BTS3900 External Alarm Monitoring System
N79598 1
BTS3900 External Alarm
Monitoring System
Prepare by: Ngo The Phong (79598)
BTS3900 External Alarm Monitoring System
N79598 2
Contents
Contents .............................................................................................................................. 2
I. Introduction ................................................................................................................. 3
II. Monitoring Components ............................................................................................. 5
2.1. BBU Monitoring Ports ........................................................................................ 5
2.2. Monitoring components ...................................................................................... 6
III. Power Alarm Data Configuration ........................................................................... 9
(For BSC6000V900R008) .................................................................................................. 9
3.1. Power Alarms...................................................................................................... 9
BTS3900 External Alarm Monitoring System
N79598 3
I. Introduction
As the other BTS, Monitoring System is integrated in to the BTS3900
System. The module that control the Monitoring system is BBU (Base Band Unit).
The BBU is located in the BTS3900 as the description below
The BTS3900 monitoring system enables the power monitoring, fan
monitoring, and environment monitoring.
BTS3900 External Alarm Monitoring System
N79598 4
BTS3900 External Alarm Monitoring System
N79598 5
II. Monitoring Components
2.1. BBU Monitoring Ports
Configure 1: BBU Monitoring Port
- The BBU provides a maximum of two RS485 buses and 16 Boolean signals.
- The modules on RS485 bus 0 cannot be interchanged with the modules on
RS485 bus 1.
In the BTS3900 system, the alarms ports vary with the optional modules
configured in the BBU3900.
- When the BBU3900 is configured with one UPEU, two RS485
buses and eight dry contact signals are provided.
FAN
0 4
1 GTMU
2 UPEU
BTS3900 External Alarm Monitoring System
N79598 6
3 7
Configure 2: BBU3900 is configured with 01 UPEU
- When the BBU3900 is configured with two UPEUs or one UPEU
plus one UEIU, 4 RS485 buses and 16 dry contact signals are
provided.
FAN
UPEU
GTMU
UPEU
Configure 3: BBU3900 is configured with two UPEUs
FAN
UEIU
GTMU
UPEU
Figure 4: BBU3900 is configured with UPEU plus one UEIU
2.2. Monitoring components
BTS3900 External Alarm Monitoring System
N79598 7
As can be seen from figure 5, there are many type of monitoring components
that connected to the BBU ports (UEIU ports, UPEU ports). From BBU, alarms
are monitored such as Power alarm (AC, DC ), External Alarms (Door, Water,
Smoke,…)
Figure 5: Monitoring Component
BTS3900 External Alarm Monitoring System
N79598 8
BTS3900 External Alarm Monitoring System
N79598 9
III. External Alarm Data Configuration
(For BSC6000V900R008)
3.1. Power Alarms
3.1.1. Alarm ports
From the figure 1, we can see 16 alarm signal , that will be used for Power
alarm of the BTS3900
Figure 6: Alarm ports
We use the ports EXT-ALM0, EXT-ALM1 in the UPEU , UEIU to connect
to the external equipment to get the monitoring signals. All the ports used RJ-45
connectors.
3.1.2. Alarm Cables
For the monitor connection, we use the RJ-45 cables.
BTS3900 External Alarm Monitoring System
N79598 10
Figure 7: BBU Alarm Cable
Each RJ-45 Cable is connected to the EXT-ALM port
Figure 8: Pin Assignment of Alarm Cable
3.1.3. Connection
To use the External Alarm, we have to set the value YES for Extended
Switch of Input Alarm in the BTS Site Attributes, the Value: Extended Switch of Input Alarm: YES
For the Upper UPEU or UEIU, we are using the Alarm Shield Flag 1 (Hex)
and Alarm Voltage Definition 1(Hex)
For the Lower UPEU or UEIU, we are using the Alarm Shield Flag 2 (Hex)
and Alarm Voltage Definition 2 (Hex)
BTS3900 External Alarm Monitoring System
N79598 11
Figure 9: Setting Alarm Value
From the following Table, Alarm Number will be enable,
Note: the type of alarm is: Open, that mean 2 wires of alarm signal cable Opened,
the Alarm will be displayed, and if 2 wires of alarm signal cable Closed, the
Alarm will be disappeared.
UEIU or UPEU
EXT-ALM1 EXT-ALM0
Alarm No. 8 7 6 5 4 3 2 1
Boolean Value
1 or 0
1 or 0
1 or 0
1 or 0
1 or 0
1 or 0
1 or 0
1 or 0
UPEU
EXT-ALM1 EXT-ALM0
Alarm No. 16 15 14 13 12 11 10 9
Boolean Value
1 or 0
1 or 0
1 or 0
1 or 0
1 or 0
1 or 0
1 or 0
1 or 0
Table 1: Value setting
BTS3900 External Alarm Monitoring System
N79598 12
For Upper UPEU or UEIU:
For the Upper UPEU or UEIU, we are using the Alarm Shield Flag 1 (Hex)
and Alarm Voltage Definition 1(Hex)
If the Value is (Hex) FF (BIN: 11111111) that mean all Alarm No. from 1
to 8 are enable. If you only select 01 alarm, you can set value (Hex) 8 (00010000)
for Alarm No. 5 as an example.
For Lower UPEU:
For the Upper UPEU or UEIU, we are using the Alarm Shield Flag 2 (Hex)
and Alarm Voltage Definition 2(Hex)
If the Value is (Hex) FF (BIN: 11111111) that mean all Alarm No. from 9
to 16 are enable. If you only select 01 alarm, you can set value (Hex) 40 (BIN:
01000000) for Alarm No. 15 as an example.
Normally, EXT-ALM0 ports are used for the interal alarm signals such as
connect to the DCDU to monitor the DCDU module. Then for the Power Alarm
Monitor, EXT-ALM1 are used, mean Alarm No. 5, 6, 7, 8 and 13, 14, 15, 16
are used for Power Alarm or other Alarm.
3.1.4. Data Configuration
There are some commands to set the Power Alarm from
BSC6000V900R008.
Assume that in the BBU, there is only one UPEU located at the lower
position, and there is no UEIU boards, and GTMU is always located in Position 5
and 6 of BBU – we call GTMU slot is 6 (As the Configure 2), we enable 04 Input
Alarm Signal in the EXT-ALM1, then the value is Hex: F0 (Binary: 11110000),
and the Decimal Value is 240. Because the MML using the Decimal value, then
we have to change the value to the Decimal mode.
- Set Alarm Value to enable all 8 alarms port from 1 to 8
MOD BTSALM: IDXTYPE=BYNAME, BTSNAME="BTS_NAME",
STTYPE=BTS3900_GSM, AlmFlag1=255, EXTFlag1=YES, AVD6=255;
- Set Alarm Value to enable all 8 alarms port from 9 to 16
MOD BTSALM: IDXTYPE=BYNAME, BTSNAME="BTS_NAME",
STTYPE=BTS3900_GSM, AlmFlag2=255, EXTFlag1=YES, AVD7=255;
BTS3900 External Alarm Monitoring System
N79598 13
- Set Alarm Value to enable all 16 alarms port from 1 to 16
MOD BTSALM: IDXTYPE=BYNAME, BTSNAME="BTS_NAME",
STTYPE=BTS3900_GSM, AlmFlag1=255, AlmFlag2=255, EXTFlag1=YES,
AVD6=255, AVD7=255;
- Set alarm Ports – equivalent to Alarm No.:
For Port 1, and assign Alarm ID=65384 for this Alarm No.:
SET ALMPORT: SITENAME="BTS-NAME", SRN=0, SN=6, PN=5,
SW=OPEN, AID=65384, PT=BOOL, AVOL=HIGH;
For Port 2, and assign Alarm ID=65385 for this Alarm No.:
SET ALMPORT: SITENAME="BTS-NAME", SRN=0, SN=6, PN=5,
SW=OPEN, AID=65385, PT=BOOL, AVOL=HIGH;
For Port 3, and assign Alarm ID=65386 for this Alarm No.:
SET ALMPORT: SITENAME="BTS-NAME", SRN=0, SN=6, PN=5,
SW=OPEN, AID=65386, PT=BOOL, AVOL=HIGH;
For Port 4, and assign Alarm ID=65387 for this Alarm No.:
SET ALMPORT: SITENAME="BTS-NAME", SRN=0, SN=6, PN=5,
SW=OPEN, AID=65387, PT=BOOL, AVOL=HIGH;
For Port 5, and assign Alarm ID=65388 for this Alarm No.:
SET ALMPORT: SITENAME="BTS-NAME", SRN=0, SN=6, PN=5,
SW=OPEN, AID=65388, PT=BOOL, AVOL=HIGH;
For Port 6, and assigns Alarm ID=65389 for this Alarm No.:
SET ALMPORT: SITENAME="BTS-NAME", SRN=0, SN=6, PN=6,
SW=OPEN, AID=65389, PT=BOOL, AVOL=HIGH;
For Port 7, and assign Alarm ID=65390 for this Alarm No.:
SET ALMPORT: SITENAME="BTS-NAME", SRN=0, SN=6, PN=7,
SW=OPEN, AID=65390, PT=BOOL, AVOL=HIGH;
For Port 8, and assign Alarm ID=65391 for this Alarm No.:
SET ALMPORT: SITENAME="BTS-NAME", SRN=0, SN=6, PN=8,
SW=OPEN, AID=65391, PT=BOOL, AVOL=HIGH;
For Port 9, and assign Alarm ID=65392 for this Alarm No.:
SET ALMPORT: SITENAME="BTS-NAME", SRN=0, SN=6, PN=8,
SW=OPEN, AID=65392, PT=BOOL, AVOL=HIGH;
For Port 10, and assign Alarm ID=65393 for this Alarm No.:
BTS3900 External Alarm Monitoring System
N79598 14
SET ALMPORT: SITENAME="BTS-NAME", SRN=0, SN=6, PN=8,
SW=OPEN, AID=65393, PT=BOOL, AVOL=HIGH;
For Port 11, and assign Alarm ID=65394 for this Alarm No.:
SET ALMPORT: SITENAME="BTS-NAME", SRN=0, SN=6, PN=8,
SW=OPEN, AID=65394, PT=BOOL, AVOL=HIGH;
For Port 12, and assign Alarm ID=65395 for this Alarm No.:
SET ALMPORT: SITENAME="BTS-NAME", SRN=0, SN=6, PN=8,
SW=OPEN, AID=65395, PT=BOOL, AVOL=HIGH;
For Port 13, and assign Alarm ID=65396 for this Alarm No.:
SET ALMPORT: SITENAME="BTS-NAME", SRN=0, SN=6, PN=8,
SW=OPEN, AID=65396, PT=BOOL, AVOL=HIGH;
For Port 14, and assign Alarm ID=65397 for this Alarm No.:
SET ALMPORT: SITENAME="BTS-NAME", SRN=0, SN=6, PN=8,
SW=OPEN, AID=65397, PT=BOOL, AVOL=HIGH;
For Port 15, and assign Alarm ID=65398 for this Alarm No.:
SET ALMPORT: SITENAME="BTS-NAME", SRN=0, SN=6, PN=8,
SW=OPEN, AID=65398, PT=BOOL, AVOL=HIGH;
For Port 16, and assign Alarm ID=65399 for this Alarm No.:
SET ALMPORT: SITENAME="BTS-NAME", SRN=0, SN=6, PN=8,
SW=OPEN, AID=65399, PT=BOOL, AVOL=HIGH;
After setting, there are 16 alarms will be displayed in the Alarm screen.
Figure 10: BTS Alarm used for external alarm
BTS3900 External Alarm Monitoring System
N79598 15
As can be seen in the figure 10, there are 16 alarms that you have set. Now,
to monitor easily, you have to change the name of alarms that you are using. The
changing of alarm as the following:
Go to Alarm Maintenance and select Query Alarm Configuration
Figure 11: Select Query Alarm Configuration
Figure 12: BTS Customer Environment Alarm
BTS3900 External Alarm Monitoring System
N79598 16
Select Alarm ID that you want to change the name of the alarm, then click
right mouse, a menu displayed, then select “Set Environment Alarm
Configuration” as the following picture
Figure 13: Set Environment Alarm Configuration
A pop-up window displayed, then Alarm name can be change by re-name “Alarm
Name”. Besides, Alarm Severity and Even Type can be change as the customer
requirement. You can see the Figure 14 for reference
Figure 14: Set Environment Alarm NAME, SEVERITY and EVENT TYPE