STATIC EXCITATION EQUIPMENT
SRATN
made by S.C. ICPE ACTEL S.A., ROMANIA, Bucharest
(Research Institute for Electrical Engineering - Electric Drives)
CATEGORY CODE
SRATNIEN/UENUPL - 1/2 - 3
S = systemR = regulationA = automatic
T = voltageN = digitalIEN = Excitation system rated current (Adc) - direct current at the excitation output
terminals which the excitation system can supply under defined conditions of
operation (taking in account the most demanding excitation requirements ofthe machine);
UEN = Excitation system rated voltage (Vdc) - direct voltage at the excitation outputterminals which the excitation system can provide when delivering excitation
rated field current;UP = Excitation ceiling voltage (Vdc) - The maximum direct voltage which the
excitation system is able to provide from its terminals under defined
conditions;1 = one rectifying bridge (without redundancy in the power circuit)
2 = two rectifying bridges (100% redundancy)3 = excitation transformer (installed in cubicle), for excitation current over 50ADC.
-
7/30/2019 Icpe Actel - Presentation of Sratn
2/18
STATIC EXCITATION EQUIPMENTSRATN ICPE-ACTEL SA
2
The parametrization range offered by ICPE ACTEL for Static ExcitationEquipment is:
Three-phase supply voltage (Usupply) +10%, -15%: 3x400Vac or another
voltage, by means of a transformer.
Rated power (PN). Generator: 3...330MW; Motor: 100kW...8MW.
Maximum rated excitation current (IEN max). Generator: 3200Adc; Motor:
1600Adc.
Rated excitation voltage (UEN): related to synchronous machine excitation
parameters.
Control accuracy: 0,5%.Maximum forcing coefficient for current and voltage: 2.
Based on the support of its highly qualified specialists, ICPE ACTEL has focused
its activities on offering not only products, but also complete solutions, custom
made to meet the clients requirements, for normal and extreme climate.
Our products are always accompanied by technical assistance and additionalservices throughout their entire lifespan, from drawing-up of then application
up to the client training.
SRATN is found in almost all hydro and steam power plants in Romania. ICPE
ACTEL has also exported such equipment in: France, Turkey, India, Republic of
Moldavia, Kenya, Thailand and Vietnam.
Concerning the applications ofSRATN for synchronous motors, some references
are as follows: Iraq, Republic of Moldavia, Arcelor Mittal- Galati, Romgaz
Medias, Hidroelectrica and SNCF (Railway National Society) in Romania.
ICPE ACTEL is a reliable long-term partner.
-
7/30/2019 Icpe Actel - Presentation of Sratn
3/18
STATIC EXCITATION EQUIPMENTSRATN ICPE-ACTEL SA
3
Static excitation equipment provides supply, control and protection ofsynchronous machine excitation: generators in hydro and steam power plants and
synchronous motors for various applications.
They ensure a stable and safe operation of synchronous machines, especially
relevant when these machines are connected to the public mains, characterized by alot of perturbations due to connecting and disconnecting of important loads, short-
circuit, etc.
Common applications are:
- supply of the generator's field windings in hydro and steam power plants,connected to a public mains;
- supply of synchronous motor's field windings for applications such as fans,air compressors, debit pumps, water feed pumps.
The excitation system provides the dc power supply required by the
synchronous machine field circuit to meet the specified ratings and operating ranges
of the generator/motor for all operating condition.
The excitation system is a static type. Its main power device consists in 3-
phase full wave thyristor rectifier bridges supplied from the ac terminals of the
synchronous generator/ motor or from an independent power supply.
The excitation system has a microproccesor based digital type automaticvoltage regulator and rectifier control that brings the suitable operating stability for
the synchronous generator/motor.
ADVANTAGES
Static excitation equipment, fitted with a digital control solution, ensures:
- higher stability of parameters related to electromagnetically perturbations andenvironmental condition variations;
- user friendly interface, with many settings and diagnosis options;- strict monitoring of internal and external failures, that lead to equipment
tripping;
- possibility of complete remote control;- enhanced reliability;
-
7/30/2019 Icpe Actel - Presentation of Sratn
4/18
STATIC EXCITATION EQUIPMENTSRATN ICPE-ACTEL SA
4
WHY ICPE ACTEL?
- Higher safety of the operating process, due to digital control and significantsubassembly redundancy;
- Enhanced availability and competence in custom-made equipment (functions,special environment conditions, new design alternatives on demand);
- Possibility of intervention, software programming and license granting for theoperating mode parameter setting;
- Enhanced efficiency;- Higher availability through additional preset options;- Advanced diagnostic capabilities for failure analysis;- Cost saving and oriented solution in accordance with the clients budget;- Technical assistance throughout the entire product lifespan from mounting to
post guarantee service.
-
7/30/2019 Icpe Actel - Presentation of Sratn
5/18
STATIC EXCITATION EQUIPMENTSRATN ICPE-ACTEL SA
5
FUNCTIONAL DESCRIPTION
Static excitation equipment, especially in hydro and steam power plants
represents a complex type of product, meant to provide the control and protection of
synchronous machine excitation in a large range of perturbations and in compliance
with the requirements of electric generators correct running.The technology of public mains is, by itself, a complex process, which has to face
several specific perturbations, such as the connecting and disconnecting of
important inductive loads, local and remote short-circuits, sudden unloading,
automatic turn-on of stand-by equipment.
The power supply systems, with static excitation equipment as their core,have to operate very stably and safety, in the event of such perturbations.
Static excitation equipment is meant to preserve generator set-points with high
accuracy, in strict respect of its stability diagrams (synchronous machine limit
values, cross current criterion, line drop compensation criterion, etc.) and provide avery accurate dynamic regime.
-
7/30/2019 Icpe Actel - Presentation of Sratn
6/18
STATIC EXCITATION EQUIPMENTSRATN ICPE-ACTEL SA
6
SRATNBloc Diagram (example)
3x...kV/3x...V
TTA...kVA
3x...kV/....V
3x...kV/3x...V
10VA
I
=........A
x
ne
U
=......V
nex
Pn=.....MW
Un=.....kV
In=........A
cos
=......
+Ex
Fieldflash
voltagedc/ac
Digitalinput
signals
SRATNEXCITATION
SYSTEM
10VA
GeneratorCircuitBreaker
BRIDGE1
BRIDGE2
DCGN=Digitalfiringpulsesboard
DCGN
PLC
AVR1
Measuring
Board
PLC
AVR2
BRIDGE1,BRIDGE2-fullwaveth
yristorrectifiers
AVR1,AVR2-PLCwithAutomaticV
oltageRegulator
MAN1,MAN2-PLCwithFieldCurrentRegulator
FFC-FieldFlashCircuit
FDC-FieldDischargeCircuit
......A/....A
DCGN
DCGN
PLC
MAN1
Operating
panel
Measuring
Board
Measuring
Board
PLC
MAN2
Measuring
Board
Optionaldevices
FFC
FDC+
Crowbar
DCGN
TTA...kVA
3x...V/....V
Auxilia
ry
power
supply
dc/ac
Digitaloutput
signals
Analogoutput
signals
Comunication
forSCADA
RS232
RS485
RJ45
-
7/30/2019 Icpe Actel - Presentation of Sratn
7/18
STATIC EXCITATION EQUIPMENTSRATN ICPE-ACTEL SA
7
Rectifier power supply voltage : Max 3 x 750V AC. +20% , -20%
Power supply frequency: 50Hz 5%
Field flash power supply: - from the power plant battery
- from the auxiliary ac power supply
Control electronics power supply
voltage
- 3 x 400V/ 230 (Vac)// max 10A
- power plant battery 24/ 110/ 200 (Vdc) // max10AMaximum output voltage: Minimum 1,2*U supply
Forcing in current: Minimum 1.8*In excitation for 30 sec
Forcing in voltage: Minimum 1.8*Un excitation
Control Modes: AVRVOLTAGE REGULATOR
POWER FACTOR REGULATOR
REACTIVE POWER REGULATOR
MANUAL:
CURRENT REGULATOR (FCR)
VOLTAGE REGULATOR (AVR)
mode has the following control
loops:
- control for machine voltage
- maximum field current limitation with inverse time
delay characteristic;
- stator current limitation with inverse time delay
characteristic for leading or lagging working of the
machine;
- lead or lag reactive power working limitation,
according to the real power;
- V/Hz limiter
- load (cross) current compensation;- soft start;
- power system stabilizer - PSS1A/ PSS2A;
POWER FACTOR REGULATOR
(APFC) mode has the following
control loops:
- control for (cos)
- maximum field current limitation with inverse time
delay characteristic;
- stator current limitation with inverse time delay
characteristic for leading or lagging working of the
machine;
- limitation of the minimum and maximum generator
voltage;
REACTIVE POWER
REGULATOR (kVAR) mode has
the following control loops:
- control for reactive power
- maximum field current limitation with inverse time
delay characteristic;
- stator current limitation with inverse time delay
characteristic for leading or lagging working of the
machine;
- limitation of the minimum and maximum generator
voltage;
CURRENT REGULATOR (FCR)
mode mode has the following
control loops:
- control for field current
- limitation of the regulator output
-
7/30/2019 Icpe Actel - Presentation of Sratn
8/18
STATIC EXCITATION EQUIPMENTSRATN ICPE-ACTEL SA
8
Starting sequence in case of field
flash
After the generator reaches 90% of its rated speed the
start command is followed by the following actions:
- the field is supplied from an auxiliary powersupply until the generator voltage reaches over
50% of the rated value then the excitation
equipment is supplied from the excitationtransformer connected to generator terminals.
Starting sequence of synchronous
motors
- Asynchronous mode start on a starting resistor with
adjustable final level of sliding.
Field discharging - During operational shut-down the field is discharged
by inverter operation of the thyristor converter;
- In case of excitation or machine fault, the synchronous
machine will be de-energized using the field discharge
circuit.Protections
by bimetallic switch Field discharge breaker fault (field discharge resistor
over-temperature)
by PLC Generator over-voltage
Excitation over-current
Loss of field excitation current
by Earth Fault Relay Generator field ground protection
by Overcurrent Relays Transformer over-current
Cooling Natural/ 2 fans for each rectifier.
-
7/30/2019 Icpe Actel - Presentation of Sratn
9/18
STATIC EXCITATION EQUIPMENTSRATN ICPE-ACTEL SA
9
A. The Power circuit contains (depending of the synchronous machine type):
1. Excitation transformerThe excitation transformer can be fed from the synchronous machine terminals or
from another power supply. The excitation transformer equipment can be fitted with
protection devices and/or switching devices.
2. Full wave thyristor rectifier bridge (1 or more);The rectifier equipment includes the following:
- Rectifier firing circuits;
- High speed over-current fuses to protect the thyristors in the event of short-circuit;- Transient voltage surge protection on the rectifier (resistor-capacitance circuit);
- Cooling equipment (if applicable);
- Optional: disconnecting switches on the input and output of the rectifiers;
3. Field discharge circuit.The field discharge circuit includes the following:- Static breaker for field discharging and crowbar for dc voltage surge protection;
- Field discharge resistor connected across the field to de-energize the generator as
fast as possible.
- Optional: DC circuit breaker one-pole or two-poles with field discharge contact.
4.
Field flashing circuit.The field discharge circuit can be feed from the power plant battery or from an AC
auxiliary power supply. The circuit consists in:
- Transformer and rectifier (AC power supply type field flash circuit);
- DC contactor;
- Blocking diode;
- Field flashing current limiting resistor;
5. Synchronous motor starting circuit.- Starting resistor;
- Short circuiting contactor for the starting resistor;- Synchronism sensing device;
-
7/30/2019 Icpe Actel - Presentation of Sratn
10/18
STATIC EXCITATION EQUIPMENTSRATN ICPE-ACTEL SA
10
B. The Control circuits are divided in:- Internal power supply circuits
- Regulating circuits (inside PLC): set points circuits; control loops and limitation
circuits in AUTOMATIC mode: AVR/APFC/kVAR; control loop and limitation
circuits in MANUAL mode- Measurement circuits
- Thyristors firing pulses generation circuits
- Protection circuits for the rectifier and control devices (by protection relays and
PLC)
- Internal power supplies circuitsThe supply of the PLC and the other control devices is made with the constant
voltage: +24V.
This voltage is obtained from 230VAC (auxiliary power supply) and from 110 (220)Vdc (battery supply), using switch mode power supplies. The switch mode power
supplies output are connected in parallel separated through diodes (common
cathode).
- Regulating circuits (inside PLC)set points circuits
Set point value in the AUTOMATIC or MANUAL mode is computed inside the
PLC. Every regulator has a register in the PLC that represents the set point value.
The range of the set point is between a minimum and a maximum value. Thesevalues can be set from the PLCs operating panel (HMI).
The variation speed of the set point between minimum and maximum value, on the
increase or decrease command, can be set from the PLCs operating panel (HMI).
control loops and limiting functions in AUTOMATIC mode
- control of the machine voltage regulator (AVR with load/ cross current correction
of the voltage set point)- control of the machine reactive powerQ regulator
- control of the machine power angle (factor)
(cos ) regulator
- time limitation of the maximum field current - field current limitation is activated
when field current is higher than a threshold value (usually 1.15Iex rated) . PLC
begins to compute the diagram (I2t) and when the time exceeds the calculated time,
the regulator output is modified so that the field current will be lowered to the rated
value. The threshold current value, the ceiling current definite time and the time
break after a forcing can be set as parameters.
- instantaneous limitation of the maximum field current (for synchronous
generators) - field current limitation is activated when the generator is connected to
the grid and the generator voltage in lower than the grid voltage in case of a near
short-circuit (at generator terminals or generator transformer).
-
7/30/2019 Icpe Actel - Presentation of Sratn
11/18
STATIC EXCITATION EQUIPMENTSRATN ICPE-ACTEL SA
11
- time limitation of the maximum stator current - stator current limitation is
activated when the stator current is higher than a threshold value (between 0.8 ...
1.5Is rated). PLC begins to compute the diagram (I2t) and when the time exceeds the
calculated time, the regulator output is modified trying to lower down the stator
current below the rated value. The threshold current value, the ceiling currentdefinite time and the time break after a forcing can be set as parameters.
- limitation of the reactive power (only in AVR mode)- the reactive power value can
be compute with the following formula:
QM - Qm
Q* = QM - P -------------- ,
Pn
Qm = the reactive power value at rated active
power;QM - the reactive power value at active power= 0.
These values can be set from HMI for both leading and lagging working.
If the reactive power is higher (in lagging working) or lower (in leading working)
than Q* value, the PLC modifies the regulator output, so that the reactive power tochange to the Q* value.
- voltage matching (for synchronous generators) in order to start the
synchronization and the paralleling process the excitation system can performed the
voltage matching between the generator and line voltages.
- V/HZ limiter (for synchronous generators) to cause the regulated voltage to
decrease in proportion with the ferquency reduction, if frequency falls below a
predetermined value.
control loop and limiting in MANUAL mode
- control of the field current - excitation current regulator
tracking and switching between functioning (control) modes(AUTO-MANUAL)
The tracking between the 2 control modes is made thus:
- if the equipment functioning mode is MANUAL, in the AUTOmatic
regulator (AVR, Q, cos ) set point register is written all time the feedback motor
voltage value (Q or cos ). This value is the set point for the AUTOC regulator that
is not in function. When the switching command is received from MANUAL to
AUTO mode, it is done with a special care for the AUTO regulator output to be the
same with MANUAL set point register.
- if the equipment functioning mode is AUTO mode, in the MANUAL setpoint register is written all time the feedback field current. The switch to MANUAL
mode can be done any time without any cautions.
-
7/30/2019 Icpe Actel - Presentation of Sratn
12/18
STATIC EXCITATION EQUIPMENTSRATN ICPE-ACTEL SA
12
At switching command, the HMI displays the selected mode and enables or disablesthe corresponding control loops of the chosen mode.
If the excitation equipment is ON, a fault in the feedbacks measurement circuit (U,
Is or cos ) doesn't allow the equipment to function in the AUTOMATIC control
mode. The control mode will be switched to MANUAL mode or the switch to
AUTO mode will not be allowed
- Measurement circuitsIn order to obtain the feed-back for UM, IM, Q, P, f, the equipment receives from the
machine the following signals:
-3x100 (110) Vac - UM (star or V connection diagram);-3x5(1) Aac - IM (star or V connection diagram);
The excitation system has processor based devices that adjust and compute the
electric feedback measures needed for the control loops of the AVR and FCR.
- Thyristors firing pulses generation circuitsUsually the excitation equipment has 2 thyristor firing pulses generating devices.The equipment automatically switches on the channel 2 if channel 1 is in fault.
The thyristors firing pulses are generated to be synchronous with the power supply
voltage. The firing pulses are moving in accordance with the command voltage U .
The thyristor firing pulse generating devices are equipped with a processor that
supervises thyristors firing pulses (their presence), the synchronization voltages andthe presence of the power supply.
- Protections circuitsThe PLC receives signals from different devices that supervise the high speed fuses,
the fans, the rectifier and transformer temperature, the field discharging circuit and
the field flashing circuit, etc.
Machine protections
a. Stator overvoltageb. Excitation overvoltage (59F)c. Excitation overcurrent (overexcitation 40)d. Loss of field excitation current (40)
Synchronous motor protections
e. Elapsing synchronism time (stall time)f. Asynchronous working protection (pull out)g. Restarting protectionh. AVR feedback measurement loss protection with switching on the MANUAL
control mode (field current regulator)
-
7/30/2019 Icpe Actel - Presentation of Sratn
13/18
STATIC EXCITATION EQUIPMENTSRATN ICPE-ACTEL SA
13
C. Sundries features- Local commands (increase, decrease, functioning modes selections, test
functions) and Local signalizations are performed using a HMI key-pad or touch
screen operating panel and/or push buttons and pilot lights.
On the HMI there are also displayed the fault log, the parameters set, the electric
measurements.
HMI screens example
- The discrete input and output signals for remote control are isolated by control
relays.
- On the Excitation System the following Internal Tests can be performed with
equipment switched off.
- Static Breaker Test (indicates if static breaker is healthy)
- Rectifier Test (indicates weather the rectifier bridges and the thyristors firing pulse
generation boards are healthy).
- Communication facilities:Ports: RS232/ RS485, RJ45
Communication protocols: ModbusRTU, Profibus, Ethernet TCP/IP, DF1.
-
7/30/2019 Icpe Actel - Presentation of Sratn
14/18
STATIC EXCITATION EQUIPMENTSRATN ICPE-ACTEL SA
14
CONSTRUCTIVE DESCRIPTION
The equipment is usually manufactured as a metal cabinet with front and back
doors. The colour, dimmensions and protection degree are depending of the
custommer requirements.
OVERALL DIMENSIONS
The overall dimensions depend on the rated field current of the synchronous
machine and the requested custom design.
For standard types, the dimensions (L x l x H) are:- for current up to 50Amps 800x800x(17002300)mm- for current over 50Amps with 100% redundancy in rectifying bridges
2400x800x2100mm
ENVIRONMENTAL CONDITIONS
operating temperature range: -100C...+40
0C
storage temperature range: -250C...+55
0C
maximum relative humidity: 80% (at 300C)
maximum altitude: 1000m above sea level (over 1000m, the current decreases
by 0,5% at each extra 100m)
PROTECTION DEGREE
The protection degree is: IP20IP54
ELECTRIC and ELECTRONIC DEVICES
The control circuits are developed using the resources of the PLC's
(Micrologix made by Allen Bradley or 313C made by Siemens)The thyristor bridge is designed and built at our company using Semikron
thyristors.
Inside the equipment it can be found several PCB's designed and planted at
our plant facilities.
Also it can be found electric devices as transducers, different protectionrelays, synchronization relay, relays, switch breakers, circuit breakers made by
Phoenix Contact, Deif, ABB, Schneider Electrique, Aeton, Siemens, Microelettrica
Scientifica, Bender, etc.
The HMI can be a key-button or/and touchscreen type, a color, grayscale, or
monochrome display, available in 315 in. size.
-
7/30/2019 Icpe Actel - Presentation of Sratn
15/18
STATIC EXCITATION EQUIPMENTSRATN ICPE-ACTEL SA
15
QUALITY ASSURANCE
Static excitation equipment operates in compliance with "SR EN ISO 9001:2001"
quality management system, concerning the design, development, production,
installation and servicing.
The company is also certified for SR EN ISO 14001:2005 environmental
management system and OHSAS 18001:2004 occupational health and safetymanagement system.
SERVICE
consulting for application definition;
custom solution design;
technical assistance at mounting and commissioning;
service within and post guarantee;
customer personnel training;
OPTIONALS
stand-by equipment, as presented in the functional description;
firing circuit, as presented in the functional description;
exciter transformer, powered from generator terminals;
rotor earth fault relay;
stand-by rectifying bridges;
AC and DC disconnecting switches for each rectifying bridge (in additional
cubicle);
Current balancing coils for two rectifier bridges power circuit;
Communication circuit optical fiber for SCADA compatibility.
-
7/30/2019 Icpe Actel - Presentation of Sratn
16/18
STATIC EXCITATION EQUIPMENTSRATN ICPE-ACTEL SA
16
FUNCTIONAL CHARACTERISTICS OF THE EXCITATION SYSTEM - SRATN
1. Resolution for measures acquisition 14bits2. Regulation accuracy
-
7/30/2019 Icpe Actel - Presentation of Sratn
17/18
STATIC EXCITATION EQUIPMENTSRATN ICPE-ACTEL SA
17
INTERNAL FAULT SIGNALS MESSAGES DISPLAYED ON THE HMI
1. Power supply missing or synchronisation voltages missing2. Thyristors firing fault3. High speed fuse fault4. Static breaker fault or overtemperature on the field discharge resistor5. Thyristors over temperature6. Fans power supply fault7. Measuring circuit fault8. Auxiliary power supply missing9. Excitation transformer overcurrent10. Fault on the AUTOMATIC control channel and switch on
the MANUAL control channel
ELECTRIC MEASURES DISPLAYED
1. Field current2. Field voltage3. Stator voltage4. Stator current5. Power factor6. Active power7. Reactive power
MINIMUM DIGITAL INPUTS
1. Main Circuit Breaker position2. START commandlocal or remote3. STOP commandlocal or remote4. EMERGENCY STOP command from machine protections5. INCREASE SETPOINTlocal or remote6. DECREASE SETPOINTlocal or remote
SUPPLEMENTARY for SYNCHRONOUS GENERATOR
7. GENERATOR SPEED >90%
MINIMUM DIGITAL OUTPUTS
1. EXCITATION ON2. EXCITATION OFF3. INTERNAL FAULT4. INTERNAL WARNING5. Limitation functions activated
OPTIONAL for SYNCHRONOUS MOTOR
MCB SWITCH ON command
MCB SWITCH OFF command(MCBmotor circuit breaker)
-
7/30/2019 Icpe Actel - Presentation of Sratn
18/18
STATIC EXCITATION EQUIPMENTSRATN ICPE-ACTEL SAREFERENCE LIST:
Excitation equipments for synchronous generators - export
Someshwara - India - 3 pcs. SRAT-N 13A/48V 2004
Ranganatha - India3 pcs. SRAT-N 11A/23V 2005Ambuthirtha - India2 pcs. SRAT-N 17A/36V 2005
Middle Kollab - India2 pcs. SRAT-N 862A/85V 2006
Varahi - India2 pcs. SRAT-N 862A/85V 2007
Gezende - Turkey - 1pc. SRAT-N 883A/110V 2008
Somanamaradi - India - 1pc. SRAT-N 16.8A/39V 2008
Kang Krachan - Thailand - 1pc. SRAT-N 1000A/ 186V 2009
Tana Kenya2 pcs.2 pcs.
SRAT-N 17A/31VSRAT-N 20A/40V
2009
Motz France2 pcs. SRAT-N 16A/30V 2010
Nam La - Vietnam - 3 pcs. SRAT-N 15A/30V 2011
Om Power - India - 2 pcs. SRAT-N 15A/30V 2011
Song Giang - Vietnam - 2 pcs. SRAT-N 871A/93V 2011