DESCRIPTION
TRANSCRIPT
-
Voltage Transducer LV 100-3000For the electronic measurement of voltages : DC, AC, pulsed...,with a galvanic isolation between the primary circuit (high voltage)and the secondary circuit (electronic circuit).
Electrical data
VPN Primary nominal r.m.s. voltage 3000 VVP Primary voltage, measuring range 0 .. 4500 VIPN Primary nominal r.m.s. current 3.33 mAR M Measuring resistance RM min RM max
with 15 V @ 3000 V max 0 170 W@ 4500 V max 0 90 W
ISN Secondary nominal r.m.s. current 50 mAK N Conversion ratio 3000 V / 50 mAVC Supply voltage ( 5 %) 15 VIC Current consumption 10 + IS mAVd R.m.s. voltage for AC isolation test, 50 Hz, 1 mn 9 kV
Accuracy - Dynamic performance data
X G Overall Accuracy @ VPN , TA = 25C 0.7 %eL Linearity < 0.1 %Typ Max
IO Offset current @ IP = 0, TA = 25C 0.2 mAIOT Thermal drift of IO 0C .. + 70C 0.2 0.3 mA
tr Response time @ 90 % of VP max 180 s
General data
TA Ambient operating temperature 0 .. + 70 CTS Ambient storage temperature - 25 .. + 85 CN Turns ratio 30000 : 2000P Total primary power loss 10 WR 1 Primary resistance @ TA = 25C 900 kWR S Secondary coil resistance @ TA = 70C 60 Wm Mass 850 g
Standards 1) EN 50178
Note : 1) A list of corresponding tests is available
Features
Closed loop (compensated) voltagetransducer using the Hall effect
Insulated plastic case recognizedaccording to UL 94-V0
Primary resistor R 1 incorporated intothe housing.
Advantages
Excellent accuracyVery good linearityLow thermal driftHigh immunity to external
interference.
Applications
AC variable speed drives and servomotor drives
Static converters for DC motor drivesUninterruptible Power Supplies
(UPS)Power supplies for welding
applications.
981102/2
VPN = 3000 V
LEM Components www.lem.com
-
Front view
Top view
Left view
Dimensions LV 100-3000 (in mm. 1 mm = 0.0394 inch)
Remarks
IS is positive when VP is applied on terminal +HT.The primary circuit of the transducer must be linked to the
connections where the voltage has to be measured.This is a standard model. For different versions (supply
voltages, turns ratios, unidirectional measurements...),please contact us.
Secondary terminals
Terminal + : supply voltage + 15 VTerminal M : measureTerminal - : supply voltage - 15 VTerminal : ground or earth
Connection
LEM reserves the right to carry out modifications on its transducers, in order to improve them, without previous notice.
Mechanical characteristics
General tolerance 0.3 mmFastening 2 holes 6.5 mmConnection of primary M5 threaded studsConnection of secondary Faston 6.3 x 0.8 mmConnection to the ground M5 threaded studFastening torque 2.2 Nm or 1.62 Lb. -Ft.
-