liob-585 i/o controller plant / equipment controller of
Post on 06-Nov-2021
5 Views
Preview:
TRANSCRIPT
buildings under controlwww.loytec.com 69
FunctionsL‑W
EB, L‑STUDIOL‑RO
CL‑IN
XL‑IO
BG
ateways
L‑VIS, L‑STATL‑D
ALI
Routers, NIC
InterfacesAccessories
L‑IOB
LIOB‑585L‑IOB I/ O Controller
LIOB‑585 I/ O Controllers are IP‑enabled, compact, programmable automation sta‑tions for LonMark Systems and BACnet/ IP networks with physical inputs and out‑puts and integrated graphical visualization.
Communication
The LIOB‑585 I/ O Controller is equipped with two Ethernet ports including a built‑in Ethernet switch. This allows for building a daisy chained line topology of up to 20 devices, which reduces costs for network installation. Dual Ethernet port devices also allow the setup of a redundant Ethernet installation (ring topol‑ogy), which increases reliability. The redundant Ethernet topology is enabled by the Rapid Spanning Tree Protocol (RSTP), which is supported by most managed switches.
Technology data points are automatically exposed as OPC tags for higher level OPC client applications or L‑WEB system via the integrated OPC server providing SSL encrypted web services (OPC XML‑DA) or UA Secure Conversation (OPC UA). The L‑IOB I/ O Controllers further allow data exchange over global connections (network‑wide data exchange), offer AST™ functions (Alarming, Scheduling, and Trending), store custom graphic pages for visualization in LWEB‑802/ 803, and can be seamlessly integrated in the LWEB‑900 Building Management System. LIOB‑585 I/ O Controllers implement the BACnet Building Controller (B‑BC) profile and are BTL certified.
IoT Integration
The IoT function (Node.js) allows connecting the system to almost any cloud ser‑vice, either for uploading historical data to analytics services, delivering alarm messages to alarm processing services or operating parts of the control system over a cloud service (e.g., scheduling based on Web calendars or booking sys‑tems). Processing Internet information such as weather data in forecast‑based control is also possible. Finally, the JavaScript kernel also allows implementing serial protocols to non‑standard equipment in primary plant control.
Local Operation and Override
All L‑IOB I/ O Controllers are equipped with an LCD display (128x64) with backlight and jog dial for manual local operation and override. Device and data point infor‑mation is displayed in text form and via graphical symbols.
Unitary and Terminal Controller
The LIOB‑585 is designed to efficiently implement unitary and terminal applica‑tions in a compact form factor. The integrated differential pressure sensor, its local I/O, and the built‑in MP‑Bus port provide connectivity for all unitary and terminal equipment. In addition, the RS‑485 port allows connection of L‑STAT room opera‑tor panels for temperature and air quality measurement and user interaction.
LOYTECCOMPETENCE PARTNER
BACnet Modbus CEA‑709 MP‑Bus KNX OPCDatasheet #89056921
BACnet
OPCXML‑DA
Local I/O
CEA‑709
OPC UA
Modbus
Gateway
VPN
serial
15 16 174 5 6 ~~+- DC
AC
statuspower
12-35 VDC INPUT or12-24 VAC, 40-70 Hz
ACTLINK
ACT
100Base-T100Base-T
Made in Austria
LOYTECwww.loytec.com
1
1 2 3
2
+ -RS-485RS-485
ABFT
RNI
PLC CNIP
LINX-110
Automation ServerL-INX
VNCy=f(x)
BACnet
SNMP
enocean® WLAN
IEC 61499
&
IEC 61131
MP‑Bus
IoT
LTE
SMS
LIOB-585I/O Controller
Building Automation Plant / Equipment
Controller of the Year
Features
• Automation station with physical inputs and outputs
• Programmable with L‑STUDIO IEC 61131‑3 and IEC 61499
• Programmable with L‑LOGICAD
• 128x64 graphic display with backlight
• Local and remote access to information about device status and data points
• Manual operation using the jog dial or VNC client
• Alarming, Scheduling, and Trending (AST™)
• Node.js support* for easy IoT integration (e.g. Google calendar, Alexa & friends, multimedia equipment,…)
• Event‑driven e‑mail notification
• Math objects to execute mathematical operations on data points
• Stores customized graphical pages
• Visualization of customized graphical pages through LWEB‑900 (Building Management), LWEB‑803 (Monitoring and Control), or LWEB‑802 (Web Browser)
• Support of the L‑STAT Room Operator Panel
• Built‑in OPC XML‑DA and OPC UA server
• Dual Ethernet/ IP interface
• Access to network statistics
• Compliant with ANSI/ ASHRAE 135‑2012 and ISO 16484‑5:2012 standard
www.loytec.com70
Acce
ssor
ies
Inte
rfac
esRo
uter
s, N
ICL‑
DA
LIL‑
VIS,
L‑S
TAT
Gat
eway
sL‑
IOB
L‑IN
XL‑
ROC
L‑W
EB, L
‑STU
DIO
Func
tions
L‑IO
B
SpecificationsType LIOB‑585
Power consumption 4.5 W
Universal Input (UI) 6
Digital Input (DI) ‑
Analog Output (AO) 2
Digital Output (DO) 5 (5 x Triac 0.5 A)
Digital Output specification Please refer to the ”General Input and Output Specification of LOYTEC devices“ at the end of the L‑IOB section for more details.
Differential Pressure Sensor 0–500 Pa
LIOB‑585L‑IOB I/ O Controller
General SpecificationsDimensions (mm) 107 x 100 x 75 (L x W x H), DIM057
Installation DIN rail mounting following DIN 43880, top hat rail EN 50022
Purpose of control Operating control
Construction of control Independently mounted control
Feature of automatic action Type 1
Operating conditions 0 °C to 50 °C, 10 – 90 % RH, noncondensing, degree of protection: IP40, IP20 (terminals), pollution degree 2
Power supply 24 V DC/ V AC SELV ±10 % via LPOW‑2415B, or with an external power supply
Rated Impulse Voltage 2500 V
Program cycle time Down to 10 ms
Interface 2 x Ethernet (100Base‑T): Web services (OPC XML‑DA, OPC UA), LonMark IP‑852, BACnet/ IP**, Modbus TCP (Master or Slave), HTTP, FTP, SSH, HTTPS, Firewall, VNC, SNMP
2 x USB‑A: WLAN (needs LWLAN‑800), EnOcean (needs LENO‑80x), LTE (needs LTE‑800)
** Router between BACnet/ IP and BACnet MS/ TP
1 x RS‑485 (ANSI TIA/ EIA‑485): BACnet MS/ TP** or Modbus RTU/ASCII (Master or Slave) or L‑STAT Room Operator Panels
1 x MP‑Bus
*requires L‑IOT1 software license
• Supports BACnet MS/ TP and BACnet/ IP
• BACnet Client Function (Write Property, Read Property, COV Subscription)
• BACnet Client Configuration with configuration tool (scan and EDE import)
• B‑BC (BACnet Building Controller) functionality, BTL certified
• Compliant with CEA‑709, CEA‑852, and ISO/ IEC 14908 Standard (LonMark System)
• Supports IP‑852 (Ethernet/ IP)
• Support of dynamically created or static NVs
• Support of user‑defined NVs (UNVTs) and Configuration Properties (SCPTs, UCPTs)
• Integrated BACnet/ IP to BACnet MS/ TP Router including BBMD as well as Slave‑Proxy functionality
• Gateway functions including Smart Auto‑Connect™
• Integrated web server for device configuration and monitoring data points
• Connection to EnOcean wireless devices via LENO‑80x Interface
• Supports WLAN through LWLAN‑800 Interface
• Supports LTE through LTE‑800 Interface
• Stores user‑defined project documentation
• Integration of damper actuator via MP‑Bus
• Differential pressure sensor
buildings under controlwww.loytec.com 71
FunctionsL‑W
EB, L‑STUDIOL‑RO
CL‑IN
XL‑IO
BG
ateways
L‑VIS, L‑STATL‑D
ALI
Routers, NIC
InterfacesAccessories
L‑IOB
Resource limitsTotal number of data points 10 000 LonMark Calendars 1 (25 calendar patterns)
OPC data points 5 000 LonMark Schedulers 10
BACnet objects 500 (analog, binary, multi‑state) LonMark Alarm Servers 1
BACnet client mappings 500 E‑mail templates 50
BACnet calendar objects 25 Math objects 50
BACnet scheduler objects 10 (64 data points per object) Alarm logs 10
BACnet notification classes 32 Modbus data points 300
Trend logs (BACnet or generic) 256 (4 000 000 entries, ≈ 60 MB) Connections (Local / Global) 500 / 100
Total trended data points 256 Number of L‑WEB clients 32 (simultaneously)
CEA‑709 network variables (NVs) 500 L‑STAT Room Operator Panels 8
CEA‑709 Alias NVs 500 EnOcean devices 10
CEA‑709 External NVs (polling) 500 EnOcean data points 100
CEA‑709 address table entries 256 (non‑ECS mode: 15) MP‑Bus devices (per channel) 8 (16 MPL)
LIOB‑585L‑IOB I/ O Controller
Order number Product descriptionLIOB‑585 L‑IOB I/O Controller: 6 UI, 2 AO, 5 DO (5 x Triac 0.5 A), 1 Pressure Sensor
L‑ACT101‑MP Actuator 5/8‘‘, 5 Nm, 45in‑lb, MP‑Bus cable
L‑ACT102‑MP Actuator 3/4‘‘, 5 Nm, 45in‑lb, MP‑Bus cable
L‑ACT‑FRAME1 Mounting frame
LPOW‑2415B Power supply unit with power connector 24 V DC, 15 W
L‑IOT1 Add‑on Software License to enable IoT functionality on LIOB‑585/586/588/589/59x, LIOB‑AIR, and LINX‑102/103/202/203
L‑TEMP2 External temperature sensor (NTC10K) for use with L‑IOB Universal Inputs
LENO‑800 EnOcean Interface 868 MHz Europe
LENO‑801 EnOcean Interface 902 MHz USA/Canada
LENO‑802 EnOcean Interface 928 MHz Japan
LWLAN‑800 Wireless LAN Interface IEEE 802.11bgn
LTE‑800 LTE Interface
LRS232‑802 USB to RS232 Interface
LSTAT‑800‑G3‑Lx Room Operator Panel, black front, white enclosure, Modbus, NFC, temperature, rel. humidity, ext. switch/NTC, Buttons (Lx)
LSTAT‑801‑G3‑Lx Room Operator Panel, front black, white enclosure, Modbus, NFC, temperature, rel. humidity, ext. switch/NTC,occupancy, IR receiver, Buttons (Lx)
LSTAT‑802‑G3‑Lx Room Operator Panel, front black, white enclosure, Modbus, NFC, temperature, rel. humidity, ext. switch/NTC,occupancy, IR receiver, CO2, Buttons (Lx)
LSTAT‑800‑G3‑L20x Room Operator Panel, white front, white enclosure, Modbus, NFC, temperature, rel. humidity, ext. switch/NTC,IR receiver, Buttons (Lx)
LSTAT‑801‑G3‑L20x Room Operator Panel, white front, white enclosure, Modbus, NFC, temperature, rel. humidity, ext. switch/NTC,occupancy, IR receiver, Buttons (Lx)
LSTAT‑802‑G3‑L20x Room Operator Panel, white front, white enclosure, Modbus, NFC, temperature, rel. humidity, ext. switch/NTC,occupancy, IR receiver, CO2, Buttons (Lx)
LSTAT‑80x‑CUSTOM Customized Room Operator Panel, minimum quantity 100 pieces, enclosure G1: silver, G2: black, G3: white;custom print Lx, EnOcean optional, including 2 working samples, typical lead time 10 weeks
Runtime licensesType LIOB‑585
Programming, Tools L‑STUDIO software (IEC 61131‑3 or IEC 61499), L‑LOGICAD, L‑INX Configurator
License L‑STUDIO: includedL‑LOGICAD: included
buildings under controlwww.loytec.com
FunctionsL‑W
EB, L‑STUDIOL‑RO
CL‑IN
XL‑IO
BG
ateways
L‑VIS, L‑STATL‑D
ALI
Routers, NIC
InterfacesAccessories
5,2
6,6
100
8960
13
107112
15[.
512]
[2.3
62]
[3.9
37]
[3.5
04]
[4.213]
[4.409]
[.59
1]
94
LIOB-585
Ethernet 2Ethernet 1 DO5DO4DO3DO2COM COM COM COM COM LOW
HIGH
DO1PRESSURE
TRIAC 500mA TRIAC 500mA TRIAC 500mA TRIAC 500mA TRIAC 500mAMade in Austria
-~+~24 VAC/DC
UI6UI5UI4UI3UI2UI1 GND GND GND AO1 AO2GND GND BUS
GND0-10V OUT RS-485
MP-BUSUSB 1USB 2
+
I/O ControllerL-IOB
statusLOYTECwww.loytec.com
[3.701]
SCALE 1 : 2
0 2010 40 60 80 100 mm
Dimensions of the devices in mm and [inch]
DIM057 LIOB‑585
The products of LOYTEC electronics GmbH are subject to constant development. Therefore, LOYTEC reserves the right to modify technical specifications at any time without prior notice. The most recent datasheet can be downloaded from www.loytec.com.
top related