Fire and Smoke damper standards
Vance Rowe
Presentation Overview
➢Overview of standards➢Background
➢Changes to AS1682 and referenced standards➢General Changes
➢Installation Overview➢General requirements
➢Product testing➢Fire dampers➢Smoke dampers
➢Summary
Watch the timer!!!!
AUS
Building Code
NBCC
AS 1668.1
(2015)
AS 1682.1 & 1682.2
(2015)
AS 1530.4 (2014)
AS 1530.7 (2007)
Fire/Smoke/Air Damper Standard
Fire & Smoke Control
Testing Standards
National & Local Building Code
Installation Label
damper frame, blades
Fire
Barrier
mounting sleeve
retaining flanges
Section through a wall opening
Total expansion gap (both sides added together) must be as tested but generally follows the rule: 10mm plus 1% of A
Must be at least minimum of prototype tested!!!
No Packing required for our dampers!! However if requiredMust have a fusion temperature greater than 1000 deg C
Retaining flanges
2 x maximum expansion Gap
Fixings to sleeve &Not to wall
position
Blade Pack when closed inside fire barrier cavity
Rigid Joint
Duct Joints
Break-away Joint
retaining flanges
Oversize hole & penny washer
Suggested Solution to one sided fixing SMACNAIn standard as acceptable variation see 1682.2
This side inaccessible, eg riser
250 mm motor side only
protrusion
DAMPER ACCESS
Drop testafterInstallationAS1851-2012
AS1682.2 states the structural adequacy of the fire barrier must be maintained.
The standard is clear that where dampers are installed less than 75mm from a adjacent wall, ceiling slab or floor slab. The installation shall comply with the fire test or opinion.
Four hour time-temperature curve
Multi- Section Dampers
Must be tested –opinionsNo longer valid
Sub- Standard Installation Examples