Control & Apparatus
Panelboard Specifi cation Chart making it easier to source and spec
your solutions
For more information:
If further assistance is required, please contact an authorized Eaton Distributor, Sales Offi ce, or Customer Service Department.
India91-124-4683888FAX: 91-124-4683899cchindia@cooperindustries.com
Australia61-2-8787-2777FAX: 61-2-9609-2342CEASales@cooperindustries.com
Korea82-2-3484-678382-2-3484-6778CCHK-sales@cooperindustries.com
China86-21-2899-3600FAX: 86-21-2899-4055cchsales@cooperindustries.com
Singapore65-6645-9888FAX: 65-6297-4819chsi-sales@cooperindustries.com
Middle East (Dubai)971 4 4272500FAX: 971 4 4298521sales.CCH.me@cooperindustries.com
Europe (Germany)49 (0) 6271 806-50049 (0) 6271 806-476sales.CCH.de@cooperindustries.com
Mexico/Latin America/Caribbean52-555-804-4000FAX: 52-555-804-4020mxmercadotecnia@cooperindustries.com
CanadaToll Free: 800-265-0502FAX: (800) 263-9504FAX Orders only: (866) 653-0645
U.S. (Global Headquarters):Eaton's Crouse-Hinds Business
1201 Wolf StreetSyracuse, NY 13208
(866) 764-5454FAX: (315) 477-5179FAX Orders Only: (866) 653-0640
crouse.customerctr@cooperindustries.com
Eaton is a registered trademark.
All other trademarks are property of their respective owners.
Eaton's Crouse-Hinds1201 Wolf StreetSyracuse, NY 13208Crouse-Hinds.com
Eaton1000 Eaton BoulevardCleveland, OH 44122United StatesEaton.com
© 2014 EatonAll Rights ReservedPrinted in USAPublication No. 5141-0714July 2014
Panelboard Specification ChartHazardous Location Classification Panel Series
Series Panel Type NEMA Rating
Main Lug Max. Rating
Main Breaker Max. Rating
Branch Breaker Max. Rating Breaker Type
Max. No. of Circuits Without Main Breaker
No. of Circuits with 3 Pole Main Breaker Poles
EPD/GFI No. of Circuits Available Group B
Factory Sealed Panel3 Sealing Requirements Enclosure Material
Approximate Weight (Lbs.)
120/240 Volt Lighting & Heat Tracing Panels
Div. 1,
Zone 1
Cl. I, Div. 1 & 2, Groups B*, C, D
Cl. II, Groups E, F, G
Cl. III
Cl. I, Zones 1 & 2, IIB + H2*
Exactra™ LP1B 3, 4, 4X, 7, 9, 12 100A 100A 35A CH BAB 24 21 1, 2, 3 6 With GB suffix Yes Seal all within 18 inches Cast aluminum 200
Exactra™ LP1C 3, 4, 4X, 7, 9, 12 100A 100A 35A CH BAB 36 33 1, 2, 3 6 With GB suffix Yes Seal all within 18 inches Cast aluminum 215
PowerPlus™ EPLBA 3, 4, 7, 9, 12 225A 100A (3) 100A, 50A CH BAB 24 21 1, 2, 3 21 With GB suffix Yes Seal all over 2 inches in Group B Cast aluminum 335
PowerPlus™ EPLBN 3, 4, 7, 9, 12 225A 100A 100A CH BAB 24 21 1, 2, 3 21 With GB suffix No Seal all within 18 inches Cast aluminum less terminal housing 225
PowerPlus™ EPLCA 3, 4, 7, 9, 12 225A 225A (3) 100A, 50A CH BAB 42 39 (<100A); 36 (110A - 225A) 1, 2, 3 21 With GB suffix Yes Seal all over 2 inches in Group B Cast aluminum 410
PowerPlus™ EPLCN 3, 4, 7, 9, 12 225A 225A 100A CH BAB 42 39 (<100A); 36 (110A - 225A) 1, 2, 3 21 With GB suffix No Seal all within 18 inches Cast aluminum less terminal housing 300
PowerPlus™ EPLDA 3, 4, 7, 9, 12 225A 225A (3) 100A, 50A CH BAB N/A 42 1, 2, 3 21 With GB suffix Yes Seal all over 2 inches in Group B Cast aluminum 420
PowerPlus™ EPLDN 3, 4, 7, 9, 12 225A 225A 100A CH BAB 42 42 1, 2, 3 42 With GB suffix No Seal all within 18 inches Cast aluminum less terminal housing 310
Div. 2,
Zone 1
Cl. I, Zone 1, AEx de IIC T4, T6
Cl. I, Zone 1, Ex de IIC T4, T6
Cl. I, Div. 2, Groups A, B, C, D
D2Z SpecOne™ D2ZA 3, 4X, 7, 12 180A2
180A 40A ABB 18 18 1, 2, 3, 4 125
Standard Yes No seals required GRP or stainless steel 75
D2Z SpecOne™ D2ZB 3, 4X, 7, 12 180A2
180A 40A ABB 36 36 1, 2, 3, 4 305
Standard Yes No seals required GRP or stainless steel 165
D2Z SpecOne™ D2ZC 3, 4X, 7, 12 180A2
180A 40A ABB 54 54 1, 2, 3, 4 485
Standard Yes No seals required GRP or stainless steel 210
D2Z SpecOne™ D2ZD 3, 4X, 7, 12 180A2
180A 40A ABB 72 72 1, 2, 3, 4 665
Standard Yes No seals required GRP or stainless steel 275
Div. 2,
Zone 2
Cl. I, Div. 2, Groups B*, C, D
Cl. II, Groups F, G
Cl. III
Cl. I, Zone 2, IIB + H2*
D2PB D2PB16
3, 7, 12 125A 100A 30A CH QC 12 12 1, 2 0 N/A Yes No seals required Cast aluminum 100
D2PB D2PB26
3, 7, 12 225A 100A 30A CH QC 24 24 1, 2 0 N/A Yes No seals required Cast aluminum 160
N2PB N2PB1 3, 7, 12 125A 100A 30A CH QC 12 12 1, 2 0 N/A Yes No seals required Krydon® 85
N2PB N2PB2 3, 7, 12 225A 100A 30A CH QC 24 24 1, 2 0 N/A Yes No seals required Krydon® 145
Exactra™ LP2B 3, 4, 4X, 7, 9, 12 100A 100A 35A CH BAB 24 21 1, 2, 3 6 With GB suffix Yes No seals required Cast aluminum 195
Exactra™ LP2C 3, 4, 4X, 7, 9, 12 100A 100A 35A CH BAB 36 33 1, 2, 3 6 With GB suffix Yes No seals required Cast aluminum 210
PowerPlus™ D2LBA 3, 4, 7, 12 100A 100A (3) 100A, 50A CH BAB 24 21 1, 2, 3 21 With GB suffix Yes No seals required Cast aluminum 325
PowerPlus™ D2LBS 3, 4, 7, 12 100A 100A (3) 100A, 50A CH BAB 24 21 1, 2, 3 21 With GB suffix Yes No seals requiredCast aluminum - bk. housing
Stainless steel - term. housing275
PowerPlus™ D2LCA 3, 4, 7, 12 225A 225A (3) 100A, 50A CH BAB 42 39 (<100A); 36 (110A - 225A) 1, 2, 3 21 With GB suffix Yes No seals required Cast aluminum 400
PowerPlus™ D2LCS 3, 4, 7, 12 225A 225A (3) 100A, 50A CH BAB 42 39 (<100A); 36 (110A - 225A) 1, 2, 3 21 With GB suffix Yes No seals requiredCast aluminum - bk. housing
Stainless steel - term. housing350
PowerPlus™ D2LDA 3, 4, 7, 12 225A 225A (3) 100A, 50A CH BAB N/A 42 1, 2, 3 21 With GB suffix Yes No seals required Cast aluminum 410
PowerPlus™ D2LDS 3, 4, 7, 12 225A 225A (3) 100A, 50A CH BAB N/A 42 1, 2, 3 21 With GB suffix Yes No seals requiredCast aluminum - bk. housing
Stainless steel - term. housing360
277/480 Volt Power Panels & 347/6004 Volt Power Panels
Div. 1,
Zone 1
Cl. I, Div. 1 & 2, Groups B*, C, D
Cl. II, Groups E, F, G
Cl. III
Cl. I, Zones 1 & 2, IIB + H2*
PowerPlus™ EXDB 3, 4, 7, 12 100A 100A (3) 100A, 70A CH GHB 24 21 1, 2, 3 0 With GB suffix Yes Seal all over 2 inches in Group B Cast aluminum 460
PowerPlus™ EXDC 3, 4, 7, 12 100A 100A (3) 100A, 70A CH GHB 42 34 1, 2, 3 0 With GB suffix No Seal all over 2 inches in Group B Cast aluminum 560
PowerPlus™ EXDD 3, 4, 7, 12 225A 225A (3) 100A, 70A CH GHB N/A 42 1, 2, 3 0 With GB suffix Yes Seal all over 2 inches in Group B Cast aluminum 560
PowerPlus™ EXDF1
3, 4, 7, 12 225A 225A (3) 100A, 70A CH EHD 30 30 1, 2, 3 0 With GB suffix Yes Seal all over 2 inches in Group B Cast aluminum 590
Div. 2,
Zone 1
Cl. I, Zone 1, AEx de IIC T4, T6
Cl. I, Zone 1, Ex de IIC T4, T6
Cl. I, Div. 2, Groups A, B, C, D
D2Z SpecOne™ D2ZA 3, 4X, 7, 12 180A2
180A 25A ABB 18 18 1, 2, 3, 4 0 Standard Yes No seals required GRP or stainless steel 75
D2Z SpecOne™ D2ZB 3, 4X, 7, 12 180A2
180A 25A ABB 36 36 1, 2, 3, 4 0 Standard Yes No seals required GRP or stainless steel 165
D2Z SpecOne™ D2ZC 3, 4X, 7, 12 180A2
180A 25A ABB 54 54 1, 2, 3, 4 0 Standard Yes No seals required GRP or stainless steel 210
D2Z SpecOne™ D2ZD 3, 4X, 7, 12 180A2
180A 25A ABB 72 72 1, 2, 3, 4 0 Standard Yes No seals required GRP or stainless steel 275
Div. 2,
Zone 2
Cl. I, Div. 2, Groups B*, C, D
Cl. II, Groups F, G
Cl. III
Cl. I, Zone 2, IIB + H2*
PowerPlus™ D2DB 3, 4, 7, 12 100A 100A (3) 100A, 70A CH GHB 24 21 1, 2, 3 0 With GB suffix Yes No seals required Cast aluminum 700
PowerPlus™ D2DC 3, 4, 7, 12 100A 100A (3) 100A, 70A CH GHB 42 34 1, 2, 3 0 With GB suffix Yes No seals requiredCast aluminum - bk. housing
Stainless steel - term. housing650
PowerPlus™ D2DD 3, 4, 7, 12 225A 225A (3) 100A, 70A CH GHB N/A 42 1, 2, 3 0 With GB suffix Yes Seal all over 2 inches in Group B Cast aluminum 650
PowerPlus™ D2DF1
3, 4, 7, 12 225A 225A (3) 100A, 70A CH EHD 30 30 1, 2, 3 0 With GB suffix Yes Seal all over 2 inches in Group B Cast aluminum 590
NOTE: For ordering information or to build a catalog number for specific panel series, please refer to Section A of the Eaton's Crouse-Hinds Full-Line Product Catalog. For wiring diagrams and dimensions, please contact Customer Service at 866-764-5454. All panelboards have a maximum short circuit rating of 10kA.
*For Group B classification, please view Group B column.1 Available with 600 VAC as options (with suffixes FB600, FD600 or HFD600).2 Main disconnect switch rating.3 Factory sealing provides time and material cost savings.
4 Refer to catalog for suffixes to accommodate higher VAC requirements.5 RCD (Residual Current Devices) with 30mA trip.6 Class I, Division 2 only.