Asset: P.S. 136 - QUEENS, 201-15 115 AVENUE, New York, 11412
Inspection Id Inspection Type Time In Last Edited
SA : Q136 Architectural - Senior 2020-08-21 7:21 AM 2020-08-27 9:34 AM
AA : Q136 Architectural - Associate 2020-08-21 7:14 AM 2020-09-03 2:58 PM
Asset Data
Question Answer
Was the building fully accessible for inspection Yes
Principal(s) Information
Principal Name Dr. Tanya Walker
Organization P.S. 136 - Queens
Did you meet with this Principal? No
Did this Principal provide feedback? Yes
Summary of Principal's Feedback A Principal questionnaire form was returned with concerns aboutadditional ventilation on the 2nd and 3rd Floors for the upcomingschool year.
Custodian Stephen McPartland
Fireman Joseph Barbieri
Building Square Footage 87000
Comments on the Area None
Comments on the Stories (Floors) plus Basements 3+B
Comments on the Number of Classrooms 38
Comments on the Year Built 1928
Student Population 640
Staff Population 80
Weather Fair
Facade Photo
Corner of 115th Avenue and 221st Street -Northeast View
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
Q136
PB/A&W Print Date: 9/13/2020Page 1 of 45
Main Entrance Photo
Facade A - 115th Avenue
Roof Photo
Roof 1 - Northeast View
Have any Systems/Major Building Components been upgraded? Yes
Systems: 1st Floor Student Toilet Rooms converted HC compliance.
Year: 2018
Systems: Loading Dock repairs.
Year: 2017
Systems: Exterior Modernization Program including Roofing andFlashing replacement; Parapets and Coping replacement;Roof Drains replacement; Bulkhead Exterior Wallsrepairs; Windows and Window Guards replacement(Partial 1st Floor and entire 2nd and 3rd Floor); PartialExterior Walls Brick Veneer replacement at 2nd Floor;Partial Foundation Walls waterproofing at Facade A .
Year: 2015
Systems: Exterior Walls repairs.
Year: 2012
Systems: Partial Basement waterproofing; Areaway Walls repairs;Exterior Doors repairs; Stairs repairs.
Year: 2010
Systems: Exterior Walls, Bulkhead and Structural repairs.
Year: 2009
Have there been any New Building Additions? Yes
Comments on New Building Additions 1937 + 29,000 S.F.
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
Q136
PB/A&W Print Date: 9/13/2020Page 2 of 45
Tandem Schools? No
Leased Space? No
Priority Condition
PriorityCondition ExistLast Year?
PriorityCategory
ConditionDescription
ComponentAffected
LocationDescription
Person(s)Notified
Person(s) Title PhotoImage
No Damaged/Deteriorated Railings
Damaged railingwith exposedsharp edges is apotential safetyhazard.
EXTERIOR |STAIRS/RAMPS: EXTERIOR |RAILINGS
Southwest Exitstair facing115th Avenue.
Joseph Barbieri Fireman
No Other Broken treebranch that issemi-attached tothe tree is aPotential SafetyHazard
DOT Sidewalk 202nd Street StephenMcPartland
Custodian
No Potential FallingDebris
Broken andloose stone wallis a PotentialSafety Hazard
INTERIOR |AUDITORIUM| Walls
Auditorium -Near ExitVestibule 9A
Joseph Barbieri Fireman
Structural Engineer Required
StructuralCondition Type
ConditionDescription
ComponentAffected
LocationDescription
Person(s)Notified
Person(s) Title PhotoImage
No condition recorded
Accessibility
Accessibility Status Question Response
Is the primary or secondary entrance on an accessible route? No
Physical Breakdown Structure Exists Required Complies Deficiency AudioInductionSystem
FireAlarmStrobe
FUNCTIONAL ACCESSIBILITY
Exterior Routes
Exterior Entrances & Exits No Saddle height > 1/2"
Exterior H/C Lifts No No
Exterior Ramps and Railings No Yes
Interior Routes
Corridor and Lobby H/C Lifts No No
Interior Corridor Doors and Hardware Yes Yes
Interior Corridors and Lobbies Yes
Interior Elevators No
Interior Lobby Doors and Hardware Yes
Interior Ramps No
Rooms & Spaces
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
Q136
PB/A&W Print Date: 9/13/2020Page 3 of 45
Physical Breakdown Structure Exists Required Complies Deficiency AudioInductionSystem
FireAlarmStrobe
Rooms & Spaces
Art Rooms No
Auditorium 1st Floor Yes No No Stage AccessNot on Accessible Route
Yes No
Cafeteria 1st Floor Yes No Not on Accessible Route Yes No
Classrooms None on Accessible Route Yes No Not on Accessible Route
Computer Rooms Room 321 Yes No Not on Accessible Route
Gymnasium 3rd Floor Yes No Not on Accessible Route Yes No
Library Room 211 Yes No Not on Accessible Route
Main Office Room 255 Yes No Not on Accessible Route
Multi-purpose Room No
Nurse's Room Room 263 Yes No Not on Accessible Route
Pool No
Science Lab No
Toilet Rooms (Boys) None on Accessible Route Yes No Not on Accessible Route
Toilet Rooms (Girls) None on Accessible Route Yes No Not on Accessible Route
Toilet Rooms (Staff) None on Accessible Route Yes No Not on Accessible Route
Building Template
Inspection
Question Response
Architectural
EXTERIOR Inspected
AREAWAY Inspected
InspectedInstance on AW1-AW10
Instance Condition 3 - Fair
Instance Quantity 10
Instance Quantity Uom EACH
Deficiency AREAWAY WALLS: CRACKS AND SPALLING
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
Q136
PB/A&W Print Date: 9/13/2020Page 4 of 45
Question Response
EXTERIOR
AREAWAY
Roof Plan reference
Deficiency Quantity 20
Quantity Uom S.F.
Potential Action REPAIR
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Facade A - AW1
Violations No violations recorded.
Deficiency AREAWAY GRATINGS: MINOR RUSTING
Roof Plan reference
Deficiency Quantity 150
Quantity Uom S.F.
Potential Action MAINTENANCE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1 No photo recorded
Violations No violations recorded.
AWNINGS AND CANOPIES Does not Exist
CHIMNEY Inspected
Material Type(s) Masonry
Condition 2 - Between Good and Fair
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
Q136
PB/A&W Print Date: 9/13/2020Page 5 of 45
Question Response
EXTERIOR
CHIMNEY Inspected
Deficiency No deficiencies recorded
COPING Inspected
Condition 1 - Good
Deficiency No deficiencies recorded
CORNICE Does not Exist
DOORS Inspected
DOORS AND FRAMES Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
DOOR HARDWARE Inspected
Condition 3 - Fair
Deficiency No deficiencies recorded
LINTELS Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
TRANSOM/SIDE LIGHT Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
EXTERIOR WALLS Inspected
Material Type(s) Masonry
Replacement Quantity 40,500
Replacement Uom S.F.
InspectedInstance on All Facades
Instance Condition 2 - Between Good and Fair
Instance Quantity 40,500
Instance Quantity Uom S.F.
Deficiency No deficiencies recorded
EXTERIOR SOFFITS Does not Exist
LOADING DOCK Inspected
Condition 4 - Between Fair and Poor
Deficiency CHEEK WALL/CRACKS, SPALLING - MAJOR
Roof Plan reference
Deficiency Quantity 20
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 4
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
Q136
PB/A&W Print Date: 9/13/2020Page 6 of 45
Question Response
EXTERIOR
LOADING DOCK
Deficiency Photo1
Facade C
Violations No violations recorded.
LOUVER Inspected
Condition 1 - Good
Deficiency No deficiencies recorded
PARAPETS Inspected
Material Type(s) Masonry
Replacement Quantity 4,000
Replacement Uom C.F.
InspectedInstance on All Facades
Instance Condition 3 - Fair
Instance Quantity 4,000
Instance Quantity Uom C.F.
Deficiency BRICK: OPEN JOINTS
Roof Plan reference
Deficiency Quantity 200
Quantity Uom S.F.
Potential Action REPOINT
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Roof 4
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
Q136
PB/A&W Print Date: 9/13/2020Page 7 of 45
Question Response
EXTERIOR
PARAPETS Inspected
Violations No violations recorded.
PLAZA DECK Does not Exist
ROOF Inspected
Roofing Inspected
Replacement Quantity 26,000
Replacement Uom S.F.
ROOF HATCH/SMOKE HATCH Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
LEADERS, GUTTERS, DOWNSPOUTS, SCUPPERS Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
ROOF BARRIER Inspected
Condition 1 - Good
Deficiency No deficiencies recorded
ROOF CAGE Does not Exist
ROOF FENCE Does not Exist
ROOFING Inspected
InspectedInstance on Modified Bitumen: All Roofs
Instance Condition 1 - Good
Instance Quantity 26,000
Instance Quantity Uom S.F.
Does the roof have major mechanical equipment sitting onDunnage Steel less than 18" above the Roofing?
No
Installation Year 2015
Source of Installation Custodial Staff
Deficiency No deficiencies recorded
ROOFING DRAINS Inspected
Condition 1 - Good
Deficiency No deficiencies recorded
Specialties Inspected
BULKHEAD/PENTHOUSE Inspected
Condition 3 - Fair
Deficiency BULKHEAD/PENTHOUSE WALLS/EXTERIOR:CRACKS/SPALLING - MINOR
Roof Plan reference
Deficiency Quantity 30
Quantity Uom S.F.
Potential Action REPAIR
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
Q136
PB/A&W Print Date: 9/13/2020Page 8 of 45
Question Response
EXTERIOR
ROOF Inspected
Specialties
BULKHEAD/PENTHOUSE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Roof 1 - Roof Vent
Violations No violations recorded.
CUPOLA/ SPIRES/ TOWERS Does not Exist
DORMER Does not Exist
DUNNAGE STEEL Does not Exist
SKYLIGHT/ROOF VENT Inspected
Material Type(s) Glass
Condition 3 - Fair
Deficiency SHAFT VENTS DAMAGED
Roof Plan reference
Deficiency Quantity 1
Quantity Uom EACH
Potential Action MAINTENANCE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Roof 1
Violations No violations recorded.
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
Q136
PB/A&W Print Date: 9/13/2020Page 9 of 45
Question Response
EXTERIOR
ROOF
Specialties
SKYLIGHT/ROOF VENT
Deficiency DAMAGED GUARDS
Roof Plan reference
Deficiency Quantity 15
Quantity Uom S.F.
Potential Action MAINTENANCE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Roof 1
Violations No violations recorded.
Deficiency BROKEN GLASS
Roof Plan reference
Deficiency Quantity 10
Quantity Uom S.F.
Potential Action MAINTENANCE
Urgency of Action PRIORITY 5
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
Q136
PB/A&W Print Date: 9/13/2020Page 10 of 45
Question Response
EXTERIOR
ROOF
Specialties
SKYLIGHT/ROOF VENT
Deficiency Photo1
Roof 1
Violations No violations recorded.
ROOF/GRAVITY TANK Does not Exist
STAIRS/RAMPS: EXTERIOR Inspected
BUILDING CHEEK/FLANK WALLS Inspected
Condition 3 - Fair
Deficiency STONE: CRACKS/SPALLING - MINOR
Roof Plan reference
Deficiency Quantity 10
Quantity Uom S.F.
Potential Action REPAIR
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Facade A
Violations No violations recorded.
Deficiency STONE: OPEN JOINTS
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
Q136
PB/A&W Print Date: 9/13/2020Page 11 of 45
Question Response
EXTERIOR
STAIRS/RAMPS: EXTERIOR
BUILDING CHEEK/FLANK WALLS
Roof Plan reference
Deficiency Quantity 10
Quantity Uom S.F.
Potential Action REPOINT
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Facade H
Violations No violations recorded.
RAILINGS Inspected
Condition 3 - Fair
Deficiency RUST - MAJOR
Roof Plan reference
Deficiency Quantity 10
Quantity Uom L.F.
Potential Action REPLACE
Urgency of Action PRIORITY 5
Purpose of Action LEVEL 6
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
Q136
PB/A&W Print Date: 9/13/2020Page 12 of 45
Question Response
EXTERIOR
STAIRS/RAMPS: EXTERIOR
RAILINGS
Deficiency Photo1
Facade A
Violations No violations recorded.
Deficiency RUST - MINOR
Roof Plan reference
Deficiency Quantity 40
Quantity Uom L.F.
Potential Action MAINTENANCE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1 No photo recorded
Violations No violations recorded.
STAIRS/RAMPS Inspected
Condition 3 - Fair
Deficiency STONE: WORN-OUT TREAD/RISER/NOSING
Roof Plan reference
Deficiency Quantity 10
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 4
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
Q136
PB/A&W Print Date: 9/13/2020Page 13 of 45
Question Response
EXTERIOR
STAIRS/RAMPS: EXTERIOR
STAIRS/RAMPS
Deficiency Photo1
Facade F
Violations No violations recorded.
Deficiency CONCRETE: CRACKS/SPALLING - MINOR
Roof Plan reference
Deficiency Quantity 10
Quantity Uom S.F.
Potential Action REPAIR
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Facade A
Violations No violations recorded.
WINDOWS Inspected
Replacement Quantity 11,030
Replacement Uom S.F.
EXTERIOR GUARDS Inspected
Condition 3 - Fair
Deficiency RUST - MINOR
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
Q136
PB/A&W Print Date: 9/13/2020Page 14 of 45
Question Response
EXTERIOR
WINDOWS
EXTERIOR GUARDS
Roof Plan reference
Elevation
Deficiency Quantity 60
Quantity Uom S.F.
Potential Action MAINTENANCE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1 No photo recorded
Violations No violations recorded.
LINTELS Inspected
Condition 2 - Between Good and Fair
Deficiency STEEL: MINOR RUSTING
Roof Plan reference
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
Q136
PB/A&W Print Date: 9/13/2020Page 15 of 45
Question Response
EXTERIOR
WINDOWS
LINTELS
Elevation
Deficiency Quantity 20
Quantity Uom L.F.
Potential Action MAINTENANCE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1 No photo recorded
Violations No violations recorded.
WINDOWS Inspected
Material Type(s) Aluminum, Solid Wood
InspectedInstance on Aluminum - Double Hung: All Facades (Basement, Partial 1stFloor)
Instance Condition 3 - Fair
Instance Quantity 4,700
Instance Quantity Uom S.F.
Installation Year 2000
Source of Installation Custodial Staff
Deficiency No deficiencies recorded
InspectedInstance on Aluminum - Double Hung: All Facades (Partial 1st Floor, Entire2nd and 3rd Floor)
Instance Condition 1 - Good
Instance Quantity 6,300
Instance Quantity Uom S.F.
Installation Year 2013
Source of Installation Custodial Staff
Deficiency No deficiencies recorded
InspectedInstance on Wood: AW1, AW2
Instance Condition 5 - Poor
Instance Quantity 30
Instance Quantity Uom S.F.
Installation Year 1939
Source of Installation Custodial Staff
Deficiency WOOD: DETERIORATED
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
Q136
PB/A&W Print Date: 9/13/2020Page 16 of 45
Question Response
EXTERIOR
WINDOWS
WINDOWS
Roof Plan reference
Elevation
Deficiency Quantity 30
Quantity Uom S.F.
Potential Action REPLACE WINDOW
Urgency of Action PRIORITY 4
Purpose of Action LEVEL 2
Deficiency Photo1
Facade A - AW1
Violations No violations recorded.
INTERIOR Inspected
POOLS Does not Exist
STRUCTURAL Inspected
COLUMNS/BEAMS/BEARING WALLS Inspected
Condition 3 - Fair
Deficiency CONCRETE COLUMNS/BEAMS:CRACKED/SPALLED/REINFORCEMENT EXPOSED
Deficiency Location/Instance Basement - Boiler Room, Fan Area
Deficiency Quantity 40
Quantity Uom S.F.
Potential Action REPAIR
Urgency of Action PRIORITY 3
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
Q136
PB/A&W Print Date: 9/13/2020Page 17 of 45
Question Response
INTERIOR
STRUCTURAL
COLUMNS/BEAMS/BEARING WALLS
Purpose of Action LEVEL 5
Deficiency Photo1
Basement - Boiler Room
Violations No violations recorded.
FLOOR STRUCTURE Inspected
Condition 3 - Fair
Deficiency CONCRETE SLAB ON GRADE: MINOR CRACKS
Deficiency Location/Instance Basement - Boiler Room
Deficiency Quantity 30
Quantity Uom S.F.
Potential Action REPAIR
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 5
Deficiency Photo1
Basement - Boiler Room
Violations No violations recorded.
Deficiency CONCRETE: CRACKS/SPALLED/REINFORCEMENT EXPOSED
Deficiency Location/Instance 1st Floor - Facade E - East Vestibule, Basement - Storage
Deficiency Quantity 60
Quantity Uom S.F.
Potential Action REPAIR
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 5
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
Q136
PB/A&W Print Date: 9/13/2020Page 18 of 45
Question Response
INTERIOR
STRUCTURAL
FLOOR STRUCTURE Inspected
Deficiency Photo1
1st Floor - Facade E - East Vestibule
Violations No violations recorded.
FOUNDATION WALLS Inspected
Material Type(s) Concrete
Condition 4 - Between Fair and Poor
Deficiency CONCRETE: CRACKED/SPALLED/REINFORCEMENTEXPOSED
Deficiency Location/Instance Basement - Boiler Room
Deficiency Quantity 20
Quantity Uom S.F.
Potential Action REPAIR
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 5
Deficiency Photo1
Basement - Boiler Room
Violations No violations recorded.
Deficiency CONCRETE: WATER INFILTRATION IN NON- INSTRUCTIONALSPACE
Deficiency Location/Instance Basement - Glass Storage
Deficiency Quantity 100
Quantity Uom S.F.
Potential Action INSTALL WATERPROOFING
Urgency of Action PRIORITY 5
Purpose of Action LEVEL 5
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
Q136
PB/A&W Print Date: 9/13/2020Page 19 of 45
Question Response
INTERIOR
STRUCTURAL
FOUNDATION WALLS Inspected
Deficiency Photo1
Basement - Glass Storage
Violations No violations recorded.
ROOF STRUCTURE Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
VAULTS-BUNKERS Inspected
Foundation Walls Inspected
Condition 3 - Fair
Deficiency CRACKS, SPALLING
Deficiency Location/Instance Basement - Ash Hoist Vault
Deficiency Quantity 30
Quantity Uom S.F.
Potential Action REPAIR
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 5
Deficiency Photo1
Basement - Ash Hoist Vault
Violations No violations recorded.
Slab Structure Inspected
Condition 3 - Fair
Deficiency CONCRETE: WATER INFILTRATION IN NON- INSTRUCTIONALSPACE
Deficiency Location/Instance Basement - Ash Hoist Vault
Deficiency Quantity 40
Quantity Uom S.F.
Potential Action INSTALL WATERPROOFING
Urgency of Action PRIORITY 5
Purpose of Action LEVEL 5
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
Q136
PB/A&W Print Date: 9/13/2020Page 20 of 45
Question Response
INTERIOR
STRUCTURAL
VAULTS-BUNKERS
Slab Structure
Deficiency Photo1
Basement - Ash Hoist Vault
Violations No violations recorded.
Vault/Ash Hoist Doors and Framing Inspected
Condition 5 - Poor
Deficiency WATER INFILTRATION
Deficiency Location/Instance Basement - Ash Hoist Vault
Deficiency Quantity 10
Quantity Uom S.F.
Potential Action REPAIR
Urgency of Action PRIORITY 5
Purpose of Action LEVEL 2
Deficiency Photo1
Basement - Ash Hoist Vault
Violations No violations recorded.
Deficiency MINOR RUSTING
Deficiency Location/Instance Basement - Ash Hoist Vault
Deficiency Quantity 3
Quantity Uom EACH
Potential Action REPAIR
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
Q136
PB/A&W Print Date: 9/13/2020Page 21 of 45
Question Response
INTERIOR
STRUCTURAL Inspected
VAULTS-BUNKERS
Vault/Ash Hoist Doors and Framing
Deficiency Photo1
Basement - Ash Hoist Vault
Violations No violations recorded.
AUDITORIUM Inspected
InspectedInstance on 1st Floor (540 Seats)
Ceiling
InspectedInstance on 1st Floor (540 Seats)
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Door(s)
InspectedInstance on 1st Floor (540 Seats)
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Fixed H/C Lift
Does not ExistInstance on 1st Floor (540 Seats)
Fixed Seating
InspectedInstance on 1st Floor (540 Seats)
Condition 2 - Between Good and Fair
Deficiency DAMAGED/BROKEN/INOPERABLE
Deficiency Location/Instance Seats B/2, H/1, L/13, 15, 17, and others
Deficiency Quantity 11
Quantity Uom EACH
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Seat H/1
Violations No violations recorded.
Floor Finish
InspectedInstance on 1st Floor (540 Seats)
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
Q136
PB/A&W Print Date: 9/13/2020Page 22 of 45
Question Response
INTERIOR
AUDITORIUM Inspected
Floor Finish
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Sliding-folding Partition
Does not ExistInstance on 1st Floor (540 Seats)
Stage
InspectedInstance on 1st Floor (540 Seats)
Stage Inspected
InspectedInstance on 1st Floor (540 Seats)
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Stage Curtain Rigging Inspected
InspectedInstance on 1st Floor (540 Seats)
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Stage Curtains Inspected
InspectedInstance on 1st Floor (540 Seats)
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Walls
InspectedInstance on 1st Floor (540 Seats)
Condition 2 - Between Good and Fair
Deficiency PLASTER: CRACKS/SPALLING
Deficiency Location/Instance Exit Vestibule 9A
Deficiency Quantity 15
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Exit Vestibule 9A
Violations No violations recorded.
Deficiency STONE MOLDINGS: CRACKS/SPALLING
Deficiency Location/Instance Near Exit Vestibule 9A
Deficiency Quantity 5
Quantity Uom L.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
Q136
PB/A&W Print Date: 9/13/2020Page 23 of 45
Question Response
INTERIOR
AUDITORIUM
Walls
Deficiency Photo1
Near Exit Vestibule 9A
Violations No violations recorded.
Deficiency STONE: CRACKS/SPALLING
Deficiency Location/Instance Auditorium - Near Exit Vestibule 9A
Deficiency Quantity 15
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 5
Purpose of Action LEVEL 6
Deficiency Photo1
Auditorium - Near Exit Vestibule 9A
Violations No violations recorded.
Window Curtains/Shades/Blinds
InspectedInstance on 1st Floor (540 Seats)
Condition 5 - Poor
Deficiency INOPERABLE CURTAINS
Deficiency Location/Instance Near windows at Left and right sides
Deficiency Quantity 3
Quantity Uom EACH
Potential Action MAINTENANCE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1 No photo recorded
Violations No violations recorded.
CAFETERIA Inspected
InspectedInstance on 1st Floor
Ceiling
InspectedInstance on 1st Floor
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
Q136
PB/A&W Print Date: 9/13/2020Page 24 of 45
Question Response
INTERIOR
CAFETERIA
Door(s)
InspectedInstance on 1st Floor
Condition 5 - Poor
Deficiency WOOD: DETERIORATED DOOR
Deficiency Location/Instance Main Entrance, rear corridor Entrance
Deficiency Quantity 3
Quantity Uom EACH
Potential Action MAINTENANCE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Main Entrance
Rear corridor Entrance
Violations No violations recorded.
Fixed Equipment
Does not ExistInstance on 1st Floor
Floor Finish
InspectedInstance on 1st Floor
Condition 3 - Fair
Deficiency CONCRETE: CRACKS
Deficiency Location/Instance Near Toilet Room , Center, Near Exit 2, Near Serving Area
Deficiency Quantity 250
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
Q136
PB/A&W Print Date: 9/13/2020Page 25 of 45
Question Response
INTERIOR
CAFETERIA
Floor Finish
Deficiency Photo1
Near Toilet Room
Violations No violations recorded.
Sliding-folding Partition
Does not ExistInstance on 1st Floor
Stage
Does not ExistInstance on 1st Floor
Walls
InspectedInstance on 1st Floor
Condition 2 - Between Good and Fair
Deficiency SALT GLAZED BRICK: CRACKS/SPALLING
Deficiency Location/Instance Near Toilet Room , Near Serving Area
Deficiency Quantity 50
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Near Toilet Room
Violations No violations recorded.
Window Curtains/Shades/Blinds
Does not ExistInstance on 1st Floor
CLASSROOMS/CORRIDORS/ADMIN SPACES Inspected
Ceiling Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Door(s) Inspected
Condition 5 - Poor
Deficiency WOOD: DETERIORATED DOOR
Deficiency Location/Instance Rooms 222, 231, 313, 320, 321, Exit Vestibule 10, and others
Deficiency Quantity 17
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
Q136
PB/A&W Print Date: 9/13/2020Page 26 of 45
Question Response
INTERIOR
CLASSROOMS/CORRIDORS/ADMIN SPACES
Door(s)
Quantity Uom EACH
Potential Action MAINTENANCE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Room 321
Violations No violations recorded.
Deficiency WOOD: DETERIORATED DOOR AND FRAME
Deficiency Location/Instance Main Entrance Vestibule
Deficiency Quantity 2
Quantity Uom EACH
Potential Action MAINTENANCE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Main Entrance Vestibule
Violations No violations recorded.
Floor Finish Inspected
Condition 2 - Between Good and Fair
Deficiency VINYL TILES: TRIPPING HAZARD - ELECTRICAL OUTLET
Deficiency Location/Instance Room 321
Deficiency Quantity 20
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 5
Purpose of Action LEVEL 6
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
Q136
PB/A&W Print Date: 9/13/2020Page 27 of 45
Question Response
INTERIOR
CLASSROOMS/CORRIDORS/ADMIN SPACES
Floor Finish
Deficiency Photo1
Room 321
Violations No violations recorded.
Deficiency VINYL TILES: DETERIORATED SUBSTRATE
Deficiency Location/Instance Room 207
Deficiency Quantity 80
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Room 207
Violations No violations recorded.
Deficiency VINYL TILES: BROKEN/DETERIORATED/MISSING TILES
Deficiency Location/Instance Rooms 101, 321
Deficiency Quantity 40
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Room 321
Violations No violations recorded.
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
Q136
PB/A&W Print Date: 9/13/2020Page 28 of 45
Question Response
INTERIOR
CLASSROOMS/CORRIDORS/ADMIN SPACES
Walls Inspected
Condition 2 - Between Good and Fair
Deficiency STONE: CRACKS/SPALLING
Deficiency Location/Instance Main Entrance Vestibule, Corridor near Auditorium
Deficiency Quantity 75
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Corridor near Auditorium
Violations No violations recorded.
Deficiency STONE MOLDINGS: CRACKS/SPALLING
Deficiency Location/Instance Main Entrance Vestibule, Corridor near Auditorium
Deficiency Quantity 25
Quantity Uom L.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Main Entrance Vestibule
Violations No violations recorded.
Deficiency PLASTER: CRACKS/SPALLING
Deficiency Location/Instance Main Entrance Vestibule
Deficiency Quantity 15
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
Q136
PB/A&W Print Date: 9/13/2020Page 29 of 45
Question Response
INTERIOR
CLASSROOMS/CORRIDORS/ADMIN SPACES
Walls
Deficiency Photo1
Main Entrance Vestibule
Violations No violations recorded.
Specialties Does not Exist
GYMNASIUM Inspected
InspectedInstance on 3rd Floor
Ceiling
InspectedInstance on 3rd Floor
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Door(s)
InspectedInstance on 3rd Floor
Condition 3 - Fair
Deficiency WOOD: DETERIORATED DOOR
Deficiency Location/Instance Office
Deficiency Quantity 1
Quantity Uom EACH
Potential Action MAINTENANCE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Office
Violations No violations recorded.
Fixed Equipment
InspectedInstance on 3rd Floor
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Floor Finish
InspectedInstance on 3rd Floor
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
Q136
PB/A&W Print Date: 9/13/2020Page 30 of 45
Question Response
INTERIOR
GYMNASIUM
Seating
InspectedInstance on 3rd Floor
Condition 3 - Fair
Deficiency DAMAGED FIXED SEATING
Deficiency Location/Instance Near Office
Deficiency Quantity 1
Quantity Uom EACH
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Near Office
Violations No violations recorded.
Sliding-folding Partition
Does not ExistInstance on 3rd Floor
Stage
Does not ExistInstance on 3rd Floor
Walls
InspectedInstance on 3rd Floor
Condition 2 - Between Good and Fair
Deficiency SALT GLAZED BRICK: CRACKS/SPALLING
Deficiency Location/Instance Near Stair 9, North side, South side, East side, West side
Deficiency Quantity 120
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Near Stair 9
Violations No violations recorded.
Window Curtains/Shades/Blinds
Does not ExistInstance on 3rd Floor
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
Q136
PB/A&W Print Date: 9/13/2020Page 31 of 45
Question Response
INTERIOR
INTERIOR DOOR HARDWARE Inspected
Condition 3 - Fair
Deficiency No deficiencies recorded
INTERIOR GUARDS Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
KITCHEN Inspected
InspectedInstance on 1st Floor
Ceiling
InspectedInstance on 1st Floor
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Door(s)
InspectedInstance on 1st Floor
Condition 3 - Fair
Deficiency METAL: DAMAGED LOUVER
Deficiency Location/Instance Serving Area
Deficiency Quantity 1
Quantity Uom EACH
Potential Action MAINTENANCE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Serving Area
Violations No violations recorded.
Floor Finish
InspectedInstance on 1st Floor
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Walls
InspectedInstance on 1st Floor
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
LIBRARY Inspected
InspectedInstance on Room 211
Built-in Furnishing
InspectedInstance on Room 211
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Ceiling
Does not ExistInstance on Room 211
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
Q136
PB/A&W Print Date: 9/13/2020Page 32 of 45
Question Response
INTERIOR
LIBRARY
Door(s)
InspectedInstance on Room 211
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Floor Finish
InspectedInstance on Room 211
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Walls
InspectedInstance on Room 211
Condition 2 - Between Good and Fair
Deficiency PLASTER: CRACKS/SPALLING
Deficiency Location/Instance Near windows
Deficiency Quantity 15
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Near windows
Violations No violations recorded.
LOCKER ROOM Does not Exist
MULTI-PURPOSE ROOM Does not Exist
SCIENCE DEMO ROOM Does not Exist
SCIENCE LAB Does not Exist
SCIENCE PREP ROOM Does not Exist
SHOWER ROOM Does not Exist
STAIRS/RAMPS: INTERIOR Inspected
Do Letter Stair Signs Exist? Partially
Ceiling Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Door(s) Inspected
Condition 5 - Poor
Deficiency WOOD: DETERIORATED DOOR
Deficiency Location/Instance Stairs AB/1, EF/1
Deficiency Quantity 6
Quantity Uom EACH
Potential Action MAINTENANCE
Urgency of Action PRIORITY 3
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
Q136
PB/A&W Print Date: 9/13/2020Page 33 of 45
Question Response
INTERIOR
STAIRS/RAMPS: INTERIOR
Door(s)
Purpose of Action LEVEL 2
Deficiency Photo1
Stair AB/1
Violations No violations recorded.
Partition Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Railings Inspected
Condition 4 - Between Fair and Poor
Deficiency METAL: MISSING
Deficiency Location/Instance Cafeteria Exit 2 Vestibule, Exit Vestibule Near Auditorium MainEntrance, Exit Vestibule 9A
Deficiency Quantity 18
Quantity Uom L.F.
Potential Action REPLACE
Urgency of Action PRIORITY 5
Purpose of Action LEVEL 6
Deficiency Photo1
Exit Vestibule Near Auditorium Main Entrance
Violations No violations recorded.
Stairs and Landings Inspected
Condition 2 - Between Good and Fair
Deficiency VINYL TILES: BROKEN/DETERIORATED/MISSING TILES
Deficiency Location/Instance Stairs EF/2, 3
Deficiency Quantity 50
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
Q136
PB/A&W Print Date: 9/13/2020Page 34 of 45
Question Response
INTERIOR
STAIRS/RAMPS: INTERIOR
Stairs and Landings
Deficiency Photo1
Stair EF/2
Violations No violations recorded.
Deficiency STONE: BROKEN/MISSING
Deficiency Location/Instance Main Entrance Vestibule
Deficiency Quantity 20
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Main Entrance Vestibule
Violations No violations recorded.
Walls Inspected
Condition 2 - Between Good and Fair
Deficiency PLASTER: CRACKS/SPALLING
Deficiency Location/Instance Stair 9/3
Deficiency Quantity 10
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
Q136
PB/A&W Print Date: 9/13/2020Page 35 of 45
Question Response
INTERIOR
STAIRS/RAMPS: INTERIOR Inspected
Walls Inspected
Stair 9/3
Violations No violations recorded.
TOILET ROOMS - STAFF Inspected
Ceiling Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Door(s) Inspected
Condition 5 - Poor
Deficiency WOOD: DETERIORATED DOOR
Deficiency Location/Instance Rooms 229, 257,
Deficiency Quantity 2
Quantity Uom EACH
Potential Action MAINTENANCE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Room 229
Violations No violations recorded.
Floor Finish Inspected
Condition 3 - Fair
Deficiency CERAMIC TILE: BROKEN/MISSING TILES
Deficiency Location/Instance Room 229
Deficiency Quantity 10
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Room 229
Violations No violations recorded.
Stalls Inspected
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
Q136
PB/A&W Print Date: 9/13/2020Page 36 of 45
Question Response
INTERIOR
TOILET ROOMS - STAFF Inspected
Stalls Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Walls Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
TOILET ROOMS - STUDENTS Inspected
Ceiling Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Door(s) Inspected
Condition 5 - Poor
Deficiency WOOD: DETERIORATED DOOR
Deficiency Location/Instance Rooms 258, 260, 357, 358
Deficiency Quantity 4
Quantity Uom EACH
Potential Action MAINTENANCE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Room 358
Violations No violations recorded.
Floor Finish Inspected
Condition 2 - Between Good and Fair
Deficiency CERAMIC TILE: BROKEN/MISSING TILES
Deficiency Location/Instance Rooms 258, 260
Deficiency Quantity 45
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
Q136
PB/A&W Print Date: 9/13/2020Page 37 of 45
Question Response
INTERIOR
TOILET ROOMS - STUDENTS
Floor Finish Inspected
Room 260
Violations No violations recorded.
Stalls Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Walls Inspected
Condition 2 - Between Good and Fair
Deficiency CERAMIC TILE: BROKEN/ MISSING
Deficiency Location/Instance Rooms 258, 357
Deficiency Quantity 25
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Room 357
Violations No violations recorded.
LIFE SAFETY Inspected
F.D. HOLDING AREA Does not Exist
STEEL STAIRS Does not Exist
SITE Inspected
CONTAINERIZATION Inspected
Condition 5 - Poor
Deficiency FENCING DAMAGED
Deficiency Location/Instance 202nd Street
Deficiency Quantity 150
Quantity Uom S.F.
Potential Action REPAIR
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
Q136
PB/A&W Print Date: 9/13/2020Page 38 of 45
Question Response
SITE
CONTAINERIZATION
202nd Street
Violations No violations recorded.
Deficiency CONCRETE PAD DAMAGED
Deficiency Location/Instance 202nd Street
Deficiency Quantity 100
Quantity Uom S.F.
Potential Action REPAIR
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
202nd Street
Violations No violations recorded.
Deficiency CONTAINER DAMAGED
Deficiency Location/Instance 202nd Street
Deficiency Quantity 2
Quantity Uom EACH
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
202nd Street
Violations No violations recorded.
Drainage System for Asphalt Inspected
Catch Basins/Manhole - Surrounded by asphalt Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Culverts - Asphalt Covering Does not Exist
Drainage System for Concrete Inspected
Catch Basins/Manhole - Surrounded by concrete Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
Q136
PB/A&W Print Date: 9/13/2020Page 39 of 45
Question Response
SITE
Drainage System for Concrete Inspected
Culverts - Concrete Covering Does not Exist
Drainage System for Soil Inspected
Catch Basins/Manhole - Surrounded by Soil Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Culverts - Soil Covering Inspected
Condition 4 - Between Fair and Poor
Deficiency DAMAGED
Deficiency Location/Instance 201st Street (3 locations)
Deficiency Quantity 18
Quantity Uom L.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
201st Street
Violations No violations recorded.
DRINKING FOUNTAINS Does not Exist
FENCES Inspected
Condition 4 - Between Fair and Poor
Deficiency CHAIN LINK: DAMAGED POST/RAIL
Deficiency Location/Instance 201st Street
Deficiency Quantity 30
Quantity Uom L.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
201st Street
Violations No violations recorded.
Deficiency WROUGHT IRON: DAMAGED/DETERIORATED
Deficiency Location/Instance Exit 2 Walkway, 115th Avenue , 202nd Street
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
Q136
PB/A&W Print Date: 9/13/2020Page 40 of 45
Question Response
SITE
FENCES
Deficiency Quantity 640
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
202nd Street
Violations No violations recorded.
Deficiency CONCRETE CURB: DAMAGED/DETERIORATED
Deficiency Location/Instance 202nd Street, 115th Avenue , 201st Street
Deficiency Quantity 150
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
202nd Street
Violations No violations recorded.
IRRIGATION SYSTEM Does not Exist
PAVING Inspected
Student Non-Use Inspected
Gravel Exists? No
Asphalt Inspected
Condition 2 - Between Good and Fair
Deficiency CRACKS - MAJOR
Deficiency Location/Instance Behind Mini Building
Deficiency Quantity 40
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
Q136
PB/A&W Print Date: 9/13/2020Page 41 of 45
Question Response
SITE
PAVING
Student Non-Use
Asphalt
Deficiency Photo1
Behind Mini Building
Violations No violations recorded.
Concrete Inspected
Condition 3 - Fair
Deficiency DAMAGED/DETERIORATED/MISSING SECTIONS
Deficiency Location/Instance 115th Avenue, 202nd Street, 201st Street
Deficiency Quantity 350
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
201st Street
Violations No violations recorded.
Pavers Does not Exist
Student Use Inspected
Gravel Exists? No
Asphalt Inspected
Condition 4 - Between Fair and Poor
Deficiency POTHOLES
Deficiency Location/Instance Near Mini Building, Courtyard
Deficiency Quantity 30
Quantity Uom S.F.
Potential Action REPAIR
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
Q136
PB/A&W Print Date: 9/13/2020Page 42 of 45
Question Response
SITE
PAVING
Student Use
Asphalt
Deficiency Photo1
Courtyard
Violations No violations recorded.
Deficiency CRACKS - MINOR
Deficiency Location/Instance Schoolyard
Deficiency Quantity 200
Quantity Uom S.F.
Potential Action MAINTENANCE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1 No photo recorded
Violations No violations recorded.
Deficiency CRACKS - MAJOR
Deficiency Location/Instance Schoolyard
Deficiency Quantity 1,200
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Schoolyard
Violations No violations recorded.
Concrete Does not Exist
Pavers Does not Exist
Site Sidewalks & Walkways Inspected
Asphalt Inspected
Condition 3 - Fair
Deficiency HEAVING
Deficiency Location/Instance 201st Street Near Loading Area
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
Q136
PB/A&W Print Date: 9/13/2020Page 43 of 45
Question Response
SITE
PAVING
Site Sidewalks & Walkways
Asphalt
Deficiency Quantity 50
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
201st Street Near Loading Area
Violations No violations recorded.
Concrete Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Pavers Does not Exist
DOT Sidewalk Inspected
Asphalt Does not Exist
Concrete Inspected
Condition 3 - Fair
Deficiency DAMAGED CURBS
Deficiency Location/Instance 201st Street, 202nd Street, 115th Avenue
Deficiency Quantity 85
Quantity Uom L.F.
Potential Action REPLACE
Urgency of Action PRIORITY 4
Purpose of Action LEVEL 4
Deficiency Photo1
115th Avenue
Violations 85691
Pavers Does not Exist
PLAYGROUNDS Inspected
InspectedInstance on Schoolyard
Benches
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
Q136
PB/A&W Print Date: 9/13/2020Page 44 of 45
Question Response
SITE
PLAYGROUNDS
Benches
Does not ExistInstance on Schoolyard
Fence
Does not ExistInstance on Schoolyard
Pavement
Does not ExistInstance on Schoolyard
Play Equipment
InspectedInstance on Schoolyard
Condition 1 - Good
Deficiency No deficiencies recorded
Safety Surfacing
InspectedInstance on Schoolyard
Condition 1 - Good
Deficiency No deficiencies recorded
Unpaved Area
Does not ExistInstance on Schoolyard
PLAYING SURFACE Does not Exist
RETAINING WALLS Does not Exist
SEATING Does not Exist
SITE WALLS (NOT RETAINING WALLS) Does not Exist
STAIRS/RAMPS: EXTERIOR Does not Exist