IT & INFRASTRUCTURE DATACENTERS CONGRESS

Brussels, 13th of October 2016

Yves Jansen

DIESEL ROTARY UPS (DRUPS) AND ITS INTERGRATION IN 

« UPTIME INSTITUTE TIER » ARCHITECTURE BASED DATA 

CENTRES

EURO‐DIESEL SADRUPS : NO‐BREAK KSTIER STANDARDNO‐BREAK KS AND THE TIER STANDARD

HQ EURO‐DIESEL SA, Belgium, Liege

EURO‐DIESEL SA

Holland

Belgium

Established in 1989

HQ Liège, Belgium

Consolidated revenue :  103 million EUR

Total number of employees : 250

Subsidiaries in Germany, UK, France, USA, Singapore, Brazil, Middle East, United Arab Emirates, Turkey, Mexico and Russia

Worldwide distributor network

Focus on power quality solutions: DRUPS

France

The Netherlands

Belgium

Luxemburg

BrusselsLiège

World Largest DRUPS Testing Facility

• 6300 M²

• Production capacity > 200 systems

• 18 Test stands

• Indoor enclosure assembly 

• 50 & 60 Hz testing

• Load banks > 18 MW

• Load banks & recordings, software operated

The Facility built in 2009:

Power Quality

Building a NO‐BREAK KS® System

Stato‐Alternator Side View

ACCU‐ROTOR < 3000 RPM 

MAIN SHAFT 1500 OR 1800 RPM 

100 kVA to 2750 kVA (50Hz); 3000 kVA (60Hz)

NO‐BREAK KS® Conditioning Mode

NO‐BREAK KS® Conditioning Mode

•Voltage regulator •Harmonics filter•Improvement of Power factor•Elimination of Microcuts

NO‐BREAK KS® Independent Mode

NO‐BREAK KS® SYSTEM CONFIGURATIONS

FOR DATA CENTRES

UPTIME Institute Tier Standard: Topology

• The functionality

• The capacity

• The availability  ( or performance) 

Tier Standard Topology is an objective basis for comparing:

of a particular site infrastructure design topology against other sites 

UPTIME Institute Tier Standard: Topology

• The functionality

• The capacity

• The availability  ( or performance) 

Tier Standard Topology is an objective basis for comparing:

of a particular site infrastructure design topology against other sites 

Tier Standard describes criteria four differentiate classifications of  site infrastructure

System Configurations for Data Centres

Tier I

Active Capacity Components to Support the IT Load N

Distribution Paths 1

Concurrently Maintainable No

Fault Tolerance No

Compartmentalization No

Diesel Engine Function Engine Limited on Consecutive Hours of Operation

Uptime Institute Design Criteria

System Configurations for Data Centres

Tier I Tier II

Active Capacity Components to Support the IT Load N N+1

Distribution Paths 1 1

Concurrently Maintainable No No

Fault Tolerance No No

Compartmentalization No No

Diesel Engine Function Engine Limited on Consecutive Hours of Operation

Engine Limited on Consecutive Hours of Operation

Uptime Institute Design Criteria

System Configurations for Data Centres

Tier I Tier II Tier III

Active Capacity Components to Support the IT Load N N+1 N+1

Distribution Paths 1 1 1 Active and 1 Alternative Path

Concurrently Maintainable No No Yes

Fault Tolerance No No No

Compartmentalization No No No

Diesel Engine Function Engine Limited on Consecutive Hours of Operation

Engine Limited on Consecutive Hours of Operation

Engine NO Limit on Consecutive Hours of Operation

Uptime Institute Design Criteria

System Configurations for Data Centres

Tier I Tier II Tier III Tier IV

Active Capacity Components to Support the IT Load N N+1 N+1 N: After a failure

Distribution Paths 1 1 1 Active and 1 Alternative Path 2 Simultaneously Active

Concurrently Maintainable No No Yes Yes

Fault Tolerance No No No Yes

Compartmentalization No No No Yes

Diesel Engine Function Engine Limited on Consecutive Hours of Operation

Engine Limited on Consecutive Hours of Operation

Engine NO Limit on Consecutive Hours of Operation

Engine NO Limit on Consecutive Hours of Operation

Uptime Institute Design Criteria

NO‐BREAK KS®    Single System – Tier I design

• Active capacity element to support active load : N

• Distribution path: 1

• Concurrently Maintainable: NO

• Fault Tolerant: NOTIER 1

NO‐BREAK KS® LV Parallel – Tier II Design

TIER 2

Critical load

• Active capacity :

• Distribution path:

• Concurrently Maintainable: 

• Fault Tolerant:

N+1

1

NO

NO

NO‐BREAK KS® LV Parallel – Tier II Design

TIER 2

Critical load

• Active capacity :

• Distribution path:

• Concurrently Maintainable: 

• Fault Tolerant:

N+1

2

NO

NO

NO‐BREAK KS® LV Parallel – Tier III Design

TIER 3

Critical load

• Active capacity :

• Distribution path:

• Concurrently Maintainable: 

• Fault Tolerant:

N+1

2

YES

NO

NO‐BREAK KS® LV Parallel – Tier III Design

TIER 3

Critical load

• Active capacity :

• Distribution path:

• Concurrently Maintainable: 

• Fault Tolerant:

N+1

2

YES

NO

NO‐BREAK KS® LV Parallel – Tier 3 Design

TIER 3

Critical load

• Active capacity :

• Distribution path:

• Concurrently Maintainable: 

• Fault Tolerant:

N+N

2

YES

YES

subject to interpretation TIER 4

NO‐BREAK KS® LV Parallel – Tier IV Design

2 NO-BREAK KS ® of 1000 kVA+ 2 NO-BREAK KS ® of 2000 kVA

ECMWF READING UK:

NO‐BREAK KS® LV Parallel – Tier IV Design

TIER 4

Critical load

• Active capacity :

• Distribution path:

• Concurrently Maintainable: 

• Fault Tolerant:

N+N

2 Active

YES

YES

NO‐BREAK KS® LV Parallel – Tier IV Design

TIER 4

PROXIMUS GAM EVERE :

PROXIMUS MECHELEN:

PROXIMUS SURFHOUSE EVERE:  

4+4 NO-BREAK KS ® of 1000 kVA

2+2 NO-BREAK KS ® of 1600 kVA

2+2 NO-BREAK KS ® of 1000 kVA

NO‐BREAK KS® MV Parallel – Tier IV Design

TIER 4

PROXIMUS MACHELEN:   5+5 NO-BREAK KS ® of 1700 kVA

NO‐BREAK KS® LV Parallel – Tier IV Design

TIER 4

Critical load

50%

• Active capacity :

• Distribution path:

• Concurrently Maintainable: 

• Fault Tolerant:

N+N

2 Active

YES

YES

50%

Load repartition

NO‐BREAK KS® Distributed Redundant

66% 66% 66%

Load repartition

NO‐BREAK KS® Distributed Redundant

TIER 4

• Active capacity element to support active load : N+N

• Distribution path: 2 active

• Concurrently Maintainable: YES

• Fault Tolerant: YES

SOME OF OUR MAJOR REFERENCESIN DATA CENTRES

NO‐BREAK KS®5  16 x 2500 kVA, 400V

Etisalat Data Centre, Khalifa City A, Abu Dhabi, UAE

NO‐BREAK KS®5  10 x 1600 kVA, 415 V

Meeza Data Center, Qatar

NO‐BREAK KS®5 SB  18 X 1650 kVA, 400V 

Standard Bank of South Africa , Samrand, Midrand

NO‐BREAK KS®5SB  2 x 2500 kVA, 13.8 kV

Telus Modular data center, Rimouski , Canada

Ascenty Data Center, Jundiaí, Brazil

NO‐BREAK KS®5SB 9 x 1700 kVA, 13,8 kV

Ascenty Data Center, Hortolândia, Brazil

NO‐BREAK KS®5SB 9 x 1700 kVA, 480 V

KEPPEL DATAHUB T27, Singapore

NO‐BREAK KS®5  6 x 2000 kVA, 415V

Cisco Systems TX‐DC2, Dallas, USA

NO‐BREAK KS®5 SB  8 x 2100 kW, 4.16 kV

NO‐BREAK KS®5 SB  16 x 2500 kVA, 400V

Natixis, France

Global Switch, London, UK

NO‐BREAK KS®5 26 x 2000 kVA, 11 kV

NO‐BREAK KS®5  8 x 2250 kVA, 11 kV

Global Switch, Sydney, Australia

Global Switch, Hong Kong

NO‐BREAK KS®7  12 x 2625 kVA, 11 kV

For More Information • Please See Us ......