indirect fired water heater - triangle · pdf filepre-installation 661a0300 - rev b 2 codes...
Post on 20-Mar-2018
235 Views
Preview:
TRANSCRIPT
Technical SpecificationsInstallation and Maintenance Guide
• Before proceeding with installation and operation, read entire manual care-fully. Failure to do so can cause injury or property damage.
• When receiving SMART Water Heaters, any claims for damage or short-age in shipment must be filed immediately against the transportationcompany by the consignee.
2010-49 SMART IWH Manual
• Warranty Registration Card must be filled out by the customer and mailedwithin thirty (30) days of installation in order to gain warranty coverage.
• Retain and affix this manual near the water heater for future reference• Installation and service should only be performed by a qualified installer or
service technician.• Installations and service should be performed by a license plumber or gas
fitter in the Commonwealth of Massachusetts.
Indirect Fired Water Heater
Date Revised 10/29/14
WARNING
IMPORTANT
L I S T E D
661A0300 - Rev B
Smart manual_Smart manual 10/29/14 10:00 AM Page 1
Table of Contents
661A0300 - Rev B
Product & Safety Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1Pre-Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2-3Installation - Piping
Temperature & Pressure (T&P) Relief Valve . . . . . . . . . . . . . . . . . .4-5Drain Valve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5Manual Air Vent . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5Thermal Expansion . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5Water Hammer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5Vacuum Breaker . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5General Piping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6Domestic Piping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6Thermostatic Mixing Valve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7Recirculation Piping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7Multiple Water Heater Systems . . . . . . . . . . . . . . . . . . . . . . . . . . . .7Boiler Piping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
Installation - Piping Drawings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8-14Installation - Wiring
Wiring Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15Circulators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15Zone Valves . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15Snap-Set Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15
Installation - Wiring Drawings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16-19Water Heater Start-Up
Filling the Inner (Domestic Water) Tank . . . . . . . . . . . . . . . . . . . . .20Filling the Outer (Boiler Water) Tank . . . . . . . . . . . . . . . . . . . . . . .20General Notes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .21Adjusting the Water Heater Thermostat . . . . . . . . . . . . . . . . . . . . . .22
Water Heater MaintenanceMaintenance Schedule . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .23Filling Water Heater . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .23Draining Water Heater . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .23-25Draining Inner (Domestic Water) Tank . . . . . . . . . . . . . . . . . . . . . . .24-25Draining Outer (Boiler Water) Tank . . . . . . . . . . . . . . . . . . . . . . . . .25
Replacement Parts ListSMART Series . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .26-27
Water Heater SpecificationsSMART Series . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .28
SMART Series Performance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .29
i
Smart manual_Smart manual 10/29/14 10:00 AM Page 2
1
DefinitionsFollowing terms are used to bring attention to thepresence of various risk levels, or to importantinformation concerning product life.
Indicates presence of a hazard which willcause severe personal injury, death or sub-stantial property damage if ignored.
Indicates the presence of a hazard whichcan cause severe personal injury, death orsubstantial property damage if ignored.
Indicates the presence of a hazard whichwill or can cause minor personal injury ordamage if ignored.
Indicates special instructions on installa-tion, operation, or maintenance which areimportant but not related to personalinjury hazards.
Indicates recommendations made byTriangle Tube for the installers which willhelp to ensure optimum operation andlongevity of the equipment.
Triangle Tube reserves the right to modifythe technical specifications and compo-nents of its products without prior notice.
Hot Water Can Scald!• Water temperatures over 125ºF can cause
severe burns instantly or death from scalding.• Children, disabled and elderly are at highest
risk of being scalded.• Never leave them unattended in or near show-
er, bathtub or sink.• Never allow small children to use a hot water
faucet or draw their own bath.• If anyone using hot water in the building fits
the above description or if local codes or statelaws require specific water temperatures at hotwater faucet, it is recommended:- to install a thermostatic mixing valve at this
appliance or at each water faucet.or
- to set the thermostat knob for the lowesttemperature which satisfies your hot waterneeds.
• Water drained from the system drain valvesmay be extremely hot. To avoid injury:– Make sure all connections are tight.– Direct water flow away from any person.
Protection must be taken against excessivetemperature and pressure!• Installation of a Temperature & Pressure
(T&P) relief valve is required.
To prevent damage to the inner tank, theInstaller must:• Always fill inner tank prior to outer tank
and always drain outer tank prior to innertank.
• Relieve primary system pressure below 15psig prior to draining inner tank.
WARNING
DANGER
DANGER
CAUTION
CAUTION
CAUTION
NOTICE
BEST PRACTICE
NOTICE
Product & Safety Information
661A0300 - Rev B
Smart manual_Smart manual 10/29/14 10:00 AM Page 3
Pre-Installation
661A0300 - Rev B 2
Codes ComplianceWater heater installation must conform with theinstructions in this manual and where applicable:
• local, state, provincial, and national codes,laws, regulations and ordinances.
• in Canada - CAN / CGA B149.1 or B149.2Installation Code.
SMART water heaters are exempt from ASMESection VIII, Division 1 Code construction perInterpretation VIII-86-136. Check with local codesfor applicability.
SMART Series water heaters will absorbless than 200,000 BTU/hr when domesticwater outlet temperature is 210ºF and boilerwater supply temperature is 240ºF. Listedoutputs are based on ASME Section VIIIInterpretation VIII-1-86-136.
Where recommendations in this manual differfrom local, or national codes, the local or nationalcodes take precedence.
Codes RestrictionsSingle wall heat exchanger in the SMART waterheater complies with National Standard PlumbingCode, provided that:
– boiler water (including additives) is practicallynon-toxic, having toxicity rating or class of 1,as listed in Clinical Toxicology of CommercialProducts, and
– boiler water pressure is limited to maximum30 psig by approved relief valve.
Single wall heat exchangers are permitted under theUniform Plumbing code - Paragraph L3.2. and L3.3if they satisfy all of the following requirements.1. The heat transfer medium is potable water or
contains only substances which are recognizedas safe by the U.S. Food and DrugAdministration.
2. The pressure of the heat transfer medium is main-tained less than the normal minimum operatingpressure of the potable water system
Exception: Steam complying with sec-tion #1 above.
3. The equipment is permanently labeled to indi-cate that only additives recognized as safe by theFDA shall be used in the heat transfer medium.
Other heat exchanger designs may be permittedwhere approved by the Administrative Authority.Operating Restrictions• Maximum domestic hot water temperature is
194ºF for commercial applications and 140ºFfor residential applications.
• Maximum boiler water temperature is 210ºF.• Maximum working pressure for inner (domes-
tic water) tank is 150 psig.• Maximum working pressure for outer (boiler
water) tank is 45 psig.• Water quality limitations (based on E.P.A
National Secondary Drinking WaterRegulations):- Chloride, less than 150 ppm or mg/l- pH value min. 6, max. 8 - Total hardness 3 - 7 grains/gallon or 50-120
ppm or mg/l.- Total Dissolved Solids (TDS), less than
120 ppm or mg/l.- Iron less than 0.3 ppm or mg/l.- Aluminum, less than 0.2 ppm or mg/l.- Copper, less than 1 ppm or mg/l.- Manganese, less than 0.05 ppm or mg/l.- Zinc, less than 5 ppm or mg/l.
In hard water areas (more than 7 grains ofhardness) soften the cold domestic supplywater to the appliance to prevent scaling.
NOTICE
BEST PRACTICE
Smart manual_Smart manual 10/29/14 10:00 AM Page 4
661A0300 - Rev B
Pre-Installation
3
Any water conditioning system must beinstalled and maintained in accordancewith manufacturer’s specifications.
Do not install the water heater on any appli-cation if the boiler piping contains non-oxy-gen barrier tubing or if the boiler piping isconsidered an “open system”. Exposing theouter tank of the water heater to oxygencontamination will lead to premature tankfailure and denial of the warranty.
Locating Water Heater• This water heater is not intended for out-
door installations.• Keep distance between boiler and water
heater to a minimum to:– reduce piping heat loss– provide minimal friction loss
• Locate water heater so that any leakage fromthe tank or water connections will not causedamage to the area adjoining the water heateror to lower floors in the structure.– When such a location is unavoidable, asuitable drain pan with adequate drainage,should be placed under the water heater.
• The SMART Series Water Heaters are designedfor vertical installation only.
Recommended Clearances• Water heater should be installed to allow
adequate clearance for servicing.• Zero clearance is permissible to any side of
the SMART Series water heater, but infor-mation labels may be hidden.
• Recommended top or vertical clearance is 12”minimum.
• Refer to boiler manual for boiler clearances.
NOTICE
NOTICE
Smart manual_Smart manual 10/29/14 10:00 AM Page 5
Installation - Piping
661A0300 - Rev B 4
Temperature & Pressure (T&P) Relief Valve
To reduce risk of excessive pressures and tem-peratures in the water heater, install tempera-ture and pressure protective equipmentrequired by local codes, but no less than a com-bination temperature and pressure relief valvecertified by a nationally recognized testing lab-oratory that maintains periodic inspection ofproduction of listed equipment or materials, asmeeting the requirements for Relief Valves andAutomatic Gas Shutoff Devices for Hot WaterSupply Systems, ANSI Z21.22. This valve mustbe marked with a maximum working pressureof the water heater.• Every SMART water heater must be protected
with a T&P relief valve.• Determine T&P relief valve size by the follow-
ing specifications, unless they conflict withlocal codes:- SMART 30/40/50: 3/4”NPT with an AGARating of 100,000 BTU/hr and a maximumpressure rating of 150 psig. (Watts 100XL-8 or equivalent).
- SMART 60/80/100/120: 3/4”NPT with anAGA Rating of 200,000 BTU/hr and a maxi-mum pressure rating of 150 psig. (Watts40XL-8 or equivalent).
For proper operation of the T&P and to pre-vent the T&P from activating due to boilerwater temperature, use a T&P relief valvewith extended element. We recommendedan 8” minimum length to ensure elementsenses domestic water.
Standard Installation• Install T&P relief valve in the Auxiliary con-
nection located behind the air vent on the top ofthe water heater (Figure 1 page 8).
or• Install the T&P relief valve in the run (straight
through leg) of a tee located at the domestic hotwater outlet when using the Auxiliary connec-tion for a recirculation return (Figure 2 page 8).
Commonwealth of Massachusetts InstallationFollow this procedure for jurisdictions requiring avacuum breaker to be installed on the domesticcold water inlet.• Install the T&P in the run (straight through leg)
of a tee located at the domestic hot water out-let. Use a long element T&P relief valve (Fig.5 page 10).
T&P Relief Valve Discharge PipingT&P relief valve discharge piping must be:- made of material serviceable for tempera-tures of 250ºF or greater.
- directed so that hot water flows away fromall persons.
- directed to a suitable place for disposal.- installed so as to allow complete drainingof the T&P relief valve and discharge line.
T&P relief valve discharge piping must not be:- excessively long. Using more than 2elbows or 15 feet of piping can reduce dis-charge capacity.
- directly connected to a drain. Terminatedischarge piping within 6” from drain.Refer to local codes.
- plugged, reduced or restricted.- subject to freezing.
CAUTION
NOTICE
Smart manual_Smart manual 10/29/14 10:00 AM Page 6
661A0300 - Rev B
Installation - Piping
5
Do not install any valve between T&P reliefvalve and tank connection or on T&P reliefvalve discharge piping. Do not plug T&Prelief valve or discharge piping. Improperplacement and piping of T&P relief valvecan cause severe personal injury, death orsubstantial property damage.
Drain ValveDrain valve and fittings are supplied by others.Standard Installation• Install a tee connection at the domestic cold
water inlet (Fig. 1 and 2 page 8 and Fig. 3on page 9).
• Pipe the drain piping with drain valve fromthe tee connection to:- a suitable place for disposalor- terminate within 12” of the floor
Commonwealth of Massachusetts Installation• Thread a 3/4” close nipple onto the
Auxiliary connection and insert an open-end dip tube into the Auxiliary connectionon top of water heater. As shown in Fig. 4page 10.
• Install a 3/4” NPT elbow to the Auxiliaryconnection, see Fig. 5 page 10.
• Pipe the drain piping with drain valve fromthe elbow connection to:- a suitable place for disposalor- terminate within 12” of the floor
Manual Air Vent 1.A manual air vent is factory installed.2.Open manual air vent. Once the tank is full
and air has stopped escaping, close the man-ual air vent.
Thermal ExpansionIf a backflow preventer, check valve or pressurereducing valve is piped on cold water supply pipingof water heater, install an expansion tank on coldwater supply line to prevent normal thermal expan-sion from repeatedly forcing open T&P relief valve.
T&P relief valve is not intended for constantduty, such as relief of pressure due torepeated normal system expansion. Correctthis condition by installing a properly sizedexpansion tank in domestic water system.Refer to expansion tank manufacturer’sinstallation instructions for proper sizing.
Water Hammer
Dishwashers, clothes washers and fast-closing pos-itive shut-off valves incorporated in the system allcontribute to creating water shock. Install a waterhammer arrester to prevent damage to pipes andappliances. See device manufacturer’s instructionsfor application and installation.
Water hammering within the domestic pip-ing system can cause premature failure ofthe inner tank of the water heater. This typeof failure is NOT covered under warranty.
Vacuum BreakerInstalling a vacuum breaker Watts N36-M1 or equiv-alent on the domestic cold water inlet will preventdamage to the inner tank if a negative pressure isdeveloped in the domestic supply line. See manu-facturer’s instructions for application and installationof the vacuum breaker.
CAUTION
WARNING
NOTICE
Smart manual_Smart manual 10/29/14 10:00 AM Page 7
Installation - Piping
661A0300 - Rev B 6
General Piping• For domestic water piping diagrams, see pages 8
through 10.• See pages 11 through 14 for:
- Boiler water piping.- Multiple water heater domestic and boilerpiping.
• See Chart 1 for domestic and boiler pipingconnection sizes .
• All plumbing must meet or exceed all local,state and national plumbing codes.
• The supplied sealant is suitable for potablewater systems. Use only the supplied sealanton all Smart fittings/joints.
• Use isolation valves to isolate system components.
Domestic Piping• Union on domestic hot water outlet should be
piped at a higher elevation than domestic waterdrain valve. This will make draining the waterheater easier.
• Install unions for easy removal of water heater. Itis recommended to use dielectric unions or cou-plings to protect hot and cold water fittings fromcorrosion when connecting dissimilar materialssuch as copper and galvanized iron pipe.
• If copper pipe is used for domestic water con-nections, first solder pipe to a threaded adapterand then screw adapter into cold water inlet ontop of water heater. Inlet contains an internalplastic dip tube which can be damaged by heatfrom soldering.
Do not apply heat to the cold water inletwhen making sweat connections to waterheater. Sweat tubing to adapter before fit-ting adapter to cold water inlet of heater. Itis imperative that no heat be applied to thecold water inlet, as it contains a non metal-lic dip tube.
• When the water supply pressure is higher than70 psig, it is recommended to install a pressurereducing valve on cold water supply line toprevent water loss through T&P relief valve.
• If water heater will replace tankless coil inboiler, disconnect piping to coil. Allow waterto drain from coil. Do not plug tankless coil.
Plugging tankless coil inlet and outlet willresult in severe personal injury, death, orsubstantial property damage.
NOTICE
DANGER
Chart 1
WaterHeaterModel
Connections (Inches) Recirculation Dip Tube Draining Dip Tube RecommendedMinimum
Boiler PipingDomesticWater
Inlet/Outlet
Boiler WaterSupply/Return
AuxiliaryConnection
Length (Inches)
Diameter(Inches)
Length(Inches)
Diameter(Inches) Diameter
(Inches)SMART 30 3/4 NPT 1 NPSC 3/4 NPSC 34 3/4 34 3/4 1SMART 40 3/4 NPT 1 NPSC 3/4 NPSC 43 3/4 43 3/4 1SMART 50 3/4 NPT 1 1/4 NPSC 3/4 NPSC 25 3/4 52 3/4 1SMART 60 3/4 NPT 1 1/4 NPSC 3/4 NPSC 34 3/4 62 3/4 1 1/4SMART 80 1 1/2 NPT 1 1/2 NPSC 1 1/2 NPSC 25 1 1/2 48 1 1/2 1 1/4SMART 100 1 1/2 NPT 1 1/2 NPSC 1 1/2 NPSC 32 1 1/2 61 1 1/2 1 1/2SMART 120 1 1/2 NPT 2 NPSC 1 1/2 NPSC 32 1 1/2 61 1 1/2 1 1/2
Smart manual_Smart manual 10/29/14 10:00 AM Page 8
661A0300 - Rev B
Installation - PipingThermostatic Mixing Valve• It is recommended to install an optional mixing
valve on the domestic hot water outlet.• Mixing valve should comply with ASSE 1017
Recirculation Piping• T&P relief valve must be installed in run
(straight through leg) of tee located at domestichot water outlet of water heater.
• It is recommended that the recirculation dip tubebe installed in auxiliary connection using a closenipple assembly as shown Fig. 3, page 9. SeeChart 1 page 6 for diameter and length of diptube.
• A stainless steel or bronze circulator is requiredon potable water systems.
• Install automatic mixing valve either at the hotwater outlet of water heater or each hot waterfaucet.
Multiple Water Heater Systems
• Parallel Pipe Recirculation Systems - Manifoldrecirculation return to all water heaters.
• Series Piped Systems - Piped return to the lead-ing (cold water inlet) water heater.
• Install automatic mixing valve either at the hotwater outlet of water heater or each hot waterfaucet.
Failure to install automatic mixing valvewhere recommended will result in severepersonal injury or death.
Boiler Piping• If plastic pipe is used for boiler water piping, it
must have a maximum oxygen diffusion rate of0.1 mg/liter-day for boiler and water heaterprotection.
The Smart IDWH must be installed on aclosed type hydronic system. Failure to pro-vide such a system will result in prematurefailure of the outer tank and annulment ofwarranty.
• Boiler water (including additives) must bepractically non-toxic, having toxicity rating orclass of 1, as listed in Clinical Toxicology ofCommercial Products.If antifreeze is used in boiler system, localcodes may require a backflow preventer oncold water supply line. Use antifreeze specifi-cally intended for hydronic heating systems.Inhibited propylene glycol is recommended ata maximum 50/50 mixture.
Do not use automotive, ethylene glycol orpetroleum-based antifreeze. Do not use anyundiluted antifreeze. This can cause severepersonal injury, death or substantial propertydamage.
DANGER
DANGER
NOTICE
7
Smart manual_Smart manual 10/29/14 10:00 AM Page 9
Cold Water Inlet 6 1
12" min. Heat Trap
Loop (Optional)
12" min. Heat Trap
Loop (Optional)
1 5
5 1
874
10M H
C
661A0300 - Rev B
Installation - Piping
7
Cold Water Inlet 6 1
Recirculating Loop
2 3 4
1 5
5 1
8
12" min. Heat Trap
Loop (Optional)
12" min. Heat Trap
Loop (Optional)
9
Standard InstallationDomestic Piping withRecirculation SMART Series
8
1. Shut-off valve2. Recirculation Circulator3. Flow Check Valve4. T&P relief valve5. Unions6. Backflow preventer or pressure reducing valve(*)
7. Drain valve8. Thermal expansion tank (potable)9. Recirculation dip tube10. Thermostatic mixing valve (*)
(*) Optional devices may be required by local codes.
Standard InstallationDomestic PipingSMART Series
Fig. 1:
Fig. 2:
Smart manual_Smart manual 10/29/14 10:00 AM Page 10
661A0300 - Rev B
7
Cold Water Inlet6 1
RecirculatingLoop
2 3
41 5
5 1
8
12" min.Heat Trap
Loop(Optional)
12" min.Heat Trap
Loop(Optional)
Optional InstallationDomestic Piping withRecirculation SMART Series
1. Shut-off valve2. Recirculation Circulator3. Flow Check Valve4. T&P relief valve5. Unions
6. Backflow preventer or pressure reducing valve(*)7. Drain valve8. Thermal expansion tank (potable)
(*) Optional devices may be required by local codes.
Fig. 3:
9
Installation - Piping
Smart manual_Smart manual 10/29/14 10:00 AM Page 11
661A0300 - Rev B
Installation - Piping
10
Cold Water Inlet 6 1
12" min. Heat Trap
Loop (Optional)
12" min. Heat Trap
Loop (Optional)
4
1 5
5 8
9
11
10M H
C 7
1. Shut-off valves4. T&P relief valve5. Unions6. Backflow preventer or pressure reducing valve (*)7. Drain valve
8. Thermal expansion tank (potable)9. Vacuum breaker10.Mixing valve (*)11. Dip tube - Draining per Chart 1
(*) Optional devices may be required by local codes.
Drain Tube Assembly-Commonwealth ofMassachusetts
Fig. 4:
Commonwealth ofMassachusetts DomesticPiping SMART Series
Fig. 5:
Smart manual_Smart manual 10/29/14 10:00 AM Page 12
Installation -Piping
11
41
3
2
2-Port Priority Valve
(normally open)
2-Port Priority Valve
(normally close)
1
6
5Cold water
inlet
1
2
41
3- Port Priority Valve
3 1
6Cold water
inlet 5
Fig. 7:
1. Shut-off valves2. Circulator3. Expansion tank
4. Drain valve5. Feed valve6. Air separator
Fig. 6: SMART System Piping with 3-Port Zone Valve(Domestic Priority)
SMART System Piping with 2-Port Zone Valves(Domestic Priority)
661A0300 - Rev B
Smart manual_Smart manual 10/29/14 10:00 AM Page 13
661A0300 - Rev B
Fig. 9:
Fig. 8:
1. Shut-off valves2. Circulator3. Flow check valve4. Expansion tank
5. Drain valve 6. Feed valve7. Air separator
SMART System Piping with Zone Valves(Non Domestic Priority)
SMART System Piping with Zone Circulators
12
Installation - Piping
Smart manual_Smart manual 10/29/14 10:00 AM Page 14
Installation - Piping
• Recommended for applications in which there is alarge water consumption in short period of time.
• A maximum of 3 water heaters may be piped in series.• Utilize the lead (hot water outlet) SMART tank ther-
mostat to control system temperature.• Install automatic mixing valve at either the hot water
outlet of the water heater system or at each hot waterfixture.
• Each tank should be piped with a drain as shown inFig. 1.
13
Multiple SMART Series Water HeaterSystem Domestic Piping - Parallel
Multiple SMART Series Water HeaterSystem Domestic Piping - Series
• Recommended for most applications.• Any one water heater tank thermostat may be
utilized to control system temperature.• Install automatic mixing valve at either the hot
water outlet of the water heater system or ateach hot water fixture.
• Each tank should be piped with a drain asshown in Fig. 1.
Fig. 10:
Fig. 11:
661A0300 - Rev B
Smart manual_Smart manual 10/29/14 10:00 AM Page 15
661A0300 - Rev B 14
1. Shut-off valves2. Circulator3. Flow check valve4. Expansion tank
5. Drain valve6. Feed valve7. Air separator
Fig. 12: Multiple SMART Series Water Heater System BoilerPiping Reverse Return Balanced Flow
Multiple SMART Series Water Heater System Boiler Piping - ManifoldFig. 13:
Installation - Piping
Smart manual_Smart manual 10/29/14 10:00 AM Page 16
Installation - Wiring
15
Wiring Requirements
Electrical shock hazard can cause severepersonal injury, death or substantial prop-erty damage. Disconnect power beforeinstalling and/or servicing.
1. All wiring must be a minimum of 18 gaugeand installed in accordance with:• U.S.A. - National Electrical Code and any
other national, state or local code require-ments having jurisdiction.
• Canada - C.S.A. C22.1 Canadian ElectricalCode Part 1 and any other national, provin-cial and local code requirements havingjurisdiction.
2. If original wire supplied with appliance mustbe replaced, Type 90ºC or its equivalent mustbe used.
3. Refer to control component instructionspacked with boiler for application information.
4. An optional service switch may be installed inwater heater electrical circuit. This switchwould only shut off the water heater, not thehome heating system. Do not shut off waterheater if there is a chance of freezing.
5. All electrical contacts shown do not havepower applied - off the shelf condition. Seepages 15 thru 19.
Circulators• Priority relay must be sized for total amp draw
of all circulators.Zone Valves• Transformer must be sized for maximum load
of all zone valves.Snap Set Connection• For easy wiring between water heater thermo-
stat and boiler controls see Installation Wiringsection pages 15 through 19.
• Make sure snap set is firmly snapped togetherafter wiring.
WARNING
Snap Set Wiring
661A0300 - Rev B
Smart manual_Smart manual 10/29/14 10:00 AM Page 17
661A0300 - Rev B 16
H NHigh Voltage
120V.A.C.
24V.A.C.
RoomThermostat
Zone 1
Additional zones Additional zones maybe added as shown above
Transformer(Power)
Zone Valve
Zone Valve
12C
Water HeaterThermostatSnap-Set
WaterHeaterZone
*Isolation Relay
BoilerThermostatTerminals
* Use isolation relay on3-wire zone valves withnon-isolated end switches.Transformer and boilercontrol can burn out if isolation relay is not used
PriorityRelay
H NHigh Voltage
120V.A.C.
24V.A.C.
RoomThermostat
Zone 1
Additional zones Additional zones maybe added as shown above
Transformer(Power)
Zone Valve
Zone Valve
12C
Water HeaterThermostatSnap-Set
WaterHeaterZone
BoilerThermostatTerminals
High VoltageLow VoltageBoiler Low Voltage
PriorityRelay
Typical 3-wire Zone Valve Zoning,with Domestic Priority
Typical 4-wire Zone Valve Zoning,with Domestic Priority
Fig. 14: Fig. 15:
Installation - Wiring
Smart manual_Smart manual 10/29/14 10:00 AM Page 18
Installation - Wiring
H NHigh Voltage
120V.A.C.
24V.A.C.
RoomThermostat
RoomThermostat
Zone 1
Zone 2
Additional zones Additional zones maybe added as shown above
Transformer(Power)
Zone Valve
Zone Valve
Zone Valve
12C
Water HeaterThermostatSnap-Set
WaterHeaterZone
*Isolation Relay
BoilerThermostatTerminals
* Use isolation relay on3-wire zone valves withnon-isolated end switches.Transformer and boilercontrol can burn out if isolation relay is not used
17
Typical 3-wire Zone Valve Zoning,without Domestic Priority
H NHigh Voltage
120V.A.C.
24V.A.C.
RoomThermostat
RoomThermostat
Zone 1
Zone 2
Additional zones Additional zones maybe added as shown above
Transformer(Power)
Zone Valve
Zone Valve
Zone Valve
12C
Water HeaterThermostatSnap-Set
WaterHeaterZone
BoilerThermostatTerminals
High VoltageLow VoltageBoiler Low Voltage
Typical 4-wire Zone Valve Zoning,without Domestic Priority
Fig. 16: Fig. 17:
661A0300 - Rev B
Smart manual_Smart manual 10/29/14 10:00 AM Page 19
661A0300 - Rev B
2
T T
1 4 3 5 6
CirculatorZone 1
Thermostatzone 1Honeywell
R845ARelay
120H
VACN
2
T T
1 4 3 6
CirculatorZone 2
Thermostatzone 2
5
2
T T
1 4 3 6
WaterHeater
Circulator
Water HeaterThermostatSnap-Set
5
12
C
BoilerThermostatTerminals
Priority Relay
18
Typical Circulator Zoningwith Domestic Priority
2
T T
1 4 3 5 6
CirculatorZone 1
Thermostatzone 1Honeywell
R845ARelay
120H
VACN
2
T T
1 4 3 6
CirculatorZone 2
Thermostatzone 2
5
2
T T
1 4 3 6
WaterHeater
Circulator
Water HeaterThermostatSnap-Set
5
12
C
High VoltageLow Voltage
BoilerThermostatTerminals
Typical Circulator Zoningwithout Domestic Priority
Fig. 18: Fig. 19:
Installation - Wiring
Smart manual_Smart manual 10/29/14 10:00 AM Page 20
Installation - Wiring
19
T T
1 4 3 5 6
Circulator Zone 1
Thermostat zone 1 Honeywell
R845A Circulator
Relay
120 H
VAC N
2
T T
1 4 3 6
Circulator Zone 2
Circulator Zone 3
Thermostat zone 2
Thermostat zone 3
5
2
T T
1 4 3 6 5
High Voltage Low Voltage
To Boiler 24 VAC Thermostat Leads
2
ON PRIORITY
ZONING CIRCULATOR
CIRC ON
PR1 LIVE NEUT
T T
2
1 C
Water Heater Thermostat Snap Set
Priority Zone Circulator
Note: Maximum of 4 total circulatorzone when wiring 1 zone for priority.
Fig. 20: Priority Zone Circulator Wiring
661A0300 - Rev B
Smart manual_Smart manual 10/29/14 10:00 AM Page 21
661A0300 - Rev B 20
Filling the Inner (Domestic Water) Tank
• Never use water heater unless inner andouter tanks are completely filled with water.
• Inner tank must be completely filled andpressurized before pressurizing outer tank.
1. Close domestic water drain valve.
2. Open domestic water isolation valves forwater heater.
3. Vent air from inner (domestic water) tank byopening nearest hot water faucet. Filldomestic water tank completely by allowingwater to run until there is a constant flow ofwater.
4. Close hot water faucet.Filling the Outer (Boiler Water) Tank
• Never use water heater unless inner andouter tanks are completely filled with water.
• Inner tank must be completely filled andpressurized before pressurizing outer tank.
1. Close boiler water drain valve at boiler wateroutlet of water heater.
2. Open water heater’s boiler water isolationvalves.
3. Allow air to escape from outer (boiler water)tank by opening manual air vent, located ontop of water heater.
4. Follow instructions furnished with boiler tofill with water.
5. When tank is full, and air stops escaping,close the manual air vent.
6. If antifreeze is used in boiler water, checkconcentration. Boiler water (including addi-tives) must be practically non-toxic, havingtoxicity rating or class of 1, as listed inClinical Toxicology of Commercial Products.
Do not use automotive, ethylene glycol orpetroleum-based antifreeze. Do not use anyundiluted antifreeze. This can cause severepersonal injury, death or substantial propertydamage.
WARNING
CAUTION
CAUTION
Water Heater Start-Up
Smart manual_Smart manual 10/29/14 10:00 AM Page 22
Water Heater Start-Up
21
HOT WATER CAN SCALD!• Water temperatures over 125ºF can cause
severe burns instantly, or death from scalds.• Feel water before bathing or showering.• Consumer Product Safety Commission and
some states recommend temperatures set-tings of 130ºF or less. Setting thermostathigher than 130ºF will increase risk of scaldinjury and cause severe personal injury ordeath.
• Water heated to a temperature suitable forclothes washing, dish washing and other san-itizing needs will scald and cause permanentinjury.
• Children and elderly, infirm, or physicallyhandicapped persons are more likely to beinjured by hot water. Never leave themunattended in or near a bathtub. If anyoneusing hot water in the building fits thisdescription, or if state laws or local codesrequire certain water temperatures at hotwater faucets, take special precautions.- Install an automatic mixing valve atwater heater or at each hot water faucet,bath and shower outlet. Selection andinstallation must comply with valvemanufacturer’s recommendation andinstructions.- Use the lowest practical temperature set-ting.- Check water temperature after anyadjustment. You must follow“Adjusting the Water HeaterThermostat” procedures.
General Notes• Household water usage patterns will affect
water temperature at any faucet or shower.Occasionally check temperature at each pointof use, then adjust thermostat accordingly.Always recheck temperature after adjustingthermostat.
• When hot water is used in repeated small quan-tities, a “stacking” effect can develop in thewater heater. The upper layer of water in tankcan be hotter than lower layer.
• Lowering the thermostat setting or installingautomatic mixing valves as indicated in theseinstructions will reduce water temperature levels.Consult your installer or service technician.
At no time should boiler limit control be setabove 210ºF. This can cause severe person-al injury, death or substantial propertydamage if ignored.
WARNING
DANGER
661A0300 - Rev B
Smart manual_Smart manual 10/29/14 10:00 AM Page 23
661A0300 - Rev B 22
Adjusting the Water Heater ThermostatWater heater thermostat is factory set to itslowest temperature. This may or may not besuitable for your needs.
Turn thermostat knob clockwise toincrease water temperature.Turn thermostat knob counter-clockwise to decreasewater temperature.
Studies have indicated that dangerous bac-teria, including legionella, pneumophila, canform in the potable water distribution sys-tem if certain minimum water temperaturesare not maintained. Contact your localhealth department for more information.
• Check water temperature at a hot water faucetimmediately after first heating cycle. Furthertemperature adjustment may be necessary aswater heating system is used. Recheck watertemperature at faucet after adjustment.
• When adjusting thermostat, be sure boiler limitcontrol is set a minimum of 20ºF higher.
WARNING
TemperatureUp
TemperatureDown
SMART Series Knob
Water Heater Start-up
Smart manual_Smart manual 10/29/14 10:00 AM Page 24
Water Heater Maintenance
23
Maintenance ScheduleAnnual service by qualified service technicianshould include the following:
Any procedure required by local codes.Check air vent operation.Verify system pressure. Manual air ventingprocedure may require adding water to bringsystem up to pressure, typically 12 psig.Manually operate T&P relief valve at leastonce a year. This will release some hot water.
Before operating T&P relief valve, makesure no one is in front of or around T&Prelief valve discharge piping. Hot dischargewater can cause severe personal injury orsubstantial property damage.
Move operating lever to open position for afew seconds and then move it back, allowing itto snap closed. After T&P relief valve is oper-ated, if it continues to release water, close coldwater inlet to water heater immediately.Follow draining instructions, to relieve pres-sure from the inner tank and replace T&P reliefvalve. If T&P relief valve weeps periodically,it may be due to thermal expansion seeThermal Expansion, page 5. Do not plug T&Prelief valve or discharge piping.
Plugging T&P relief valve or discharge pip-ing can cause excessive pressure in waterheater, resulting in severe personal injury,death, or substantial property damage.Follow instructions on circulator to oil it, ifrequired.Check mixing valve, valves, pipes and fit-tings for leaks.Check function of field-installed controlsand valves. See component manufacturer’sinstructions.
Review homeowner’s maintenance responsi-bilities and their frequencies, including anynot listed in the following section.
Homeowner monthly maintenance to include:Check for air.
• Manual air vent-open and close briefly torelease any air.
• Visually check valves, pipes and fittings forleaks. Call qualified service technician torepair any leaks.
Filling Water HeaterSee “Filling the Inner (Domestic Water) Tank and“Filling the Outer (Boiler Water) Tank” on page 20.Draining Water HeaterDrain water heater if it will be shut off and exposedto freezing temperatures. Freezing water willexpand and damage water heater.
• If boiler water contains sufficientantifreeze, then only the domestic waterneeds to be drained.
Close boiler water isolation valves andrelieve system pressure to below 15 psig inouter tank before draining inner tank toprevent damage to inner tank.• If boiler water does not contain sufficient
antifreeze, then the boiler water anddomestic water must be drained.
If antifreeze is used in boiler water, check concen-tration. Boiler water (including additives) must bepractically non-toxic, having toxicity rating orclass of 1, as listed in Clinical Toxicology ofCommercial Products. A maximum 50/50 mixtureof inhibited propylene glycol is recommended.Follow antifreeze manufacturer’s instruction.
WARNING
WARNING
DANGER
661A0300 - Rev B
Smart manual_Smart manual 10/29/14 10:00 AM Page 25
661A0300 - Rev B 24
Do not use automotive, ethylene glycol orpetroleum-based antifreeze. Do not useany undiluted antifreeze. This can causesevere personal injury, death or substantialproperty damage.
Water from opened drain valves, unionsand other connections may be extremelyhot. To avoid severe personal injury, deathor substantial property damage:- Tighten all drain hose connections.- Direct hot water away from all persons.
Draining Inner (Domestic Water) Tank
There are 3 methods typically used in thedraining of the inner tank. The first methodoutlined as Option 1 is to siphon the waterout. This method is typically the easiest toperform, but may be lengthly in time to com-plete. The second method, shown as Option 2,uses compressed air. This method is morecomplicated however it is generally quickerin draining the tank. The final method,Option 3, use a pump to drain the tank. Aswith Option 2, Option 3 is generally morecomplicated, but is quicker in draining thetank.
Prior to draining the inner tank, ensure thefollowing is completed:1. The snap-set wiring connection at the
water heater is disconnected.2. The DHW system supply isolation valve
is closed.3. The outer (boiler water) tank pressure is
less than 15 psig.Reference domestic piping diagrams Figs. 1,2 and 3 on page 8 and 9.
Draining Inner Tank - Option 11. Connect a hose to the domestic water drain
valve at the cold water inlet. The hose shouldextend to a drain at floor level to allow siphon-ing of the domestic inner tank.
2. Open a hot water faucet at the highest pointabove the water heater.
3. Open the domestic water drain valve to startthe siphoning of the domestic inner tank.
4. When draining is complete, close the hotwater faucet and the domestic drain valve.
Draining Inner Tank - Option 21. Connect a hose to the domestic water drain
valve at the cold water inlet. Direct the hose toa proper drain/suitable place for drainage.
2. Close the isolation valve on the DHW systemhot outlet of the water heater.
3. On the hot water outlet piping between thewater heater and the isolation valve install ashrader (air tank) valve or some other fitting ormeans that allows connection of an air hosefrom a compressor.
4. Open the domestic water drain valve on thecold water inlet.
WARNING
BEST PRACTICE
NOTICEWARNING
Water Heater Maintenance
Smart manual_Smart manual 10/29/14 10:00 AM Page 26
5. Apply compressed air at a maximum regulatedpressure of 40 psig.
6. When draining is complete, remove the airhose and fittings needed to connect the airhose.
7. Close the domestic water drain valve on thecold water inlet and open the isolation valve onthe hot water outlet.
Draining Inner Tank - Option 31. Connect the suction side of the pump to the
domestic water drain valve using a hose and/orpiping fittings.
2. Connect a hose to the discharge side of thepump. Direct the hose to a proper drain or asuitable place for drainage.
3. Open a hot water faucet at the highest pointabove the water heater.
4. Open the domestic water drain valve and startthe pump to begin draining the inner tank.
5. When draining is complete stop the pump,close the hot water faucet and close the domes-tic drain valve. Remove the pump and allhoses and fittings.
Draining Outer (Boiler Water) Tank1. Disconnect snap set wiring connection at
water heater.2. Close boiler water isolation valves between
boiler and water heater.3. Connect hose to boiler water drain valve at
water heater. Open and drain water to a safeplace.
4. To speed draining procedure, open manualair vent on top of tank.
5. When draining is complete, close drain valveand close manual air vent.
25 661A0300 - Rev B
Water Heater Maintenance
Smart manual_Smart manual 10/29/14 10:00 AM Page 27
661A0300 - Rev B
Replacement Parts
26
SMART Series
Item Part # Models Description1 P3KITAV02 All Air vent, manual
2P3KITTH01 All Aquastat - 160ºF residentialP3KITTH03 All Aquastat - 194ºF commercial
3P3KITBTM02 SMART 30, 40, 50 60
Bottom capP3KITBTM03 SMART 80, 100P3KITBTM04 SMART 120
4P3KITTOP02 SMART 30, 40, 50 60
Top capP3KITTOP03 SMART 80, 100P3KITTOP04 SMART 120
5
P3DW05 SMART 30
Drywell
P3DW01 SMART 40P3DW02 SMART 50
P3DW03SMART 60SMART 80
P3DW04SMART 100SMART 120
6
P3WKITDT01 SMART 30
Dip tube
P3WKITDT02 SMART 40P3WKITDT03 SMART 50P3WKITDT04 SMART 60
P3WKITDT08SMART 80SMART 100
P3WKITDT09 SMART 120
7(Not shown)
P3WKITDT01 SMART 30
Dip Tube - recirculation (optional)
P3WKITDT02 SMART 40P3WKITDT02 SMART 50P3WKITDT01 SMART 60
P3WKITDT08(cut to length)
SMART 80SMART 100SMART 120
8 P3KITWRS01 All Snap-set wire harness9 P3KNB02 All Knob10 P3CVR04 All Cover plate
Smart manual_Smart manual 10/29/14 10:00 AM Page 28
Replacement Parts
27
10
2
8
9
Thermostat Cover Plate Assembly
Thermostat Cover PlateAssembly
Located Below ThermostatCover Plate Assembly
2
6
3
4
5
SMART
661A0300 - Rev B
Smart manual_Smart manual 10/29/14 10:00 AM Page 29
661A0300 - Rev B 28
Water Heater Specifications
E
F
Hot Water Outlet
Cold Water Inlet
Auxiliary Connection
Thermostat& Cover Plate
Air Vent
Top View
Rear View
BAC
D
Cold Water Inlet Hot Water
Outlet
Auxiliary
BoilerReturn
BoilerSupply
Smart manual_Smart manual 10/29/14 10:00 AM Page 30
29 661A0300 - Rev B
Performances
MODEL Boiler HeatingCapacity MBH
Peak Flowgal./ 10 min.
1st Hour FlowGal./Hour
Continuous FlowGal./ Hour
CirculatorMin. GPM
SMART 30 87 40 140 115 5SMART 40 112 50 180 150 7SMART 50 140 65 220 185 8SMART 60 270 100 410 360 16SMART 80 300 125 460 400 18SMART 100 337 150 525 450 25SMART 120 420 190 650 560 28
Conditions: - 50ºF Domestic cold water inlet temperature- 140ºF Domestic hot water outlet temperature- 200ºF Boiler water supply temperature
MODEL Boiler HeatingCapacity MBH
Peak Flowgal./ 10 min.
1st Hour FlowGal./Hour
Continuous FlowGal./ Hour
CirculatorMin. GPM
SMART 30 115 60 235 210 8SMART 40 130 70 270 240 9SMART 50 180 95 370 330 12SMART 60 320 145 635 590 21SMART 80 340 165 690 630 24SMART 100 380 185 775 700 26SMART 120 445 235 915 820 30
Conditions: - 50ºF Domestic cold water inlet temperature- 115ºF Domestic hot water outlet temperature- 200ºF Boiler water supply temperature
Smart manual_Smart manual 10/29/14 10:00 AM Page 31
Additional quality water heating equipment available from: Triangle Tube-ACV
Prestige Condensing Wall Mounted Boiler
Challenger Solo
- Up to 94% AFUE- Fully modulating- Natural gas or propane- Combination copper water tube/aluminum block
heat exchanger- Direct vent, PVC, CPVC, PP and SS- Outdoor reset- Low NOx
MAXI-FLO AND SPA HEAT EXCHANGERS
Triangle Tube - 1 Triangle Lane - Blackwood, NJ 08012 - (856) 228 8881 Fax (856) 228 3584www.triangletube.com / sales@triangletube.com.
- 95% AFUE - Energy Star - Fully modulating- Natural gas or propane- Stainless Steel Contruction- Direct vent PVC, CPVC, PP and SS- Outdoor Reset- Low NOx
661A0300 - Rev B
- Construction of high quality corrosion resistantstainless steel (AISI 316) or titanium
- Specially designed built-in flow restrictor to assuremaximum heat exchange
- Compact and light weight- Available in 5 sizes that can accommodate any size
pool or spa
Smart manual_Smart manual 10/29/14 10:00 AM Page 32
top related