Ajuste de AVR

TRANSCRIPT

New AVR adjustment

De: Dupont, Jason [mailto:Jason.Dupont@terex.com] Enviado el: Domingo, 26 de Octubre de 2014 09:11 p.m.Para: Eduardo SolanoAsunto: RE: Technical support for new components

Hi Eduardo,

I have attached the steps to change the level sensor.

I do not remember which generator you have so when you get the new AVR please send me a picture and I will send the correct manual.It is very easy to set the AVR. You need to have the diesel running with the main switch off. Adjust the voltage potty and read with a meter a voltage of about 438 V. Now turn the stability potty until the voltage starts to become unstable. Once this point is reached, turn the potty in the opposite direction slightly. The other potty are not important because the overloads for the generator never get used because the Simoregs have better protection and switch off the main switch first.

Hope this is helpful so far.