Electrical System AnalysisPrepared For:
Sabino Electric, Inc.
Page of1 1
VR_230-667191 69kV Voltage Regulators / 1 Problem 1 Corrected69kV Voltage Regulators
TRO2_5 -667194 SES-3 / 1 Problem None Corrected5-15kV Oil Filled Transformers 501-5000 kVA
TRD_250 -667193 T-001 / 1 Problem None CorrectedTransformer Dry - <=600V => 250 kva
SWG_MCCB-66718 Switchgear Molded Case Breakers > 400A /Switchgear Molded Case Breakers > 400A
SWG_DRAW-66718 MCC-2 / 1 Problem None CorrectedSwitchgear Drawout Breakers
SWG_DISC-667184 Chiller-2 /Switchgear Safety Disconnects > 400A
MVDO-001-667192 MV Drop Out Fuse / 1 Problem None CorrectedMV Drop Out Fuse
Motors <= 50hpMOT_50 -667190 P-1 / 1 Problem None Corrected
BCP_400A-667187 LP-1 /Branch Circuit Panel <= 400 amp
ATS_401A-667195 ATS /Auto Transfer Switch > 400A
(t) Main Electrical
Agreement: t-Training 1Site Name: Sabino Electric, Inc.
Sabino Electric Inc.945 W 29th StreetTucson, AZ 85713
Equipment Item ProblemCount Summary
Location Within FacilityEquip Tag ID Equipment Item Description / Equipment Type Problem Count
Site Visit Dates: Sep 5, 2013 - Sep 9, 2013Site Visit Status: Completed
Page of1 5
BCP_400A-667187 - LP-1 Branch Circuit Panel <= 400 amp
Serial #: Manufacturer: Model:
ITE E0612ML1125F
ATS_401A-667195 - ATS Auto Transfer Switch > 400A
Serial #: Manufacturer: Model:
Tag ID: Equipment Type:
Tag ID: Equipment Type:
S&C Padmount Equipment PMH-9 with ATS
(t) Main Electrical
May 4, 2015 Equipment Inventory - Short Form with Images
Sabino Electric, Inc. - t-Training 1
Sabino Electric Inc.945 W 29th StreetTucson, AZ 85713
Page of2 5
MVDO-001-667192 - MV Drop Out Fuse MV Drop Out Fuse
Serial #: Manufacturer: Model:
U/A 122412
MOT_50 -667190 - P-1 Motors <= 50hp
Serial #: Manufacturer: Model:
Tag ID: Equipment Type:
Tag ID: Equipment Type:
SNT-121212 Baldor Industrial Motors EM3311T
(t) Main Electrical
May 4, 2015 Equipment Inventory - Short Form with Images
Sabino Electric, Inc. - t-Training 1
Sabino Electric Inc.945 W 29th StreetTucson, AZ 85713
Page of3 5
SWG_DRAW-667186 - MCC-2 Switchgear Drawout Breakers
Serial #: Manufacturer: Model:
Westinghouse SPB50
SWG_DISC-667184 - Chiller-2 Switchgear Safety Disconnects > 400A
Serial #: Manufacturer: Model:
Tag ID: Equipment Type:
Tag ID: Equipment Type:
Square D Company QMB-363-TW
(t) Main Electrical
May 4, 2015 Equipment Inventory - Short Form with Images
Sabino Electric, Inc. - t-Training 1
Sabino Electric Inc.945 W 29th StreetTucson, AZ 85713
Page of4 5
TRD_250 -667193 - T-001 Transformer Dry - <=600V => 250 kva
Serial #: Manufacturer: Model:
SQUARE D (CAT) 1205957625
SWG_MCCB-667185 - Switchgear Molded Case Breakers > 400A Switchgear Molded Case Breakers > 400A
Serial #: Manufacturer: Model:
Tag ID: Equipment Type:
Tag ID: Equipment Type:
(t) Main Electrical
May 4, 2015 Equipment Inventory - Short Form with Images
Sabino Electric, Inc. - t-Training 1
Sabino Electric Inc.945 W 29th StreetTucson, AZ 85713
Page of5 5
Tag ID: Equipment Type:
VR_230-667191 - 69kV Voltage Regulators 69kV Voltage Regulators
Serial #: Manufacturer: Model:
Ohio Brass Company #560
Tag ID: Equipment Type:
TRO2_5 -667194 - SES-3 5-15kV Oil Filled Transformers 501-5000 kVA
12345678 SQUARE D (cat)14662777-001Serial #: Manufacturer: Model:
(t) Main Electrical
May 4, 2015 Equipment Inventory - Short Form with Images
Sabino Electric, Inc. - t-Training 1
Sabino Electric Inc.945 W 29th StreetTucson, AZ 85713
Tuesday May 5 13:17:14 MST 2015 Equipment Inventory Sabino Electric Inc.
Page of1 13
Tag ID: ATS_401A-667195 Item Desc: ATSSerial #: Equip Type: Auto Transfer Switch > 400A
Equipment Location: (t) Main Electrical
Agreement: t-Training 1Site Name: Sabino Electric, Inc.
Mfg: S&C Padmount Equipment Model: PMH-9 with ATS
Safety Notes: See Attachments
Frequency 60 HertzRating Factor 95% Unitless
BIL 95% KVolts
Class 3 UnitlessAccuracy Class 99% Unitless
NFPA 70E: Emergency Feeder Conductor Length 200' FeetNFPA 70E: Normal Conduit Type and Size 4" PVC Inch
NFPA 70E: Normal Feeder Conductor Length 4" PVC Feet
Emergency Feeder Conductor Size/Type/Al-Cu 4/0 Cu UnitlessLoad Side Feeder Conductor Size/Type/Al-Cu 40' Unitless
NFPA 70E: Emergency Conduit Type and Size 4" PVC Inch
Normal Supply Conductor Size/Type/Al-Cu 4/0 Cu kcmil/gaugeNumber of Poles 3 Text
Current Rating 200 Amps
Ratio 20:1 Unitless
Working Voltage 13,800 Volts
Ambient Temperature 32*C degrees CHumidity 30% %
AIC Rating 65 KAmps
NEMA Type 3R NEMAControl Voltage 120 Volts
Specifications Value Unit
Application:
Tuesday May 5 13:17:14 MST 2015 Equipment Inventory Sabino Electric Inc.
Page of2 13
.002
.002
.002
.002
.002
.002
.002
.002
.002
.002
.002
.002
.002
.002
.002
.002
.002
.002
.002
.002
.002
.002
.002
.0022TΩ2TΩ2TΩ2TΩ2TΩ2TΩ2TΩ2TΩ2TΩ2TΩ2TΩ2TΩ2TΩ2TΩ2TΩ2TΩ2TΩ2TΩ2TΩ2TΩ
[D] ATS Emergency Contact Resist. C As Left/uOhms[D] ATS Emergency Contact Resist. B As Left/uOhms[D] ATS Emergency Contact Resist. A As Left/uOhms[D] ATS Emergency Contact Resist. C As Found/uOhms[D] ATS Emergency Contact Resist. B As Found/uOhms[D] ATS Emergency Contact Resist. A As Found/uOhms[D] ATS Normal Contact Resistance B As Left/uOhms[D] ATS Normal Contact Resistance C As Left/uOhms[D] ATS Normal Contact Resistance C As Found/uOhms[D] ATS Normal Contact Resistance B As Found/uOhms[D] ATS Normal Contact Resistance A As Left/uOhms[D] ATS Normal Contact Resistance A As Found/uOhms[D] ATS Phase B as Left Load/uOhms[D] ATS Phase C as Left Load/uOhms[D] ATS Phase A as Left Load/uOhms[D] ATS Phase C as Found Load/uOhms[D] ATS Phase B as Found Load/uOhms[D] ATS Phase A as Found Load/uOhms[D] ATS Phase C as Left Line/microohms[D] ATS Phase C as Found Line/microohms[D] ATS Phase B as Left Line/microohms[D] ATS Phase B as Found Line/microohms[D] ATS Phase A as Left Line/microohms[D] ATS Phase A as Found Line/microohms[D] ATS N-G Emergency/Megohms[D] ATS N-G Normal/Megohms[D] ATS C-N Emergency/Megohms[D] ATS C-N Normal/Megohms[D] ATS B-N Emergency/Megohms[D] ATS B-N Normal/Megohms[D] ATS A-N Emergency/Megohms[D] ATS A-N Normal/Megohms[D] ATS B-C Emergency/Megohms[D] ATS B-C Normal/Megohms[D] ATS A-C Emergency/Megohms[D] ATS A-C Normal/Megohms[D] ATS A-B Emergency/Megohms[D] ATS A-B Normal/Megohms[D] ATS C-G Emergency/Megohms[D] ATS C-G Normal/Megohms[D] ATS B-G Emergency/Megohms[D] ATS B-G Normal/Megohms[D] ATS A-G Emergency/Megohms[D] ATS A-G Normal/Megohms
9/5/2013TM - Variable/Unit
Equipment Variables
Tuesday May 5 13:17:14 MST 2015 Equipment Inventory Sabino Electric Inc.
Page of3 13
Tag ID: BCP_400A-667187 Item Desc: LP-1Serial #: Equip Type: Branch Circuit Panel <= 400 amp
Equipment Location: (t) Main Electrical
Agreement: t-Training 1Site Name: Sabino Electric, Inc.
Mfg: ITE Model: E0612ML1125F
301.9519.0025277527752777505480455448012405480
[E] THDC % Ground/%[E] RMS Current GND/Amps[E] THDC % Neutral/%THD[E] RMS Current Neutral/Amps[E] RMS Voltage Neutral-GND/Volts[E] THDV % Phase C-Neutral/%THD[E] RMS Voltage Phase C-Neutral/Volts[E] THDV % Phase B-Neutral/%THD[E] RMS Voltage Phase B-Neutral/Volts[E] THDV % Phase A-Neutral/%THD[E] RMS Voltage Phase A-Neutral/Volts[E] THDC % Phase C/%THD[E] RMS Current Phase C/Amps[E] THDV % Phase C-A/%THD[E] RMS Voltage Phase C-A/Volts[E] THDC % Phase B/%THD[E] RMS Current Phase B/Amps[E] THDV % Phase B-C/%THD[E] RMS Voltage Phase B-C/Volts[E] THDC % Phase A/%THD[E] RMS Current Phase A/Amps[E] THDV % Phase A-B/%THD[E] RMS Voltage Phase A-B/Volts
9/5/2013TM - Variable/Unit
Equipment Variables
Safety Notes:
AIC Rating 65 KAmpsNEMA Type 1R Number
NFPA 70E: Conduit Type and Size 2.5" EMT Inch
Main Conductor Size Type / Al-Cu 4/0 Cu kcmil/AWG
NFPA 70E: Feeder Conductor Length 200 FeetGround Conductor Size / Type / Al-Cu 4 Cu kcmil/AWGNeutral Conductor Size / Type / Al-Cu 4/0 Cu kcmil/AWG
Current Rating 200 AmpsWorking Voltage 480Y/277 Volts
Breaker Poles/Spaces Spares/Unused 4 Spare
Main Breaker Type N/A Model #
Breaker Poles/Spaces In Use 38 UsedBreaker Poles/Spaces Total 42 TotalBranch Breaker Type BA Model #
Specifications Value Unit
Application:
Tuesday May 5 13:17:14 MST 2015 Equipment Inventory Sabino Electric Inc.
Page of4 13
Tag ID: MOT_50 -667190 Item Desc: P-1Serial #: SNT-121212 Equip Type: Motors <= 50hp
Equipment Location: (t) Main Electrical
Agreement: t-Training 1Site Name: Sabino Electric, Inc.
Mfg: Baldor Industrial Motors Model: EM3311T
510510510
[E] THDC % FLC 3-Phase C/%THD[E] RMS FLC 3-Phase C/Amps[E] THDC % FLC 3-Phase B/%THD[E] RMS FLC 3-Phase B/Amps[E] THDC % FLC 3-Phase A/%THD[E] RMS FLC 3-Phase A/Amps
9/5/2013TM - Variable/Unit
Equipment Variables
Safety Notes:
Conductor Size/Type/Al-Cu 8 Cu kcmil/AWGSpecification Number 12 Unitless
Number of Phases 3 Phase
Temperature Rise 100 C RiseEfficiency (NEMA Nom. Eff) 9 %EFF
Motor Type (Induction or Synchronus) Induction UnitlessNFPA 70E: Feeder Conductor Length 200 Feet
NEMA Locked Rotor Code Letter G Unitless
NFPA 70E: Controlled by VFD (Y/N) Y UnitlessNFPA 70E: Normally Running (Y/N) Y Unitless
NFPA 70E: Conduit Type and Size 1" EMT Inch
Horsepower 5 HPPower Factor (PF) 85 %
Current Rating 20 Amps
Maximum Ambient Temperature 110 C Max
Working Voltage 480 Volts
Duty Rating (Cont.) Cont UnitlessService Factor 1.15 SF
Motor Rated RPM 1500 RPM
Motor Insulation F ClassFrame Type PT-201 Unitless
Specifications Value Unit
Application:
Tuesday May 5 13:17:14 MST 2015 Equipment Inventory Sabino Electric Inc.
Page of5 13
Tag ID: MVDO-001-667192 Item Desc: MV Drop Out FuseSerial #: Equip Type: MV Drop Out Fuse
Equipment Location: (t) Main Electrical
Agreement: t-Training 1Site Name: Sabino Electric, Inc.
Mfg: U/A Model: 122412
Equipment Variables
Safety Notes:
Type overhead conductor Multi Single Strand/Multi
Ground obsticals present Yes Yes/No
Type of Drop-out Open Open/enclosed
Drop-out condition Fair Good/Fair/BadFuse size 12 Amp
Working Voltage 4160 Voltage
Underbuilt/Overbuilt condition Overbuilt/OK Good/OK/Poor
Working Height 28 Feet
Ground installed Yes Yes/NoPole type Steel H Tower Wood/Metal/Concrete
Specifications Value Unit
Application:
Tuesday May 5 13:17:14 MST 2015 Equipment Inventory Sabino Electric Inc.
Page of6 13
Tag ID: SWG_DISC-667184 Item Desc: Chiller-2Serial #: Equip Type: Switchgear Safety Disconnects > 400A
Equipment Location: (t) Main Electrical
Agreement: t-Training 1Site Name: Sabino Electric, Inc.
Mfg: Square D Company Model: QMB-363-TW
92.023112015480121993480122004480
[E] THDC % Ground/%[E] RMS Current GND/Amps[E] THDC % Phase C/%THD[E] RMS Current Phase C/Amps[E] THDV % Phase C-A/%THD[E] RMS Voltage Phase C-A/Volts[E] THDC % Phase B/%THD[E] RMS Current Phase B/Amps[E] THDV % Phase B-C/%THD[E] RMS Voltage Phase B-C/Volts[E] THDC % Phase A/%THD[E] RMS Current Phase A/Amps[E] THDV % Phase A-B/%THD[E] RMS Voltage Phase A-B/Volts
9/5/2013TM - Variable/Unit
Equipment Variables
Safety Notes:
Load Side Phase Conductor Size / Type / Al-Cu 350 Kcmil Cu kcmil/AWGGround Conductor Size / Type / Al-Cu 2 Cu kcmil/AWGContinuous Amps Rating 400 AmpsMaximum Voltage 600 Volts
Fuse Type / Model # LPN-400SP Unitless
Working Voltage 480 VoltsCurrent Rating 400 Amps
Specifications Value Unit
Application:
Tuesday May 5 13:17:14 MST 2015 Equipment Inventory Sabino Electric Inc.
Page of7 13
Tag ID: SWG_DRAW-667186 Item Desc: MCC-2Serial #: Equip Type: Switchgear Drawout Breakers
Equipment Location: (t) Main Electrical
Agreement: t-Training 1Site Name: Sabino Electric, Inc.
Mfg: Westinghouse Model: SPB50
Equipment Variables
Safety Notes:
Short Time P/U Setting .2 AmpsShort Time Delay Setting .2 seconds
Long Time P/U Setting .2 AmpsLong Time Delay Setting .2 seconds
Ground Fault Delay Setting .2 secondsInstantaneous Setting 0 Amps
Short Time I2T Setting .2 In UnitlessGround Fault P/U Setting .2 Amps
Conductor or Bus Size (Line Side) 4" x 1/4" x 4 Unitless
Frame Current Rating 2000 AmpsBreaker Plug Rating 80% Amps
Trip Unit Setting .2 Unitless
Working Voltage 480 Volts
Trip Unit Catalog or Model Number 123456 UnitlessAIC Rating 65 KAmps
Breaker Plug Type or Model Number Microversa UnitlessConductor or Bus Size (Load Side) Bussing kcmil/AWG
Specifications Value Unit
Application:
Tuesday May 5 13:17:14 MST 2015 Equipment Inventory Sabino Electric Inc.
Page of8 13
Tag ID: SWG_MCCB-667185 Item Desc: Switchgear Molded Case Breakers > 400ASerial #: Equip Type: Switchgear Molded Case Breakers > 400A
Equipment Location: (t) Main Electrical
Agreement: t-Training 1Site Name: Sabino Electric, Inc.
Mfg: Model:
Equipment Variables
Safety Notes:
Specifications Value Unit
Application:
Tuesday May 5 13:17:14 MST 2015 Equipment Inventory Sabino Electric Inc.
Page of9 13
Tag ID: TRD_250 -667193 Item Desc: T-001Serial #: Equip Type: Transformer Dry - <=600V => 250 kva
Equipment Location: (t) Main Electrical
Agreement: t-Training 1Site Name: Sabino Electric, Inc.
Mfg: SQUARE D Model: (CAT) 1205957625
Safety Notes:
Secondary Neutral Conductor Size / Type / Al-Cu 4/0 Cu kcmil/gaugeSecondary Ground Conductor Size / Type / Al-Cu 4 Cu kcmil/gaugeBonding Jumper Conductor Size / Type / Al-Cu 4/0 Cu kcmil/gauge
Number of Taps 7 TapsPrimary Conductor Size / Type / Al-Cu 2 Cu kcmil/gaugeSecondary Conductor Size / Type / Al-Cu 4/0 Cu kcmil/gauge
NFPA 70E: Feeder Conductor Length - PRIMARY 200 FeetNFPA 70E: Feeder Conductor Length -SECONDARY 50 FeetNFPA 70E: Conduit Type and Size - PRIMARY 2" EMT Inch
Temperature Rise 150 degrees CElectrostatic Shield Yes UnitlessK-Rating N/A Unitless
NFPA 70E: Conduit Type and Size - SECONDARY 2.5" EMT Inch
KVA Rating 75 KVAPrimary Voltage 480 VoltsPrimary Current (Calculated Maximum) 90 Amps
Tap Position 3 Unitless
Transformer Name T-001 UnitlessConfiguration (Delta/Wye) Wye Unitless
Manufacturer Date 12/2004 datePhase (1 or 3) 3 UnitlessWinding Impedance 5.7 %Z
Secondary Voltage 208Y/120 VoltsSecondary Current (Calculated Maximum) 208 AmpsWeight 500 Lbs
Specifications Value Unit
Application:
Tuesday May 5 13:17:14 MST 2015 Equipment Inventory Sabino Electric Inc.
Page of10 13
.002
.002
.002
.002
.002
.002
.002
.002
.002
.002
.002
.002
.002
.002
.002
.002
.002
.002
.002
.002
.002
.002
.002
.002
.0025.01252.0025125512551255405208580520858052085.002540548054054805405480
[D] Ratio "B" Tap #6/Text[D] Ratio "B" Tap #5/Text[D] Ratio "B" Tap #4/Text[D] Ratio "B" Tap #3/Text[D] Ratio "B" Tap #2/Text[D] Ratio "B" Tap #1/Text[D] Ratio "A" Tap #7/Text[D] Ratio "A" Tap #6/Text[D] Ratio "A" Tap #5/Text[D] Ratio "A" Tap #4/Text[D] Ratio "A" Tap #3/Text[D] Ratio "A" Tap #2/Text[D] Ratio "A" Tap #1/Text[D] Winding Resistance X3-X0/milliohms[D] Ductor/DLRO Scale X3-X0/milli/uOhms[D] Winding Resistance X2-X0/milliohms[D] Ductor/DLRO Scale X2-X0/milli/uOhms[D] Winding Resistance X1-X0/milliohms[D] Ductor/DLRO Scale X1-X0/milli/uOhms[D] Winding Resistance H3-H1/milliohms[D] Ductor/DLRO Scale H3-H1/milli/uOhms[D] Winding Resistance H2-H3/milliohms[D] Ductor/DLRO Scale H2-H3/milli/uOhms[D] Winding Resistance H1-H2/milliohms[D] Ductor/DLRO Scale H1-H2/milli/uOhms[E] Sec THDC % GND/%[E] Sec RMS Current GND/Amps[E] Sec THDC % Neutral/%[E] Sec RMS Current Neutral/Amps[E] Sec RMS Voltage Neutral-GND/Volts[E] Sec THDV % Phase C-N/%[E] Sec RMS Voltage Phase C-N/Volts[E] Sec THDV % Phase B-N/%[E] Sec RMS Voltage Phase B-N/Volts[E] Sec THDV % Phase A-N/%[E] Sec RMS Voltage Phase A-N/Volts[E] Sec THDC % Phase C/%[E] Sec RMS Current Phase C/Amps[E] Sec THDV % Phase C-A/%[E] Sec RMS Voltage Phase C-A/Volts[E] Sec THDC % Phase B/%[E] Sec RMS Current Phase B/Amps[E] Sec THDV % Phase B-C/%[E] Sec RMS Voltage Phase B-C/Volts[E] Sec THDC % Phase A/%[E] Sec RMS Current Phase A/Amps[E] Sec THDV % Phase A-B/%[E] Sec RMS Voltage Phase A-B/Volts[E] Pri THDC % GND/%[E] Pri RMS Current GND/Amps[E] Pri THDC % Phase C/%[E] Pri RMS Current Phase C/Amps[E] Pri THDV % Phase C-A/%[E] Pri RMS Voltage Phase C-A/Volts[E] Pri THDC % Phase B/%[E] Pri RMS Current Phase B/Amps[E] Pri THDV % Phase B-C/%[E] Pri RMS Voltage Phase B-C/Volts[E] Pri THDC % Phase A/%[E] Pri RMS Current Phase A/Amps[E] Pri THDV % Phase A-B/%[E] Pri RMS Voltage Phase A-B/Volts
9/5/2013TM - Variable/Unit
Equipment Variables
Tuesday May 5 13:17:14 MST 2015 Equipment Inventory Sabino Electric Inc.
Page of11 13
2GΩ2GΩ2GΩ2GΩ2GΩ2GΩ6002GΩ2GΩ2GΩ2GΩ2GΩ2GΩ600.002.002.002.002.002.002.002.002.002.002.002.002.002.002.002.002.002.002.002.002.002.002.002.002.002.002.002.002.002
[D] 10 Minute Primary to Secondary/Text[D] 5 Minute Primary to Secondary/Text[D] 4 Minute Primary to Secondary/Text[D] 3 Minute Primary to Secondary/Text[D] 2 Minute Primary to Secondary/Text[D] 1 Minute Primary to Secondary/Text[D] Test Voltage Pri-Sec/Text[D] 10 Minute Primary to Ground/Text[D] 5 Minute Primary to Ground/Text[D] 4 Minute Primary to Ground/Text[D] 3 Minute Primary to Ground/Text[D] 2 Minute Primary to Ground/Text[D] 1 Minute Primary to Ground/Text[D] Test Voltage Pri-Ground/Volts[D] Amp Rating Tap #7/Text[D] Amp Rating Tap #6/Text[D] Amp Rating Tap #5/Text[D] Amp Rating Tap #4/Text[D] Amp Rating Tap #3/Text[D] Amp Rating Tap #2/Text[D] Amp Rating Tap #1/Text[D] Tap #7 Voltage/Text[D] Tap #6 Voltage/Text[D] Tap #5 Voltage/Text[D] Tap #4 Voltage/Text[D] Tap #3 Voltage/Text[D] Tap #2 Voltage/Text[D] Tap #1 Voltage/Text[D] Calculated Ratio Tap #7/Text[D] Calculated Ratio Tap #6/Text[D] Calculated Ratio Tap #5/Text[D] Calculated Ratio Tap #4/Text[D] Calculated Ratio Tap #3/Text[D] Calculated Ratio Tap #2/Text[D] Calculated Ratio Tap #1/Text[D] Ratio "C" Tap #7/Text[D] Ratio "C" Tap #6/Text[D] Ratio "C" Tap #5/Text[D] Ratio "C" Tap #4/Text[D] Ratio "C" Tap #3/Text[D] Ratio "C" Tap #2/Text[D] Ratio "C" Tap #1/Text[D] Ratio "B" Tap #7/Text
9/5/2013TM - Variable/Unit
Tuesday May 5 13:17:14 MST 2015 Equipment Inventory Sabino Electric Inc.
Page of12 13
Agreement: t-Training 1
Serial #: 12345678 Equip Type: 5-15kV Oil Filled Transformers 501-5000 kVAMfg: SQUARE D Model: (cat)14662777-001
Tag ID: TRO2_5 -667194 Item Desc: SES-3
Site Name: Sabino Electric, Inc.
Equipment Location: (t) Main Electrical
Equipment Variables
Safety Notes:
Number of Taps 5 TapsPrimary Conductor Size / Type / Al-Cu 2/0 Cu kcmil/gaugeSecondary Conductor Size / Type / Al-Cu 500 MCM Cu x 6 kcmil/gauge
Primary Bushing Manufacturer Square-D Text
Tap Position 3 UnitlessInsulating Fluid Type FR-3 Unitless
Temperature Rise 150 degrees CElectrostatic Shield N/A UnitlessK-Rating N/A Unitless
Secondary Neutral Conductor Size / Type / Al-Cu 500 MCM Cu x 6 kcmil/gaugeSecondary Ground Conductor Size / Type / Al-Cu 2 Cu x 6 kcmil/gaugeBonding Jumper Conductor Size / Type / Al-Cu Factory Strapping kcmil/gauge
KVA Rating 2500 KVAPrimary Voltage 12,470 VoltsPrimary Current (Calculated Maximum) 2000 Amps
Weight 2097 Lbs
Transformer Name SES-3 UnitlessConfiguration (Delta/Wye) Wye Unitless
Phase (1 or 3) 3 UnitlessWinding Impedance 3.7 %ZGallons of Fluid 400 Gallons
Secondary Voltage 480Y/277 VoltsSecondary Current (Calculated Maximum) 2000 AmpsManufacturer Date 12/2004 date
Specifications Value Unit
Application:
Tuesday May 5 13:17:14 MST 2015 Equipment Inventory Sabino Electric Inc.
Page of13 13
Application:
Provides Power To 15kV Switchgear TextStyle (CVT, Solid-State) Solid-state TextOutput Conductor Size / Type / Al-Cu 4" x .25" Cu Buss kcmil/gauge
NFPA 70E: Feeder Conductor Length (Load Side) 45' Unitless
NFPA 70E: Feeder Conductor Length (Line Side) 45' FeetCT Ratio 20:1 UnitlessNFPA 70E: Conduit Type and Size (Load Side) 4" PVC Unitless
NFPA 70E: Conduit Type and Size (Line Side) 4" PVC Inch
Frequency 60 HertzkVA Rating 2500 KVA
Output Current Rating 4000 Amps
Input Voltage Tolerance (a to b volts) 69000 Volts
Output Voltage Range 12470 VoltsInput Conductor Size / Type / Al-Cu 4/0 Al kcmil/gaugeInput Amperage Rating 2000 Amps
Specifications Value Unit
Safety Notes:
Equipment Variables
Mfg: Ohio Brass Company Model: #560
Site Name: Sabino Electric, Inc.
Agreement: t-Training 1
Equipment Location: (t) Main Electrical
Serial #: Equip Type: 69kV Voltage Regulators
Tag ID: VR_230-667191 Item Desc: 69kV Voltage Regulators
Severity Criteria for Similar ComparisonsMVDO-001-667192 MV Drop Out Fuse MV Drop Out Fuse
Normal Alert Severe Critical
Reference Temperature Problem Temperature Difference TemperatureLess Than 4.1C 4.1C - 8.0C 8.1C - 15.0C Greater Than 15.0C
Tag ID: Equipment Type:
Sabino Electric Inc.945 W 29th Street , Tucson, AZ 85713
Sabino Electric, Inc. - t-Training 1
9/5/2013 Infrared Inspection Report Sheet Page 2A
Jon Aalberg (t) Main ElectricalTechnician: Location:
Recommendations For Repair X Repair Equipment Replace Equipment
Recondition as needed.
Overloaded Circuit Excessive Current Harmonics Stripped/Cross-threaded Hardware
Problem Corrected Tightened/Torqued Connection Corroded/Discolored
Fuse assemble is a higher than normal temperature.
42.3C 111.5C 69.2C
Variables Problem Spot Voltage Drop (Volts)THDC (%THD-F)Current Draw (Amps)Current Rating (Amps)
Unable to Obtain Unable to Obtain Unable to Obtain Unable to ObtainxxPhase A
Phase B Unable to Obtain Unable to Obtain Unable to Obtain Unable to Obtain
Phase C Unable to Obtain Unable to Obtain Unable to Obtain Unable to Obtain
Problem Description Immediate Hazard Customer Notified Immediately
Corrective ActionsFixed During Visit Contractor Will Correct Customer Will Correct X Estimate Required
Premature failure of the device can result in unscheduled outages and additional equipment damage.
Problem
X Equipment Failure X Fire Hazard X Safety Hazard X Power/Business Interruption
Sabino Electric Inc.945 W 29th Street , Tucson, AZ 85713
Sabino Electric, Inc. - t-Training 1
9/5/2013 Infrared Inspection Report Sheet Page 2BTechnician: Location:
MVDO-001-667192 MV Drop Out Fuse MV Drop Out Fuse
Consequences if Not Corrected
Jon Aalberg (t) Main ElectricalTag ID: Equipment Type:
Severity Criteria for Similar ComparisonsTRD_250 -667193 T-001 Transformer Dry - <=600V => 250 kva
Normal Alert Severe Critical
Reference Temperature Problem Temperature Difference TemperatureLess Than 4.1C 4.1C - 8.0C 8.1C - 15.0C Greater Than 15.0C
Tag ID: Equipment Type:
Sabino Electric Inc.945 W 29th Street , Tucson, AZ 85713
Sabino Electric, Inc. - t-Training 1
9/5/2013 Infrared Inspection Report Sheet Page 3A
Jon Aalberg (t) Main ElectricalTechnician: Location:
Recommendations For Repair X Repair Equipment Replace Equipment
De-energize the termination and clean the contact surfaces. Re-torque all the electrical connections. (Take voltage drop and resistance readings before and after the repairs. Record findings.)
Overloaded Circuit Excessive Current Harmonics Stripped/Cross-threaded Hardware
Problem Corrected Tightened/Torqued Connection Corroded/Discolored
Hot Termination. This may be caused by under or over torqued connections, carbon build up, or improper installation.
44.5C 60.8C 16.3C
Variables Primary Current Draw Winding Temperature (Deg C)
Secondary THDC (%THD-F)
Secondary Current Draw (Amps)
Primary THDC (%THDC-F)
15 114 15 4890Phase A
Phase B 90 12 110 12 51
Phase C 90 18 112 10 48
Problem Description Immediate Hazard Customer Notified Immediately
Corrective ActionsFixed During Visit Contractor Will Correct Customer Will Correct Estimate Required
If the termination is not properly cared for, the heat may cause damage to the conductor or failure in the breaker. Breaker failure may result in damage to the bussing and possible meltdown of the panel or gear.
Problem
X Equipment Failure X Fire Hazard Safety Hazard X Power/Business Interruption
Sabino Electric Inc.945 W 29th Street , Tucson, AZ 85713
Sabino Electric, Inc. - t-Training 1
9/5/2013 Infrared Inspection Report Sheet Page 3BTechnician: Location:
TRD_250 -667193 T-001 Transformer Dry - <=600V => 250 kva
Consequences if Not Corrected
Jon Aalberg (t) Main ElectricalTag ID: Equipment Type:
Severity Criteria for Similar ComparisonsTRO2_5 -667194 SES-3 5-15kV Oil Filled Transformers 501-5000 kVA
Normal Alert Severe Critical
Reference Temperature Problem Temperature Difference TemperatureLess Than 4.1C 4.1C - 8.0C 8.1C - 15.0C Greater Than 15.0C
Tag ID: Equipment Type:
Sabino Electric Inc.945 W 29th Street , Tucson, AZ 85713
Sabino Electric, Inc. - t-Training 1
9/5/2013 Infrared Inspection Report Sheet Page 4A
Jon Aalberg (t) Main ElectricalTechnician: Location:
Recommendations For Repair X Repair Equipment X Replace Equipment
Deenergize circiuit, inspect and repair contacts as a matched set if applicable, or install properly rated replacement Load Break.
Overloaded Circuit Excessive Current Harmonics Stripped/Cross-threaded Hardware
Problem Corrected Tightened/Torqued Connection Corroded/Discolored
Load Break contact is displaying abnormal thermal pattern.
37.4C 56.4C 19.0C
Variables Primary Current Draw Winding Temperature (Deg C)
Secondary THDC (%THD-F)
Secondary Current Draw (Amps)
Primary THDC (%THDC-F)
12 200 5 Not Applicable100Phase A
Phase B 100 12 200 5 Not Applicable
Phase C 100 12 200 5 Not Applicable
Problem Description Immediate Hazard Customer Notified Immediately
Corrective ActionsFixed During Visit Contractor Will Correct Customer Will Correct X Estimate Required
Additional loading and continued exposure to this condition will more than likely accelerate a failure of this device.
Problem
X Equipment Failure Fire Hazard Safety Hazard X Power/Business Interruption
Sabino Electric Inc.945 W 29th Street , Tucson, AZ 85713
Sabino Electric, Inc. - t-Training 1
9/5/2013 Infrared Inspection Report Sheet Page 4BTechnician: Location:
TRO2_5 -667194 SES-3 5-15kV Oil Filled Transformers 501-5000 kVA
Consequences if Not Corrected
Jon Aalberg (t) Main ElectricalTag ID: Equipment Type:
4 5-15kV Oil Filled Transformers 501-5000 kVA (t) Main Electrical 56.4C 37.4C 19.0C
3 Transformer Dry - <=600V => 250 kva (t) Main Electrical 60.8C 44.5C 16.3C
2 MV Drop Out Fuse (t) Main Electrical 111.5C 42.3C 69.2C
Page 5 Alert Severe Critical
SUMMARY PAGE
Sabino Electric Inc.945 W 29th Street
Sabino Electric, Inc. - t-Training 1
Tucson, AZ 85713
Page # Equipment Type Location Problem Ref/Amb. Diff.
Recommendations For Repair X Repair Equipment Replace Equipment
Bearing failure
Consequences if Not CorrectedX Equipment Failure Fire Hazard Safety Hazard X Power/Business Interruption
Replace bearing.
Fixed During Visit Contractor Will Correct Customer Will Correct X Estimate Required
Corrective Actions Problem Corrected
Technician: Location:Jon Aalberg (t) Main Electrical
9/5/2013 Equipment Item Problems Report Page 1
Sabino Electric Inc.945 W 29th Street , Tucson, AZ 85713
Sabino Electric, Inc. - t-Training 1
Tag ID: Equipment Type:
Ultrasonic Anomaly, Bad Bearing, see WAVE file in attachments.
Problem Description - Alert Immediate Hazard Customer Notified Immediately
MOT_50 -667190 P-1 Motors <= 50hp
Recommendations For Repair X Repair Equipment Replace Equipment
Breaker may not operate under emergency conditions or under scheduled P.M. An unmaintained breaker will have an adverse affect on any arc fault study. An unmaintained breaker may not operate within the proper perimeters.
Consequences if Not CorrectedX Equipment Failure Fire Hazard X Safety Hazard X Power/Business Interruption
Breaker should be cleaned,exercised,load injected.
Fixed During Visit Contractor Will Correct Customer Will Correct X Estimate Required
Corrective Actions Problem Corrected
Technician: Location:Jon Aalberg (t) Main Electrical
9/5/2013 Equipment Item Problems Report Page 2
Sabino Electric Inc.945 W 29th Street , Tucson, AZ 85713
Sabino Electric, Inc. - t-Training 1
Tag ID: Equipment Type:
Breaker shows no sign of testing or exercising. Manufacturer will show that a breaker must be exercised and maintained for proper operation.
Problem Description - Severe Immediate Hazard Customer Notified Immediately
SWG_DRAW-667186 MCC-2 Switchgear Drawout Breakers
Recommendations For Repair X Repair Equipment Replace Equipment
15kV oil is not rated for 69kV equipment. This will cause lower flash point leading to devastating damage, long down time.
Consequences if Not CorrectedX Equipment Failure X Fire Hazard X Safety Hazard X Power/Business Interruption
Recondition tap changer, replacing seals as needed.
Overhauled tap changer.
Fixed During Visit Contractor Will Correct Customer Will Correct Estimate Required
Corrective Actions Problem CorrectedX
Technician: Location:Jon Aalberg (t) Main Electrical
9/5/2013 Equipment Item Problems Report Page 3
Sabino Electric Inc.945 W 29th Street , Tucson, AZ 85713
Sabino Electric, Inc. - t-Training 1
Tag ID: Equipment Type:
Oil test results show that the oil from the 15kV tap changer has been passing through the seals and contaminating the 69kV oil.
Problem Description - Critical Immediate Hazard Customer Notified Immediately
VR_230-667191 69kV Voltage Regulators 69kV Voltage Regulators
Technician: Location:
VR_230-667191 69kV Voltage Regulators 69kV Voltage RegulatorsTag ID: Equipment Type:
Jon Aalberg (t) Main Electrical
9/5/2013 Equipment Item Problems Report Page 3B
Sabino Electric Inc.945 W 29th StreetTucson, AZ 85713
Sabino Electric, Inc. - t-Training 1
-- Immediate attention required!
CriticalPriorityCode: -- Attention Required within the next
30-90 days!
Severe-- Needs attention as time permits!
Alert
TGO-119 (03/25/10) ©2010 TEGG CorporationPage 1 of 2
9/5/2013 Oil test results show that the oil from the 15kV tap changer has been passing through the seals and contaminating the 69kV oil. X
VR_230-667191 69kV Voltage Regulators Repaired
9/5/2013 HEAT Load Break contact is displaying abnormal thermal pattern.TRO2_5 -667194 SES-3 Repaired
9/5/2013 HEAT Hot Termination. This may be caused by under or over torqued connections, carbon build up, or improper installation.
TRD_250 -667193 T-001 Repaired
9/5/2013 BREAKERS Breaker shows no sign of testing or exercising. Manufacturer will show that a breaker must be exercised and maintained for proper operation.
SWG_DRAW-667186
MCC-2 Repaired
9/5/2013 HEAT Fuse assemble is a higher than normal temperature.MVDO-001-667192 MV Drop Out Fuse Repaired
9/5/2013 ULTRASONIC Ultrasonic Anomaly, Bad Bearing, see WAVE file in attachments.MOT_50 -667190 P-1 Repaired
Location: (t) Main Electrical
Problem Summary
EDS Component
Sabino Electric Inc.945 W 29th StreetTucson, AZ 85713
Date Category Problem DescriptionTag ID Customer IdentificationSabino Electric, Inc. t-Training 1
-- Immediate attention required!
CriticalPriorityCode: -- Attention Required within the next
30-90 days!
Severe-- Needs attention as time permits!
Alert
TGO-119 (03/25/10) ©2010 TEGG CorporationPage 2 of 2
Review Date:
Customer Representative TEGG Service Representative
t-Training 1
Tuesday May 5 13:41:14 Ins. = Installed Rec. = Recommended Page of1 1
SWG_DISC-667184
Chiller-2 X
MVDO-001-667192
MV Drop Out Fuse
MOT_50 -667190 P-1 X
SWG_DRAW-667186
MCC-2 X
TRO2_5 -667194 SES-3 X
TRD_250 -667193 T-001 X
SWG_MCCB-667185
Switchgear Molded Case Breakers > 400A X
VR_230-667191 69kV Voltage Regulators
BCP_400A-667187
LP-1 X
ATS_401A-667195 ATS X
Location: (t) Main ElectricalTag ID Customer Identification Ins. Rec.
Surge Suppression Summary
Sabino Electric Inc.945 W 29th StreetTucson, AZ 85713
Site: Sabino Electric, Inc.Customer: Sabino Electric, Inc. Agreement No.: t-Training 1
Tuesday May 5 13:42:46 Ins. = Installed Rec. = Recommended Page of1 1
SWG_DISC-667184
Chiller-2 X
MVDO-001-667192
MV Drop Out Fuse
MOT_50 -667190 P-1 X
SWG_DRAW-667186
MCC-2 X
TRO2_5 -667194 SES-3 X
TRD_250 -667193 T-001 X
SWG_MCCB-667185
Switchgear Molded Case Breakers > 400A X
VR_230-667191 69kV Voltage Regulators X
BCP_400A-667187
LP-1 X
ATS_401A-667195 ATS X
Location: (t) Main ElectricalTag ID Customer Identification Ins. Rec.
Arc Flash Labeling Summary
Sabino Electric Inc.945 W 29th StreetTucson, AZ 85713
Site: Sabino Electric, Inc.Customer: Sabino Electric, Inc. Agreement No.: t-Training 1
Tuesday May 5 13:42:12 Ins. = Installed Rec. = Recommended Page of1 1
SWG_DISC-667184
Chiller-2
MVDO-001-667192
MV Drop Out Fuse
MOT_50 -667190 P-1
SWG_DRAW-667186
MCC-2
TRO2_5 -667194 SES-3 X
TRD_250 -667193 T-001
SWG_MCCB-667185
Switchgear Molded Case Breakers > 400A
VR_230-667191 69kV Voltage Regulators X
BCP_400A-667187
LP-1
ATS_401A-667195 ATS X
Location: (t) Main ElectricalTag ID Customer Identification Ins. Rec.
Infrared Windows Summary
Sabino Electric Inc.945 W 29th StreetTucson, AZ 85713
Site: Sabino Electric, Inc.Customer: Sabino Electric, Inc. Agreement No.: t-Training 1
Sabino Electric Inc.945 W 29th Street, Tucson, Arizona, 85713
Phone: 5 2 0-6 2 3-6 0 6 1Fax: 5 2 0-6 2 3-1 6 5 5
Customer:Sabino Electric, Inc.
Site:Sabino Electric, Inc.
Agreement No: t -Training 1
Date:5/5/2015 12:16:55 PM
Technician:Aalberg, Jon
Location:(t) Main Electrical
Equipment Tag ID: TRD_250 -667193
Mfr:SQUARE D
Model:(CAT) 1205957625
SN:
Type/Class: Transformer Name: T-001
KVA:75
Primary Voltage: 480
Secondary Voltage: 208Y/120
Weight:500
Mfr. Date: 12/2004
Phase:3
Impedance:5.7
Tap Position: 3
ANNUAL INSPECTION
Inspect physical and mechanical condition including evidence of moisture,
corona or brittleness
Ok Repair Replace NA See Notes DUST ON WINDOWS
verify that control and alarm setting on temperature indicators are operational
Ok Repair Replace NA See Notes
verify that cooling fans and/or pumps operate correctly
Ok Repair Replace NA See Notes
inspect all bolted electrical connections for high resistance (as per NETA)
Ok Repair Replace NA See Notes
Perform specific inspection and mechanical tests as recommended by
manufacturer
Ok Repair Replace NA See Notes
Verify that resiliant mounts are free and that any shipping brackets have been
removed
Ok Repair Replace NA See Notes
Verify that the core, frame and enclosure are grounded (check connections)
Ok Repair Replace NA See Notes
arresters (check condition and connections)
Ok Repair Replace NA See Notes
Thoroughly clean unit prior to testing unless as found and as left tests are
required
Ok Repair Replace NA See Notes
Verify that as left connections are specified
Ok Repair Replace NA See Notes
Bushings Ok Repair Replace NA See Notes
Case Exterior Ok Repair Replace NA See Notes
N O T E S
DEFICIENCIES
1Loose term has effected insulation on core.
2
3
Form #20 TEGG Corporation Page 1 of 2
Sabino Electric Inc.945 W 29th Street, Tucson, Arizona, 85713
Phone: 5 2 0-6 2 3-6 0 6 1Fax: 5 2 0-6 2 3-1 6 5 5
Customer:Sabino Electric, Inc.
Site:Sabino Electric, Inc.
Agreement No: t -Training 1
Date:5/5/2015 2:14:36 PM
Technician:Aalberg, Jon
Location:(t) Main Electrical
Equipment Tag ID: SWG_DRAW-667186
Mfr:Westinghouse
Model 1: S/N 1:
Ambient F: 82
Percent Humidity: 12
Model 2: S/N 2:
NAMEPLATE DATACatalog No: Frame Rating:
2000
Trip Unit: Microversa
Other:
MECHANICAL INSPECTIONOperation:
121
Cell Fit: Ok
Connections:Ok
Lubrication:Moble 1
TRIP UNIT SETTINGSLong Time P/U:
.2
Short Time P/U: .2
Ground Fault P/U: .2
Long Time Delay: .2
Short Time Delay: .2
Ground Fault Delay: .2
Short Time: .2
Inst:0
PRIMARY INJECTION TESTS
TEST SETTINGS TEST VALUES A B C L IMITS
LONG TIME P/U .2
S
10 A M P S1/10 A M P S1/10 A M P S1/10 A M P S1/10
LONG TIME DELAY .2
10 S E
C
1/10 S E
C
1/10 S E
C
1/10 S E
C
1/10
SHORT TIME P/U .2
10 A M P S1/10 A M P S1/10 A M P S1/10 A M P S1/10
SHORT TIME DELAY .2 10 S E C1/10 S E C1/10 S E C1/10 S E C1/10
GROUND FAULT P/U.2
10 A M P S1/10 A M P S1/10 A M P S1/10 A M P S1/10
GROUND FAULT DELAY .2 10 S E C1/10 S E C1/10 S E C1/10 S E C1/10
INSTANTANEOUS 0 3
CONTACT RESISTANCE(MILLI-OHMS)A
.002
B.002
C.002
INSULATION RESISTANCE (READING IN MEGOHMS)
PHASE TO GROUND A B C
PHASE TO PHASE A -B B-C C -A
LINE TO LOAD A B C
OVERCURRENT TRIP INFORMATIONElectromechanical:N/A
Solid State: N/A
Frame Rating: N/A
Type:N/A
Plug:N/A
Trip/CT Rating: N/A
T/C Curve: N/A
Current Setting: N/A
Ins Range: N/A To:N/A
Inst Setting: N/A
Std Range: N/A To:N/A
Std Setting: N/A
Std Band: N/A To:N/A
Band Setting: N/A
Ltd Range: N/A To:N/A
Ltd Setting: N/A
Ltd Band: N/A To:N/A
Band Set: N/A
Gr Flt Range: N/A To:N/A
Gf Setting: N/A
Gr Flt Band: N/A To:N/A
Band Set 2: N/A
Form #310 TEGG Corporation Page 1 of 2
RECORD OF OVERCURRENT TRIP DEVICE PERFORMANCE
T E S T TEST @ TEST AMPS CURVE SEC. PHASE A PHASE B PHASE C
INST. 500 40 1/10 X X X
S.T.D. 500 40 1/10 X X X
L.T.D. 500 40 1/10 X X X
G.F. 500 40 1/10 X X X
MEGGER TEST @ 1KV IN MEGOHMS
A -B B-C C -A A -GROUND B-GROUND C -GROUND
CONTACT RESISTANCE IN M I C O-O H M S
A B C
.002 .002 .002
VISUAL AND MECHANICAL CHECKLIST
Primary Fingers Ok Repair Replace NA See NotesArch Chutes Ok Repair Replace NA See Notes
Breaker Contacts Ok Repair Replace NA See NotesAlignment Ok Repair Replace NA See NotesPressure Ok Repair Replace NA See Notes
Mechanical Operation Ok Repair Replace NA See NotesLubrication Ok Repair Replace NA See Notes
Racking Device Ok Repair Replace NA See NotesAuxiliary Contacts Ok Repair Replace NA See Notes
Trip Mechanism Ok Repair Replace NA See NotesCell Interlocks Ok Repair Replace NA See Notes
General Physical Condition Ok Repair Replace NA See Notes
P H A S E A M P T A P TIME DIAL PICKUPA M P S
MULTAMPS. 3X
T I M E MULTAMPS 5X
T I M E INST. TARGETSEAL IN
OTHEC O I L
AS FOUND N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A
AS LEFT N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A
NOTES
Form #310 TEGG Corporation
Sabino Electric Inc.945 W 29th Street, Tucson, Arizona, 85713
Phone: 5 2 0-6 2 3-6 0 6 1Fax: 5 2 0-6 2 3-1 6 5 5
Customer:Sabino Electric, Inc.
Site:Sabino Electric, Inc.
Agreement No: t -Training 1
Date:5/5/2015 12:16:55 PM
Technician:Aalberg, Jon
Location:(t) Main Electrical
Equipment Tag ID: TRD_250 -667193
Mfr:SQUARE D
Model:(CAT) 1205957625
SN:
Type/Class: Transformer Name: T-001
KVA:75
Primary Voltage: 480
Secondary Voltage: 208Y/120
Weight:500
Mfr. Date: 12/2004
Phase:3
Impedance:5.7
Tap Position: 3
ANNUAL INSPECTION
Inspect physical and mechanical condition including evidence of moisture,
corona or brittleness
Ok Repair Replace NA See Notes DUST ON WINDOWS
verify that control and alarm setting on temperature indicators are operational
Ok Repair Replace NA See Notes
verify that cooling fans and/or pumps operate correctly
Ok Repair Replace NA See Notes
inspect all bolted electrical connections for high resistance (as per NETA)
Ok Repair Replace NA See Notes
Perform specific inspection and mechanical tests as recommended by
manufacturer
Ok Repair Replace NA See Notes
Verify that resiliant mounts are free and that any shipping brackets have been
removed
Ok Repair Replace NA See Notes
Verify that the core, frame and enclosure are grounded (check connections)
Ok Repair Replace NA See Notes
arresters (check condition and connections)
Ok Repair Replace NA See Notes
Thoroughly clean unit prior to testing unless as found and as left tests are
required
Ok Repair Replace NA See Notes
Verify that as left connections are specified
Ok Repair Replace NA See Notes
Bushings Ok Repair Replace NA See Notes
Case Exterior Ok Repair Replace NA See Notes
N O T E S
DEFICIENCIES
1Loose term has effected insulation on core.
2
3
Form #20 TEGG Corporation Page 1 of 2