Copyright © 2016 NTT DATA INTELLILINK Corporation
Green Solution Business Unit
Environmental Technology Division
NTT DATA INTELLILINK Corporation
Latest trends of High Voltage Direct Current (HVDC) system
2016.11.9
2 Copyright © 2016 NTT DATA INTELLILINK Corporation
Power Supply
DC AC
< Pic.3 : Inside of LCD TV >
Power Supply
DC AC
< Pic.2 : Note PC >
Power Supply
DC AC
< Pic.1 : Server >
Most electric appliances have a power supply converting AC to DC.
In principle, we all can't convert any energy without loss.
3 Copyright © 2016 NTT DATA INTELLILINK Corporation
4 Copyright © 2016 NTT DATA INTELLILINK Corporation
Google Datacenter (Finland Hamina)
Source:TechRepublic2016/11/3
5 Copyright © 2016 NTT DATA INTELLILINK Corporation
Facebook Datacenter (Sweden Lulea)
Source:TechRepublic2016/11/3
6 Copyright © 2016 NTT DATA INTELLILINK Corporation
Source:TechRepublic2016/11/3
7 Copyright © 2016 NTT DATA INTELLILINK Corporation
Source:TechRepublic2016/11/3
8 Copyright © 2016 NTT DATA INTELLILINK Corporation
Open Compute Project(OCP), recommended by Facebook
9 Copyright © 2016 NTT DATA INTELLILINK Corporation
Google Datacenter (Iowa)
Source:TechRepublic2016/11/3
10 Copyright © 2016 NTT DATA INTELLILINK Corporation
Facebook Datacenter (North Carolina)
Fuel cell & Solar power 20MW
11 Copyright © 2016 NTT DATA INTELLILINK Corporation
「Green Datacenter」
in Switzerland
・2MW:AC ・1MW:HVDC
12 Copyright © 2016 NTT DATA INTELLILINK Corporation
Pezy Computing Co.Ltd. ・1024Core 「PEZY-SC」 256pieces ・3.0TFLOPS ・Liquid cooling
13 Copyright © 2016 NTT DATA INTELLILINK Corporation
From Sakura Internet Evaluation Reports
Ishikari
( AC )
Ishikari
( HVDC )
Previous Data
Center
Cooling
with
Outside
Air
HVDC
Reduction Rate
ITE
Air Conditioning
System
Others
19. Case study
Power Consumption
Sakura Internet had applied the outside air cooling system that reduces power consumption by 40% compared to the previous data center.
The test-bed technologies have already demonstrated energy savings of more than 10%.
Case study Service In ! / Sakura Internet Ishikari DC
14 Copyright © 2016 NTT DATA INTELLILINK Corporation
■ System: DC12V Type HVDC Power Supply System (Product: FRESH HVDC® and XECHNO® Power) ■ Location: Ishikari DC of Sakura Internet ■ Range: 19Racks 140kW
Service In ! / Sakura Internet Ishikari DC
15 Copyright © 2016 NTT DATA INTELLILINK Corporation
DC Solar Electricity Transmitted to Data
Center Using Private Power Line (2015/8/10 12:34) SAKURA Internet Inc. announced that they have built a 200kW solar power station in Ishikari City, Hokkaido, Japan, and started to transmit electricity to its data center.
In March 2013, SAKURA Internet introduced HVDC+DC12V system to Ishikari data center. The DC power generated at the solar power station is transmitted over a private power line without being converted to AC, directly powering DC12V servers.
Business Case: Integrating solar power with HVDC (SAKURA Internet Inc.)
HVDC 電力会社 (交流)
優先① 380V
非常電池
太陽光発電所
サーバ
優先② 340V
優先③ 264V
16 Copyright © 2016 NTT DATA INTELLILINK Corporation
Achieved 3 important performance factors for practical superconducting transmission
Successful Superconducting DC Power Transmission over a distance of 500m (Updated: 2015/08/07 12:00)
Business Case: Superconducting transmission with HVDC (SAKURA Internet Inc.)
Super Conductors Cable
Solar Power
Project Outline
2015 MARCH
17 Copyright © 2016 NTT DATA INTELLILINK Corporation
Benefit1
Energy-saving effect High reliability
Safety The future technology
●Total Efficiency – higher than 90% with reducing the number of conversion!
●High efficiency with real loading factor, unlike UPS
●Intensive PS system with central power
supply unit in server rack ●Reduction of electricity charge
●Non-stop maintenance and expansion through n+1
redundancy! ●Seamless connection to battery during power outage!
●Less AC conversion!
●Eliminating PS form ITE, long-lasting, highly-reliable!
Fanless, liquid-capacitor less!
Benefit2
Benefit3
●Solving high voltage-current problems ! ・Arc suppression circuit ・Middle point ground ・DC12V
●Solar power ●LED Illumination ●Fuel cell ●Cooling system with outside air ●Superconductors etc…
What HVDC DC12V type can do for You
HVDC DC12V can help you succeed in the future with greater productivity and lower costs.
Benefit4
18 Copyright © 2016 NTT DATA INTELLILINK Corporation
HVDC DC12V Power Supply System reduces AC/DC conversions between commercial power and ITE. Power loss is reduced by approximately 10-20%.
Energy-saving effect: Energy reduction
CPU/MEMORY/HDD
CPU/MEMORY/HDD
19 Copyright © 2016 NTT DATA INTELLILINK Corporation
0.0 %
2.0 %
4.0 %
6.0 %
8.0 %
10.0 %
12.0 %
14.0 %
16.0 %
18.0 %
20.0 %
60.0 %
65.0 %
70.0 %
75.0 %
80.0 %
85.0 %
90.0 %
95.0 %
12.5% 25.0% 37.5% 50.0% 62.5% 75.0% 87.5% 100.0%
差異効率
負荷率 ( % )
効率比較
XECHNO+Fresh 総合効率
AC方式総合効率
XECHNO+Fresh 総合効率
AC方式総合効率
差異 ( % )
XECHNO+Fresh
AC方式総合効率
差異 ( % )
9.0%
18.0%
8.4%
Energy-saving effect: Total efficiency of HVDC
comparative chart of efficiency Eff[%]
Load Factor[%]
difference
■ XECHNO+Fresh Total Efficiency ■ AC Type Total Efficiency ■ Difference(%) XECHNO+Fresh Total Efficiency AC Type Total Efficiency Difference(%)
20 Copyright © 2016 NTT DATA INTELLILINK Corporation
Reliability: fewer failure points
AC DC AC AC
In DC
Battery
Switch
UPS
DC AC Mother
Board
AC ITE ( Server )
DC AC
DC AC AC
In
Battery HVDC
Mother
Board
DC12V ITE ( Server )
Path-
Through DC DC
Non-Voltage Flicker,
Non-Stop, Non-
Interruptible Power
through N+1 Redundant
Operation
Failure
Point
Natural flow like a River
Failure
Point
Failure
Point
Failure
Point
Failure
Point
Non-Voltage Flicker,
Non-Stop, Non-
Interruptible Power
through N+1 Redundant
Operation
Simpler architecture = less component count and failure points.
HVDC + DC12V
21 Copyright © 2016 NTT DATA INTELLILINK Corporation
Safety
Multiple safety guard ! Server
rack
Battery
PS rack
DC AC ~
PDU
HVDC
AC DC12V Mother board
CPU Memory HDD
Server(DC12V)
Key technology : Middle point ground Key technology : Bus bar
DC HVDC
DC340V DC340V
Key technology :
Arc suppression circuit
The current is limited within safety current for human
through high resistors of 47KΩ.
Dangerousness by
the high voltage
had been pointed
out. But ,,,
W/O Suppression Circuit W/ Suppression Circuit
Resolved the arc discharge issue at the time of switch-on/off and disconnection.
Central Redundant Power Supply
22 Copyright © 2016 NTT DATA INTELLILINK Corporation
Solar Power + HVDC Beyond The Legacy
For effective power generation, the solar battery needs the power conditioner that is controlling the operating point ,or rather the " MPPT ".
It's true.
In the following illustration, battery and solar panels are prioritized by their voltage. DC allows this simple architecture by applying diodes which prevent reverse current.
However, this theory will become legendary. NTT Data Intellilink had developed a simple and outstanding idea to establish their own legacy.
PATPEND
23 Copyright © 2016 NTT DATA INTELLILINK Corporation
NEDO Demonstration Project Aims for 15% Energy Saving with a High-Voltage Direct Current (HVDC) Feeding System
-Data Center Energy Conservation Demonstration Launches in Texas-
24 Copyright © 2016 NTT DATA INTELLILINK Corporation
MITSUBISHI ELECTRIC
SONY
25 Copyright © 2016 NTT DATA INTELLILINK Corporation
Society of the clean energy by HVDC
Solar power Window power
Fuel cell
Data-center
consecutive system Battery
26 Copyright © 2016 NTT DATA INTELLILINK Corporation