
“decreasing your energy consumption while creating a healthier indoor air climate”
CO2 special transmitter
CF3-W-EU-Displ-FLI
Special CO2 transmitters wall mount:
• Measurement range : 0…2000 ppm• Method Infrared (NDIR) w. Auto calibration • Accuracy : ± 30 ppm• Supply : 24 VDC/AC• Output 1 : 0…10 VDC (CO2)• Sound & light indication• Operation temperature : 0…50 °C• Dimensions (H x W x D): EU: 100x 80 x 28 mm // US: 130x 85 x 30 mm
CF3-W-US-Displ-FLI
CO2 special transmitter
Special CO2 transmitters alarm and relays:
• Measurement range : 0..4% CO2• Accuracy : ± 200 ppm
• Supply : 24 VDC/AC• Output 1 : 0 … 20mA or 0/2 ... 10 VDC (CO2)• Output 2: 0 … 20mA or 0/2 ... 10 VDC (CO2)• Output 3 (relay 1): Open > 1.4% closed >1.5% (CO2)• Output 4 (relay 2): Open > 2.9% closed >3.0% (CO2)
• Operation temperature : 0…50 °C• Dimensions (H x W x D): 142 x 84 x 46mm
CF8-W-Disp-AL
CO2 special transmitter
Special CO2 transmitters for Green House:
• Measurement range : 0…4000 ppm• Accuracy : ± 200 ppm
• Supply : 24 VDC/AC• Output 1 : 0 … 20mA or 0/2 ... 10 VDC (CO2)• Output 2: 0 … 20mA or 0/2 ... 10 VDC (°C)• Output 3 (relay): Open > 2.0% closed >1.9% (CO2)
• Operation temperature : 0…50 °C• Dimensions (H x W x D): 142 x 84 x 46mm
CF8-W-Disp-GH
CO2 special transmitter
Special CO2 transmitters for incubators:
• Measurement range : 0…3000 ppm• Accuracy : ± 200 ppm
• Supply : 24 VDC/AC• Output 1 : 0... 5 VDC, 0…2% (CO2)• Output 2: 0… 5 VDC, 0…3 % (CO2)
• Operation temperature : 0…50 °C• Dimensions (H x W x D): 142 x 84 x 46mm
CF8-D_W-Disp-IN