ifb tender bus duct 19 may 10 tc
Post on 24-Mar-2015
263 Views
Preview:
TRANSCRIPT
JINDAL POWER LIMITED
Specification for 11kV & 3.3kV Segregated Phase Busduct
(SPBD) & Neutral Grounding Resistor (NGR)
O.P. Jindal Super Thermal Power Project (4 x600 MW)
JINDAL POWER LIMITED
OP JINDAL SUPER THERMAL POWER PLANT (4 X 600 MW)
TECHNICAL SPECIFICATION
FOR
11KV & 3.3KV SEGREGATED PHASE BUSDUCT (SPBD) &
NEUTRAL GROUNDING RESISTOR (NGR)
BIDDING DOCUMENT NO. K8B15-SPC-E-0025
DEVELOPMENT CONSULTANTS PRIVATE LIMITED CONSULTING ENGINEERS BLOCK DG/4, SECTOR-II, SALT LAKE CITY, KOL - 99, INDIA
Document No.: K8B15-SPC-E-0025_Rev-2 Development Consultants Pvt. Ltd.
JINDAL POWER LIMITED
Specification for 11kV & 3.3kV Segregated Phase Busduct
(SPBD) & Neutral Grounding Resistor (NGR)
O.P. Jindal Super Thermal Power Project (4 x600 MW)
DOCUMENT CONTROL SHEET
PROJECT : OP JINDAL SUPER THERMAL POWER PLANT 4 X 600 MW UNITS CLIENT : JINDAL POWER LIMITED.
DOCUMENT TITLE : SPECIFICATION FOR 11KV & 3.3KV SEGREGATED PHASE BUSDUCT (SPBD) & NEUTRAL GROUNDING RESISTOR (NGR)
DOCUMENT NO. : K8B15-SPC-E-0025 REV. NO. : 2 ENDORSEMENTS
2 20.05.10 FINAL SPEC. RS NB SKC
1 14.05.10 FINAL SPEC. RS NB SKC
a 01.12.09 DRAFT ISSUE AGP NB SKC
REV NO. DATE DESCRIPTION PREPARED
BY REVIEWED
BY APPROVED
BY
Document No.: K8B15-SPC-E-0025_Rev-2 Development Consultants Pvt. Ltd.
JINDAL POWER LIMITED
Specification for 11kV & 3.3kV Segregated Phase Busduct
(SPBD) & Neutral Grounding Resistor (NGR)
O.P. Jindal Super Thermal Power Project (4 x600 MW)
OVERALL CONTENT
SECTIONS DESCRIPTION SECTION-I GENERAL CONDITION OF CONTRACT SECTION-II TECHNICAL SPECIFICATION SECTION-III PROPOSAL EXHIBIT SHEETS [SCHEDULES]
Document No.: K8B15-SPC-E-0025_Rev-2 Development Consultants Pvt. Ltd.
JINDAL POWER LIMITED
Specification for 11kV & 3.3kV Segregated Phase Busduct
(SPBD) & Neutral Grounding Resistor (NGR)
O.P. Jindal Super Thermal Power Project (4 x600 MW)
SECTION – I
CONDITIONS OF CONTRACT
[TO BE PREPARED BY JPL]
Document No.: K8B15-SPC-E-0025_Rev-2 Development Consultants Pvt. Ltd.
JINDAL POWER LIMITED
Specification for 11kV & 3.3kV Segregated Phase Busduct
(SPBD) & Neutral Grounding Resistor (NGR)
O.P. Jindal Super Thermal Power Project (4 x600 MW)
SECTION-II
TECHNICAL SPECIFICATION
Document No.: K8B15-SPC-E-0025_Rev-2 Development Consultants Pvt. Ltd.
JINDAL POWER LIMITED
Specification for 11kV & 3.3kV Segregated Phase Busduct
(SPBD) & Neutral Grounding Resistor (NGR)
O.P. Jindal Super Thermal Power Project (4 x600 MW)
CONTENTS
CLAUSE NO. DESCRIPTION PAGE NO. PART-I: General 1.00.00 INTENT OF SPECIFICATION 1 2.00.00 SCOPE OF WORK 1 3.00.00 SITE CONDITIONS 8 4.00.00 GENERAL REQUIREMENTS 9 5.00.00 SPECIAL TOOLS & TACKLE 13 6.00.00 SPARES 13 7.00.00 PAINTING 13 8.00.00 NAME PLATE 14 9.00.00 TEST CERTIFICATES 14 PART-II: 11kV & 3.3kV Segregated Phase Busduct (SPBD) 1.00.00 DESIGN CRITERIA 17 2.00.00 SPECIFIC REQUIREMENTS 18 3.00.00 TESTS 22 4.00.00 DRAWINGS, DATA & MANUALS 23
ATTACHMENTS
ANNEXURE-A : RATINGS & REQUIREMENTS 26
ANNEXURE-B : BILL OF MATERIALS 28
ANNEXURE-C : MAKES OF BOUGHT OUT ITEMS 31
ANNEXURE-D : LIST OF MANDATORY SPARES 32
ANNEXURE-E : DELIVERY & COMMISSIONING SCHEDULE 33
Document No.: K8B15-SPC-E-0025_Rev-2 Development Consultants Pvt. Ltd.
JINDAL POWER LIMITED
Specification for 11kV & 3.3kV Segregated Phase Busduct
(SPBD) & Neutral Grounding Resistor (NGR)
O.P. Jindal Super Thermal Power Project (4 x600 MW)
PART-III: Neutral Grounding Resistor (NGR) 1.00.00 DESIGN CRITERIA 34 2.00.00 SPECIFIC REQUIREMENTS 34 3.00.00 TESTS 36 4.00.00 DRAWINGS DATA & MANUALS 37
ATTACHMENTS ANNEXURE-A : RATINGS & REQUIREMENTS 39
ANNEXURE-B : LIST OF MANDATORY SPARES 41
ANNEXURE-C : DELIVERY & COMMISSIONING SCHEDULE 42
DRAWINGS
Drawing No. Rev
Description
K8B15-DWG-E-0101 4 Key Single Line Diagram
K8B15-DWG-E-0401 5 Composite Layout - Transformer Yard, Generator Busduct & HT Busduct – Unit # 1&2
K8B15-DWG-E-0402, Sht.1 of 2 5 Composite Layout - Transformer Yard, Generator
Busduct & HT Busduct – Unit # 3&4 K8B15-DWG-E-0402, Sht.2 of 2 5 Composite Layout - Transformer Yard, Generator
Busduct & HT Busduct SKE-12 1 HT Switchgear Room Layout – Unit# 1,2,3 & 4
Document No.: K8B15-SPC-E-0025_Rev-2 Development Consultants Pvt. Ltd.
JINDAL POWER LIMITED
Specification for 11kV & 3.3kV Segregated Phase Busduct
(SPBD) & Neutral Grounding Resistor (NGR)
O.P. Jindal Super Thermal Power Project (4 x600 MW)
PART- I : General
Document No.: K8B15-SPC-E-0025_Rev-2 Development Consultants Pvt. Ltd.
JINDAL POWER LIMITED
Specification for 11kV & 3.3kV Segregated Phase Busduct
(SPBD) & Neutral Grounding Resistor (NGR)
O.P. Jindal Super Thermal Power Project (4 x600 MW)
TECHNICAL SPECIFICATION
FOR 11KV & 3.3KV SEGREGATED PHASE BUSDUCT (SPBD)
NEUTRAL GROUNDING RESISOR (NGR)
1.00.00 INTENT OF SPECIFICATION 1.01.00 This specification is intended to cover the design, engineering, fabrication,
manufacture, assembly, inspection, testing at manufacturer's works, supply & delivery, properly packed for transport F.O.R. site of 11000V & 3300V Segregated phase Busduct (SPBD) including all supporting GI steel structures, indoor or outdoor post, hangers, fasteners and necessary hardware for complete bus-duct installation, Hot Air Blowing equipment, Air Pressurization Cubicle and Neutral Grounding Resistor (NGR) including supporting steel work and hardware, fittings & accessories, equipment fastener hardware for complete NGR installation complete with all other accessories for efficient and trouble-free operation in a manner acceptable to Owner for OP Jindal Super Thermal Power Project of 4x600MW Units near village Tamnar in Raigarh District in the state of Chhattisgarh, India.
1.02.00 The scope of work shall also includes unloading, storage at site, erection, testing,
commissioning and putting into successful commercial operation including supply of all labor, supervision, tools & tackles consumables and implements of all equipment furnished under this specification.
1.03.00 The work is subject to all the terms and conditions detailed in the documents listed
below, which shall form part of this specification as if bound together. a. Tender Notice b. Instruction to Bidders c. General conditions of contract for supply, delivery & installation of plant and
materials. 1.04.00 In the event of any discrepancy with listed documents, the stipulation of this
specification & good engineering practices shall be taken into account by the Contractor without any extra cost and /or time implication to the Owner. In absence of any specific data at this stage, the requirement and the interpretation of Owner shall be final. In the event of conflict between requirements of any two clauses of these specification/documents the more stringent requirements as per the interpretation of the Owner shall apply.
1.05.00 Omission of any specific reference to an item in the specification shall not relieve the
Contractor from the responsibility of providing the same meeting the overall performance requirements stated in the specification. In the event of any discrepancy with listed documents, the stipulation of this specification shall govern.
2.00.00 SCOPE OF WORK 2.01.00 Scope of Supply 2.01.01 11000V Phase Segregated Bus duct, terminal adaptor boxes and other necessary
accessories for connection of the following are given below:
Document No.: K8B15-SPC-E-0025_Rev-2 Page 1 of 46 Development Consultants Pvt. Ltd.
JINDAL POWER LIMITED
Specification for 11kV & 3.3kV Segregated Phase Busduct
(SPBD) & Neutral Grounding Resistor (NGR)
O.P. Jindal Super Thermal Power Project (4 x600 MW)
Busduct Identification SL.
No. B.D No. As per Key SLD Busduct Arrangement
1 BD 101 1UT11SR1 Interconnection between Unit Transformer (31.5 MVA) UT#1HUT1 and 11kV Unit Switchgear # 1KSR1(2000 A)
2 BD 102 1UT21SR2 Interconnection between Unit Transformer (31.5 MVA) UT#1HUT2 and 11kV Unit Switchgear # 1KSR2 (2000 A)
3 BD 103 2UT12SR1 Interconnection between Unit Transformer (31.5 MVA) UT#2HUT1 and 11kV Unit Switchgear # 2KSR1 (2000 A)
4 BD 104 2UT22SR2 Interconnection between Unit Transformer (31.5 MVA) UT#2HUT2 and 11kV Unit Switchgear # 2KSR2 (2000 A)
5 BD 105 3UT13SR1 Interconnection between Unit Transformer (31.5 MVA) UT# 3HUT1and 11kV Unit Switchgear # 3KSR1 (2000 A)
6 BD 106 3UT23SR2 Interconnection between Unit Transformer (31.5 MVA) UT#3HUT2 and 11kV Unit Switchgear # 3KSR2 (2000 A)
7 BD 107 4UT14SR1 Interconnection between Unit Transformer (31.5 MVA) UT#4HUT1 and 11kV Unit Switchgear # 4KSR1 (2000 A)
8 BD 108 4UT24SR2 Interconnection between Unit Transformer (31.5 MVA) UT#4HUT2 and 11kV Unit Switchgear # 4KSR2 (2000 A)
9 BD 109 1SR10SR1 Interconnection between 11kV Station Switchgear #0KSR1 and 11kV Unit Switchgear # 1KSR1(2000 A)
10 BD 110 1SR20SR2 Interconnection between 11kV Station Switchgear #0KSR2 and 11kV Unit Switchgear # 1KSR2 (2000 A)
11 BD 111 2SR10SR3 Interconnection between 11kV Station Switchgear #0KSR3 and 11kV Unit Switchgear # 2KSR1 (2000 A)
12 BD 112 2SR20SR4 Interconnection between 11kV Station Switchgear #0KSR4 and 11kV Unit Switchgear # 2KSR2 (2000 A)
13 BD 113 3SR10SR5 Interconnection between 11kV Station Switchgear #0KSR5 and 11kV Unit Switchgear # 3KSR1 (2000 A)
14 BD 114 3SR20SR6 Interconnection between 11kV Station Switchgear #0KSR6 and 11kV Unit Switchgear #3KSR2 (2000 A)
15 BD 115 4SR10SR7 Interconnection between 11kV Station Switchgear #0KSR7 and 11kV Unit Switchgear #4KSR1 (2000 A)
16 BD116 4SR20SR8 Interconnection between 11kV Station Switchgear #0KSR8 and 11kV Unit Switchgear #4KSR2 (2000 A)
17 BD 117 1ST10SR1 Interconnection between LV Winding-1A of ST(90/45/45 MVA) # 0BST1and 11kV Station Switchgear #0KSR1(3000 A)
18 BD 118 1ST20SR2 Interconnection between LV Winding-1B of ST (90/45/45 MVA)# 0BST1and 11kV Station Switchgear #0KSR2 (3000 A)
19 BD 119 2ST10SR3 Interconnection between LV Winding-2A of ST (90/45/45 MVA)# 0BST2 and 11kV Station Switchgear #0KSR3 (3000 A)
20 BD 120 2ST20SR4 Interconnection between LV Winding-2B of ST (90/45/45 MVA)# 0BST2 and 11kV Station Switchgear #0KSR4 (3000 A)
21 BD 121 3ST10SR5 Interconnection between LV Winding-3A of ST (90/45/45 MVA)# 0BST3 and 11kV Station Switchgear #0KSR5 (3000 A)
22 BD 122 3ST20SR6 Interconnection between LV Winding-3B of ST(90/45/45 MVA) # 0BST3 and 11kV Station Switchgear #0KSR6 (3000 A)
23 BD 123 0SR10SR5 Interconnection between 11kV Station Switchgear#0KSR1 and 11kV Station Switchgear #0KSR5 (3000 A)
Document No.: K8B15-SPC-E-0025_Rev-2 Page 2 of 46 Development Consultants Pvt. Ltd.
JINDAL POWER LIMITED
Specification for 11kV & 3.3kV Segregated Phase Busduct
(SPBD) & Neutral Grounding Resistor (NGR)
O.P. Jindal Super Thermal Power Project (4 x600 MW)
Busduct Identification SL.
No. B.D No. As per Key SLD Busduct Arrangement
24 BD 124 0SR10SR3 Interconnection between 11kV Station Switchgear #0KSR1 and 11kV Station Switchgear #0KSR3 (3000 A)
25 BD 125 0SR20SR4 Interconnection between 11kV Station Switchgear #0KSR2 and 11kV Station Switchgear #0KSR4 (3000 A)
26 BD 126 0SR20SR6 Interconnection between 11kV Station Switchgear #0KSR2 and 11kV Station Switchgear #0KSR6 (3000 A)
27 BD 129 0SR30SR7 Interconnection between 11kV Station Switchgear #0KSR3 and 11kV Station Switchgear #0KSR7 (3000 A)
28 BD 130 0SR40SR8 Interconnection between 11kV Station Switchgear #0KSR4 and 11kV Station Switchgear #0KSR8 (3000 A)
29 BD 131 0SR50SR7 Interconnection between 11kV Station Switchgear #0KSR5 and 11kV Station Switchgear #0KSR7 (3000 A)
30 BD 132 0SR60SR8 Interconnection between 11kV Station Switchgear #0KSR6 and 11kV Station Switchgear #0KSR8 (3000 A)
31 BD 127 RWT1SR01 Interconnection between 33/11KV Transformer(25 MVA) # 0GRWHT1 and 11kV River WTR Switchgear #0KRWSR1 (2000A)
32 BD 128 RWT2SR01 Interconnection between 33/11KV Transformer(25 MVA) # 0GRWHT2 and 11kV River WTR Switchgear #0KRWSR1 (2000A)
2.01.02 3300V Phase Segregated Bus ducts and associated equipment with all necessary
accessories as given below:
Sl. No. Busduct Identification
B.D No. As per Key SLD Busduct Layout
1 BD 201 1KUAT1-1MSR1 Interconnection between Unit Auxiliary Transformer UAT#1KUAT1 (16MVA) and 3.3kV Unit Switchgear #1MSR1 (3000 A)
2 BD 202 1KUAT2-1MSR2 Interconnection between Unit Auxiliary Transformer UAT#1KUAT2 (16MVA) and 3.3kV Unit Switchgear #1MSR2 (3000 A)
3 BD 203 2KUAT1-2MSR1 Interconnection between Unit Auxiliary Transformer UAT#2KUAT1 (16MVA) and 3.3kV Unit Switchgear #2MSR1 (3000 A)
4 BD 204 2KUAT2-2MSR2 Interconnection between Unit Auxiliary Transformer UAT#2KUAT2 (16MVA) and 3.3kV Unit Switchgear #2MSR2 (3000 A)
5 BD 205 3KUAT1-3MSR1 Interconnection between Unit Auxiliary Transformer UAT#3KUAT1 (16MVA) and 3.3kV Unit Switchgear #3MSR1 (3000 A)
6 BD 206 3KUAT2-3MSR2 Interconnection between Unit Auxiliary Transformer UAT#3KUAT2 (16MVA) and 3.3kV Unit Switchgear #3MSR2 (3000 A)
7 BD 207 4KUAT1-4MSR1 Interconnection between Unit Auxiliary Transformer UAT#4KUAT1 (16MVA) and 3.3kV Unit Switchgear #4MSR1 (3000 A)
8 BD 208 4KUAT2-4MSR2 Interconnection between Unit Auxiliary Transformer UAT#4KUAT2 (16MVA) and 3.3kV Unit Switchgear #4MSR2 (3000 A)
9 BD 209 0KSAT1-0MSR1 Interconnection between Station Auxiliary Transformer # 0KSAT1 (6.3MVA) and 3.3kV Station Switchgear #0MSR1 (1250 A)
10 BD 210 0KSAT2-0MSR2 Interconnection between Station Auxiliary Transformer # 0KSAT2 (6.3MVA) and 3.3kV Station Switchgear #0MSR2 (1250 A)
11 BD 211 0KSAT3-0MSR3 Interconnection between Station Auxiliary Transformer # 0KSAT3 (6.3MVA) and 3.3kV Station Switchgear #0MSR3 (1250 A)
Document No.: K8B15-SPC-E-0025_Rev-2 Page 3 of 46 Development Consultants Pvt. Ltd.
JINDAL POWER LIMITED
Specification for 11kV & 3.3kV Segregated Phase Busduct
(SPBD) & Neutral Grounding Resistor (NGR)
O.P. Jindal Super Thermal Power Project (4 x600 MW)
Sl. No. Busduct Identification
B.D No. As per Key SLD Busduct Layout
12 BD 212 0KSAT4-0MSR4 Interconnection between Station Auxiliary Transformer # 0KSAT4 (6.3MVA)and 3.3kV Station Switchgear #0MSR4 (1250 A)
13 BD 213 0KCHHT1-0MCHSR1
Interconnection between CHP Service Transformer # 0KCHHT1 (8MVA)and 3.3Kv Switchgear # 0MCHSR1 (2500 A)
14 BD 214 0KCHHT2-0MCHSR2
Interconnection between CHP Service Transformer # 0KCHHT2 (8MVA)and 3.3Kv Switchgear # 0MCHSR2 (2500 A)
15 BD 215 0KAFHT1-0MAFSR1
Interconnection between Fly ASH COMPRESSOPR Transformer # 0KAFHT1 (5MVA) and 3.3kV Fly compressor Switchgear# 0MAFSR1 (1250 A)
16 BD 216 0KAFHT2-0MAFSR1
Interconnection between Fly ASH COMPRESSOPR Transformer # 0KAFHT2 (5MVA) and 3.3kV Fly compressor Switchgear# 0MAFSR1 (1250A)
17 BD 217 0GARHT1-0MARSR1
Interconnection between Ash Dyke transformer # 0GARHT1 (5MVA) and 3.3kV ASH DYKE Switchgear# 0MARSR1 (1250 A)
18 BD 218 0GARHT2-0MARSR1
Interconnection between ASH DYKE transformer # 0GARHT2 (5MVA) and 3.3kV ASH DYKE Switchgear# 0MARSR1 (1250 A)
19 BD 219 0KAWHT1-0MAWSR1
Interconnection between ASH WTR. Transformer# 0KAWHT1 (3MVA) and 3.3kV ASH WTR. Switchgear 0MAWSR1 (1250A)
20 BD 220 0KAWHT2-0MAWSR1
Interconnection between ASH WTR. Transformer (3MVA)# 0KAWHT2 and 3.3kV ASH WTR. Switchgear 0MAWSR1 (1250 A)
21 BD 221 0KADHT1-0MADSR1
Interconnection between ASH SLRY Transformer# 0KADHT1 (5MVA) and 3.3kV ASH SLRY. Switchgear #0MADSR1 (1250 A)
22 BD 222 0KADHT2-0MADSR1
Interconnection between ASH SLRY Transformer (5MVA)# 0KADHT2 and 3.3kV ASH SLRY. Switchgear #0MADSR1 (1250 A)
23 BD 223 0GRTHT1-0MRTSR1
Interconnection between RAW WTR. Transformer# 0GRTHT1 (5MVA) and 3.3kV RAW WTR. Switchgear# 0MRTSR1 (1250 A)
24 BD 224 0GRTHT2-0MRTSR1
Interconnection between RAW WTR. Transformer (5MVA)# 0GRTHT2 and 3.3kV RAW WTR. Switchgear# 0MRTSR1 (1250 A)
25 BD 225 1MSR1 -1MSR2 Interconnection between 3.3kV Unit Switchgear #1MSR1 and 3.3kV Unit Switchgear # 1MSR2 (3000 A)
26 BD 226 2MSR1-2MSR2 Interconnection between 3.3kV Unit Switchgear #2MSR1 and 3.3kV Unit Switchgear # 2MSR2 (3000 A)
27 BD 227 3MSR1-3MSR2 Interconnection between 3.3kV Unit Switchgear #3MSR1and 3.3kV Unit Switchgear # 3MSR2 (3000 A)
28 BD 228 4MSR1-4MSR2 Interconnection between 3.3kV Unit Switchgear #4MSR1 and 3.3kV Unit Switchgear # 4MSR2 (3000 A)
29 BD 229 0MSR1-0MSR2 Interconnection between 3.3kV Station Switchgear #0MSR1 and 3.3kV Station Switchgear # 0MSR2 (1250 A)
30 BD 230 0MSR3-0MSR4 Interconnection between 3.3kV Station Switchgear #0MSR3 and 3.3kV Station Switchgear # 0MSR4 (1250 A)
31 BD 232 0MCHSR1-0MCHSR2
Interconnection between 3.3KV CHP Switchgear # 0MCHSR1 and 3.3KV CHP Switchgear #0MCHSR2 (2500 A)
Document No.: K8B15-SPC-E-0025_Rev-2 Page 4 of 46 Development Consultants Pvt. Ltd.
JINDAL POWER LIMITED
Specification for 11kV & 3.3kV Segregated Phase Busduct
(SPBD) & Neutral Grounding Resistor (NGR)
O.P. Jindal Super Thermal Power Project (4 x600 MW)
2.01.03 Neutral grounding Resistor (NGR)
Sl. No. NGR Description Qty
(Nos.)
1. 22.13 Ohms, 11000 V, 300 A for 10 seconds for Unit Transformers. 1KXYNG1, 1KXYNG2, 2KXYNG1, 2KXYNG2, 3KXYNG1 & 3KXYNG2, 4KXYNG1, 4KXYNG2. Eight (8)
2 22.13 Ohms, 11000 V, 300 A for 10 seconds for Station Transformers. 0KXYNG1, 0KXYNG2, 0KXYNG3, 0KXYNG4, 0KXYNG5 & 0KXYNG6. Six (6)
3 22.13 Ohms, 11000 V, 300 A for 10 seconds for River Water Transformer. 0KRWNG1 and 0KRWNG2. Two (2)
4 6.64 Ohms, 3300 V, 300 Amps for 10 seconds for Raw Water Transfer Transformers.0MRTNG1 and 0MRTNG2. Two (2)
5 6.64 Ohms, 3300 V, 300 Amps for 10 seconds for 3.3kV Station Aux. Transformer.0MXYNG1, 0MXYNG2, 0MXYNG3 and 0MXYNG4. Four (4)
6 6.64 Ohms, 3300 V, 300 Amps for 10 seconds for 3.3kV Ash Slurry Transformer.0MAPNG1 and 0MAPNG2. Two (2)
7 6.64 Ohms, 3300 V, 300 Amps for 10 seconds for 3.3kV Ash Water Transformer.0MAWNG1 and 0MAWNG2. Two (2)
8 6.64 Ohms, 3300 V, 300 Amps for 10 seconds for Ash Silo Transformer. OMASNG1 and 0MASNG2. Two (2)
9 6.64 Ohms, 3300 V, 300 Amps for 10 seconds for Ash Dyke Transformer. 0MARNG1 and 0MARNG2. Two (2)
10 6.64 Ohms, 3300 V, 300 Amps for 10 seconds for Fly Ash Compressor Transformer. 0MAFNG1 and 0MAFNG2. Two (2)
11 6.64 Ohms, 3300 V, 300 Amps for 10 seconds for CHP Transformer. 0MCHNG1 and 0MCHNG2. Two (2)
12 6.64 Ohms, 3300 V, 300 Amps for 10 seconds for Unit Auxiliary Transformer. 1MXYNG1, 1MXYNG2, 2MXYNG1, 2MXYNG2, 3MXYNG1, 3MXYNG2, 4MXYNG1 and 4MXYNG2.
Eight (8)
2.01.04 Bill of Materials for Segregated Phase Busduct (SPBD) including supporting structures
is given in Annexure–B under Part-II. The quantity indicated therein is for bidding purpose only. Exact requirement shall be finalized by the successful bidder based on the approved bus duct layout drawing.
2.01.05 Two set of hot air blower including electric heater and other electric in a single carriage,
including flexible portable hot air duct for hot air blowing in HT bus duct. 2.01.06 Necessary phase segregated terminal adopter boxes with matching flanges, wall frame
assembly, seal off bushing, copper flexible, 90° bend, phase crossover chamber, Aluminum flexible, rubber bellows, breather, drain-cock with filters etc. gasket with all necessary accessories for connection to H.T. Switchgear Incomer/Tie panel and for termination on the Unit/Station/ HT Auxiliary transformers.
2.01.07 Each set of H.T. Bus duct shall consist of all supporting steel structures, indoor or
outdoor post, hangers, fasteners and necessary hardware for complete bus-duct installation.
2.01.08 Each set of Neutral Grounding Resistor shall be furnished complete with: a) Fittings and accessories. b) Auxiliary Equipment c) All supporting GI steel work and hardware, fittings and accessories, equipment
fastener hardware for complete NGR installation.
Document No.: K8B15-SPC-E-0025_Rev-2 Page 5 of 46 Development Consultants Pvt. Ltd.
JINDAL POWER LIMITED
Specification for 11kV & 3.3kV Segregated Phase Busduct
(SPBD) & Neutral Grounding Resistor (NGR)
O.P. Jindal Super Thermal Power Project (4 x600 MW)
d) Copper connection link between each Transformer neutral bushing to NGR and
GI link for NGR neutral point and earthing. e) All removable cable glands of adequate size required for termination at NGR
cubicle. 2.01.09 Mandatory spare parts as listed for SPBD in ANNEXURE-D under Part-II and for NGR
in Annexure-B under Part-III respectively. 2.01.10 Two steel carriage (trolley) for mounting of portable hot air blowing equipment complete
with all accessories for each unit. 2.01.11 One set of special tools and tackle. 2.01.12 Power and control cables for connections between equipment supplied by the bidder. 2.01.13 One set of space heater panel (wall mounted) for supplying power to internally
mounted space heaters of each bus duct. 2.01.14 If any special testing equipments is required for testing and commissioning, the same
shall be provided by the bidder. 2.01.15 Recommended spare parts for three (3) years of satisfactory operation. 2.01.16 All relevant drawings, data and instruction manuals. 2.02.00 Scope of Services It includes unloading, handling & storage at site and complete erection, testing and
commissioning for the supplied equipment/material. The contractor shall furnish all labour (skilled & unskilled) , supervisory and administrative personnel, erection, tools & tackles, testing equipment, implements, supplies & transport etc. for timely and efficient execution of contract.
2.02.01 Complete checking of materials at site and advising the Owner of any discrepancy
thereof. 2.02.02 Ensuring proper storage of equipment/material, detailed storage instruction shall be
furnished to the Owner well in advance. 2.02.03 Submission of sequence of erection to be followed by agency and erection drawing. 2.02.04 Repairing the minor damages such as scratches, removal of paints, loosening of
components of the assembly, cleaning before erection and application of anticorrosive paint after cleaning. Complete assembly and erection including opening and closing of all disconnect links for the purpose of equipment testing.
2.02.05 Pre-commissioning check up to ensure correctness. 2.02.06 Trial operation for fifteen (15) days, rectifying defects, if any and making adjustments as
necessary and putting the equipment into successful operation for each set of Bus duct and NGR.
2.02.07 Testing, commissioning and putting the equipment into successful commercial
operation in presence of Owner’s representative.
Document No.: K8B15-SPC-E-0025_Rev-2 Page 6 of 46 Development Consultants Pvt. Ltd.
JINDAL POWER LIMITED
Specification for 11kV & 3.3kV Segregated Phase Busduct
(SPBD) & Neutral Grounding Resistor (NGR)
O.P. Jindal Super Thermal Power Project (4 x600 MW)
2.02.08 The bidder shall submit along with the bid a realistic schedule indicating the sequence
of erection and also posting of his supervisory staff of different categories and the estimated period of their stay at site
2.02.09 Handing over of one set of “As Built” marked up drawing to the Owner for preparation of
final “As Built” drawing. 2.02.10 All relevant civil inputs such as foundation plan and loading of each busduct supporting
structure, co ordinates of foundation, size of insert plates (for supporting indoor portion of busduct) etc
2.02.11 Transport vehicles required for intra-site transportation of equipment. 2.02.12 Complete assembly, erection / supervision of installation and connection grounding,
testing and commissioning, putting into successful and satisfactory commercial operation of the Segregated Phase Busduct.
2.02.13 Receiving, unloading and loading, transporting at site to owner’s and/ or contractor’s
stores and there up to actual place of erection. Storage/security of the material at site shall be in the scope of Bidder.
2.02.14 Opening of packing in the presence of owner (if necessary) and inspection of the
equipment and materials at site and reporting damages, shortages etc. if any, immediately after opening to the owner.
2.02.15 Proper storing arrangement at plant site with suitable enclosure for protection from
weather and pilferage of items their scope of supply and materials, consumable, testing equipment etc, brought to site by the contractor.
2.02.16 If any special testing equipment is required for testing and commissioning the same
shall be provided by the supplier without any price implication to the owner. 2.02.17 Maintaining and managing of contractor’s own store and reconciliation or completion of
job. 2.02.18 Arranging to repair and/ or re-order all damaged and short supply items. 2.02.19 Necessary co-ordination between works done by other contractors. 2.02.20 Pre-commissioning check-up to ensure correctness of erection as per actual
manufacturer’s instruction. 2.02.21 Final checking, testing and commissioning of all equipment in presence of owners
representatives including checking of interlocking and correctness of wiring and as per scheme.
2.02.22 Modification jobs in schemes, wiring etc., if required by consultants/ owner till the date
of handing over the equipment. 2.02.23 Preparing the protocols in the mutually agreed format for the satisfactory erection,
testing and commissioning of the equipment. 2.02.24 Submission of various test reports, protocols etc. to purchaser along with
commissioning of the equipment. 2.02.25 Satisfactory routine and emergency maintenance of the equipment/systems erected
and commissioned by the contractor till the completion of the contract.
Document No.: K8B15-SPC-E-0025_Rev-2 Page 7 of 46 Development Consultants Pvt. Ltd.
JINDAL POWER LIMITED
Specification for 11kV & 3.3kV Segregated Phase Busduct
(SPBD) & Neutral Grounding Resistor (NGR)
O.P. Jindal Super Thermal Power Project (4 x600 MW)
2.02.26 Obtaining engineer’s approval and owner’s acceptance of satisfactory performance. 2.02.27 Handing over of all equipment for commercial operations. 2.02.28 Field modification carried out shall be marked–up in red in (3) set of erection drawing
and submitted to the owner for approval. Preparation of ‘As Built’ drawings based on approved field modification.
2.02.29 Attending meetings to all rules and regulations in vogue at owner’s premises in
reference particularly to the administration, security, safety etc. 2.03.00 Terminal Points
a. 11kV Unit, Station, River Water & Raw water Transfer Switchgear, cubicle power terminal flange
b. Unit / Station Transformer LV terminal flange
c. 3.3kV Unit / Station / AHP / CHP , Raw Water Transfer, Ash Dyke Switchboard cubicle power terminal flange
d. HT Auxiliary Transformer LV terminal flange
e. Earthing : Nearest earth riser from Owner’s station earth mat 300mm above ground level
f. Cables for connection between SPBD and equipment supplied by others.
2.04.00 Exclusion from Scope of Work 2.04.01 All concrete foundation works. However, supply of foundation bolts, grouting is included
within scope of supply and erection. 2.04.02 Fire detection & Fire fighting system. 2.04.03 Illumination and lightning protection. 2.05.00 Commissioning Schedule 2.05.01 The commissioning schedule of SPBD has been tabulated in Annexure-E.
Commissioning period shall be reckoned from the date of issue of Effective date of contract (EDC).
2.05.02 The commissioning schedule of NGR has been tabulated in Annexure-C.
Commissioning period shall be reckoned from the date of issue of Effective date of contract (EDC).
2.05.03 The delivery of the bus ducts shall be complete with its supporting structure and
accessories. 2.05.04 Commissioning period shall be inclusive of the time to be allowed for approval of
drawings & test certificates and shall include transportation time to site including erection & commissioning of complete set of segregated phase busduct (SPBD) & NGR.
2.05.05 Auxiliary equipment, mandatory spares, special tools and tackle shall be supplied with
the first consignment.
Document No.: K8B15-SPC-E-0025_Rev-2 Page 8 of 46 Development Consultants Pvt. Ltd.
JINDAL POWER LIMITED
Specification for 11kV & 3.3kV Segregated Phase Busduct
(SPBD) & Neutral Grounding Resistor (NGR)
O.P. Jindal Super Thermal Power Project (4 x600 MW)
3.00.00 SITE CONDITIONS 3.01.00 The equipment specified herein will be installed at OP Jindal Super Thermal Power
Plant of Jindal Power Limited. 3.02.00 The job site is situated near Village Tamnar in Raigarh District in the State of
Chhattisgarh, India. The job site is approachable from Raigarh by the State Highway, which branches off at Punjipathra, about 12 Km from the site and 34 Km from Raigarh Town. The nearest broad gauge rail Link is at Raigarh, which is about 35 Km and the nearest Airport is at Raipur, which is about 280 Kms from the job site
3.03.00 Equipment shall be packaged for transportation so as to meet the space and weight
limitation of transport facilities, specially along the railroad right-of-way. 3.04.00 For the purpose of equipment design, the following data shall be taken into
consideration:-
a) Average Grade : 260M above MSL
b) Design Ambient Air Temperature : 50°C max and 6.4°C Min
c) Average Relative Humidity : 90%
d) Average Wind Speed : 39 m/sec
e) Seismic Zone (As per relevant IS) : III
4.00.00 GENERAL REQUIREMENTS 4.01.00 Codes and Standards 4.01.01 All equipment and materials shall be designed, manufactured and tested in accordance
with the latest applicable Indian Standards (IS) and IEC except where modified and/or supplemented by this specification.
4.01.02 Equipment and materials conforming to any other standard that ensures equal or better
quality may be accepted. In such case, copies of the English version of the standard adopted shall be submitted along with the bid.
4.01.03 The electrical installation shall meet the requirements of Indian Electricity Rules as
amended up to date and relevant IS Codes of Practice. In addition, other rules or regulations applicable to the work shall be followed. In case of any discrepancy, the more restrictive rule shall be binding.
4.01.04 While selecting various equipment, due consideration shall given to interchangeability
in order to reduce spare requirement, and to maintainability by local skill level. Equipment of a type or design, which requires limited/infrequent or no maintenance, are preferred
4.02.00 Drawings & Annexure 4.02.01 All drawings and annexure appended to this specification shall form part of this
specification and supplement the requirements specified herein.
Document No.: K8B15-SPC-E-0025_Rev-2 Page 9 of 46 Development Consultants Pvt. Ltd.
JINDAL POWER LIMITED
Specification for 11kV & 3.3kV Segregated Phase Busduct
(SPBD) & Neutral Grounding Resistor (NGR)
O.P. Jindal Super Thermal Power Project (4 x600 MW)
4.02.02 This specification shall be read and construed in conjunction with the drawings and
annexure to determine the scope of work and terminal points. 4.02.03 The quantities shown on drawings and annexure are tentative for bidding purpose only.
Any variation arising during detailed engineering stage shall be taken into account for adjustment of contract price based on unit rates quoted in the bid.
4.03.00 Completeness of supply 4.03.01 It is not the intent to specify completely herein all details of the equipment.
Nevertheless, the equipment shall be complete and operative in all aspects and shall conform to highest standard of engineering, design & workmanship and be capable of performing in continuous commercial operation up to the guarantees in a manner acceptable to the purchaser, who will interpret the meaning of drawings & specifications and shall be entitled to reject any work or material which in his judgment is not in full accordance therewith.
4.03.02 Any material or accessory which may not have been specifically mentioned but which is
necessary or usual for satisfactory and trouble-free operation and maintenance of the equipment shall be furnished without any extra charge.
4.03.03 The Contractor shall supply all brand new equipment and accessories as specified
herein with such modification and alteration as agreed upon in writing after mutual discussion.
4.04.00 Proposal Data The proposal data sheets (Schedules) to this specification shall be filled in without any
ambiguity by typing in appropriate place on each page. These pages must be properly signed by authorized representative of the Bidder as verification of the data and submitted along with the bid to form part of the Bidder's formal proposal.
4.05.00 Guaranteed Performance 4.05.01 The performance figures quoted in Technical Particular sheets shall be guaranteed
within the tolerance permitted by relevant standards. In case of failure of the equipment to meet the guarantee, the equipment may be liable for rejection.
4.05.02 The loss figure quoted by the bidder for 3.3 & 11 KV bus duct shall be guaranteed
under penalty. Penalty shall be charged on the tested losses in excess of the guaranteed figures at the rate of Rs. 1,97,000/-per KW. For fraction of a KW penalty shall be pro-rata.
4.06.00 Deviation 4.06.01 Should the Bidder wish to deviate from this specification in any way, he shall draw
specific attention to such deviation. 4.06.02 All such deviations shall be clearly mentioned on the Deviation sheet enclosed, with
reference to the respective clause of the specification. Acceptance or Non-acceptance of Deviation is the sole discretion of the Owner.
4.06.03 Unless such deviations are recorded in the Deviation sheets and submitted with the
offer, it shall be taken for granted that the offer is made in conformity with this specification in all respects.The deviation listed elsewhere in the text of the tender will not be considered
Document No.: K8B15-SPC-E-0025_Rev-2 Page 10 of 46 Development Consultants Pvt. Ltd.
JINDAL POWER LIMITED
Specification for 11kV & 3.3kV Segregated Phase Busduct
(SPBD) & Neutral Grounding Resistor (NGR)
O.P. Jindal Super Thermal Power Project (4 x600 MW)
4.07.00 Drawing Approval 4.07.01 Before starting manufacture of any equipment, the contractor shall have to take
approval of relevant drawings and data from Owner in writing. 4.07.02 Any manufacture done prior to the approval of drawings/data shall be rectified in
accordance with the approved drawings/data by the Contractor at his own cost and the equipment shall be supplied within the stipulated period.
4.08.00 Record of Past Experience 4.08.01 Necessary information about the financial and technical resources of
organization & experience to undertake the manufacturing and supply of such equipment shall be supplied by the Bidder as an evidence of his capability for satisfaction of the Owner.
4.08.02 The Bidder shall submit along with his bid a list of major contracts of supply and
erection of similar equipment already executed or under execution, giving detailed particulars such as equipment rating, contract value, name of the Owner, year of commissioning, etc.
4.08.03 Apart from the requirements stipulated elsewhere in this specification, the following
shall constitute the minimum technical qualifying requirement of the bidder offering against this bid.
a) The bidder must be an established manufacturer of 11000V & 3300V segregated
phase busduct as well as NGR & must have designed, manufactured, tested, supplied and commissioned in not less than three projects equipment of similar ratings. Such equipments have been in successful operation for at least three years on the date set for opening of the bid.
b) The bidder must be a regular manufacturer of high voltage busduct and must have
facilities to manufacture such equipment of the type and rating specified.
c) Not withstanding anything stated above, the purchaser reserves the right to assess bidder’s financial and other capabilities to execute the contract.
d) The bidder shall have adequate and established quality assurance system and
organization to achieve high levels of equipment reliability.
e) The bidder shall submit type test reports conducted not later than five years certified by reputed agencies.
4.09.00 Quality Assurance
4.09.01 The Contractor shall follow his standard procedures for quality assurance and control. A copy of the said standard procedures shall be submitted to the Owner for his reference. However, Owner reserves the right to review the same and give his observations, if any, for compliance.
4.09.02 The procedures shall be in such a form as to clearly delineate the manufacturing sequence, inspection points, tests and test procedures, acceptable ranges / values, reference drawings etc.
Document No.: K8B15-SPC-E-0025_Rev-2 Page 11 of 46 Development Consultants Pvt. Ltd.
JINDAL POWER LIMITED
Specification for 11kV & 3.3kV Segregated Phase Busduct
(SPBD) & Neutral Grounding Resistor (NGR)
O.P. Jindal Super Thermal Power Project (4 x600 MW)
4.09.03 The Owner shall inform the Contractor as to which of the inspection points and tests
shall be witnessed. As a minimum, inspection and testing of the finished equipment shall be made prior to shipment, unless specifically waived by the Owner. The contractor shall give at least Thirty (30) days advance notice regarding readiness of the equipment.
4.09.04 Manufacturing and quality control procedures shall be available for audit to the Owner and/or its representative at the place of manufacture.
4.09.05 The Owner reserves the right to inspect the equipment at the point of manufacture and witness factory and other such tests as may be necessary to ensure conformance to the specification.
4.09.06 The Owner may inspect the Contractor's facilities prior to award of contract.
4.09.07 The Owner may witness any or all of the tests stipulated in the relevant standards and this specification.
4.09.08 The Owner may conduct surveillance of the Contractor's facilities for compliance to his standard procedures of Quality Assurance and Quality Control while work on the specified equipment is in progress.
4.09.10 All material for Bus duct like enclosure, flexible etc. shall be procured as per National/International code and shall be free from internal defects. Fully representative test pieces shall be tested for Electrical, Chemical and Mechanical properties.
4.09.11 All welding shall be carried out as per Qualified procedures and welders. The WPS & PGR
shall be as per ASMF and shall be submitted for Owner’s approval. In case of Aluminum welding, the strength of weld/heat affected zone shall not be less than that specified for the particular grade of Aluminum in its annealed condition. Accordingly, the bus duct shall be designed.
4.09.12 The flexible shall be checked for workmanship, electrical conductivity, thickness of coating
etc. 4.09.13 The material for structure shall be of tested quality. The galvanized shall be carried out as
per relevant IS and shall be checked for thickness, uniformity and weight of zinc coating. 4.09.14 Suitable quality assurance program shall be prepared and Submitted to the Purchaser for
approval 4.10.00 Packing for Shipment 4.10.01 The equipment complete with its accessories, spares, special tools and tackles shall be
suitably protected by respective packing for shipment considering handling during transit, distance and weather conditions involved. The Contractor shall submit the packaging method for shipment to be adopted by him, if so desired by the Owner/Purchaser.
4.10.02 Each consignment shall be marked with Equipment name, Owner/Purchaser’s name &
address, Project details, handling instruction etc. It shall be completed with part list and identification details. The copies of the part list of each consignment shall also be furnished to the Owner/Purchaser after dispatch.
Document No.: K8B15-SPC-E-0025_Rev-2 Page 12 of 46 Development Consultants Pvt. Ltd.
JINDAL POWER LIMITED
Specification for 11kV & 3.3kV Segregated Phase Busduct
(SPBD) & Neutral Grounding Resistor (NGR)
O.P. Jindal Super Thermal Power Project (4 x600 MW)
4.10.03 Equipment shall be packaged for transportation so as to meet the space and weight
limitation of transport facilities. The contractor shall obtain approval from concerned authorities for transportation of over dimensioned consignment/package, if any, before starting manufacture of such equipment.
4.10.04 To ensure proper storage of equipment, detailed storage instructions shall be furnished to
the Owner well in advance of dispatch of equipment. 4.11.00 Bid Evaluation 4.11.01 Bus duct losses will be taken into account during bid evaluation. 4.11.02 The loss figures quoted shall be guaranteed without any positive tolerance.
4.11.03 Evaluation of losses and penalties shall be calculated at the rate of Rs.1,97,000/-per KW.
4.11.04 For fraction of a KW, the penalties shall be on pro-rata basis. 5.00.00 Special Tools & Tackle 5.01.00 A set of special tools & tackle which are necessary or convenient for erection,
commissioning, maintenance and overhauling of the equipment shall be supplied. 5.02.00 The tools shall be shipped in separate containers, clearly marked with the name of the
equipment for which they are intended.
6.00.00 Spares 6.01.00 The Bidder shall submit a list of recommended spare parts for three (3) years satisfactory
and trouble-free operation, indicating the itemized price of each item of the spares each for Segregated phase busduct & NGR. The final quantity shall be decided during placement of order.
6.02.00 The Bidder shall quote and supply mandatory spare parts as per the list. The final
quantity shall be decided during placement of order. 6.03.00 Each list shall be complete with specification, make, identification number, unit rate,
quantity etc.
7.00.00 Painting 7.01.00 All surfaces shall be thoroughly cleaned and cleared of all blemishes. Derusting,
degreasing, etc. shall be done before painting or galvanizing. Paints shall be carefully selected to withstand heat and weather conditions. The paints shall not scale off or crinkle or get removed by abrasion due to normal handling.
7.02.00 Except for supporting steel structures, which shall be galvanized, all equipment shall be
finished with an undercoat of high quality primer followed by two coats of synthetic enamel paints unless otherwise epoxy paints as specifically required.
7.03.00 All equipment shall be furnished with an undercoat (50-60 microns) of high quality, primer
followed by two coats of epoxy paints (30-40 microns each). The interior surface finish shall be as per manufacturer’s standard. The shade of exterior surface finish will be RAL 7032.
7.04.00 Sufficient quantities of all paints and preservatives required for touching up at sites shall be
furnished.
Document No.: K8B15-SPC-E-0025_Rev-2 Page 13 of 46 Development Consultants Pvt. Ltd.
JINDAL POWER LIMITED
Specification for 11kV & 3.3kV Segregated Phase Busduct
(SPBD) & Neutral Grounding Resistor (NGR)
O.P. Jindal Super Thermal Power Project (4 x600 MW)
7.05.00 Paints shall be carefully selected to withstand heat and weather conditions. The paint
shall not scale-off or crinkles or gets removed by abrasion due to normal handling. 7.06.00 Surface of all supporting steel structures shall be prepared by pickling and/or blast
cleaning. The cleaned surface shall conform to surface preparation quality grade Clause 4.3 as per IS -1477 (Part-1). The cleaned surface shall be coated by a layer of zinc by hot dipping. Fluxing will be by immersion in an aqueous pre-fluxing bath followed by drying or by addition of molten flux on the molten metal bath or both. The coating thickness shall not be lower than 200 microns.
8.00.00 Name Plate 8.01.00 Suitable nameplate shall be furnished with each piece of equipment. 8.02.00 Materials for nameplate shall be Anodized Aluminum, 3 mm thick, using white letters on
black background. 8.03.00 Nameplate shall be held by self-tapping screws. Nameplate for each NGR cubicle shall
be minimum 40 x 150 mm and shall be located at the top of cubicle both on the front and on the rear.
8.04.00 Complete rating plate, in addition to the name plate shall also be provided both on the front as well as within the cubicle.
8.05.00 Danger plate shall be provided both on the front and on the rear side of the cubicle.
8.06.00 Name plate shall be marked up according to the final designation list. 9.00.00 Test Witness 9.01.00 Tests shall be performed in presence of Owner's representative if so desired by the
Owner. The Contractor shall give at least thirty (30) days' advance notice of the date when the tests are to be carried out.
10.00.00 Test Certificates 10.01.00 All equipment to be supplied shall be of type tested quality. The bidder shall submit for
approval the reports of all the type tests as pe r re levan t IS / IEC and carried out within last five years from the date of bid opening. These reports should be for the test conducted on the equipment similar to those proposed to be supplied under this contract and the test (s) should have been either conducted at an independent laboratory or should have been witnessed by a client.
10.02.00 In case the bidder is not able to submit report of the type test(s) conducted within last
five years from the date of bid opening, or in the case of type test report(s) are not found to be meeting the specification requirements, the bidder shall conduct all such tests under this contract free of charge to p rove the des ign and submit the reports for approval.
10.03.00 All acceptance and routine tests as per the specification and relevant standards shall
be carried out. Charges for these shall be deemed to be included in the equipment price.
Document No.: K8B15-SPC-E-0025_Rev-2 Page 14 of 46 Development Consultants Pvt. Ltd.
JINDAL POWER LIMITED
Specification for 11kV & 3.3kV Segregated Phase Busduct
(SPBD) & Neutral Grounding Resistor (NGR)
O.P. Jindal Super Thermal Power Project (4 x600 MW)
PART-II
TECHNICAL SPECIFICATION FOR
11KV & 3.3KV SEGREGATED PHASE BUSDUCT (SPBD)
Document No.: K8B15-SPC-E-0025_Rev-2 Page 15 of 46 Development Consultants Pvt. Ltd.
JINDAL POWER LIMITED
Specification for 11kV & 3.3kV Segregated Phase Busduct
(SPBD) & Neutral Grounding Resistor (NGR)
O.P. Jindal Super Thermal Power Project (4 x600 MW)
PART- II
TECHNICAL SPECIFICATION
FOR 11KV & 3.3KV SEGREGATED PHASE BUSDUCT (SPBD)
1.00.00 DESIGN CRITERIA 1.01.00 The 11000V and 3300V phase segregated bus ducts (SPBD) will serve as
interconnection between outdoor transformers & indoor switchgears and also between station to station switchgear and between unit to station Switchgear. Busduct shall be installed partially indoor and partially outdoor and 11000V & 3300V segregated phase busduct interconnecting between switchgears will be installed indoor.
1.02.00 The bus ducts shall be installed in a hot, humid and tropical atmosphere. The selection
and sizing shall take due consideration of the effects. 1.03.00 Bus duct and its associated equipments shall be provided with tropical finish to prevent
fungus growth. All ventilation openings shall be screened and drains shall be filtered to prevent entrance of dust and insects.
1.04.00 The portion of bus duct at the transformer end shall be subject to vibration normally
prevalent for this type of installation in a power generating station. Suitable means shall be provided to isolate the transformer vibration from rest of the bus structure/ bus duct.
1.05.00 The busduct shall be designed for continuous current rating as specified in Annexure-
A. 1.06.00 For continuous operation at specified ratings, temperature rise of the busduct and
auxiliary equipment shall be limited to the site permissible values stipulated in relevant standards and/or this specification.
1.07.00 Busduct and auxiliary equipment shall be capable of withstanding the mechanical
forces and thermal stresses of the short circuit current as listed in the Annexure-A without any damage or deterioration of material. Bus conductor support insulator span shall be chosen considering minimum safety factor of 2.5 for cantilever strength under short circuit condition.
1.08.00 The bus ducts and supporting structures shall be designed & constructed so as to
withstand without damage the horizontal/ vertical ground accelerations due to earthquake.
1.09.00 The bus ducts shall be self cooled without any forced ventilation.
1.10.00 The equipment rating shall be based on an ambient temperature of 50°C. For the portion of the bus-duct installed outdoor and exposed to direct sun-rays, the effect of solar heat shall be considered in the determination of the design ambient temperature.
1.11.00 The contractor shall design the busduct and supporting structure in such a way as to permit transformers removal, after opening the terminations but without dismantling busduct run or supporting structure. The outdoor section shall withstand the wind loading of 150 Kg/Sq. mm.
1.12.00 The relevant drawing of switchgear and transformer terminal flange connections shall be
supplied to successful bidder after award of contract. Bidder shall take all necessary matching flange, adaptor box, bolts, nuts, washers, other hardware for connecting the busduct to switchboard and transformer.
Document No.: K8B15-SPC-E-0025_Rev-2 Page 16 of 46 Development Consultants Pvt. Ltd.
JINDAL POWER LIMITED
Specification for 11kV & 3.3kV Segregated Phase Busduct
(SPBD) & Neutral Grounding Resistor (NGR)
O.P. Jindal Super Thermal Power Project (4 x600 MW)
2.00.00 SPECIFIC REQUIREMENTS 2.01.00 General 2.01.01 The 11000V and 3300V bus ducts shall be segregated phase (three phase) natural air
cooled enclosure type. 2.01.02 All parts and accessories shall have appropriate match mark and part numbers for easy
identification and installation at site. 2.01.03 The layout of the bus ducts shall be generally in accordance with enclosed drawings. The
details shown however are only typical. Bidder may propose changes to suit his particular design.
2.02.00 Enclosures 2.02.01 The three (3) phases shall be enclosed in a weather-proof, dust-tight, phase
segregated type with non-magnetic metal (Al. alloy of minimum 3 mm thickness), preferably rectangular in shape, phase barrier (welded to the enclosure, as specified in the Annexure-A. Busduct shall be adequately rigid with stiffeners as required complying to enclosure protection specified in the datasheet. Busduct shall also meet the requirements for water tightness test and air leakage test.
2.02.02 All horizontal runs of the busduct shall have a suitably sloped enclosure top to prevent
accumulation of water. 2.02.03 The shape of the busduct enclosure shall be rectangular. Circumferential neoprene
rubber gaskets (joint less type) shall be provided for dust tight joints with adjacent enclosure sections. Bus-duct enclosure shall have a degree of protection of IP-55 for indoor part & IP-55 for outdoor part. All gasketed flanged joints shall be suitably protected against direct splashing of rain water in case of outdoor runs.
2.02.04 The bus enclosure shall have expansion bellows or equivalent means to allow for
temperature changes and vibrations. Flexible joints shall be provided in enclosures at all points where the bus duct terminates at equipment to withstand vibration, expansion/contraction and at suitable intervals in any straight run of the bus duct where expansion and contraction would otherwise result in stresses in the supporting structures. Number of such expansion bellows considered with technical features shall be indicated in the offer.
2.02.05 All outdoor bus-enclosures shall be so designed & constructed as to prevent
accumulation of rain water on top sheet. Similarly all gasketed-flanged joints shall be suitably protected against direct splashing of rainwater in case of outdoor runs.
2.02.06 Suitable inspection openings shall be provided for access to support insulators, bus joints, transformer terminals, switch gear terminals, etc. at the bottom part of busduct. All inspection openings shall have reliable sealing arrangement with neoprene gaskets.
2.02.07 Epoxy resin cast seal-off bushings complete with wall-frame and support plates shall be
provided where the bus duct run from indoor to outdoor penetrating the building wall. Seal off bushings shall also be provided at each switchgear termination. Where busduct crosses internal wall of the building, wall frame assembly shall be provided. The details of wall frame assembly with seal off bushing shall be furnished in the offer.
Document No.: K8B15-SPC-E-0025_Rev-2 Page 17 of 46 Development Consultants Pvt. Ltd.
JINDAL POWER LIMITED
Specification for 11kV & 3.3kV Segregated Phase Busduct
(SPBD) & Neutral Grounding Resistor (NGR)
O.P. Jindal Super Thermal Power Project (4 x600 MW)
2.02.08 Silica-gel breather shall be provided on both indoor and outdoor portions of the bus
duct. Details/numbers and location of silica gel breather considered in the proposal shall be furnished in the offer.
2.02.09 Filtered drains for drainage of condensate shall be provided at the lowest points, where
accumulation of condensate can be expected. 2.02.10 Shipping length of the bus duct shall be not more than three (3) meters in length. Each
shipping section shall have at least two (2) supports both for conductor in each phase and enclosure.
2.02.11 Suitable blanked flanges with cover shall be provided on the enclosure of the busduct
(indoor and outdoor) to allow connection of hot air duct of hot air blowing necessary to improve insulation level after long shut down etc.
2.03.00 Bus Conductor 2.03.01 The bus conductor shall be of high conductivity, aluminium alloy, supported on wet
processed insulators designed to withstand dynamic stress due to the specified short circuit current and other forces expected such as seismic forces.
2.03.02 The bus conductor shall be designed for bolted connections throughout the run (high
grade stainless steel nuts bolts plain and belle-ville washers). 2.03.03 Aluminum Flexible connections shall be provided minimum at 10 meters interval
between bus sections to allow for expansion and contraction of the conductor. Flexible connection shall also be provided at all equipment terminations (transformer end and switchgear end). Details of transformer bushing and switchgear terminal shall be intimated to successful bidder during detailed engineering. Clearances provided by removable connections shall be adequate for independently testing the equipment being connected by these. The bidder shall detail out the type of flexible conductor proposed (braids or multiple lamination) with complete specification.
2.03.04 All contact surfaces shall be silver plated to ensure an efficient and trouble-free
connection. All connection hardware shall be non-magnetic and shall have high corrosion resistance. The details of hardware considered shall be furnished in the offer and the same is subjected to purchaser’s approval during detail engineering. At all silver plated joints suitable jointing compound shall be used to prevent galvanic corrosion and detoriation of joint. The Busbar sizing calculation shall be submitted to the purchaser along with the drawings and documentation for approval. All derating factors applicable shall be taken into consideration. A design margin of 10% shall be maintained.
Bimetallic connectors of approved make shall be used for connections where bus conductor material is different.
2.03.05 All bolted joints shall be provided with high grade stainless steel nuts bolts plain & belle-
ville washers.
Document No.: K8B15-SPC-E-0025_Rev-2 Page 18 of 46 Development Consultants Pvt. Ltd.
JINDAL POWER LIMITED
Specification for 11kV & 3.3kV Segregated Phase Busduct
(SPBD) & Neutral Grounding Resistor (NGR)
O.P. Jindal Super Thermal Power Project (4 x600 MW)
2.04.00 Insulators 2.04.01 Bus support insulators shall be interchangeable, very high creep, high strength, wet
processed, fine glazed porcelain type or cast resin type. The creep age distance shall be considered as minimum 25 mm/kV.
2.04.02 Insulator shall be designed to avoid any stresses due to expansion and contraction and
stress concentration due to direct engagement of the porcelain with the metal fittings. All ferrous metal part of insulator shall be hot dipped galvanized.
2.04.03 Insulator shall be mounted in such a way so as to permit easy inspection, removal or replacement without disassembly of the bus. The insulator mounting plate shall be designed for cantilever loading to withstand the short circuit force.
2.04.04 The conductor shall be fastened on the insulator through fixed and slip joints so as to
allow conductor expansion or contraction without straining the insulator. The span and number of insulators required shall be decided based on the expected dynamic forces due to short circuit and other forces, the same shall be supported with calculations. Additional support insulators shall be provided at bend, tap offs.
2.04.05 All the insulators type shall be approved by reputed testing authority and shall be routine tested as per relevant IS. Type test certificate not conducted later than five years shall be submitted for approval, failing which the bidder shall take up the type tests at no extra cost to purchaser.
2.04.06 The insulator shall be designed for high resistance ground system. 2.05.07 The space heater shall be provided preferably located near to each insulator to avoid
moisture condensation within busduct. Number and wattage rating of space heater shall be decided by contractor.
2.05.00 Bus Disconnecting Links 2.05.01 Removable bolted type disconnect links shall be provided in the bus as required for the
purpose of isolation. 2.05.02 Disconnect links shall consist of a removable section of conductor and shall be
constructed to permit easy removal or reinsertion without alignment difficulties. 2.05.03 The bus on both sides of the link shall be rigidly supported so that the disconnect link is
equal in mechanical strength to any other section of the bus. 2.05.04 A minimum clearance of 300 millimeters shall be provided between the disconnected bus
sections with the link removed.
2.06.00 Connections & Terminations 2.06.01 All matching flanges, seal-off bushings, gaskets, fittings, hardware and supports along
with the segregated phase adaptor box required for termination of the bus duct at the switchgears and transformers shall be furnished.
Document No.: K8B15-SPC-E-0025_Rev-2 Page 19 of 46 Development Consultants Pvt. Ltd.
JINDAL POWER LIMITED
Specification for 11kV & 3.3kV Segregated Phase Busduct
(SPBD) & Neutral Grounding Resistor (NGR)
O.P. Jindal Super Thermal Power Project (4 x600 MW)
2.06.02 The connection details at transformer end & switchgear end will be furnished to the
successful bidder during detail engineering. The successful Bidder is required to co-ordinate through the Owner with the suppliers of the Unit / Station transformers, 11kV & 3.3kV switchgears and 11/3.45kV HT auxiliary transformers with regard to connection details, mechanical and thermal stresses.
2.06.03 Flexible connection both for conductor and enclosure shall be furnished:
a) At all equipment termination to provide for misalignment up to 25 mm. (1") in all directions.
b) Between the bus duct portions supported from building steel to prevent transmission
of vibration. The equipment terminal connections shall be readily accessible and shall provide sufficient air gap for safe isolation of equipment during testing.
2.06.05 If the material of bus conductor and that of the equipment terminal connectors are
different then suitable bi-metallic connectors shall be furnished. 2.07.00 Grounding 2.07.01 A separately run 75x12 mm hot dipped Galvanized Steel flat suitably clamped along
the enclosure shall be used as the ground bus. All parts of the bus enclosure, supporting structures and equipment frames shall be bonded to above ground bus.
2.07.02 Ground pad shall be bolted type to accommodate 50x6 mm. Galvanized steel flats at
two points at each end of termination. Complete with suitable tapped holes, bolts and washers.
2.08.00 Supporting Structures 2.08.01 All supporting structures required for hanging and/or supporting the complete bus duct
shall be furnished. These include all members, indoor/outdoor posts, bolts, shims, base plates, beams, hangers, brackets, bracings and hardware.
2.08.02 All buses shall be adequately supported and braced to successfully withstand normal
operation, vibration, thermal expansion, short circuit forces and all specified design loads including that of seismic forces.
2.08.03 Support shall be designed to provide tolerance of ± 12 mm. (1/2") in the horizontal and
vertical directions. 2.08.04 All hardware shall be of high strength steel with weather resistant finish. Suitable
structures will also be needed to fabricate locally as per site requirement. All steel members shall be hot-dip galvanized after fabrication.
2.08.05 In the indoor portion, busduct shall be supported from roof/floor beam or steel insert in
concrete slab as hanger supports, while in outdoor portion busduct shall be supported by means of steel structures on ground.
2.08.06 Concrete foundation, building steel, concrete, and inserts/plates will be provided by
Owner. The Contractor shall co-ordinate with the Owner for this purpose giving well in advance the details of his requirements so as to enable the Owner to arrange for the same in time.
Document No.: K8B15-SPC-E-0025_Rev-2 Page 20 of 46 Development Consultants Pvt. Ltd.
JINDAL POWER LIMITED
Specification for 11kV & 3.3kV Segregated Phase Busduct
(SPBD) & Neutral Grounding Resistor (NGR)
O.P. Jindal Super Thermal Power Project (4 x600 MW)
2.08.07 The support details including number of spans shall be furnished in the offer, and the
same shall be furnished during drawing approval with supporting calculation. 2.09.00 Wiring 2.09.01 Terminal box shall be box-clamp type ELMEX 10 sqmm with marking strips or
approved equal for control and power cable and CATD type for CT’s. 2.09.02 Not more than two (2) wires shall be connected to one terminal. At least 20% spare
terminals shall be furnished in the terminal block. 2.09.03 All wiring for space heaters shall be done with insulated stranded copper conductor of
not less than 2.5 sqmm cross section. Each wire shall be identified at both ends with designation as per contractors wiring diagram and shall be brought out to a terminal box outside the bus duct.
2.10.00 Space Heater
Thermostat controlled space heaters shall be provided inside the bus duct enclosure to prevent moisture condensation. The space heater shall be controlled by an adjustable thermostat, set to close at 30° C (ON) and open at 35° C (OFF). For space heater galvanized conduit shall be provided along with necessary J.B. For space heater connection FRLSH PVC 2.5 sqmm/4 sqmm cable to be provided.
2.11.00 Portable Hot Air Blowing Equipment 2.11.01 Portable hot air blowing equipment mounted on a steel carriage (trolley) for easy
movement shall be provided. Hot air blowing system shall be complete with blower, fan, electric heater, starter, MCCB’s, main incoming MCCB’s with flexible cables and plugs etc. for connection to power receptacle.
2.11.02 The capacity of Hot Air Blowing system shall be such that dry out of complete bus duct is
possible within four (4) hours. During hot air blowing the bus duct enclosure temperature shall not exceed 70°C.
3.00.00 TESTS 3.01.00 Routine Test Bus Duct shall be subjected to the following tests: a) Visual inspection and verification of dimensions. b) Dry power frequency voltage withstand for 1-minute. c) Milli-volt drop test. d) Water tightness test. e) Dust tightness test. 3.02.00 Type Test The following type tests shall be performed on a representative section of segregated
phase bus duct, otherwise following type test certificates of similar equipment shall be submitted by the Bidder:
Document No.: K8B15-SPC-E-0025_Rev-2 Page 21 of 46 Development Consultants Pvt. Ltd.
JINDAL POWER LIMITED
Specification for 11kV & 3.3kV Segregated Phase Busduct
(SPBD) & Neutral Grounding Resistor (NGR)
O.P. Jindal Super Thermal Power Project (4 x600 MW)
a) Impulse test
b) Temperature rise test on representative section of three phase bus duct with at least one straight run, one bend and one flexible joint. The millivolt drop of the joints shall be measured before and after temperature rise test.
c) Degree of Protection: Air leakage and Water tightness test
d) Short circuit mechanical strength and thermal withstand test on representative section. The section selected shall have longest span between support insulators.
3.03.00 Auxiliary Equipment
a) All component parts and auxiliary equipment such as space heater, insulator etc. shall be routine tested as per relevant Indian Standards.
b) All cubicles shall be completely wired up at the factory and subject to wiring check
and power frequencies withstand tests on control/secondary wiring. 3.04.00 Site Tests The bus duct shall be erected as per good engineering practice and all checks/tests
necessary to ensure receipt of correct material component, proper storage of material/component, correctness of erection as per drawing/specification including check/tests on welds as done at ship shall be carried out. Further the assembled bus duct shall be tested for following but not limited to the same.
a) Functional and performance test of various auxiliary panels etc. b) Milli-volt drop test of bolted joints. c) Insulation Resistance & High Voltage Test of busduct and it's auxiliaries. d) Temperature rise measurement as performance test of bus duct. 4.00.00 DRAWINGS, DATA & MANUALS 4.01.00 Drawings, Data & Manuals shall submitted in number of copies as specified elsewhere
in the document with the bid and in quantities and procedures as specified in General Conditions of contract and/or elsewhere in the specification for approval & subsequent distribution after the issue of Letter of Intent.
4.02.00 To be Submitted with the Bid 4.02.01 General Arrangement Drawing – Plan and Sections. 4.02.02 Typical details of space heater cubicle, bus-insulator assembly, conductor/enclosure
connections rigid & flexible, seal-off bushings, connection with transformer & switchgear terminals, etc.
4.02.03 Bill of Materials. 4.02.04 Technical leaflets/Write-ups on various pieces of equipment offered. 4.02.05 Calculation for temperature rise for bus and enclosure as per IEEE No. 298.
Document No.: K8B15-SPC-E-0025_Rev-2 Page 22 of 46 Development Consultants Pvt. Ltd.
JINDAL POWER LIMITED
Specification for 11kV & 3.3kV Segregated Phase Busduct
(SPBD) & Neutral Grounding Resistor (NGR)
O.P. Jindal Super Thermal Power Project (4 x600 MW)
4.02.06 Calculation for short circuit forces justifying the proposed arrangement.
4.02.07 Calculations with supporting technical data for
- Conductor size - Guaranteed KW losses in conductor and enclosure
4.02.08 Calculation for selection of the support details including number of spans. 4.02.09 GA of hot air blowing system 4.02.10 Type test reports of similar equipment. The type test certificates shall not be more than
5 years old. In case Type test certificates as per I.S. or I.E.C. of identical equipment of the offered items are not submitted, the bidders shall have to conduct the Type test on the offered equipment before delivery free of charge to the Owner or Bidder’s testing charges are to be mentioned in the offer.
4.03.00 To be Submitted for Approval and Distribution 4.03.01 Guaranteed Technical Particulars (A) and Quality assurance plan (R) 4.03.02 Dimensional general arrangement drawings with cross-sections of Bus Duct layout. (A) 4.03.03 Detailed material list with parts number. (A) 4.03.04 Typical details of bus-insulator assembly, rigid and flexible connections of both bus
conductor and enclosure, grounding provision, seal-off bushings, wall frame assembly, equipment termination arrangement, etc. (A)
4.03.05 Foundation Plan and loading. (A) 4.03.06 Supporting steel structure and calculations. (A) 4.03.07 Dimensional General Arrangement Drawing of supporting structure– Plan and
Sections. (A) 4.03.08 Calculations with supporting technical data for (A)
- Conductor size - Guaranteed KW losses in conductor and enclosure
- Bus bar sizing calculation 4.03.09 Calculation for selection of the support details including number of spans. (A) 4.03.10 Test reports on representative section of bus duct. (A) 4.03.11 Instruction manual for Bus Duct and associated equipment. (R) The manual shall clearly indicate the installation methods, check-ups and tests to be
carried out before commissioning of the equipment. 4.03.12 All drawings shall be prepared by using AutoCAD and documents shall be generated
using Electronic version. The paper copy of the drawings & document shall be submitted for approval & reference. All final drawings and documents shall be submitted in CD in AutoCAD 2006 and MS office format as applicable for Owner’s future reference. (R)
Document No.: K8B15-SPC-E-0025_Rev-2 Page 23 of 46 Development Consultants Pvt. Ltd.
JINDAL POWER LIMITED
Specification for 11kV & 3.3kV Segregated Phase Busduct
(SPBD) & Neutral Grounding Resistor (NGR)
O.P. Jindal Super Thermal Power Project (4 x600 MW)
4.03.13 Quality Assurance plan (A) 4.04.00 The Owner reserves the right to interact with the vendor to get removed any
discrepancy/shortcoming which may come to notice from the above documents mentioned under clause no. 4.03.00. Irrespective of such interaction, the responsibility for correctness and completeness of these documents in conformity with the requirements of the specification and/or relevant standard shall be solely with the vendor.
4.05.00 The Bidder may note that the drawings, data and manuals listed herein are minimum
requirements only. The Bidder shall ensure that all other necessary write-ups, curves and information required to fully describe the equipment are submitted with his bid.
Document No.: K8B15-SPC-E-0025_Rev-2 Page 24 of 46 Development Consultants Pvt. Ltd.
JINDAL POWER LIMITED
Specification for 11kV & 3.3kV Segregated Phase Busduct
(SPBD) & Neutral Grounding Resistor (NGR)
O.P. Jindal Super Thermal Power Project (4 x600 MW)
ANNEXURE-A
RATINGS & REQUIREMENTS
1.0 DESCRIPTION 11000 V SYSTEM 3300 V SYSTEM 1.1 System nominal voltage : 11000 V 3300 V 1.2 System maximum voltage : 12000 V 3600 V 1.3 Number of phases : 3 1.4 Frequency : 50Hz
1.5 Neutral Grounding : Non-effectively grounded through
resistance to limit earth fault current to 300A for 10 seconds.
1.6 Insulation level a. 1-min. power frequency withstand : 28 kVrms 10 kVrms
b. Impulse withstand : 75 kVpeak 40 KVpeak
c. Creepage distance : 25 mm/kV 1.7 Short Circuit Level
Breaking capacity (symmetrical kArms for 3 sec.)
: 40KA 40KA
Making capacity (momentary kApeak) : 100 1.8 Reference Standard : IS:8084 2.0 BUS DUCT 2.1 a)Type : Phase segregated self cooled
b) Cooling System Natural 2.2 Service : Indoor/Outdoor 2.3 Rated Continuous Current in Amp : 1250A/2000A /2500A/ 3000A
2.4 Rated hottest-spot temperature rise (Over 50oC ambient)
a. Bus conductor i. Plain joint : 35 deg C ii. Silver plated joints : 55 deg C b. Bus enclosure & structure : 20 deg C
c. Final temperature of Bus bar after short Circuit
200 Deg. C
2.5 Material
a. Bus conductor : Aluminium Alloy grade 63401 (WP type), 55% IACS
b. Bus enclosure : Aluminium Alloy grade 19501, 60% IACS (min 3 mm thick)
c Inter-phase barrier : Aluminium alloy (min 3 mm thick)
2.6 Enclosure Protection Class : IP-55 for Indoor Installation IPW-55 for Outdoor Installation
2.7 Service Voltage a) Hot air blowing equipment : 415 V ± 10%, 3ph, 50 Hz, ± 5% 4 wire.
2.8 Material a) Bus conductor : Aluminum alloy grade 63401
Document No.: K8B15-SPC-E-0025_Rev-2 Page 25 of 46 Development Consultants Pvt. Ltd.
JINDAL POWER LIMITED
Specification for 11kV & 3.3kV Segregated Phase Busduct
(SPBD) & Neutral Grounding Resistor (NGR)
O.P. Jindal Super Thermal Power Project (4 x600 MW)
.
DESCRIPTION 11000 V SYSTEM 3300 V SYSTEM
b) Bus enclosure : Aluminum alloy (Grade 19501) c) Bus enclosure material thickness : 3 mm (minimum)
d) Phase Barrier : 3 mm thick Aluminum welded e) Porcelain Insulator : 12kV 3.6kV
2.9 Conductivity Conductor
: 55% IACS (IACS: International Annealed copper Standard)
Document No.: K8B15-SPC-E-0025_Rev-2 Page 26 of 46 Development Consultants Pvt. Ltd.
JINDAL POWER LIMITED
Specification for 11kV & 3.3kV Segregated Phase Busduct
(SPBD) & Neutral Grounding Resistor (NGR)
O.P. Jindal Super Thermal Power Project (4 x600 MW)
ANNEXURE-B
BILL OF MATERIALS
Bill of quantity mentioned below for 11kV & 3.3kV busduct is estimated and for bidding purpose only. Exact bill of quantity for 11kV & 3.3kV Busduct and other equipment and accessories shall be finalized by the successful bidder based on approved layout drawing of Transformer Yard and relevant HT Switchgear drawings. Variation in quantity shall be taken into account by applying the unit rates offered by the Bidder under price breakdown sheet, for final adjustment of contract price.
11KV PHASE SEGREGATED BUSDUCT
SL. N
o.
B
usdu
ct
Iden
tific
atio
n
Bus
duct
Rat
ing
Am
p)
Term
inal
con
nect
or –
Tr
ansf
orm
er e
nd
incl
udin
g fle
xibl
e co
nnec
tor
Term
inal
con
nect
or –
Sw
itchg
ear e
nd
incl
udin
g fle
xibl
e co
nnec
tor
Stra
ight
run
(m) –
le
ngth
alo
ng th
e ce
nter
line
of t
he b
us
duct
Hor
izon
tal b
end
Vert
ical
ben
d
Wal
l fra
me
asse
mbl
y co
mpl
ete
with
m
ount
ing
plat
e se
al
off b
ushi
ng &
flex
ible
li
kPh
ase
chan
ge o
ver
box
Flex
ible
join
ts fo
r st
raig
ht ru
n
B. D No. As per Key SLD
set set meter set set set set set
1 BD 101 1UT11SR1 2000 1 1 120 3 2 1 1 Lot 2 BD 102 1UT21SR2 2000 1 1 120 3 2 1 1 Lot 3 BD 103 2UT12SR1 2000 1 1 75 3 2 1 1 Lot 4 BD 104 2UT22SR2 2000 1 1 60 3 2 1 1 Lot 5 BD 105 3UT13SR1 2000 1 1 120 3 2 1 1 Lot 6 BD 106 3UT23SR2 2000 1 1 120 3 2 1 1 Lot 7 BD 107 4UT14SR1 2000 1 1 55 3 2 1 1 Lot 8 BD 108 4UT24SR2 2000 1 1 70 3 2 1 1 Lot 9 BD 109 1SR10SR1 2000 - 2 10 --- 2 --- 1 Lot
10 BD 110 1SR20SR2 2000 - 2 10 --- 2 --- 1 Lot 11 BD 111 2SR10SR3 2000 - 2 10 3 2 1 1 Lot 12 BD 112 2SR20SR4 2000 - 2 10 3 2 1 1 Lot 13 BD 113 3SR10SR5 2000 - 2 10 3 2 1 1 Lot 14 BD 114 3SR20SR6 2000 - 2 10 3 2 1 1 Lot 15 BD 115 4SR10SR7 2000 - 2 10 3 2 1 1 Lot 16 BD116 4SR20SR8 2000 - 2 10 3 2 1 1 Lot 17 BD 117 1ST10SR1 3000 1 1 85 3 4 1 1 Lot 18 BD 118 1ST20SR2 3000 1 1 85 3 4 1 1 Lot 19 BD 119 2ST10SR3 3000 1 1 60 3 4 1 1 Lot 20 BD 120 2ST20SR4 3000 1 1 60 3 4 1 1 Lot 21 BD 121 3ST10SR5 3000 1 1 85 3 4 1 1 Lot 22 BD 122 3ST20SR6 3000 1 1 85 3 4 1 1 Lot 23 BD 123 0SR10SR5 3000 - 2 310 6 8 2 1 Lot 24 BD 124 0SR10SR3 3000 - 2 45 --- 2 ---- 1 Lot
Document No.: K8B15-SPC-E-0025_Rev-2 Page 27 of 46 Development Consultants Pvt. Ltd.
JINDAL POWER LIMITED
Specification for 11kV & 3.3kV Segregated Phase Busduct
(SPBD) & Neutral Grounding Resistor (NGR)
O.P. Jindal Super Thermal Power Project (4 x600 MW)
SL. N
o.
B
usdu
ct
Iden
tific
atio
n
Bus
duct
Rat
ing
Am
p)
Term
inal
con
nect
or –
Tr
ansf
orm
er e
nd
incl
udin
g fle
xibl
e co
nnec
tor
Term
inal
con
nect
or –
Sw
itchg
ear e
nd
incl
udin
g fle
xibl
e co
nnec
tor
Stra
ight
run
(m) –
le
ngth
alo
ng th
e ce
nter
line
of t
he b
us
duct
Hor
izon
tal b
end
Vert
ical
ben
d
Wal
l fra
me
asse
mbl
y co
mpl
ete
with
m
ount
ing
plat
e se
al
off b
ushi
ng &
flex
ible
li
kPh
ase
chan
ge o
ver
box
Flex
ible
join
ts fo
r st
raig
ht ru
n
B. D No. As per Key SLD
set set meter set set set set set
25 BD 125 0SR20SR4 3000 - 2 15 ---- 2 ---- 1 Lot 26 BD 126 0SR20SR6 3000 - 2 375 4 14 2 1 Lot 27 BD 129 0SR30SR7 3000 - 2 390 8 14 2 1 Lot 28 BD 130 0SR40SR8 3000 - 2 390 8 14 2 1 Lot 29 BD 131 0SR50SR7 3000 - 2 50 --- 2 2 1 Lot 30 BD 132 0SR60SR8 3000 - 2 40 --- 2 2 1 Lot 31 BD 127 RWT1SR01 2000 1 1 20 --- 2 1 1 Lot
32 BD 128 RWT2SR01 2000 1 1 20 --- 2 1 1 Lot
BILL OF MATERIALS FOR 3.3KV PHASE SEGREGATED BUSDUCT
SL. N
o.
B
usdu
ct
Iden
tific
atio
n
Bus
duct
Rat
ing
Am
p)
Term
inal
con
nect
or –
Tr
ansf
orm
er e
nd
incl
udin
g fle
xibl
e co
nnec
tor
Term
inal
con
nect
or –
Sw
itchg
ear e
nd
incl
udin
g fle
xibl
e co
nnec
tor
Stra
ight
run
(m) –
le
ngth
alo
ng th
e ce
nter
line
of t
he b
us
duct
Hor
izon
tal b
end
Vert
ical
ben
d
Wal
l fra
me
asse
mbl
y co
mpl
ete
with
m
ount
ing
plat
e se
al
off b
ushi
ng &
flex
ible
Ph
ase
chan
ge o
ver
box
Flex
ible
join
ts fo
r st
raig
ht ru
n B. D No. As per Key
SLD set set meter set set set set set
1 BD 201 1KUAT1-1MSR1 3000 1 1 105 2 4 1 1 Lot
2 BD 202 1KUAT2-1MSR2 3000 1 1 90 2 4 1 1 Lot
3 BD 203 2KUAT1-2MSR1 3000 1 1 105 2 4 1 1 Lot
4 BD 204 2KUAT2-2MSR2 3000 1 1 90 2 4 1 1 Lot
5 BD 205 3KUAT1-3MSR1 3000 1 1 105 2 4 1 1 Lot
6 BD 206 3KUAT2-3MSR2 3000 1 1 90 2 4 1 1 Lot
7 BD 207 4KUAT1-4MSR1 3000 1 1 105 2 4 1 1 Lot
8 BD 208 4KUAT2-4MSR2 3000 1 1 90 2 4 1 1 Lot
Document No.: K8B15-SPC-E-0025_Rev-2 Page 28 of 46 Development Consultants Pvt. Ltd.
JINDAL POWER LIMITED
Specification for 11kV & 3.3kV Segregated Phase Busduct
(SPBD) & Neutral Grounding Resistor (NGR)
O.P. Jindal Super Thermal Power Project (4 x600 MW)
SL. N
o.
B
usdu
ct
Iden
tific
atio
n
Bus
duct
Rat
ing
Am
p)
Term
inal
con
nect
or –
Tr
ansf
orm
er e
nd
incl
udin
g fle
xibl
e co
nnec
tor
Term
inal
con
nect
or –
Sw
itchg
ear e
nd
incl
udin
g fle
xibl
e co
nnec
tor
Stra
ight
run
(m) –
le
ngth
alo
ng th
e ce
nter
line
of t
he b
us
duct
Hor
izon
tal b
end
Vert
ical
ben
d
Wal
l fra
me
asse
mbl
y co
mpl
ete
with
m
ount
ing
plat
e se
al
off b
ushi
ng &
flex
ible
Ph
ase
chan
ge o
ver
box
Flex
ible
join
ts fo
r st
raig
ht ru
n
B. D No. As per Key SLD
set set meter set set set set set
9 BD 209 0KSAT1-0MSR1 1250 1 1 80 4 4 1 1 Lot
10 BD 210 0KSAT2-0MSR2 1250 1 1 80 4 4 1 1 Lot
11 BD 211 0KSAT3-0MSR3 1250 1 1 80 4 4 1 1 Lot
12 BD 212 0KSAT4-0MSR4 1250 1 1 80 4 4 1 1 Lot
13 BD 213 0KCHHT1-0MCHSR1 2500 1 1 20 2 2 1 1 Lot
14 BD 214 0KCHHT2-0MCHSR2 2500 1 1 20 2 2 1 1 Lot
15 BD 215 0KAFHT1-0MAFSR1 1250 1 1 20 2 2 1 1 Lot
16 BD 216 0KAFHT2-0MAFSR1 1250 1 1 20 2 2 1 1 Lot
17 BD 217 0GARHT1-0MARSR1 1250 1 1 20 2 2 1 1 Lot
18 BD 218 0GARHT2-0MARSR1 1250 1 1 20 2 2 1 1 Lot
19 BD 219 0KAWHT1-0MAWSR1 1250 1 1 20 2 2 1 1 Lot
20 BD 220 0KAWHT2-0MAWSR1 1250 1 1 20 2 2 1 1 Lot
21 BD 221 0KADHT1-0MADSR1 1250 1 1 20 2 2 1 1 Lot
22 BD 222 0KADHT2-0MADSR1 1250 1 1 20 2 2 1 1 Lot
23 BD 223 0GRTHT1-0MRTSR1 1250 1 1 15 2 2 1 1 Lot
24 BD 224 0GRTHT2-0MRTSR1 1250 1 1 15 2 2 1 1 Lot
25 BD 225 1MSR1 -1MSR2 3000 - 2 10 --- 2 --- 1 Lot
26 BD 226 2MSR1-2MSR2 3000 - 2 10 --- 2 --- 1 Lot
27 BD 227 3MSR1-3MSR2 3000 - 2 10 --- 2 --- 1 Lot
28 BD 228 4MSR1- 3000 - 2 10 --- 2 --- 1 Lot
Document No.: K8B15-SPC-E-0025_Rev-2 Page 29 of 46 Development Consultants Pvt. Ltd.
JINDAL POWER LIMITED
Specification for 11kV & 3.3kV Segregated Phase Busduct
(SPBD) & Neutral Grounding Resistor (NGR)
O.P. Jindal Super Thermal Power Project (4 x600 MW)
SL. N
o.
B
usdu
ct
Iden
tific
atio
n
Bus
duct
Rat
ing
Am
p)
Term
inal
con
nect
or –
Tr
ansf
orm
er e
nd
incl
udin
g fle
xibl
e co
nnec
tor
Term
inal
con
nect
or –
Sw
itchg
ear e
nd
incl
udin
g fle
xibl
e co
nnec
tor
Stra
ight
run
(m) –
le
ngth
alo
ng th
e ce
nter
line
of t
he b
us
duct
Hor
izon
tal b
end
Vert
ical
ben
d
Wal
l fra
me
asse
mbl
y co
mpl
ete
with
m
ount
ing
plat
e se
al
off b
ushi
ng &
flex
ible
Ph
ase
chan
ge o
ver
box
Flex
ible
join
ts fo
r st
raig
ht ru
n
B. D No. As per Key SLD
set set meter set set set set set
4MSR2
29 BD 229 0MSR1-0MSR2 1250 --- 2 10 --- 2 --- 1 Lot
30 BD 230 0MSR3-0MSR4 1250 --- 2 10 --- 2 --- 1 Lot
31 BD 232 0MCHSR1-0MCHSR2 2000 --- 2 15 --- 2 --- 1 Lot
Document No.: K8B15-SPC-E-0025_Rev-2 Page 30 of 46 Development Consultants Pvt. Ltd.
JINDAL POWER LIMITED
Specification for 11kV & 3.3kV Segregated Phase Busduct
(SPBD) & Neutral Grounding Resistor (NGR)
O.P. Jindal Super Thermal Power Project (4 x600 MW)
ANNEXURE–C
MAKE OF BOUGHT OUT ITEMS.
The make of all components shall be subject to purchaser’s approval during drawing approval. The bidder shall take appropriate considerations for the same. The bidder to ensure the vendors meet the minimum qualifying criteria specified elsewhere in the tender document. Sl. No. Description of Item Preferred ‘Makes’ 1 Electrolytic grade Aluminium Hindalco, Sterlite 2 Bus support insulator BHEL,Birla NGK, Modern Insulators 3 Seal off bushing Baroda Bushing 4 Flexible bellow * 5 Flexible conductor * 6 Gaskets *
* Vendor to take the prior permission of JPL
Document No.: K8B15-SPC-E-0025_Rev-2 Page 31 of 46 Development Consultants Pvt. Ltd.
JINDAL POWER LIMITED
Specification for 11kV & 3.3kV Segregated Phase Busduct
(SPBD) & Neutral Grounding Resistor (NGR)
O.P. Jindal Super Thermal Power Project (4 x600 MW)
ANNEXURE-D
LIST OF MANDATORY SPARES The equipment wise quantities indicated in the list of mandatory spares below are for each type & rating of equipment:
Sl. No. Description Quantity
1. Bus support insulators 20% of total
2. Flexible equipment terminal connection (3 Ph) complete with hardware for :
a) 3000 A 02 Set b) 2500 A 02 Set c) 2000 A 02 Set d) 1250 A 02 Set
3. Wall seal off bushing rated for : a) 3000 A (3 phase) 02 Set b) 2500 A (3 phase) 02 Set c) 2000 A (3 phase) 02 Set d) 1250 A (3 phase) 02 Set
4. Expansion bellows for : a) 3000 A 02 No. b) 2500 A 02 No. c) 2000 A 02 No. d) 1250 A 02 No.
Document No.: K8B15-SPC-E-0025_Rev-2 Page 32 of 46 Development Consultants Pvt. Ltd.
JINDAL POWER LIMITED
Specification for 11kV & 3.3kV Segregated Phase Busduct
(SPBD) & Neutral Grounding Resistor (NGR)
O.P. Jindal Super Thermal Power Project (4 x600 MW)
ANNEXURE E
DELIVERY & COMMISSIONING SCHEDULE OF PHASE SEGREGATED BUSDUCT PACKAGE
A) 11000 V Phase Segregated Bus ducts and associated equipment with all necessary accessories Busduct Identification SL.
No. B.D No. As per Key SLD
Busduct Commissioning date
1 BD 101 1UT11SR1 Interconnection between Unit Transformer (31.5 MVA) UT#1HUT1 and 11kV Unit Switchgear # 1KSR1(2000 A)
April 2011
2 BD 102 1UT21SR2 Interconnection between Unit Transformer (31.5 MVA) UT#1HUT2 and 11kV Unit Switchgear # 1KSR2 (2000 A)
April 2011
3 BD 103 2UT12SR1 Interconnection between Unit Transformer (31.5 MVA) UT#2HUT1 and 11kV Unit Switchgear # 2KSR1 (2000 A)
July 2011
4 BD 104 2UT22SR2 Interconnection between Unit Transformer (31.5 MVA) UT#2HUT2 and 11kV Unit Switchgear # 2KSR2 (2000 A)
July 2011
5 BD 105 3UT13SR1 Interconnection between Unit Transformer (31.5 MVA) UT# 3HUT1and 11kV Unit Switchgear # 3KSR1 (2000 A)
Sep 2011
6 BD 106 3UT23SR2 Interconnection between Unit Transformer (31.5 MVA) UT#3HUT2 and 11kV Unit Switchgear # 3KSR2 (2000 A)
Sep 2011
7 BD 107 4UT14SR1 Interconnection between Unit Transformer (31.5 MVA) UT#4HUT1 and 11kV Unit Switchgear # 4KSR1 (2000 A)
Nov 2011
8 BD 108 4UT24SR2 Interconnection between Unit Transformer (31.5 MVA) UT#4HUT2 and 11kV Unit Switchgear # 4KSR2 (2000 A)
Nov 2011
9 BD 109 1SR10SR1 Interconnection between 11kV Station Switchgear #0KSR1 and 11kV Unit Switchgear # 1KSR1(2000 A)
March 2011
10 BD 110 1SR20SR2 Interconnection between 11kV Station Switchgear #0KSR2 and 11kV Unit Switchgear # 1KSR2 (2000 A)
March 2011
11 BD 111 2SR10SR3 Interconnection between 11kV Station Switchgear #0KSR3 and 11kV Unit Switchgear # 2KSR1 (2000 A)
June 2011
12 BD 112 2SR20SR4 Interconnection between 11kV Station Switchgear #0KSR4 and 11kV Unit Switchgear # 2KSR2 (2000 A)
June 2011
13 BD 113 3SR10SR5 Interconnection between 11kV Station Switchgear #0KSR5 and 11kV Unit Switchgear # 3KSR1 (2000 A)
Aug 2011
14 BD 114 3SR20SR6 Interconnection between 11kV Station Switchgear #0KSR6 and 11kV Unit Switchgear #3KSR2 (2000 A)
Aug 2011
15 BD 115 4SR10SR7 Interconnection between 11kV Station Switchgear #0KSR7 and 11kV Unit Switchgear #4KSR1 (2000 A)
Sep 2011
16 BD116 4SR20SR8 Interconnection between 11kV Station Switchgear #0KSR8 and 11kV Unit Switchgear #4KSR2 (2000 A)
Sep 2011
17 BD 117 1ST10SR1 Interconnection between LV Winding-1A of ST(90/45/45 MVA) # 0BST1and 11kV Station Switchgear #0KSR1(3000 A)
March 2011
18 BD 118 1ST20SR2 Interconnection between LV Winding-1B of ST (90/45/45 MVA)# 0BST1and 11kV Station Switchgear #0KSR2 (3000 A)
March 2011
19 BD 119 2ST10SR3 Interconnection between LV Winding-2A of ST (90/45/45 MVA)# 0BST2 and 11kV Station Switchgear #0KSR3 (3000 A)
June 2011
20 BD 120 2ST20SR4 Interconnection between LV Winding-2B of ST (90/45/45 MVA)# 0BST2 and 11kV Station Switchgear #0KSR4 (3000 A)
June 2011
Document No.: K8B15-SPC-E-0025_Rev-2 Page 33 of 46 Development Consultants Pvt. Ltd.
JINDAL POWER LIMITED
Specification for 11kV & 3.3kV Segregated Phase Busduct
(SPBD) & Neutral Grounding Resistor (NGR)
O.P. Jindal Super Thermal Power Project (4 x600 MW)
Busduct Identification SL.
No. B.D No. As per Key SLD
Busduct Commissioning date
21 BD 121 3ST10SR5 Interconnection between LV Winding-3A of ST (90/45/45 MVA)# 0BST3 and 11kV Station Switchgear #0KSR5 (3000 A)
Aug 2011
22 BD 122 3ST20SR6 Interconnection between LV Winding-3B of ST(90/45/45 MVA) # 0BST3 and 11kV Station Switchgear #0KSR6 (3000 A)
Aug 2011
23 BD 123 0SR10SR5 Interconnection between 11kV Station Switchgear#0KSR1 and 11kV Station Switchgear #0KSR5 (3000 A)
March 2011
24 BD 124 0SR10SR3 Interconnection between 11kV Station Switchgear #0KSR1 and 11kV Station Switchgear #0KSR3 (3000 A)
March 2011
25 BD 125 0SR20SR4 Interconnection between 11kV Station Switchgear #0KSR2 and 11kV Station Switchgear #0KSR4 (3000 A)
March 2011
26 BD 126 0SR20SR6 Interconnection between 11kV Station Switchgear #0KSR2 and 11kV Station Switchgear #0KSR6 (3000 A)
March 2011
27 BD 129 0SR30SR7 Interconnection between 11kV Station Switchgear #0KSR3 and 11kV Station Switchgear #0KSR7 (3000 A)
Aug 2011
28 BD 130 0SR40SR8 Interconnection between 11kV Station Switchgear #0KSR4 and 11kV Station Switchgear #0KSR8 (3000 A)
June 2011
29 BD 131 0SR50SR7 Interconnection between 11kV Station Switchgear #0KSR5 and 11kV Station Switchgear #0KSR7 (3000 A)
Aug 2011
30 BD 132 0SR60SR8 Interconnection between 11kV Station Switchgear #0KSR6 and 11kV Station Switchgear #0KSR8 (3000 A)
Aug 2011
31 BD 127 RWT1SR01 Interconnection between 33/11KV Transformer(25 MVA) # 0GRWHT1 and 11kV River WTR Switchgear #0KRWSR1 (2000A)
March 2011
32 BD 128 RWT2SR01 Interconnection between 33/11KV Transformer(25 MVA) # 0GRWHT2 and 11kV River WTR Switchgear #0KRWSR1 (2000A)
March 2011
B) 3300 V Phase Segregated Bus ducts and associated equipment with all necessary accessories
Sl. No. Busduct Identification
B.D No.
As per Key SLD
Busduct Commissioning date
1 BD 201
1KUAT1-1MSR1
Interconnection between Unit Auxiliary Transformer UAT#1KUAT1 (16MVA) and 3.3kV Unit Switchgear #1MSR1 (3000 A)
April 2011
2 BD 202
1KUAT2-1MSR2
Interconnection between Unit Auxiliary Transformer UAT#1KUAT2 (16MVA) and 3.3kV Unit Switchgear #1MSR2 (3000 A)
April 2011
3 BD 203
2KUAT1-2MSR1
Interconnection between Unit Auxiliary Transformer UAT#2KUAT1 (16MVA) and 3.3kV Unit Switchgear #2MSR1 (3000 A)
July 2011
4 BD 204
2KUAT2-2MSR2
Interconnection between Unit Auxiliary Transformer UAT#2KUAT2 (16MVA) and 3.3kV Unit Switchgear #2MSR2 (3000 A)
July 2011
5 BD 205
3KUAT1-3MSR1
Interconnection between Unit Auxiliary Transformer UAT#3KUAT1 (16MVA) and 3.3kV Unit Switchgear #3MSR1 (3000 A)
Sep 2011
Document No.: K8B15-SPC-E-0025_Rev-2 Page 34 of 46 Development Consultants Pvt. Ltd.
JINDAL POWER LIMITED
Specification for 11kV & 3.3kV Segregated Phase Busduct
(SPBD) & Neutral Grounding Resistor (NGR)
O.P. Jindal Super Thermal Power Project (4 x600 MW)
Sl. No. Busduct Identification
B.D No.
As per Key SLD
Busduct Commissioning date
6 BD 206
3KUAT2-3MSR2
Interconnection between Unit Auxiliary Transformer UAT#3KUAT2 (16MVA) and 3.3kV Unit Switchgear #3MSR2 (3000 A)
Sep 2011
7 BD 207
4KUAT1-4MSR1
Interconnection between Unit Auxiliary Transformer UAT#4KUAT1 (16MVA) and 3.3kV Unit Switchgear #4MSR1 (3000 A)
Sep 2011
8 BD 208
4KUAT2-4MSR2
Interconnection between Unit Auxiliary Transformer UAT#4KUAT2 (16MVA) and 3.3kV Unit Switchgear #4MSR2 (3000 A)
Sep 2011
9 BD 209 0KSAT1-0MSR1 Interconnection between Station Auxiliary Transformer # 0KSAT1
(6.3MVA) and 3.3kV Station Switchgear #0MSR1 (1250 A) March 2011
10 BD 210 0KSAT2-0MSR2 Interconnection between Station Auxiliary Transformer # 0KSAT2
(6.3MVA) and 3.3kV Station Switchgear #0MSR2 (1250 A) March 2011
11 BD 211 0KSAT3-0MSR3 Interconnection between Station Auxiliary Transformer # 0KSAT3
(6.3MVA) and 3.3kV Station Switchgear #0MSR3 (1250 A) Sep 2011
12 BD 212 0KSAT4-0MSR4 Interconnection between Station Auxiliary Transformer # 0KSAT4
(6.3MVA)and 3.3kV Station Switchgear #0MSR4 (1250 A) Sep 2011
13 BD 213
0KCHHT1-0MCHSR1
Interconnection between CHP Service Transformer # 0KCHHT1 (8MVA)and 3.3Kv Switchgear # 0MCHSR1 (2500 A)
May 2011
14 BD 214
0KCHHT2-0MCHSR2
Interconnection between CHP Service Transformer # 0KCHHT2 (8MVA)and 3.3Kv Switchgear # 0MCHSR2 (2500 A)
May 2011
15 BD 215
0KAFHT1-0MAFSR1
Interconnection between Fly ASH COMPRESSOPR Transformer # 0KAFHT1 (5MVA) and 3.3kV Fly compressor Switchgear# 0MAFSR1 (1250 A)
Sep 2011
16 BD 216
0KAFHT2-0MAFSR1
Interconnection between Fly ASH COMPRESSOPR Transformer # 0KAFHT2 (5MVA) and 3.3kV Fly compressor Switchgear# 0MAFSR1 (1250A)
Sep 2011
17 BD 217
0GARHT1-0MARSR1
Interconnection between Ash Dyke transformer # 0GARHT1 (5MVA) and 3.3kV ASH DYKE Switchgear# 0MARSR1 (1250 A)
Nov 2011
18 BD 218
0GARHT2-0MARSR1
Interconnection between ASH DYKE transformer # 0GARHT2 (5MVA) and 3.3kV ASH DYKE Switchgear# 0MARSR1 (1250 A)
Nov 2011
19 BD 219
0KAWHT1-0MAWSR1
Interconnection between ASH WTR. Transformer# 0KAWHT1 (3MVA) and 3.3kV ASH WTR. Switchgear 0MAWSR1 (1250A)
Sep 2011
20 BD 220
0KAWHT2-0MAWSR1
Interconnection between ASH WTR. Transformer (3MVA)# 0KAWHT2 and 3.3kV ASH WTR. Switchgear 0MAWSR1 (1250 A)
Sep 2011
21 BD 221
0KADHT1-0MADSR1
Interconnection between ASH SLRY Transformer# 0KADHT1 (5MVA) and 3.3kV ASH SLRY. Switchgear #0MADSR1 (1250 A)
Sep 2011
22 BD 222
0KADHT2-0MADSR1
Interconnection between ASH SLRY Transformer (5MVA)# 0KADHT2 and 3.3kV ASH SLRY. Switchgear #0MADSR1 (1250 A)
Sep 2011
23 BD 223
0GRTHT1-0MRTSR1
Interconnection between RAW WTR. Transformer# 0GRTHT1 (5MVA) and 3.3kV RAW WTR. Switchgear# 0MRTSR1 (1250 A)
March 2011
24 BD 224
0GRTHT2-0MRTSR1
Interconnection between RAW WTR. Transformer (5MVA)# 0GRTHT2 and 3.3kV RAW WTR. Switchgear# 0MRTSR1 (1250 A)
March 2011
25 BD 225 1MSR1 -1MSR2 Interconnection between 3.3kV Unit Switchgear #1MSR1 and
3.3kV Unit Switchgear # 1MSR2 (3000 A) April 2011
Document No.: K8B15-SPC-E-0025_Rev-2 Page 35 of 46 Development Consultants Pvt. Ltd.
JINDAL POWER LIMITED
Specification for 11kV & 3.3kV Segregated Phase Busduct
(SPBD) & Neutral Grounding Resistor (NGR)
O.P. Jindal Super Thermal Power Project (4 x600 MW)
Sl. No. Busduct Identification
B.D No.
As per Key SLD
Busduct Commissioning date
26 BD 226 2MSR1-2MSR2 Interconnection between 3.3kV Unit Switchgear #2MSR1 and
3.3kV Unit Switchgear # 2MSR2 (3000 A) July 2011
27 BD 227 3MSR1-3MSR2 Interconnection between 3.3kV Unit Switchgear #3MSR1and
3.3kV Unit Switchgear # 3MSR2 (3000 A) Sep 2011
28 BD 228 4MSR1-4MSR2 Interconnection between 3.3kV Unit Switchgear #4MSR1 and
3.3kV Unit Switchgear # 4MSR2 (3000 A) Sep 2011
29 BD 229 0MSR1-0MSR2 Interconnection between 3.3kV Station Switchgear #0MSR1 and
3.3kV Station Switchgear # 0MSR2 (1250 A) March 2011
30 BD 230 0MSR3-0MSR4 Interconnection between 3.3kV Station Switchgear #0MSR3 and
3.3kV Station Switchgear # 0MSR4 (1250 A) Oct 2011
31 BD 232
0MCHSR1-0MCHSR2
Interconnection between 3.3KV CHP Switchgear # 0MCHSR1 and 3.3KV CHP Switchgear #0MCHSR2 (2500 A)
May 2011
Document No.: K8B15-SPC-E-0025_Rev-2 Page 36 of 46 Development Consultants Pvt. Ltd.
JINDAL POWER LIMITED
Specification for 11kV & 3.3kV Segregated Phase Busduct
(SPBD) & Neutral Grounding Resistor (NGR)
O.P. Jindal Super Thermal Power Project (4 x600 MW)
Part-III
TECHNICAL SPECIFICATION FOR
NEUTRAL GROUNDING RESISTOR
Document No.: K8B15-SPC-E-0025_Rev-2 Page 37 of 46 Development Consultants Pvt. Ltd.
JINDAL POWER LIMITED
Specification for 11kV & 3.3kV Segregated Phase Busduct
(SPBD) & Neutral Grounding Resistor (NGR)
O.P. Jindal Super Thermal Power Project (4 x600 MW)
Part-III
TECHNICAL SPECIFICATION
FOR NEUTRAL GROUNDING RESISTOR
1.00.00 DESIGN CRITERIA 1.01.00 The Neutral Grounding Resistor shall be used for non-effective grounding of 11000 V
and 3300 V system of the plant.
NGR shall be connected between the 11000 V star connected winding neutral point of station transformers, unit transformers and other HT auxiliary transformers and earth.
NGR shall also be connected between the 3300 V star connected winding neutral point of HT auxiliary transformers and earth.
1.02.00 Neutral Grounding Resistor shall be used to limit the magnitude of earth fault current so
that damage of electrical equipment is reduced, safety of personnel is increased and sensitive, selective earth fault protection can be provided.
1.03.00 The NGR shall be installed in dust prone, hot, humid and tropical atmosphere. All
equipment, accessories and wiring shall be provided with tropical finish to prevent fungus growth.
1.04.00 The rated time for the earth fault current or specified thermal current shall be 10
seconds. 1.05.00 The Bidder shall quote for neutral grounding resistor with final temperature as per
allowable limit due to the specified current for specified time. 1.06.00 The resistor unit shall be air-cooled type suitable for installation at outdoor locations. 1.07.00 Rating and requirements of NGR are indicated under Annexure-A. 2.00.00 SPECIFIC REQUIREMENTS 2.01.00 Resistor 2.01.01 The resistor element shall be made of non-aging stainless steel or equivalent corrosion
resistant material having high electrical resistivity and low temperature co-efficient of resistant. The NGR shall have temperature limited to the maximum allowable temperature for the material offered considering the air ambient temperature at site as mentioned earlier.
2.01.02 The resistor unit shall consist of a no. of elements. All the elements shall be mounted
inside the cubicle so as to ensure ease of inspection and replacement of individual element. The resistors shall be edge-wound type.
2.01.03 Each resistor element shall possess a balanced combination of both mechanical and
electrical properties over the entire intended operating temperature range without any harmful effect on the elements and their accessories.
2.01.04 All the resistor elements constituting the NGR shall be assembled and supported inside
the cubicle in such a way that no distortion or breakage shall occur during the passage of through fault current to earth.
Document No.: K8B15-SPC-E-0025_Rev-2 Page 38 of 46 Development Consultants Pvt. Ltd.
JINDAL POWER LIMITED
Specification for 11kV & 3.3kV Segregated Phase Busduct
(SPBD) & Neutral Grounding Resistor (NGR)
O.P. Jindal Super Thermal Power Project (4 x600 MW)
2.01.05 All element connections shall be bolted type to ensure stable resistance value
throughout the working life of the unit. 2.01.06 Wet process type brown glaze porcelain insulators shall be used for supporting resistor
elements. Porcelain insulators shall have high creep age value suitable for heavily polluted atmosphere charged with dust particles.
2.02.00 Enclosure 2.02.01 Each neutral grounding resistor shall have structural steel work enclosed on all sides
and also on top by sheet steel having a minimum thickness of 3 mm. Suitable ventilating louvers shall be provided on sides to ensure proper ventilation. The louvers shall be provided with fire wire mesh to make it vermin proof.
2.02.02 Each enclosure shall be self supporting, weather proof type suitable for outdoor
mounting having a protection class as indicated in annexure. 2.02.03 Each cubicle shall be complete with a front access door with handles, lock and also a
removable bolted cover. All doors and removable covers shall be properly gasketed with neoprene rubber gaskets. All cubicle door hinges shall be concealed type.
2.02.04 Each cubicle shall be complete with a suitably mounted cable end box fitted with
removable double compression brass type cable gland for fixing cable gland. The cable size shall be as indicated in the annexure. Double compression cable gland and tinned copper lugs shall be provided.
2.02.05 Each cubicle shall be provided with suitable base channels for direct bolting to the
foundation at site. All necessary galvanized bolts, nuts, washers etc. shall be supplied by the Bidder for installation of Cubicle at site.
2.02.06 Cable entry in NGR enclosure shall be from bottom only. 2.02.07 Fine mesh screen of corrosion resistant material shall be furnished on all ventilating
opening to prevent entry of insects. 2.03.00 Current Transformer 2.03.01 The current Transformer shall be cast resin type, insulation class ‘B’, suitably mounted
inside the NGR cubicle in such a way as to ensure easy removal and replacement. 2.03.02 Flash over shall not take place from bus bar to CT at sharp edges of bus bar. 2.03.03 The secondary leads of CT shall have polarity markings as per IS. The secondary leads
shall be brought out to the terminals at terminal box provided at suitable location completely isolated from high voltage equipment.
2.03.04 Current transformers are applicable for transformers rated 5MVA and above. 2.04.00 Cubicle lamp and sockets 2.04.01 Each cubicle shall be provided with 5A, 3 pin plug socket and door-switch controlled
cubicle illumination lamp. 2.04.02 Two pole MCB shall be provided for receiving 240 V single phase AC supply for cubicle
lamp and illumination circuit.
Document No.: K8B15-SPC-E-0025_Rev-2 Page 39 of 46 Development Consultants Pvt. Ltd.
JINDAL POWER LIMITED
Specification for 11kV & 3.3kV Segregated Phase Busduct
(SPBD) & Neutral Grounding Resistor (NGR)
O.P. Jindal Super Thermal Power Project (4 x600 MW)
2.05.00 Wiring 2.05.01 All internal wiring between equipment and terminal block shall be carried out by PVC
insulated 1100 V grade 2.5 Sq.mm stranded copper conductor wires. 2.05.02 All wiring shall be suitably ferruled with corresponding wiring identification marks used
in the schematic / wiring diagrams. 2.05.03 All devices and terminal blocks within the terminal box shall be clearly identified by
symbol corresponding to those used on applicable schematic/wiring diagram. 20% spare terminals shall be provided in terminal block.
2.06.00 Grounding 2.06.01 All parts of enclosure, supporting structures, equipment frames etc. shall be properly
grounded at two points separately. 2.06.02 Each cubicle shall be completed with two (2) nos. ground pads, tapped holes and bolts
suitable for connection of 50 x 6 mm galvanized steel flats. 3.00.00 TESTS 3.01.00 Routine Tests Each equipment shall be completely assembled, wired, adjusted and routine tested as
per relevant standards at manufacturer's works. The tests shall include: 3.01.01 Resistance measurement 3.01.02 Voltage measurement 3.01.03 Insulation resistance measurement 3.01.04 Dielectric test 3.02.00 Type Tests
Bidder should have performed the following type tests on one rating of each type as type tests. Type Test Reports not older than five (5) years shall be submitted to this effect. All such type test reports shall be subject to the approval of Owner. In case the bidder has to carry out these type tests, all such tests shall be done at bidders risk and cost within the schedule specified herein. No deviation in this regard is acceptable.
3.02.01 Heat Run test & Short Circuit Test shall be carried out on one unit of each rating. The
cost of such test, if any, shall be quoted separately. 4.00.00 DRAWINGS, DATA & MANUALS 4.01.00 Drawings, data and manuals shall be submitted with the bid and in quantities and
procedures as specified in General Conditions on Contract and / or elsewhere in this specification for approval and subsequent distribution after the issue of Letter of Intent.
4.02.00 To be Submitted with the Bid 4.02.01 Proposal sheets duly filled in. 4.02.02 Scheme showing series/parallel combination of resistor elements.
Document No.: K8B15-SPC-E-0025_Rev-2 Page 40 of 46 Development Consultants Pvt. Ltd.
JINDAL POWER LIMITED
Specification for 11kV & 3.3kV Segregated Phase Busduct
(SPBD) & Neutral Grounding Resistor (NGR)
O.P. Jindal Super Thermal Power Project (4 x600 MW)
4.02.03 Bill of Material. 4.02.04 Dimensional general arrangement drawings showing constructional features etc. along
with necessary foundation plan.
4.02.05 Cable termination details. 4.02.06 Technical leaflets on each piece of electrical equipment along with write up on salient
features. 4.02.07 Type test certificate of similar type and rating of offered equipment. 4.03.00 To be submitted for Purchaser’s Approval and Distribution (A) : ‘Approval Category’ (R) : ‘Reference Category’ 4.03.01 Guaranteed Technical Particulars (A) and Quality assurance plan (R) 4.03.02 Dimensioned General Arrangement drawings of cubicle showing disposition of all
electrical equipment such as resistor elements, cable termination etc. inside the cubicle. (A)
4.03.03 Consolidated Bill of Materials. (A) 4.03.04 Foundation Plan and loading of cubicle. (A) 4.03.05 Control schematic (A) and wiring diagram of the whole system. (R) 4.03.06 Erection drawings of cubicle and resistor elements. 4.03.07 Transport/shipping dimension and the dimension of space required for handling various
parts for maintenance. (R) 4.03.08 Test certificates (A) 4.03.09 Instruction manuals for the complete system. (R) The manual shall clearly indicate method of installation, check ups and tests to be
carried out before commissioning of the equipment. 4.04.00 Any other relevant drawing or data necessary for satisfactory installation, operation and
maintenance. 4.05.00 The drawings and document marked with (A) above are of ‘Approval’ category and are
subject to review by Purchaser. Those marked (R) are for ‘reference’ category. The Purchaser may also review the documents marked (R) if found necessary. The
Bidder shall note that the approval of drawings & documents by the Purchaser does not relieve him of his contractual obligation.
4.06.00 All drawings shall be prepared by using Auto CAD, approved version and documents
shall be generated using MS Office. The paper copy of the drawings & document shall be submitted for approval & reference. All final drawings and documents shall be submitted in CD in Auto CAD 2006 and MS office format as applicable for Purchaser’s future reference.
Document No.: K8B15-SPC-E-0025_Rev-2 Page 41 of 46 Development Consultants Pvt. Ltd.
JINDAL POWER LIMITED
Specification for 11kV & 3.3kV Segregated Phase Busduct O.P. Jindal Super Thermal
(SPBD) & Neutral Grounding Resistor (NGR)
Power Project (4 x600 MW)
The Bidder may note that the drawings, data and manuals listed herein are minimum
requirements only. The Bidder shall ensure that all other necessary write-ups, curves and information required to fully describe the equipment are submitted with his bid.
Document No.: K8B15-SPC-E-0025_Rev-2 Page 42 of 46 Development Consultants Pvt. Ltd.
JINDAL POWER LIMITED
Specification for 11kV & 3.3kV Segregated Phase Busduct O.P. Jindal Super Thermal
(SPBD) & Neutral Grounding Resistor (NGR)
Power Project (4 x600 MW)
ANNEXURE-A
RATINGS AND REQUIREMENTS 1.0 General 1.1 Applicable standard : IEEE-32 1.2 Service : Outdoor, free standing 1.3 Rated system Voltage & allowable variation : 11KV±10% 3.3KV±10% 1.4 Rated frequency and allowable variation : 50Hz±5% 2.0 Rating 2.1 Rated Voltage KV : 11KV & 3.3KV 2.2 Rated current at rated time duration Amp : 300A 2.3 Rated time duration Sec. : 10 2.4 Resistance in design ambient temp. Ohm : 22.13Ω & 6.64Ω 2.5 Allowable Tolerance in resistance value% : ±10 2.6 Design ambient Temperature ° C : 50 2.7 Maximum permissible temperature rise of resistor °C : 250 (above 50°C ambient) 2.8 Temp rise of Enclosure °C : 30 2.9 Basic Insulation level and system insulation class: 11KV 3.3KV System insulation class for line end & ground end KVrms : 75/28 KV 40/10KV (peak/r.m.s) (peak/r.m.s) Insulation level (applied 1min. power frequency potential) KVrms : 75/28 KV 40/10KV (peak/r.m.s) (peak/r.m.s) 3.0 NGR & NGR Cubicle 3.1 Materials of resistor : Non-aging, corrosion proof, punched
grid stainless steel. 3.2 Resistor element combination : Series-parallel (6X6) 3.3 Enclosure material : Sheet steel 3.4 Min. Thickness of aluminum sheet mm : 2 3.5 Enclosure protection class : IP-55 with canopy
Document No. K8B15-SPC-E-0025, Rev-1 Page 43 of 46 Development Consultants Pvt. Ltd.
JINDAL POWER LIMITED
Specification for 11kV & 3.3kV Segregated Phase Busduct O.P. Jindal Super Thermal
(SPBD) & Neutral Grounding Resistor (NGR)
Power Project (4 x600 MW)
3.6 Finish paint of a) Interior : As per manufacturer’s standard b) Exterior : RAL 7032 : 3.7 Terminal arrangement : Through cable 3.8 Type & size of cable to be terminated : 2-1/C-70sq. mm XLPE 4.0 Insulators 4.1 Type : Support insulator 4.2 Materials : Porcelain 4.3 Bushing rating KVrms : 12 KV & 3.6 KV 4.4 Creepage distance mm : 31 mm/KV
Document No. K8B15-SPC-E-0025, Rev-1 Page 44 of 46 Development Consultants Pvt. Ltd.
JINDAL POWER LIMITED
Specification for 11kV & 3.3kV Segregated Phase Busduct O.P. Jindal Super Thermal
(SPBD) & Neutral Grounding Resistor (NGR)
Power Project (4 x600 MW)
ANNEXURE-B
LIST OF MANDATORY SPARES
Sl. no. Items Qty
1. Brown glazed porcelain insulators for supporting between mounting frame and each resistor assembly
6 Nos.
2. Interposing insulator assembly 6 Nos.
3 Live end bushing with metal parts 6 Nos.
4 Dead end bushing with metal parts 6 Nos.
5 Current transformers 4 Nos.
Document No. K8B15-SPC-E-0025, Rev-1 Page 45 of 46 Development Consultants Pvt. Ltd.
JINDAL POWER LIMITED
Specification for 11kV & 3.3kV Segregated Phase Busduct O.P. Jindal Super Thermal
(SPBD) & Neutral Grounding Resistor (NGR)
Power Project (4 x600 MW)
ANNEXURE-C DELIVERY & COMMISSIONING SCHEDULE OF NEUTRAL GROUNDING RESISTOR PACKAGE
Neutral grounding Resistor (NGR) and associated equipment with all necessary accessories
Sl. No.
NGR Description Commissioning date
1. 22.13 Ohms, 11000 V, 300 A for 10 seconds for Unit Transformers. 1KXYNG1, 1KXYNG2, 2KXYNG1, 2KXYNG2, 3KXYNG1 & 3KXYNG2, 4KXYNG1, 4KXYNG2.
April 2011 for first Set balance set shall be commissioned progressively at an interval of 2 months thereafter
2 22.13 Ohms, 11000 V, 300 A for 10 seconds for Station Transformers. 0KXYNG1, 0KXYNG2, 0KXYNG3, 0KXYNG4, 0KXYNG5 & 0KXYNG6.
July 2011 for first Set balance set shall be commissioned progressively at an interval of 2 months thereafter
3 22.13 Ohms, 11000 V, 300 A for 10 seconds for River Water Transformer. 0KRWNG1 and 0KRWNG2.
March 2011
4 6.64 Ohms, 3300 V, 300 Amps for 10 seconds for Raw Water Transfer Transformers.0MRTNG1 and 0MRTNG2.
April 2011
5 6.64 Ohms, 3300 V, 300 Amps for 10 seconds for 3.3kV Station Aux. Transformer.0MXYNG1, 0MXYNG2, 0MXYNG3 and 0MXYNG4.
April 2011 for first Set balance set shall be commissioned progressively at an interval of 2 months thereafter
6 6.64 Ohms, 3300 V, 300 Amps for 10 seconds for 3.3kV Ash Slurry Transformer.0MAPNG1 and 0MAPNG2.
July 2011
7 6.64 Ohms, 3300 V, 300 Amps for 10 seconds for 3.3kV Ash Water Transformer.0MAWNG1 and 0MAWNG2.
Oct 2011
8 6.64 Ohms, 3300 V, 300 Amps for 10 seconds for Ash Silo Transformer. OMASNG1 and 0MASNG2.
Oct 2011
9 6.64 Ohms, 3300 V, 300 Amps for 10 seconds for Ash Dyke Transformer. 0MARNG1 and 0MARNG2.
June 2011
10 6.64 Ohms, 3300 V, 300 Amps for 10 seconds for Fly Ash Compressor Transformer. 0MAFNG1 and 0MAFNG2.
Aug 2011
11 6.64 Ohms, 3300 V, 300 Amps for 10 seconds for CHP Transformer. 0MCHNG1 and 0MCHNG2.
May 2011
12 6.64 Ohms, 3300 V, 300 Amps for 10 seconds for Unit Auxiliary Transformer. 1MXYNG1, 1MXYNG2, 2MXYNG1, 2MXYNG2, 3MXYNG1, 3MXYNG2, 4MXYNG1 and 4MXYNG2.
June 2011 for first Set balance set shall be commissioned progressively at an interval of 2 months thereafter
Document No. K8B15-SPC-E-0025, Rev-1 Page 46 of 46 Development Consultants Pvt. Ltd.
JINDAL POWER
Specification for 11kV & 3.3kV Segregated Phase Busduct O.P. Jindal Super Thermal
LIMITED (SPBD) & Neutral Grounding Resistor (NGR)
Power Project (4x600MW)
SECTION-III
PROPOSAL EXHIBIT SHEETS
Document No.: K8B15-SPC-E-0025_Rev-2 Development Consultants Pvt. Ltd.
JINDAL POWER LIMITED
Specification for 11kV & 3.3kV Segregated Phase Busduct O.P. Jindal Super Thermal
Power Project (4 (SPBD) & Neutral Grounding Resistor (NGR) x600MW)
CONTENTS
SCHEDULE NO. DESCRIPTION PAGE NO.
SECTION IIIA PROPOSAL DATA (TO BE SUBMITTED WITH TECHNICAL BID)
SCHEDULE - I PROPOSAL PARTICULARS 1
SCHEDULE - II TECHNICAL PARTICULARS 3
SCHEDULE - III LIST OF SPECIAL TOOLS AND TACKLE 8
SCHEDULE - IV DRAWING SUBMISSION SCHEDULE 9
SCHEDULE - V DEVIATION SHEET: TECHNICAL 10
SCHEDULE - VI DEVIATION SHEET: GENERAL CONDITION OF CONTRACT 11
SCHEDULE - VII SALIENT EVALUATION CRITERIA 12
SCHEDULE - VIII VENDOR RATING CRITERIA 14
SECTION IIIB PROPOSAL DATA (TO BE SUBMITTED WITH PRICE BID)
SCHEDULE - IX PRICE TABULATION SHEET 16
SCHEDULE - X PRICE BREAKDOWN SHEET 21
SCHEDULE - XI SPARE PARTS PRICE SHEET 22
SCHEDULE - XII SPECIAL TOOLS & TACKLE PRICE SHEET 23
SCHEDULE - XIII DEVIATION SHEET - PRICE 24
SCHEDULE - XIV DECLARATION SHEET 25
Document No.: K8B15-SPC-E-0025_Rev-2 Development Consultants Pvt. Ltd.
JINDAL POWER LIMITED
Specification for 11kV & 3.3kV Segregated Phase Busduct O.P. Jindal Super Thermal
Power Project (4 (SPBD) & Neutral Grounding Resistor (NGR) x600MW)
PROPOSAL DATA – SECTION- IIIA
(TO BE SUBMITTED WITH TECHNICAL BID)
SCHEDULE - I TO VIII
Document No.: K8B15-SPC-E-0025_Rev-2 Development Consultants Pvt. Ltd.
JINDAL POWER LIMITED
Specification for 11kV & 3.3kV Segregated Phase Busduct
(SPBD) & Neutral Grounding Resistor (NGR)
O.P. Jindal Super Thermal Power Project (4 x600MW)
SCHEDULE- I PROPOSAL PARTICULARS
1. Bidder's Complete Company Name and address, tel no. fax no. and E-mail ID 2. Bidder's Proposal Number : 3. Bidder's Proposal Date : 4. Bidder's Proposal Validity : 5. Name and Designation of the Officer of the Bidder to whom all references shall be made for expeditious technical co-ordination : 6. Earnest money deposit : a. If deposited, give references b. If not, give reasons 7. D.G.S. & D registration : a. Whether registered
b. If so, give registration Number and copy of reference letter :
8. Copy of Income Tax Clearance Certificate furnished : 9. Terms of Payment : a. Terms of payment as per Owner's Specification is acceptable b. If not, specify terms of payment
Document No.: K8B15-SPC-E-0025_Rev-2 Page 1 of 29 Development Consultants Pvt. Ltd.
JINDAL POWER LIMITED
Specification for 11kV & 3.3kV Segregated Phase Busduct
(SPBD) & Neutral Grounding Resistor (NGR)
O.P. Jindal Super Thermal Power Project (4 x600MW)
SCHEDULE – I : PROPOSAL PARTICULARS (Contd.) 10. Delivery : a. Delivery period in months for complete equipment from the date of issue of 'Letter of Intent' (allowing time for approval of drawings and test certificates) b. Is the delivery period guaranteed under penalty
11. Conformance : a. Is the equipment offered strictly in accordance with Owner's Specification? b. If not, have the Deviation sheet been duly filled-up ? c. Are proposal data sheets duly filled-up ? d. All drawings, document, type test Certificates furnished? 12. Performance guarantee period for the equipment offered : a. From the date of commissioning at site b. From the date of dispatch
Document No.: K8B15-SPC-E-0025_Rev-2 Page 2 of 29 Development Consultants Pvt. Ltd.
JINDAL POWER LIMITED
Specification for 11kV & 3.3kV Segregated Phase Busduct
(SPBD) & Neutral Grounding Resistor (NGR)
O.P. Jindal Super Thermal Power Project (4 x600MW)
SHEDULE-II TECHNICAL PARTICULARS
FOR SEGREGATED PHASE BUSDUCT
1.0 SEGREGATED PHASE BUSDUCT 11000 V 3300 V 1.1 Make : 1.2 Type : 1.3 Reference Standard : 1.4 Service : 1.5 Cooling System : 1.6 Rated Voltage (Volts) : 1.7 Maximum System Voltage (Volts) : 1.8 Phase (Nos) : 1.9 Frequency (Hz) : 1.10 Insulation Level a. 1 min. Power Frequency Withstand (kVrms) : b. Basic Impulse (kVpeak) : 1.11 Rated continuous current (Amp) : 1.12 Maximum temperature rise over 50oC ambient a. Bus conductor (oC) i. Plain Joints : ii. Silver Plated Joints : b. Bus enclosure (oC) : 1.13 Guaranteed Calculated Losses per set of Bus Duct without
any positive tolerance
a. Bus conductor (kW) : b. Bus enclosure (kW) : c. Total (kW) : 1.14 Degree of Protection : 1.15 Rated Short Circuit Current : a. Symmetrical kArms for 3 Sec. : b. Momentary kApeak : 1.16 Weight per metre run of Bus Duct (kg) : 1.17 Shipping Data a. Weight of heaviest package (Kg) : b. Dimension of largest package (LxBxH) mm : 1.18 Material a. Conductor : b. Enclosure : c. Phase Barrier : d. Earth BUS : e. BUS Insulator :
Document No.: K8B15-SPC-E-0025_Rev-2 Page 3 of 29 Development Consultants Pvt. Ltd.
JINDAL POWER LIMITED
Specification for 11kV & 3.3kV Segregated Phase Busduct
(SPBD) & Neutral Grounding Resistor (NGR)
O.P. Jindal Super Thermal Power Project (4 x600MW)
1.19 Conductivity a. Conductor : b. Enclosure : 1.20 Conductor Data a. Conductor Shape : b. Conductor Size (mm2) : c. Conductor treatment (Painting/insulation) : d. Flexible conductor type : e. Flexible conductor dimension : f. Flexible conductor connection : g. Type of joints : h. Silver plated : i. Compound for preventing galvanic corrosion at joints : 1.21 Enclosure Data a. Enclosure Shape : b. Phase spacing (mm) : c. Phase to neutral spacing (mm) : d. Overall dimension (enclose drawing) (BxH) mm : e. Thickness (mm) : 1.22 Interphase Barrier plate for segregated bus duct a. Material : b. Thickness (mm) : c. Means for absorbing expansion/vibration i. At equipment terminal : ii. At straight run : d. Expansion bellows Type i. Equipment terminal : ii. Straight run : e. Number of expansion bellows considered i. Equipment terminal : ii. Straight run : f. Technical details of expansion below enclosed? (Yes
/ No) :
g. Dimension drawing of expansion below enclosed? (Yes / No)
:
1.23 D.C. Resistance at in micro Ohm/meter/phase a. Conductor i. 20oC : ii. 85oC :
b. Enclosure i. 20oC :
Document No.: K8B15-SPC-E-0025_Rev-2 Page 4 of 29 Development Consultants Pvt. Ltd.
JINDAL POWER LIMITED
Specification for 11kV & 3.3kV Segregated Phase Busduct
(SPBD) & Neutral Grounding Resistor (NGR)
O.P. Jindal Super Thermal Power Project (4 x600MW)
ii. 70oC : 1.24 Skin-effect Ratio : 1.25 50 Cycle Reactance in Ohm/meter/phase : 1.26 Capacitance to Ground in Microfarad/meter/phase : 1.27 Losses in Watt/meter/phase a. Conductor : b. Enclosure : 1.28 Enclosure Finish a. Base (synthetic enamel / epoxy) : b. Outside : c. Inside : 1.29 Phase to earth clearance provided (mm) : 1.30 Bus Insulator a. Make : b. Type : c. Reference Standard : d. Number of insulator per support : e. Voltage Class (kV) : f. Creepage distance (mm) : g. Compression strength (kg) : h. Cantilever strength (kg) : i. 1 min. Wet Power Frequency Withstand (kVrms) : j. Impulse volt withstand (kVpeak) : k. Average Span (M) : l. Weight per insulator (kg) : m. Support insulator provided per phase near both ends
of each shipping section of busduct ? :
1.31 Supporting Steel Structure a. Hot dip galvanized? (Yes/No) : b. Typical drg of hanger support enclosed? (Yes/No) : c. Typical drawing of ground support enclosed?
(Yes/No) :
d. Number of hanger supports considered (span) : e. Number of ground support considered (span) : 1.32 Grounding a. Material and size of ground bus provided separately : b. Number of ground pads provided for 50 x 6 mm
galvanized steel flats :
1.33 Switchgear Terminal Adaptor Box a. Material of enclosure : b. Thickness of enclosure (mm) : c. Material of Interphase barrier, if any :
Document No.: K8B15-SPC-E-0025_Rev-2 Page 5 of 29 Development Consultants Pvt. Ltd.
JINDAL POWER LIMITED
Specification for 11kV & 3.3kV Segregated Phase Busduct
(SPBD) & Neutral Grounding Resistor (NGR)
O.P. Jindal Super Thermal Power Project (4 x600MW)
d. Thickness of interphase barrier (mm) : e. Phase to earth Clearance (mm) : f. Seal off bushing provided? (Yes/No) : 1.34 Transformer Terminal Adaptor Box a. Material of Enclosure : b. Thickness (mm) : c. Phase barrier material : d. Phase barrier thickness (mm) : e. Phase to earth clearance (mm) : 1.35 Seal-off Bushings a. Make : b. Type : c. Material : d. Reference Standard : e. Rated Voltage (kV) : f. 1 minute power frequency withstand voltage i. Dry (kVrms) : ii. Wet (kVrms) : g. Impulse withstand (kVpeak) : h. Creepage distance (mm) : i. Weight of each bushing (Kg) : 1.36 Wall frame assembly a. Type of wall frame assembly : b. Number considered in scope : c. Number of silica gel breather : 1.37 Space heater with thermostat a. Number : b. Rating : c. Voltage rating : d. Cable type/spec : e. Marshalling Box : 1.38 Provision for connecting hot air blowing equipment hose?
(Yes/No) :
1.39 BUSBAR Sizing Calculation enclosed? (Yes/No) : 1.40 Type test certificate enclosed? (Yes/No) : 1.41 Catalogue enclosed for various pieces of equipment?
(Yes/No) :
2.0 HOT AIR BLOWING UNIT (PORTABLE) 2.1 General a. Make : b. Trolley Type :
Document No.: K8B15-SPC-E-0025_Rev-2 Page 6 of 29 Development Consultants Pvt. Ltd.
JINDAL POWER LIMITED
Specification for 11kV & 3.3kV Segregated Phase Busduct
(SPBD) & Neutral Grounding Resistor (NGR)
O.P. Jindal Super Thermal Power Project (4 x600MW)
c. Rated KW, Volt, Ph. & Frequency : i. Wattage (KW) ii. Voltage (Volts) iii. Phase iv. Frequency (Hz) d. Flexible Hot Air Duct : i. Type ii. Material iii. Length (M) e. Total Weight 2.2 Fans a. Make : b. Type : c. Capacity Cu.m/hr : 2.3 Motor a. Make : b. Type : c. Rated KW, Volt, Ph. & Frequency : 2.4 Filter Set a. Make : b. Type : c. Size : 2.5 Heater a. Make : b. Rated/KW : c. Voltage, Phase, Frequency : 2.6 Thermostat a. Make : b. Type : c. Model No. : d. Nos. furnished per set :
Document No.: K8B15-SPC-E-0025_Rev-2 Page 7 of 29 Development Consultants Pvt. Ltd.
JINDAL POWER LIMITED
Specification for 11kV & 3.3kV Segregated Phase Busduct
(SPBD) & Neutral Grounding Resistor (NGR)
O.P. Jindal Super Thermal Power Project (4 x600MW)
SCHEDULE – II TECHNICAL PARTICULARS
FOR NEUTRAL GROUNDING RESISTOR
A. NEUTRAL GROUNDING RESISTOR
1.0 General
:
1.1 Make
:
1.2 Service
:
1.3 Reference Standard
:
1.4 Rating
a Rated voltage
:
b Resistance in Ohm at 50oC
:
c Value of Resistance at final operating temperature
:
d Tolerance in declared value of Resistance in %
:
e Electrical Resistivity
:
f Temperature Co-efficient of Resistance
:
g Current Rating (... Amps)
i Short rating for 10 sec
:
ii Continuous Rating
:
3.0 Temperature
3.1 Temperature rise over Reference Ambient
a For duty at continuous current rating (....oC)
:
b For duty at short time current rating of 300 Amp for 10 sec. (....oC)
:
3.2 Change in Resistance over temperature (over operating temperature)
:
4.0 Insulation level
4.1 One (1) minute power frequency withstand voltage ... KV (rms)
:
Document No.: K8B15-SPC-E-0025_Rev-2 Page 8 of 29 Development Consultants Pvt. Ltd.
JINDAL POWER LIMITED
Specification for 11kV & 3.3kV Segregated Phase Busduct
(SPBD) & Neutral Grounding Resistor (NGR)
O.P. Jindal Super Thermal Power Project (4 x600MW)
SCHEDULE – II : TECHNICAL PARTICULARS ……… ............. Bidder's Name
4.2 Basic impulse withstand level.. KV
(Peak)
:
5.0 Construction
5.1 Material used
:
5.2 Cross-section area
:
5.3 Type of Resistor Element
:
5.4 Material composition
:
5.5 Number of Elements per unit (series/parallel combination to be indicated)
:
5.6 Type of Insulation provided
a Between resistor & mounting frame
:
b Between mounting frame & earth
:
5.7 Corrosion Resistance
:
5.8 Method of connection between element to element
B NGR CUBICLES
1.0 Make
:
2.0 Type
:
3.0 Service
:
4.0 Reference Standard
:
5.0 Thickness of aluminium alloy sheet
:
6.0 Overall Dimensions
:
7.0 Weight
a Self weight
:
b With all internally installed equipment
:
8.0 Colour shade, Inside/Outside
:
9.0 Ventilating louvers provided? : 10.0 Internal wiring size :
Document No.: K8B15-SPC-E-0025_Rev-2 Page 9 of 29 Development Consultants Pvt. Ltd.
JINDAL POWER LIMITED
Specification for 11kV & 3.3kV Segregated Phase Busduct
(SPBD) & Neutral Grounding Resistor (NGR)
O.P. Jindal Super Thermal Power Project (4 x600MW)
Document No.: K8B15-SPC-E-0025_Rev-2 Page 10 of 29 Development Consultants Pvt. Ltd.
JINDAL POWER LIMITED
Specification for 11kV & 3.3kV Segregated Phase Busduct
(SPBD) & Neutral Grounding Resistor (NGR)
O.P. Jindal Super Thermal Power Project (4 x600MW)
SCHEDULE – II : TECHNICAL PARTICULARS …… .............
Bidder's Name
11.0 Complete with necessary terminal boxes
:
12.0 Two (2) nos. Ground Pads complete with hardware furnished
:
Document No.: K8B15-SPC-E-0025_Rev-2 Page 11 of 29 Development Consultants Pvt. Ltd.
JINDAL POWER LIMITED
Specification for 11kV & 3.3kV Segregated Phase Busduct O.P. Jindal Super Thermal
Power Project (4 (SPBD) & Neutral Grounding Resistor (NGR) x600MW)
SCHEDULE – III
....................... Bidder's Name
LIST OF SPECIAL TOOLS AND TACKLE The Bidder shall tabulate below the item wise list of tools furnished by him for the operation and maintenance of the equipment supplied under this Specification and whose total cost has been indicated separately in PRICE TABULATION SHEET. Sl. No. Description Quantity Offered
1
2
3
4
5
6
7
8
9
10
The Bidder shall prepare this list separately for “Segregated Phase Busduct (SPBD) & Neutral Grounding Resistor (NGR) respectively.
Document No.: K8B15-SPC-E-0025_Rev-2 Page 12 of 29 Development Consultants Pvt. Ltd.
Specification for 11kV & 3.3kV JINDAL POWER LIMITED Segregated Phase Busduct
(SPBD) & Neutral Grounding Resistor (NGR)
O.P. Jindal Super Thermal Power Project (4 x600MW)
Document No.: K8B15-SPC-E-00025_Rev-2 13 of 29 Development Consultants Pvt. Ltd.
SCHEDULE – IV
……………….. Bidder's Name
DRAWING SUBMISSION SCHEDULE
Sl. No. Drawings Submission of drawings for approval from Effective Date of Contract (EDC) (in weeks)
1. 2. 3. 4. 5. 6. 7. 8. 9 10. The Bidder shall prepare this list separately for “Segregated Phase Busduct (SPBD) & Neutral Grounding Resistor (NGR) respectively. The Bidder shall prepare this list separately for “For Approval” and “For Reference” drawings/documents. The Bidder shall also furnish the time in weeks for resubmission of reviewed/commented drawings from Owner from the date of receipt.
Specification for 11kV & 3.3kV JINDAL POWER LIMITED Segregated Phase Busduct
(SPBD) & Neutral Grounding Resistor (NGR)
O.P. Jindal Super Thermal Power Project (4 x600MW)
Document No.: K8B15-SPC-E-00025_Rev-2 14 of 29 Development Consultants Pvt. Ltd.
SCHEDULE -V DEVIATION SHEET: TECHNICAL
........................ Bidder's Name
If the proposal has got any deviation from the Technical Specification, the Bidder shall tabulate these deviations clause by clause in this Schedule. Add more sheets, if required.
Clause No. D e v i a t i o n s
The Bidder shall furnish the list of deviations separately for “Segregated Phase Busduct (SPBD) & Neutral Grounding Resistor (NGR) respectively.
Specification for 11kV & 3.3kV JINDAL POWER LIMITED Segregated Phase Busduct
(SPBD) & Neutral Grounding Resistor (NGR)
O.P. Jindal Super Thermal Power Project (4 x600MW)
Document No.: K8B15-SPC-E-00025_Rev-2 15 of 29 Development Consultants Pvt. Ltd.
SCHEDULE -VI
DEVIATION SHEET: GENERAL CONDITION OF CONTRACT
....................... Bidder's Name
If the proposal has got any deviation from the tendering conditions and the General Conditions of Contract, the Bidder shall tabulate these deviations clause by clause in this Schedule. Add more sheets, if required.
Clause No. D e v i a t i o n s
Specification for 11kV & 3.3kV JINDAL POWER LIMITED Segregated Phase Busduct
(SPBD) & Neutral Grounding Resistor (NGR)
O.P. Jindal Super Thermal Power Project (4 x600MW)
Document No.: K8B15-SPC-E-00025_Rev-2 16 of 29 Development Consultants Pvt. Ltd.
SCHEDULE – VII
SALIENT EVALUATION CRITERIA
........................ Bidder's Name
Sl. No.
Description Contractual Commitment
Bidder’s offer Remarks
1. Technical Particulars of all segregated phase busducts & NGR as per Annexure-A offered (Yes/No)
Yes
2. Fittings and accessories as per Annexure B provided.
Yes
3. Mandatory Spares offered as per Annexure-D
Yes
4. Loss figures quoted for Busduct without any positive tolerance
4.1 No load loss in KW
…max
4.2 Load loss in KW
…max
5. Is Delivery Schedule as per specification accepted?
Yes
6. Whether complete scope of work offered?
Yes
7. Whether earnest money deposited?
Yes
8. Whether Schedule-I to Schedule-VIII of Proposal Exhibit duly filled-up?
Yes
9. Whether Schedule-IX to Schedule-XIV of Proposal Exhibit duly filled-up?
Yes
10. Validity of the Offer
11. Whether the busduct & NGR are guaranteed as per the general terms and conditions?
Yes
12. Whether LD clause as per general condition of contract accepted?
Yes
Specification for 11kV & 3.3kV JINDAL POWER LIMITED Segregated Phase Busduct
(SPBD) & Neutral Grounding Resistor (NGR)
O.P. Jindal Super Thermal Power Project (4 x600MW)
Document No.: K8B15-SPC-E-00025_Rev-2 17 of 29 Development Consultants Pvt. Ltd.
SCHEDULE – VII:
SALIENT EVALUATION CRITERIA (CONTD) ........................
Bidder's Name Sl. No.
Description Contractual Commitment
Bidder’s offer Remarks
13. Whether type test certificate of similar rated SPBD & NGR furnished with the bid?
Yes
14. Whether drawing/data/manual as asked in the specification each for SPBD & NGR furnished with the bid?
Yes
Specification for 11kV & 3.3kV JINDAL POWER LIMITED Segregated Phase Busduct
(SPBD) & Neutral Grounding Resistor (NGR)
O.P. Jindal Super Thermal Power Project (4 x600MW)
Document No.: K8B15-SPC-E-00025_Rev-2 18 of 29 Development Consultants Pvt. Ltd.
SCHEDULE – VIII
VENDOR RATING CRITERIA ........................ Bidder's Name
Sl. No. Description Bidder’s Compliance
Remarks
1 Whether bidder is manufacturer of SPBD & NGR? Yes/No
2
If not manufacturer, whether back to back guarantee furnished? Yes/No
3 Manufacture’s QAP accredited by.
4 No. of similar rated SPBD & NGR manufactured in last five (5) years.
…….. Nos.
5
No. of similar rated SPBD & NGR in operation. Furnish at least three (3) certificates of each equipment from different users …… Yes/No
…….. Nos.
6 Since when similar rated SPBD & NGR are being manufactured.
7 Whether similar rated SPBD & NGR type tested? Yes/No
8 Turnover of the manufacturer in last three (3) years
9
Turnover of the bidder in last three (3) years, if the bidder is not Original Equipment Manufacturer (OEM)
10 Details of current job booking of the OEM.
Specification for 11kV & 3.3kV JINDAL POWER LIMITED Segregated Phase Busduct
(SPBD) & Neutral Grounding Resistor (NGR)
O.P. Jindal Super Thermal Power Project (4 x600MW)
Document No.: K8B15-SPC-E-0008A 19 of 29 Development Consultants Pvt. Ltd.
PROPOSAL DATA – SECTION-IIIB
(TO BE SUBMITTED WITH PRICE BID)
SCHEDULE IX TO XIV
JINDAL POWER LIMITED
Specification for 11kV & 3.3kV Segregated Phase Busduct O.P. Jindal Super Thermal
Power Project (4 (SPBD) & Neutral Grounding Resistor (NGR) -DRAFT x600MW)
SCHEDULE-IX
........................ Bidder's Name
PRICE TABULATION SHEET 1. Bidder's Complete Company Name and address, tel no., fax no. and E-mail ID : 2. Bidder's Proposal Number : 3. Bidder's Proposal Date : 4. Bidder's Proposal Validity Period : 5. Bidder's Ex-works quoted price for the supply of 11KV, 3.3kV SPBD & NGR as specified (as per break-up below) properly packed for transportation (Price to be inclusive of all taxes and duties, but exclusive of transit insurance, spare parts, tools and charges for tests, if any. Rs. (A29+B31+C13) : A. 11 kV Segregated Phase Busduct
(Price for each length of busduct is inclusive of straight run, flexible terminal connector both at transformer end & at switchgear end, horizontal bend, vertical bend, wall frame assembly complete with mounting plate seal off bushing & flexible links, phase change over box (if any) & flexible joints for straight run as per Annexure-B, Bill of Material)
SL. No.
Busduct
identification
Busduct Rating (Amp)
Straight length along the center line of the
bus duct (meters) Price (Rs.)
1 1UT11SR1 2000 120 2 1UT21SR2 2000 120 3 2UT12SR1 2000 75 4 2UT22SR2 2000 60 5 3UT13SR1 2000 120 6 3UT23SR2 2000 120 7 4UT14SR1 2000 55 8 4UT24SR2 2000 70 9 1SR10SR1 2000 10
10 1SR20SR2 2000 10 11 2SR10SR3 2000 10 12 2SR20SR4 2000 10 13 3SR10SR5 2000 10 14 3SR20SR6 2000 10
Document No.: K8B15-SPC-E-0025_REV-2 20 of 29 Development Consultants Pvt. Ltd.
JINDAL POWER LIMITED
Specification for 11kV & 3.3kV Segregated Phase Busduct O.P. Jindal Super Thermal
Power Project (4 (SPBD) & Neutral Grounding Resistor (NGR) -DRAFT x600MW)
SL. No.
Busduct
identification
Busduct Rating (Amp)
Straight length along the center line of the
bus duct (meters) Price (Rs.)
15 4SR10SR7 2000 10 16 4SR20SR8 2000 10 17 1ST10SR1 3000 85 18 1ST20SR2 3000 85 19 2ST10SR3 3000 60 20 2ST20SR4 3000 60 21 3ST10SR5 3000 85 22 3ST20SR6 3000 85 23 0SR10SR5 3000 310 24 0SR10SR3 3000 45 25 0SR20SR4 3000 15 26 0SR20SR6 3000 375 27 0SR30SR7 3000 390 28 0SR40SR8 3000 390 29 0SR50SR7 3000 50 30 0SR60SR8 3000 40 31 RWT1SR01 2000 20 32 RWT2SR01 2000 20
33 11 kV Segregated Phase Busduct Total
B 3.3 kV Segregated Phase Busduct
(Price for each length of busduct is inclusive of straight run, flexible terminal connector both at transformer end & at switchgear end, horizontal bend, vertical bend, wall frame assembly complete with mounting plate seal off bushing & flexible links, phase change over box (if any) & flexible joints for straight run as per Annexure-B, Bill of Material)
SL. No. Busduct identification Busduct Rating Amp)
Straight length along the center line of the
bus duct (meters) Price (Rs.)
1 1KUAT1-1MSR1 3000 105 2 1KUAT2-1MSR2 3000 90
3 2KUAT1-2MSR1 3000 105 4 2KUAT2-2MSR2 3000 90
5 3KUAT1-3MSR1 3000 105 6 3KUAT2-3MSR2 3000 90
7 4KUAT1-4MSR1 3000 105 8 4KUAT2-4MSR2 3000 90
Document No.: K8B15-SPC-E-0025_REV-2 21 of 29 Development Consultants Pvt. Ltd.
JINDAL POWER LIMITED
Specification for 11kV & 3.3kV Segregated Phase Busduct O.P. Jindal Super Thermal
Power Project (4 (SPBD) & Neutral Grounding Resistor (NGR) -DRAFT x600MW)
SL. No. Busduct identification Busduct Rating Amp)
Straight length along the center line of the
bus duct (meters) Price (Rs.)
9 0KSAT1-0MSR1 1250 80
10 0KSAT2-0MSR2 1250 80 11 0KSAT3-0MSR3 1250 80
12 0KSAT4-0MSR4 1250 80 13 0KCHHT1-0MCHSR1 2500 20
14 0KCHHT2-0MCHSR2 2500 20
15 0KAFHT1-0MAFSR1 1250 20
16 0KAFHT2-0MAFSR1 1250 20
17 0GARHT1-0MARSR1 1250 20
18 0GARHT2-0MARSR1 1250 20
19 0KAWHT1-0MAWSR1 1250 20
20 0KAWHT2-0MAWSR1 1250 20
21 0KADHT1-0MADSR1 1250 20
22 0KADHT2-0MADSR1 1250 20
23 0GRTHT1-0MRTSR1 1250 15
24 0GRTHT2-0MRTSR1 1250 15
25 1MSR1 -1MSR2 3000 10
26 2MSR1-2MSR2 3000 10
27 3MSR1-3MSR2 3000 10
28 4MSR1-4MSR2 3000 10
29 0MSR1-0MSR2 1250 10
30 0MSR3-0MSR4 1250 10
31 0MCHSR1-0MCHSR2 2000 15
3.3 kV Segregated Phase Busduct Total
C. Neutral grounding Resistor (NGR)
Sl. No. Description Qty (Nos.) Price (Rs.)
1.
22.13 Ohms, 11000 V, 300 A for 10 seconds for Unit Transformers. 1KXYNG1, 1KXYNG2, 2KXYNG1, 2KXYNG2, 3KXYNG1 & 3KXYNG2, 4KXYNG1, 4KXYNG2.
Eight (8)
2
22.13 Ohms, 11000 V, 300 A for 10 seconds for Station Transformers. 0KXYNG1, 0KXYNG2, 0KXYNG3, 0KXYNG4, 0KXYNG5 & 0KXYNG6.
Six (6)
Document No.: K8B15-SPC-E-0025_REV-2 22 of 29 Development Consultants Pvt. Ltd.
JINDAL POWER LIMITED
Specification for 11kV & 3.3kV Segregated Phase Busduct O.P. Jindal Super Thermal
Power Project (4 (SPBD) & Neutral Grounding Resistor (NGR) -DRAFT x600MW)
3 22.13 Ohms, 11000 V, 300 A for 10 seconds for River Water Transformer. 0KRWNG1 and 0KRWNG2.
Two (2)
4 6.64 Ohms, 3300 V, 300 Amps for 10 seconds for Raw Water Transfer Transformers.0MRTNG1 and 0MRTNG2.
Two (2)
5 6.64 Ohms, 3300 V, 300 Amps for 10 seconds for 3.3kV Station Aux. Transformer.0MXYNG1, 0MXYNG2, 0MXYNG3 and 0MXYNG4.
Four (4)
6 6.64 Ohms, 3300 V, 300 Amps for 10 seconds for 3.3kV Ash Slurry Transformer.0MAPNG1 and 0MAPNG2.
Two (2)
Sl. No. Description Qty (Nos.) Price (Rs.)
7 6.64 Ohms, 3300 V, 300 Amps for 10 seconds for 3.3kV Ash Water Transformer.0MAWNG1 and 0MAWNG2.
Two (2)
8 6.64 Ohms, 3300 V, 300 Amps for 10 seconds for Ash Silo Transformer. OMASNG1 and 0MASNG2.
Two (2)
9 6.64 Ohms, 3300 V, 300 Amps for 10 seconds for Ash Dyke Transformer. 0MARNG1 and 0MARNG2.
Two (2)
10 6.64 Ohms, 3300 V, 300 Amps for 10 seconds for Fly Ash Compressor Transformer. 0MAFNG1 and 0MAFNG2.
Two (2)
11 6.64 Ohms, 3300 V, 300 Amps for 10 seconds for CHP Transformer. 0MCHNG1 and 0MCHNG2.
Two (2)
12
6.64 Ohms, 3300 V, 300 Amps for 10 seconds for Unit Auxiliary Transformer. 1MXYNG1, 1MXYNG2, 2MXYNG1, 2MXYNG2, 3MXYNG1, 3MXYNG2, 4MXYNG1 and 4MXYNG2.
Eight (8)
13 Neutral Grounding Resistor Total
6. Bidder's charges for : Rs.
a Transportation of equipment as
specified f.o.r. site
: Rs………………………………..
b Transit Insurance including 60 days
storage at site
: Rs………………………………..
7. Bidder's Charges for the Tests Specified
a.
: Rs………………………………..
b.
: Rs………………………………..
Total (a + b + ……)
: Rs………………………………..
Document No.: K8B15-SPC-E-0025_REV-2 23 of 29 Development Consultants Pvt. Ltd.
JINDAL POWER LIMITED
Specification for 11kV & 3.3kV Segregated Phase Busduct O.P. Jindal Super Thermal
Power Project (4 (SPBD) & Neutral Grounding Resistor (NGR) -DRAFT x600MW)
8. Bidder's charges for erection, testing & commissioning of
a. 11kV SPBD per mtr : Rs.
b 3.3kV SPBD per mtr : Rs.
c NGR : Rs.
Bidder's total charges for erection, testing & commissioning of (8a+8b+8c) :
9. Bidder's Total Price f.o.r. Site (Items 5 + 6 + 7+8)
: Rs………………………………..
10.
Bidder's charges for supply of special tools & tackle f.o.r. Site (inclusive of all taxes, duties & transit insurance)
:
Rs………………………………..
11.
Bidder's charge for supply of mandatory spare parts of SPBD & NGR f.o.r. Site (inclusive of all taxes, duties & transit insurance)
: Rs………………………………..
12.
Bidder's charge for supply of recommended spare parts for 3-years' operation f.o.r. Site (inclusive of all taxes, duties & transit insurance)
:
Rs………………………………..
13.
Bidder's Engineer's per diem charge for supervision of erection, testing and commissioning The price includes to & fro charges, all pocket expenses, lodging and boarding expenses.
:
Rs………………………………..
14. Prevailing rates on which quoted f.o.r. price is based :-
a. Ocean freight and Marine Insurance for imported items
:
b. Customs duty for imported items
:
c. Excise Duty
:
d. Sales Tax
:
e. Octroi Duty
:
f. Any other leviable taxes
:
g.
Freight & transit insurance :
15 Are the quoted price: -
15.1 Firm?
Document No.: K8B15-SPC-E-0025_REV-2 24 of 29 Development Consultants Pvt. Ltd.
JINDAL POWER LIMITED
Specification for 11kV & 3.3kV Segregated Phase Busduct O.P. Jindal Super Thermal
Power Project (4 (SPBD) & Neutral Grounding Resistor (NGR) -DRAFT x600MW)
15.2 If not, state
a. What is ceiling? b. Price variation formula with prevailing
rates of labour and materials (Add separate sheet, if required)
16. Is the Deviation Sheet filled up?
17. Prices of Items (if any) not included in the above quoted price
Document No.: K8B15-SPC-E-0025_REV-2 25 of 29 Development Consultants Pvt. Ltd.
JINDAL POWER LIMITED
Specification for 11kV & 3.3kV Segregated Phase Busduct O.P. Jindal Super Thermal
Power Project (4 (SPBD) & Neutral Grounding Resistor (NGR) -DRAFT x600MW)
SCHEDULE-X
PRICE BREAK-DOWN SHEET ........................ Bidder's Name
Since there may be addition or deletion of items on finalization of the Contract, the Bidder shall quote for break-down prices of items listed as below. The prices shall be firm and f.o.r. site inclusive of all taxes, duties and transit insurance. Sl. No. Description Unit Price f.o.r site
1.0 Terminal connector with adaptor box – Transformer end including flexible connector (set)
: Rs. …………………
2.0 Terminal connector with adaptor box– Switchgear end including flexible connector (set)
: Rs. …………………
3.0 Straight run – length along the center line of the bus duct (meter) of
: Rs. …………………
4.0 Horizontal bend (set) : Rs. ………………… 5.0 Vertical bend (set) : Rs. ………………… 6.0 Wall frame assembly complete with mounting plate seal off
bushing & flexible links (set) : Rs. …………………
7.0 Phase change over box (set) : Rs. ………………… 8.0 Galvanized structure for busduct support
Enclosure expansion bellows-straight run Enclosure expansion bellows-equipment terminal
: Rs. …………………
9.0 : Rs. ………………… 10.0 : Rs. ………………… 11.0 : Rs. …………………
Document No.: K8B15-SPC-E-0025_REV-2 26 of 29 Development Consultants Pvt. Ltd.
JINDAL POWER LIMITED
Specification for 11kV & 3.3kV Segregated Phase Busduct O.P. Jindal Super Thermal
Power Project (4 (SPBD) & Neutral Grounding Resistor (NGR) -DRAFT x600MW)
SCHEDULE-XI
SPARE PARTS PRICE SHEET ........................ Bidder's Name
The Bidder shall quote Mandatory spares for erection & commissioning and recommended spare parts for five (5) years’ continuous operation. The prices shall be to site inclusive of all taxes, duties, freight and transit insurance. Add more sheets, if necessary.
Quantity Offered (Nos.)
Total Price (Rs.)
Sl. No.
Description
Unit Price (Rs.)
Mandatory Spares
Recommended Spare
Mandatory Spares
Recommended Spares
1. 2. 3. 4. 5. 6. 7. 8. 9. 10.
Document No.: K8B15-SPC-E-0025_REV-2 27 of 29 Development Consultants Pvt. Ltd.
JINDAL POWER LIMITED
Specification for 11kV & 3.3kV Segregated Phase Busduct O.P. Jindal Super Thermal
Power Project (4 (SPBD) & Neutral Grounding Resistor (NGR) -DRAFT x600MW)
SCHEDULE-XII
SPECIAL TOOLS AND TACKLE PRICE SHEET ........................ Bidder's Name
The Bidder shall quote below item wise prices to site for tools and tackle furnished by him for the operation and maintenance of equipment supplied under this specification. The price shall inclusive of all taxes & duties, freight & transit insurance. Sl. No.
Description
Quantity
Unit Price F.O.R. (Rs.)
Total Price (Rs.)
1. 2. 3. 4. 5. 6. 7. 8. 9. 10.
Document No.: K8B15-SPC-E-0025_REV-2 28 of 29 Development Consultants Pvt. Ltd.
JINDAL POWER LIMITED
Specification for 11kV & 3.3kV Segregated Phase Busduct O.P. Jindal Super Thermal
Power Project (4 (SPBD) & Neutral Grounding Resistor (NGR) -DRAFT x600MW)
SCHEDULE-XIII
DEVIATION SHEET: PRICE ........................ Bidder's Name
Against each and every deviation from the Technical and commercial conditions as enumerated in Deviation Sheet : Technical & General condition contract, the amount by which the Bid Price will thereby be increased or decreased shall be given clause by clause in this Schedule. In case the amount is not mentioned in the Schedule against any of the deviation mentioned in Deviation Sheet, it will be taken for granted that the same does not involve any change in the Bid Price. Add more sheets, if required.
Amount by which the Bid Price will change Clause No.
Deviation, if any
Increase (Rs.) (+) Decrease (Rs.) (-)
Document No.: K8B15-SPC-E-0025_REV-2 29 of 29 Development Consultants Pvt. Ltd.
JINDAL POWER LIMITED
Specification for 11kV & 3.3kV Segregated Phase Busduct O.P. Jindal Super Thermal
Power Project (4 (SPBD) & Neutral Grounding Resistor (NGR) -DRAFT x600MW)
SCHEDULE -XIV
DECLARATION SHEET I, ............................ certify that all the above typed-in data and information pertaining to this specification are correct and are true representation of the equipment covered by our formal Proposal dated ............. I hereby certify that I am duly authorized representative of the supplier whose name appears above my signature. Bidder's Name : ............................... Authorised Representative's Signature : ............................... Authorised Representative's Name (Typed) : ............................... Manufacturer's Intent : The Manufacturer hereby agrees fully to comply with the
requirements and intent of this specification for the price indicated.
Authorised Representative's Signature : ..............................
Document No.: K8B15-SPC-E-0025_REV-2 30 of 29 Development Consultants Pvt. Ltd.