deep see 5510
Post on 14-Apr-2018
227 Views
Preview:
TRANSCRIPT
-
7/29/2019 Deep See 5510
1/28
DSEPOWER
SHARING
WITHSIMPLICITY.
DSE5510
AUTOSTARTCONTROLMODULE(ELECTRONICENGINEENABLED)
ELECTRONICENGINECAPABILITYTheDSE5510isanAutomaticEngineControlModule,designedtoprovide
advancedloadsharefunctionalityfordieselandgasgeneratingsetsthatincludenon-
electronicandelectronicengines.Themodulealsoprovidesexcellentengine
-
7/29/2019 Deep See 5510
2/28
monitoringandprotectionfeatures.
Themodulesloadsharefunctionsinclude,automaticsynchronisingwithbuiltinsynchroscopeandclosingontodeadbus.Direct
andflexibleoutputsfromthemoduleareprovidedtoallowconnectiontothe
mostcommonlyusedspeedgovernorsandautomaticvoltageregulators(AVRs).
The
modulehasbeendesignedtocombineamaximumof16
-
7/29/2019 Deep See 5510
3/28
generatorsand16mains(utility)suppliesuptoamaximumof20inonesystem,e.g.16generatorsand4mains(utility)supplies(DSE5560
requiredtosynchronisewiththemains).
Themodulehastheability
tomonitorunder/overgeneratorvolts,overcurrent,under/overgeneratorfrequency,underspeed,over
speed,chargefail,emergencystop,lowoilpressure,highengine
-
7/29/2019 Deep See 5510
4/28
temperature,failtostart,low/highDCbatteryvolts,failtostop,generatorshortcircuitprotection,
reversepower,generatorphaserotationerror,earth
faultprotection,lossofspeedsignal,failtoopen,failtoclose,out
ofsync,MPUopencircuitfailure,negativephasesequenceandlossofexcitation.
FEATURES
Electronicenginecapability
-
7/29/2019 Deep See 5510
5/28
RS232orRS485remotecommunicationsModbusRTUPinnumberprotectedfrontpanelprogrammingEngineexercisetimerBack-litLCD4-linetext
displayMultipledisplaylanguagesVoltagemeasurementConfigurableinputs(9)
Configurableoutputs(5)AutomaticstartManualstartAudiblealarm
LEDindicatorsBuilt-ingovernorandAVRcontrolEngine
-
7/29/2019 Deep See 5510
6/28
historyeventlogEngineprotectionFaultconditionnotificationtoadesignatedPCFrontpanelmountingPCconfigurationBusfailure
detectionConfigurablealarmtimersConfigurablestart&stoptimersAutomatic
loadtransferSMSalertmessagingFrontpanelmountingRemotemonitoring
Magneticpick-upLOADSHAREFEATURES
ROCOF
-
7/29/2019 Deep See 5510
7/28
&vectorshiftAutomaticstarting&stoppingofgeneratoronloaddemandAutomatichoursrunbalancingofgeneratorsetsDeadbus
sensingModulehastheabilitytointerfacewithexistingloadsharelines
DirectcommunicationfromthemoduletothegovernorandAVRLink
upto16generatorsVolts&frequencymatching
-
7/29/2019 Deep See 5510
8/28
KWandKvarloadsharingwithmultiplegeneratorsBENEFITS
SendsSMSmessagestoengineerstonotifyspecificengineproblems(GSMModem
andSIMcardrequired)On-siteandremote(modemrequired)moduleconfiguration
In-builtenginediagnosticsremovestherequirementforserviceequipmentFullengineprotection
&instrumentationwithouttheneedforadditionalsenders(Electronicengines
-
7/29/2019 Deep See 5510
9/28
only)RemotemonitoringofthemoduleusingcomprehensiveDSEPCsoftwareLicensefreePCsoftwareSPECIFICATIONDCSUPPLY
8Vto
35Vcontinuous
CRANKINGDROPOUTS
Abletosurvive0Vfor
50mS,providingsupplywasatleast10Vbeforedropoutandsupplyrecoversto
5V.Thisisachievedwithouttheneedforinternalbatteries
-
7/29/2019 Deep See 5510
10/28
MAXIMUMOPERATINGCURRENT
460mAat12V.245mAat24V
MAXIMUMSTANDBYCURRENT
375mAat12V.200mA
at24V
ALTERNATORINPUTRANGE
15V(L-N)to333VAC
(L-N)absolutemaximum
ALTERNATORINPUTFREQUENCY
50Hz-60Hzat
ratedenginespeed(Minimum:15VACL-N)
MAGNETIC
-
7/29/2019 Deep See 5510
11/28
PICK-UPVOLTAGERANGE
+/-0.5Vto70VPeak
MAGNETICINPUTFREQUENCY
10,000Hz(max)
STARTRELAYOUTPUT
16ADCatsupplyvoltage
FUELRELAYOUTPUT
16ADCatsupplyvoltage
AUXILIARYRELAYOUTPUTS
Threeoutputs5ADCatsupplyvoltageTwooutputsvolt
-
7/29/2019 Deep See 5510
12/28
free8Aat250VAC
DIMENSIONS
240mmx172mmx57mm9.4x6.8x2.2
PANELCUTOUT
220mmx160mm8.7x6.3
CHARGEFAIL/EXCITATIONRANGE
0Vto35V
BUILTINGOVERNORCONTROL
FullyIsolatedMinimumLoadImpedence:1000.GainVolts0V-10V
-
7/29/2019 Deep See 5510
13/28
DCOffsetVolts+/-10VDC
BUILTINAVRCONTROL
FullyIsolatedMinimumLoadImpedence:1000.GainVolts0V
-10VDCOffsetVolts+/-10VDC
ENCLOSUREPROTECTION
(frontofmodule)IP55(withoptionalgasket)IP42(withoutgasket)
-
7/29/2019 Deep See 5510
14/28
ELECTROMAGNETICCAPABILITYBSEN61000-6-2EMCGenericEmissionStandardfortheIndustrialEnvironmentBSEN61000-6-4EMCGenericEmissionStandardfortheIndustrialEnvironmentELECTRICALSAFETYBSEN60950SafetyofInformationTechnologyEquipment,includingElectricalBusinessEquipmentTEMPERATUREBSEN60068-2-2TestAbto+70oC60067-2-2HotTestAbto-30oC60068-2-1ColdVIBRATIONBSEN60068-2-6Tensweepsineachofthreemajoraxes5Hzto8Hz@+/-7.5mm,8Hzto500Hz@2gnHUMIDITYBS2011part2.160068-2-30TestCbObCyclic93%RH@40oCfor48hoursSHOCKBSEN60068-2-27Threeshocksineachofthreemajoraxes15gnin11mSENVIRONMENTALTESTINGSTANDARDSELECTROMAGNETICCAPABILITYBSEN61000-6-2EMCGenericEmissionStandardfortheIndustrialEnvironmentBSEN61000-6-4EMCGenericEmissionStandardfortheIndustrialEnvironmentELECTRICALSAFETYBSEN60950SafetyofInformationTechnologyEquipment,includingElectricalBusinessEquipmentTEMPERATUREBSEN60068-2-2TestAbto+70oC60067-2-2HotTestAbto-30oC60068-2-1ColdVIBRATIONBSEN60068-2-6Tensweepsineachofthreemajoraxes5Hzto8Hz@+/-7.5mm,8Hzto500Hz@2gnHUMIDITYBS2011part2.160068-2-30TestCbObCyclic93%RH@40oCfor48hoursSHOCKBSEN60068-2-27Threeshocksineachofthreemajoraxes15gnin11mSENVIRONMENTALTESTINGSTANDARDSTYPICALLOADSHAREAPPLICATION
LOADG1G2G3
OPERATION
ThemoduleisoperatedusingthefrontSTOP/RESET,MANUAL,AUTO
andSTARTpushbuttons.ThreeofthesepushbuttonsincludeanLEDindicator.
AdditionalpushbuttonsprovideLCDdisplayscroll,lamptest,mute
-
7/29/2019 Deep See 5510
15/28
functionalityandbreakercontrol.
TIMERS&INPUTFUNCTIONS
Themodulehasbeendesignedtoincludethefollowingtimersandinput
functions:
StartdelaytimerStopdelaytimerCrank
timerCrankresttimerEngageattempt&manualcranklimittimers
SafetyondelaytimerWarmuptimer
-
7/29/2019 Deep See 5510
16/28
CoolingtimerEnergisetostopholdtimerPre-heattimerPre-heatbypasstimerSmokelimitingcontroltimerFailtostop
timerOverspeedovershoottimerBreakerpulsecontroltimers
DCbatteryalarmdelaytimersSync/failtosynctimerBUILT-INFUNCTIONS
Alternatorunder/overvoltsAlternatorunder/overfrequency
-
7/29/2019 Deep See 5510
17/28
Warningorshutdownonenginetemperature,over/underspeed,oilpressureWarning,shutdownorelectricaltriponbatteryvoltsorovercurrentShutdown
orelectricaltriponreversepower,phaserotationorshortcircuitfault
EarthfaultshutdownAdjustablecrankcycle/attemptsFullremotecontrolandtelemetry
9configurabledigitalinputs5configurableand2
-
7/29/2019 Deep See 5510
18/28
fixedrelayoutputsSystemlockinputLoadswitchingcontrolpush-buttoninputsROCOF/vectorshift(mains/utilitydecoupling)NegativephasesequenceLoss
ofexcitationINSTRUMENTATIONANDALARMS
TheDSE5510moduleprovidesadvancedmetering
andalarmfunctionalityviatheLCDdisplay.Theinformationcanbeaccessedusing
thedisplayscrollpushbuttons.Thetablebelowshowsthe
-
7/29/2019 Deep See 5510
19/28
instrumentationandalarmfeaturesthemoduleprovides.
GeneratorVoltsL1-N,L2-N,L3-NGeneratorVoltsL1-L2,L2-L3,L3-L1GeneratorAmpsL1,L2,L3
GeneratorFrequencyHzGeneratorkVAL1,L2,L3,TotalGeneratorkWL1,L2,
L3,TotalGeneratorpfL1,L2,L3,AverageGeneratorkVArL1,L2,L3,
TotalGeneratorKWhGeneratorKVAhGeneratorKVArhGeneratorPhaseSequence
-
7/29/2019 Deep See 5510
20/28
SynchroscopeDisplayEngineSpeedRPMEngineOilPressureEngineTemperaturePlantBatteryVoltsEngineHoursRunNumberofStartAttemptsMaintenanceDisplayEngineECU
diagnosticsinformationviaindustrystandardCANinterfaceEnhancedmeteringviaCANwhenconnected
toanelectronicengine
TELEMETRY
Themodulegivesthe
userfulltelemetryfacilitieswhenusingtheoptionalcommunicationssoftware.
-
7/29/2019 Deep See 5510
21/28
ThemodulecanbeconnectedtoaPCusingtheDSE810PCinterfaceorbyusingasuitablemodem.
ThePCsoftware
isMicrosoftWindowsbased.Allaccessintothemodulecanbeconfiguredto
becomepasswordprotectedtopreventunauthorisedentry.ThePCsoftwareallowsthemodule
tobecontrolledfromaremotelocation.
COMMUNICATIONS
-
7/29/2019 Deep See 5510
22/28
TheDSE5510hasanumberofdifferentcommunicationcapabilities.
SMSMessaging
Whenthemoduledetectsanalarmcondition,
ithastheabilitytosendanSMSmessagetoadedicatedmobile
number,notifyinganengineeroftheproblem.(GSMModemandSIMCardrequired).
RemoteCommunications
Whenthemoduledetects
-
7/29/2019 Deep See 5510
23/28
analarmcondition,itdialsouttoaPCnotifyingtheuseroftheexactalarmcondition(modemrequired).
BuildingManagement
Themodulehasbeendesignedtobeintegratedintonewandexisting
buildingmanagementsystems.
PCSoftware
Themodulehasthe
abilitytobeconfiguredandmonitoredfromaremotePC,
-
7/29/2019 Deep See 5510
24/28
usingtheDSE810interface.
EVENTLOG
Themoduleincludesacomprehensiveeventlogthatshowsthe25mostrecentalarm
conditionsandthedateandtimethattheyoccurred.Thisfunctionassiststhe
userwhenfaultfindingandmaintainingthegeneratingset.
EXPANSIONMODULES
DSE123LoadShareLinesInterfaceModuleDSE157Relay
-
7/29/2019 Deep See 5510
25/28
InputExpansionModuleDSE545&DSE548RemoteAnnunciationExpansionModuleDSE130InputExpansionModule
ELECTRONICENGINECOMPATIBILITY
Cummins
DeutzJohnDeereMTUPerkinsScaniaVolvo
GenericPlusadditionalmanufacturers
-
7/29/2019 Deep See 5510
26/28
DSE5510
TOGENSWITCHINGDEVICECIRCUITRY2AMPFUSESTOLOADFROMGENERATOR2AMPFUSESAUTOMATICMCCBAUTOMATICACBorCONTACTOR3or4POLECTsMUSTBE5AMPSECODARYP1S1S2P2L1L3NL2L1L3NL2TOMAGPICKUPIFUSEDSCREENEARTHEDATTHISENDONLYDONOTCONNECTSCREENTOENGINETOENGINEECUSCREENEARTHEDATTHISENONLYDONOTCONNECTSCREENTOENGINECT1CT2CT3CT4COML151L251L351N52L1L2L3NGENVOLTSSCRMPUSCRBARS485SCRBLJ1939CLOSEGENOUTPUT4OUTPUT5UNUSDL1L2L3NBUSVOLTSGENCURRENT49505153524546474839402021223738545556293031232425414243442134557585960910111213141516171867819323334536GOVERNORAVRO/PBAO/PBAUNUSEDPLANT+VE3OUTPUTS9INPUTS157P810MODULE5510262728SCRHLMSCRS232CONECTSCREENATGENERATORONLYSCREENEARTHEDATTHISENDONLYTOGOVERNORTOAVRCONECTCREENATGENERATORONLYREMOVELINKFORUPTO32AMPSFUSEFORREMOTEEMSTOPMIN2AMPSMAX20AMPANTI-SURGEFUSETOFUELSOLENOIDMAX16AMPTOCRANKSOLENOIDMAX16AMPLOWOILPRESSUREHIGHCOOLANTTEMPFUELTEMPTOENGINEEARTHCHARGEALTERNATORUSERCONIGURATIONINPUT1USERCONFIGURATIONINPUT2USERCONFIGURATIONINPUT3USERCONFIGURATIONINPUT4USERCONFIGURATIONINPUT5USERCONFIGURATIONINPT6USERCONFIGURATIONINPUT7USERCONFIGURATIONINPUT8USERCONFIGURATIONINPUT9USERCONFIGURATIONINPUT+VEOUTPUTUSERCONFIGURATIONINPUT+VEOUTPUTUSERCONFIGURATIONINPUT+VEOUTPUTBATTERY+VE(12OR24VDC)ALLBATTERYNEGATIVESMUSTBECONNECTEDTOGETHERTOOTHER5510AND5560MSCCONNECTIONSMAX250METERS120OHMSCREENCABLETHEFIRSTANDLASTUNITSMSCMSTBEFITTEDWITHA120OHMRESISTORACRO
SSH(27)ANDL(28)BATTERY-VEOILPRESSUREWATERTEMPFUELCOMMONGROUNDCHARGEALTBATTERY+VE-VEFUELCRANKRELATEDMATERIALS
TITLEPARTNOS
DSE5560Data
Sheet055-041DSE5510Manual057-015DSE5560Manual057-017DSE123DataSheet055-044Load
ShareDesign&Commissioning057-047GuidetoSynchronisingand057-045/6
-
7/29/2019 Deep See 5510
27/28
LoadSharing55xxSoftwaremanual057-007CAN&DSEwiringguide057-004
-