1Assembled Enclosed Circuit Breakers & Enclosures
Asse
mb
led
En
clo
sed
Cir
cu
itB
reakers
& E
nclo
su
res
Description Page
Enclosed Circuit Breakers and Enclosures
Product Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2
Application Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2
Features, Benefits and Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3
Standards and Certifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3
Catalogue Numbering System
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4
Circuit Breaker Selection and Interrupting Ratings . . . . . . . . . . . . . . . . . . .
5
Enclosure Only Catalogue Numbers Selection Guide . . . . . . . . . . . . . . . .
6
Options and Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
7
Technical Data and Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
9
RFDN100 SFDN100 SFDN225
RJDN250
JLDN600
WKDN400
SFDN100E
Contents
September 2006
2
For more information visit:
www.EatonElectrical.com
PG.29C.02C.S.K
Assembled Enclosed Circuit Breakers & Enclosures
Product Description and Application Description
Enclosed Circuit Breakers
Product Description
■
15 – 1200 ampere range.
■
Enclosed device used to open and close a circuit.
Application Description
EEMAC 1 General Purpose
Surface Mounting 15 – 1200 Ampere Range 600V AC, 500V DC
Flush Mounting 15 – 400 Ampere Range 600V AC, 500V DC
EEMAC 1 enclosed breakers are designed for indoor use in commercial buildings, apartment buildings and other areas where a general purpose enclosure is applicable. The breaker is front operable and is capable of being padlocked in the OFF position. Ratings through 1200 amperes are listed with CSA and UL as suitable for service entrance application (Optional neutral assembly is required). Both surface and flush mounted enclosures are available.
■
CSA File Number LR84319.
■
UL File Number E7819.
EEMAC 1 General Purpose
EEMAC 3R Rainproof Surface Mounting
Interchangeable Hubs (through 400 Amperes) 15 – 1200 Ampere Range 600V AC, 500V DC
This general purpose outdoor service center employs a circuit breaker inside a weatherproof sheet steel enclosure to serve as a main disconnect and pro-tective device for feeder circuits. The operating handle can be padlocked in the OFF position, and is interlocked to prevent the door from opening when the breaker is ON. Ratings through 1200 amperes are listed by CSA and UL as suitable for service entrance applica-tion. (Optional neutral assembly is required)
■
CSA File Number LR84319.
■
UL File Number E7819.
EEMAC 3R Rainproof Surface Mounting
EEMAC 4/4X, 5 Water and Dustproof
Stainless Steel — Surface Mounting 15 – 1200 Ampere Range 600V AC, 500V DC
This enclosure meets EEMAC 4/4X and 5 requirements for water and dustproof applications and has no knockouts or other openings. It is particularly well suited for use in dairies, borax mines, breweries, paper mills and other pro-cess industries. The operating handle can be padlocked in the OFF position, and is interlocked to prevent the door from opening when the breaker is ON. Ratings through 1200 amperes are listed with CSA and UL as suitable for service entrance application. (Optional neutral assembly is required)
■
CSA File Number LR84319.
■
UL File Number E7819.
EEMAC 4/4X Water and Dustproof
September 2006
PG.29C.02C.S.K For more information visit:
www.EatonElectrical.com
3Assembled Enclosed Circuit Breakers & Enclosures
Product Description and Application Description (cont’d)
Application Description, Features/Benefits & Functions, Standards & Certifications
EEMAC 12 Dustproof Surface Mounting
No Knockouts or Other Openings15 – 1200 Ampere Range600V AC, 500V DC
The Type 12 enclosure is designed in line with specifications for special industry application where unusually severe conditions involving oil, coolant, dust and other foreign materials exist in the operating atmosphere. The handle padlocks in the OFF position and the cover is interlocked with the handle mechanism to prevent opening the cover with the circuit breaker in the ON position. Ratings through 1200 amperes are listed with CSA and UL as suitable for service entrance applica-tion. (Optional neutral assembly is required)
■
CSA File Number LR84319.
■
UL File Number E7819.
EEMAC 12 Dustproof Surface Mounting
EEMAC 7/9 Hazardous Location
Cast Aluminum, Explosion-proofSurface Mounting 15 – 1200 Ampere Range600V AC, 250V DC
Hazardous location, Type 7: Class
I
, Groups B, C, D; Type 9: Class
II
, Groups E, F, G. This special service cast alumi-num enclosure is supplied with a wide, machined flanged cover to prevent igniting outside atmospheres by arc-ing from inside the enclosure. Front operable, the handle padlocks in the OFF position. Enclosures rated 600 amperes and above have lift-off hinges for ease of assembly.
Note:
XFDN050B is not Group B compliant.
■
CSA File Number LR42131-6.
■
UL File Number E84577.
EEMAC 7/9 Hazardous Location
Features, Benefits and Functions
■
Side-opening door on EEMAC 3R enclosures.
■
Padlockable in the OFF position.
■
Surface or flush mounted enclo-sures available through 400A on EEMAC 1 enclosures.
■
Interlocked handle on EEMAC 3R, 4/4X, 5 and 12 enclosures to prevent opening when the breaker is in the ON position.
■
Interchangeable hubs.
■
Numerous factory options.
Standards and Certifications
■
CSA 22.2 No. 5-02.
■
UL 489.
■
EEMAC 250.
September 2006
4
For more information visit:
www.EatonElectrical.com
PG.29C.02C.S.K
Assembled Enclosed Circuit Breakers & Enclosures
Catalogue Numbering System
Catalogue Numbering System
This information is presented only as an aid to understanding Catalogue numbers.
For Basic Assembled Enclosed Thermal Magnetic Circuit Breakers with Standard Line and Load Terminals
S FDN 3 125- - --
Enclosure Type Breaker Type Number of Poles Amperage
- Flush, EEMAC 1A- Surface, EEMAC 1- Rain Tight, EEMAC 3R- Dust Tight, EEMAC 12- Water Tight, EEMAC 4/4X, 5
GHC, GCH, GDED, EHD, EDCEHDFDB, FD, HFD, FDCJD, HJD, JDCDKKD, HKD, KDCLD, HLDLGE, LGS, LGHMDL, HMDL
2, 32, 32, 32, 32, 32, 32, 32, 32, 32, 3
15100151570100100300250300
---------
100225100225250400400600600800
For specifying Enclosed Circuit Breakers with a complex catalolgue number, such as the thermal magnetic breaker c/w optional terminals and internal accessories or the electronics breakers c/w Digitrip 310 trip unit/Digitrip Optim trip unit, please utilize the Cutler-Hammer’s Bid Manager pricing and configuration software.
By using the Standard products’ Enclosed Circuit Breaker Takeoff and make selection according to the following parameter, the program will configure and generate a detailed product catalogue number base on the user ’s specification.
Service VoltageContinuous Ampere RatingRequired KA RatingNumber of PolesType of Circuit Breaker FrameType of Trip Unit (Thermal Magnetic, Digitrip 310 / Digitrip Optim 550)Fix or Adjustable Rating PlugStandard or Optional Line / Load TerminalsType of Internal Accessory (Left Pole)Type of Internal Accessory (Right Pole)Type of EnclosureNeutral AssemblyType of Rain Tight Hub and Size (EEMAC 3R Enclosure)
Example: Catalogue Number RNHKD3400FZ15K09P24A13S10
This catalogue number specifies a Factory Assembled Enclosed 400A HKD Electronic circuit breaker in an EEMAC 3R enclo-sure. This enclosed cicuit breaker includes the 3 Pole 400A HKD breaker frame, KES 400A Digitrip RMS 310 LSI trip unit, 400A fixed rating plug, standard Line/Load terminals, 2a/2b auxiliary switches mounted in right pole with pigtail leads exit to rear, a 120Vac shunt trip mounted in left pole with pigtail leads exit to rear and the 400A Neutral kit N400.
The assembled enclosed circuit breakers are completely factory assembled and packaged in single ship-ping cartons. Each enclosed circuit breaker assembly includes the enclosure, breaker frame, trip unit and rating plug (where applicable), standard or optional line and load pressure terminals. Customer specified optional breaker accessories and neutral assembly will also be factory installed.
The assembled enclosed circuit breakers are CSA approved for use as Service Entrance Equipment when optional neutral assembly is installed.
R HLDN 3 500- - --
F SRJW
W JDN 3 250- - --
Option
Neutral Assembly Specify when Neutral Assembly is required
N:
- L
Suffix
Line and Load Ter-minals.Must be specified for F-Frame enclosed circuit breaker to form a complete cata-logue number. (Not required for other breaker frames)
L:
September 2006
PG.29C.02C.S.K For more information visit:
www.EatonElectrical.com
5Assembled Enclosed Circuit Breakers & EnclosuresEnclosed Circuit Breakers
Circuit Breaker Selection and Interrupting Ratings
Industrial Circuit Breakers
CircuitBreakerType
Cont.Amp.Rating@ 40°C
No.Poles
Volts Type of Trip
�
CSA/UL Listed Interrupting Ratings rms Symmetrical Amperes (kA)
AC DC AC Ratings Volts DC
�
120 120/240
240 277 347 480Y/277
480 600Y/347
600 125 250 125/250
G-Frame
GHCGHC
15 – 10015 – 100
12, 3
277480Y/277
125125/250
N.I.T.N.I.T.
65 —
——
—65
14—
——
—14
——
——
——
14—
——
—14
GCH
�
GCH
�
15 – 10015 – 100
12, 3
347600Y/347
125125/250
N.I.T.N.I.T.
65 —
——
—65
14—
10—
—14
——
—10
——
14—
——
—14
GDGD
15 – 5015 – 100
23
480480
125/250250
N.I.T.N.I.T.
——
——
6565
——
——
——
1422
——
——
——
—10
10—
F-Frame
EDEDHEDC
100 – 225100 – 225100 – 225
2, 32, 32, 3
240240240
125125125
N.I.T.N.I.T.N.I.T.
———
———
65100200
———
———
———
———
———
———
101010
———
———
EHDEHD
15 – 10015 – 100
12, 3
277480
125250
N.I.T.N.I.T.
——
——
—18
14—
——
——
—14
——
——
10—
—10
——
FDBFDB
15 – 15015 – 225
12, 3
347600
125250
N.I.T.N.I.T.
——
——
—18
——
14—
——
—14
——
—14
10—
—10
——
FDFD
15 – 15015 – 225
12, 3
347600
125250
N.I.T.N.I.T.
— —
— —
—65
25—
18—
——
—25
——
—18
10—
—10
— —
HFD
➂
HFD15 – 3015 – 225
12,3
347600
125250
N.I.T.N.I.T.
— —
— —
—100
65—
25—
——
—65
——
—25
10—
—22
— —
FDC
➂
FDC15 – 3015 – 225
12, 3
347600
125250
N.I.T.N.I.T.
——
——
—200
——
30—
——
—100
——
—35
10—
—22
——
J-Frame
JDHJDJDC
70 – 25070 – 25070 – 250
2, 32, 32, 3
600600600
250250250
I.T.I.T.I.T.
———
———
65100200
———
3565100
182535
———
102222
———
K-Frame
DK 250 – 400 2, 3 240 250 I.T. — — 65 — — — — 10 —
KDCKDHKDCHKDKDC
100 – 400100 – 400100 – 400100 – 400100 – 400
2, 32, 32, 32, 32, 3
600600600600600
250250250250250
I.T.I.T.I.T.I.T.I.T.
—————
—————
6565100100200
—————
35356565100
2525353550
—————
1010222222
—————
LG-Frame
LGELGSLGH
250 – 600250 – 600250 – 600
3, 43, 43, 4
600600600
250250250
I.T.I.T.I.T.
———
———
6585100
———
355065
182535
———
222242
———
L-Frame
LDHLD
300 – 600300 – 600
2, 32, 3
600600
250250
I.T.I.T.
——
——
65100
——
3565
2535
——
2225
——
MDL-Frame
MDLHMDL
300 – 800300 – 800
2, 32, 3
600600
250250
I.T.I.T.
— —
— —
65100
— —
5065
2535
— —
2225
— —
N-Frame
ND (800A Frame)ND (1200A Frame)CND (800A Frame)HND (800A Frame)HND (1200A Frame)CHND (800A Frame)
400 – 800600 – 1200400 – 800400 – 800600 – 1200400 – 800
333333
600600600600600600
——————
N.I.T.N.I.T.N.I.T.N.I.T.N.I.T.N.I.T.
— —————
— —————
656565100100100
— —————
505050656565
252525353535
— —————
— —————
— —————
�
N.I.T. is non-interchangeable trip unit and I.T. is interchangeable trip unit.
�
Two-pole circuit breaker, or two poles of three-pole circuit breaker at 250V DC.
�
Interrupting rating @ 347V AC are listed with CSA only. Not UL listed.
�
CSA listed only, Not UL listed.
September 2006
6
For more information visit:
www.EatonElectrical.com
PG.29C.02C.S.K
Assembled Enclosed Circuit Breakers & EnclosuresEnclosed Circuit Breakers
Enclosure Only Catalogue Numbers Selection Guide
Enclosure Only Catalogue Numbers Selection Guide
�
SGDN100 enclosure is suitable for use with one-pole GHC and GCH breaker. Base mounting plate kit is required. (Cat. # QC6BP)
�
SFDN100 Series “B” released 9/15/01.
�
RFDN100 Series “B” released 9/15/01.
�
Maximum wire size: 4/0.
Enclosure Only Catalogue Numbers Selection Guide (Continued)
Note: For availability or pricing information in regards to the following special assembled enclosed circuit breakers in EEMAC 1, 3R, 12 or 4X rated enclosures, please contact your local Cutler-Hammer Satellite Service Centre.
1. LDC
2. CLD, CHLD, CLDC
3. CMDL, CHMDL
4. NDC
5. CND, CHND (1200A frame only)
6. RD
7. PB
8. PC
9. Current Limit-R Breakers (FCL, LCL)
10. TRI-PAC Breakers (FB, LA, NB, PB)
11. Combination of Series-C F Frame circuit breakerwith the LFD Current Limiter
BreakerFrame
BreakerAmpereRange
Enclosure
EEMACClass
CatalogueNumber
Series C Breakers
GHC, GCH, GD(2- and 3-Pole only)GHCGFEP(1-Pole Only)
15 – 100 1 Surface3R124/4X, 5 St. Steel
SGDN100
�
RGDN100JGDN100WGDN100
ED, EDH, EDC (100A only)EHD, FDB, FD, HFD
15 – 100 1 Surface1 Flush3R124/4X, 5 St. Steel
SFDN100
�
FFDN100RFDN100
�
JFDN100WFDN100
ED, EDH, EDC, FD, FDB,HFD
110 – 225 1 Surface1 Flush3R124/4X, 5 St. Steel
SFDN225FFDN225RFDN225JFDN225WFDN225
FDC 15 - 225 1 Surface1 Flush3R124/4X, 5 St. Steel
SFDN225FFDN225RFDN225JFDN225WFDN225
EHD, FD, FDB, HFD, FDC 15 – 50 7/9 Cast Alum.
XFDN050B
60 – 225
�
7/9 Cast Alum.
XFDN225B
JD, HJD, JDC 125 – 250 1 Surface1 Flush3R124/4X, 5 St. Steel
SJDN250FJDN250RJDN250JJDN250WJDN250
JD, HJD, JDC 125 – 250 7/9 Cast Alum.
XJDN250B
DKKD, CKD, HKD, CHKD, KDC
125 – 400 1 Surface1 Flush3R124/4X, 5 St. Steel
SKDN400FKDN400RKDN400JKDN400WKDN400
KD, HKD, KDC, DK 125 – 400 7/9 Cast Alum.
XKDN400B
LGE, LGS, LGH 250 – 600 1 Surface3R124/4X, 5 St. Steel
SLG630RLG630JLG630WLG630
LD, HLD 300 – 600 1 Surface3R124/4X, 5 St. Steel
SLDN600RLDN600JLDN600WLDN600
LD, HLD 300 – 600 7/9 Cast Alum.
XMCN800B
MDL, HMDLND, HNDCND (800A frame only)CHND (800A frame only)
400 – 800400 – 1200400 – 800400 – 800
1 Surface3R124/4X, 5 St. Steel
SNDN1200RNDN1200JNDN1200WNDN1200
MDL, HMDL 400 – 800 7/9 Cast Alum.
XMCN800B
ND, HND 400 – 1200 7/9 Cast Alum.
XNDN1200B
BreakerFrame
BreakerAmpereRange
Enclosure
EEMACClass
CatalogueNumber
Earth Leakage Breakers
ELFD, ELHFD & ELFDC (3-Pole Only)
15 – 100 1 Surface1 Flush3R124/4X
SFD100EFFD100ERFDN100EJFDN100EWFDN100E
LGE, LGS, LGH used with ELLBN
250 – 600 1 Surface3R124/4X, 5 St. Steel
SLG630ERLG630JLG630WLG630
September 2006
PG.29C.02C.S.K For more information visit:
www.EatonElectrical.com
7Assembled Enclosed Circuit Breakers & Enclosuresnclosed Circuit Breakers
Options and Accessories
Factory Installed Circuit Breakers Internal Accessories
CSA Listed Neutral Kits, Insulated and Groundable
UL Listed Neutral Kits, Insulated and Groundable
CSA and UL Listed Neutral Kits, Insulated and Groundable for use with LGE, LGS and LGH Enclosed Circuit Breakers
Accessories Modifications Breaker Frame Description
AuxiliarySwitches
G, F, J, K, L, M, N 1A, 1B
G, F, J, K, L, M, N 2A, 2B
K, L, M, N 3A, 3B
R 2A, 2B4A, 4B
Shunt Trips
G, F, J, K, L, M, N, R
AlarmSwitches
G, F, J, K, L, M, N, R 1 Make, 1 Break
F, K, L, M, N, R 2 Make, 2 Break
UndervoltageRelease
G, F, J, K, L, M, N, R
Maximum Enclosure Rating (A)
Main Lug SizeCu/Al
# ofLugs
Ground Lug SizeCu/Al
# ofLugs
CatalogueNumber
100 SFDN100
�
RFDN100
�
(1) #14 – 1/0 2 (1) #14 – #2 2
DH100NK
100 (all others) (1) #14 – 1/0 2 (1) #14 – #4 2
N100
250 (1) #6– 350MCM 2 (1) #14 – 1/0 2
N250
400 (2) 3/0 – 250MCM 2 (1) #6 - 300MCM 2
N400
600 (2) #1– 500MCM 2 (1) #6 - 250MCM 2
N600
1200 (4) #2– 600MCM 2 (1) #6 - 250MCM 2
N1200
Maximum Enclosure Rating (A)
Main Lug SizeCu/Al
Ground Lug SizeCu/Al
CatalogueNumber
100 SFDN100
�
RFDN100
�
(1) #14 – 1/0 (1) #14 – #2
DH100NK
100 (all others) (1) #14 – 1/0 (1) #14 – 1/0
INK100
250 (1) #4 – 350 kcmil (1) #4 – 300 kcmil
INK250
400 (1) #4 – 600 kcmil or(2) 1/0 – 250 kcmil
(1) #4- 300 kcmil
INK400
600 (2) 250 – 500 kcmil (1) #4- 300 kcmil
INK600
1200 (4) 1/0 – 750 kcmil (1) #6 - 250 kcmil
INK1200
Maximum AmpereRating (A)
Main Lug SizeCu/Al
# ofLugs
Ground Lug SizeCu/Al
# ofLugs
CatalogueNumber
400 (1) 1/0 – 750MCM or(2) 1/0 – 300MCM
2 (1) #6 - 250MCM 3
DS400NK
600 (1) 1/0 – 750MCM (1) #2 – 600MCM
2 (1) #6 - 250MCM 3 DS600NK
1200 (4) 3/0 – 750MCM 2 (1) #6 - 250MCM 3 DS800NK
a
b
a
ST
Make
Break
ST
� SFDN100 Series “B” released 9/15/01.� RFDN100 Series “B” released 9/15/01.
September 2006
8
For more information visit: www.EatonElectrical.com PG.29C.02C.S.K
Assembled Enclosed Circuit Breakers & Enclosures
Options and Accessories
Raintight HubsAll rainproof enclosures 30 through 400 amperes are shipped with plate over cutout. Hubs are not supplied with screws on 30 through 400 ampere enclosures. Use screws from plate.
Raintight Hubs
Breather and Drain, Hazardous EnclosuresA Universal Breather/Drain Fitting is installed in the top of an enclosure to provide ventilation to minimize condensation and in the bottom to allow drainage of accumulated condensation while maintaining explosion-proof integrity.
Hubs Hub Diameter CatalogueNumberInches mm
SmallFor use with RGDN and RFDN .75
1.001.251.502.00
19.125.431.838.150.8
DS075H1DS100H1DS125H1DS150H1DS200H1
LargeFor use with RJDN. RKDN has 2 cutouts 2.00
2.503.00
50.863.576.2
DS200H2DS250H2DS300H2
Required if using small DS hubs on RJDN and RKDN enclosures. DS900AP
Type Compliance ConduitOpening
CatalogueNumberNEMA 7 NEMA 9
BD Class I, Groups C, D; Class I, Zone 1, Group IIB
Class II, Groups F, G
1/2 XPBD2
DBB Class I, Groups B, C, D; Class I, Zone 1, Group IIB + Hydrogen
Class II, Groups E, F, G
1/2 XPDBB50
PG.29C.02C.S.K For more information visit: www.EatonElectrical.com
9Assembled Enclosed Circuit Breakers & Enclosures
September 2006Technical Data and Specifications
Technical Data and Specifications
NEMA 1, 12, 12K, 3RNote: Not to be used for construction purposes unless approved.
NEMA 1 Surface Mounted (See Figure 2)
� SFDN100 Series “B” released 9/15/01. (See Figure 1)� Maximum wire size: 4/0.� Total width, including door clip is 9.95 inches (253 mm).� Single centered mounting hole provided.� Maximum wire size: 500 kcmil.
NEMA 1 Flush Mounted (See Figure 3)
� Maximum wire size: 4/0.� Maximum wire size: 500 kcmil.
Figure 1. NEMA 1 Surface Mounted SFDN100 Series “B”
Frame MaximumAmperes
Dimensions in Inches (mm) Approximate Weightin Lbs. (kg)
A B C D E F
GF �Earth Leakage (F)F �
J
100 100 100 225 250
17.50 (444.5)19.13 (485.9)23.25 (590.6)23.25 (590.6)34.70 (881.4)
8.56 (217.4) 9.13 (231.9) � 8.56 (217.4) 8.56 (217.4)10.92 (277.4)
6.28 (159.5) 5.20 (132.1) 6.28 (159.5) 6.28 (159.5) 7.20 (182.9)
13.03 (331.0)17.00 (431.8)18.75 (476.3)18.75 (476.3)30.00 (762.0)
1.20 (30.5)N/A �1.20 (30.5)1.20 (30.5)1.88 (47.8)
17.19 (436.6)18.81 (477.8)22.94 (582.7)22.94 (582.7)34.39 (873.5)
12 (5) 13 (6) 15 (7) 15 (7) 31 (14)
K �
LGEarth Leakage (LG)LM, N
400 600 600 6001200
38.81 (985.8)51.06 (1296.9)51.06 (1296.9)45.88 (1165.4)61.22 (1555.0)
11.06 (280.9)21.87 (555.5)21.87 (555.5)14.31 (363.5)21.44 (544.6)
10.94 (277.9) 9.96 (253.0) 9.96 (253.0)12.38 (314.5)15.41 (391.4)
34.00 (863.6)51.63 (1311.5)51.63 (1311.5)46.56 (1182.6)61.84 (1570.7)
9.28 (235.7)1.94 (49.3)1.94 (49.3)1.91 (48.5)1.97 (50.0)
38.50 (977.9)50.13 (1273.3)50.13 (1273.3)45.56 (1157.2)60.91 (1547.1)
53 (24) 90 (41) 90 (41) 81 (37)178 (81)
Frame MaximumAmperes
Dimensions in Inches (mm) Approximate Weightin Lbs. (kg)
A B C D E F
FEarth Leakage (F)F �
JK �
100100225250400
18.81 (477.8)24.56 (623.8)24.56 (623.8)36.02 (914.9)40.13 (1019.3)
9.72 (246.9) 9.72 (246.9) 9.72 (246.9)12.23 (310.6)12.38 (314.5)
6.28 (159.5) 6.28 (159.5) 6.28 (159.5) 7.20 (182.9)10.94 (277.9)
13.03 (331.0)18.75 (476.3)18.75 (476.3)30.00 (762.0)34.00 (863.6)
1.86 (47.2)1.86 (47.2)1.86 (47.2)1.88 (47.8)2.94 (74.7)
18.50 (469.9)24.25 (616.0)24.25 (616.0)35.70 (906.8)39.81 (1011.2)
12 (5)15 (7)15 (7)32 (15)53 (24)
NEED ARTDWG...95-1562
MARK SCHMIDTFROM
18.81(478.0)
1.84(46.7)
1.84(46.7)
1.91(48.5)
4.23(107.4)
5.20(132.0)
19.12(485.6)
1.78(45.2)
1.78(45.2)
17.00(431.8)
.81(20.6)
.38(9.7)
7.25(184.1) 3.50
(89.0)
1.91(48.5)
.69(17.5)
8.82(224.0)
.281 (7.1) DiameterKnockout Quantity: 2
.27 (6.8) Diameter3 Mounting Holes
9.13 (232.0)
9.95 (252.7) .71(18.0)
2.13(54.1)
1.91(48.5)
1.84(46.7)
Concentric Knockoutsfor 1, 1-1/4, 1-1/2 (25.4, 31.8, 38.1) 2 ConduitQuantity: 10
1.84(46.7)
Figure 2. NEMA 1 Surface Mounted
Figure 3. NEMA 1 Flush Mounted
E
D A
CB
F
D
EB C
A F
September 2006
10
For more information visit: www.EatonElectrical.com PG.29C.02C.S.K
Assembled Enclosed Circuit Breakers & EnclosuresTechnical Data and Specifications
Technical Data and Specifications
NEMA 12, 12X Dustproof (See Figure 5)
� Maximum wire size: 4/0.� Maximum wire size: 500 kcmil.
NEMA 3R Rainproof (See Figure 6)
� RFDN100 Series “B” released 9/15/01. (See Figure 4)� Maximum wire size: 4/0.� Single centered mounting hole provided on RFDN100, Series “B.”� Maximum wire size: 500 kcmil.
Figure 4. NEMA 3R Rainproof RFDN100 Series “B”
Frame MaximumAmperes
Dimensions in Inches (mm) Approximate Weightin Lbs. (kg)
A B C D E
G, FEarth Leakage (F)F �
JK �LGEarth Leakage (LG)LM, N
100 100 225 250 400 600 600 600 1200
19.91 (505.7)19.91 (505.7)25.66 (651.8)37.53 (953.3)41.69 (1058.9)53.37 (1355.6)53.37 (1355.6)48.31 (1227.1)63.59 (1615.2)
9.16 (232.7) 9.16 (232.7) 9.16 (232.7)11.88 (301.8)12.31 (312.7)23.06 (585.7)23.06 (585.7)15.56 (395.2)22.63 (574.8)
9.31 (236.5) 9.31 (236.5) 9.31 (236.5)10.22 (259.6)14.06 (357.1)14.10 (358.1)14.10 (358.1)15.50 (393.7)17.63 (447.8)
18.53 (470.7)18.53 (470.7)24.28 (616.7)35.77 (908.6)39.94 (1014.5)51.63 (1311.4)51.63 (1311.4)46.56 (1182.6)61.84 (1570.7)
1.70 (43.2)1.70 (43.2)1.70 (43.2)1.94 (49.3)1.97 (50.0)1.94 (49.3)1.94 (49.3)1.92 (48.8)1.97 (50.0)
16 (7) 19 (9) 19 (9) 37 (17) 58 (26) 94 (43) 94 (43) 84 (38)175 (80)
Frame MaximumAmperes
Dimensions in Inches (mm) Approximate Weightin Lbs. (kg)
A B C D E
G, F �Earth Leakage (F)F �
J
100 100 225 250
19.91 (505.7)19.91 (505.7)25.66 (651.8)37.50 (952.5)
9.16 (232.7) 9.19 (232.7) 9.16 (232.7)11.88 (301.8)
9.31 (236.5) 9.31 (236.5) 9.31 (236.5)10.22 (259.6)
18.53 (470.7)18.53 (470.7)24.28 (616.7)35.77 (908.6)
1.70 (43.2) �1.70 (43.2)1.70 (43.2)1.94 (49.3)
16 (7) 19 (9) 19 (9) 37 (17)
K �
LGEarth Leakage (LG)LM, N
400 600 600 6001200
41.69 (1058.9)53.37 (1355.6)53.37 (1355.6)48.31 (1227.1)63.59 (1615.2)
12.31 (312.7)23.06 (585.7)23.06 (585.7)15.56 (395.2)22.63 (574.8)
14.06 (357.1)14.10 (358.1)14.10 (358.1)15.50 (393.7)17.63 (447.8)
39.94 (1014.5)51.63 (1311.4)51.63 (1311.4)46.56 (1182.6)61.84 (1570.7)
1.97 (50.0)1.94 (49.3)1.94 (49.3)1.92 (48.8)1.97 (50.0)
58 (26) 94 (43) 94 (43) 84 (38)175 (80)
NEED ARTDWG...95-1562
MARK SCHMIDTFROM
Concentric Knockoutsfor 1, 1-1/4, 1-1/2 (25.4, 31.8, 38.1) 2 ConduitQuantity: 5
1.84(46.7)
1.91(48.5)7.25
(184.0)
.27 (6.8) Diameter3 Mounting Holes
.38(9.7)
3.50(89.0)
19.12(485.6)
1.78(45.2)
17.00(431.8)
.81(20.6)
1.91(48.5)
.69(17.5)
8.82(224.0)
.281 (7.1) DiameterKnockout Quantity: 2
1.84(46.7)
1.91(48.5)
4.23(107.4) 5.20
(132.0)
19.27(489.4)
18.81(478.0)
9.13 (232.0)
9.95 (252.7) .71(18.0)
Figure 5. NEMA 12, 12K Dustproof
Figure 6. NEMA 3R Rainproof
EE CC
AADD
BB
CC
ONON
FOFF
EE
AAD
BB
PG.29C.02C.S.K For more information visit: www.EatonElectrical.com
11Assembled Enclosed Circuit Breakers & Enclosures
September 2006
Technical Data and Specifications
Technical Data and Specifications
NEMA 4/4X, 5, 7/9Note: Not to be used for construction purposes unless approved.
NEMA 4/4X, 5 Stainless Steel (See Figure 8)
� Maximum wire size: 4/0.� Maximum wire size: 500 kcmil.
NEMA 7/9 Cast Aluminum with Weather-Resistant Seals — 15 – 250 Amperes (See Figure 7)
� Maximum wire size: 4/0.
Figure 7. NEMA 7/9 Cast Aluminum with Weather-Resistant Seals — Dual 3 and 4 Point Mounting Available as Standard on F Frame 100 Amperes and Below
Frame MaximumAmperes
Dimensions in Inches (mm) ApproximateWeight in Lbs. (kg)
A B C D E
G, F 100 19.91(505.7)
8.84(224.5)
9.31(236.5)
18.53(470.7)
1.70(43.2)
16 (7)
Earth Leakage (F) 100 19.91(505.7)
8.84(224.5)
9.31(236.5)
18.53(470.7)
1.70(43.2)
20 (9)
F � 225 25.66(651.8)
8.84(224.5)
9.31(236.5)
24.28(616.7)
1.70(43.2)
20 (9)
J 250 37.50(952.5)
11.56(293.6)
10.22(259.6)
35.77(908.6)
1.94(49.3)
39 (18)
K � 400 41.69(1058.9)
11.75(298.5)
14.06(357.1)
39.94(1014.5)
1.97(50.0)
60 (27)
LG 600 53.38(1355.9)
23.06(585.7)
14.11(358.4)
51.64(1311.7)
1.94(49.3)
96 (44)
Earth Leakage (LG) 600 53.38(1355.9)
23.06(585.7)
14.11(358.4)
51.64(1311.7)
1.94(49.3)
96 (44)
L 600 48.31(1227.1)
14.91(378.7)
15.50(393.7)
46.56(1182.6)
1.92(48.8)
88 (40)
M, N 1200 63.59(1615.2)
22.00(558.8)
17.63(447.8)
61.84(1570.7)
1.97(50.0)
185 (84)
BreakerFrame
Breaker Size Amperes
Numberof Outlets
Dimensions in Inches (mm) ApproximateWeight in Lbs. (kg)
Mounting � Inside � Outside � K �
DimStandardConduitSize �
A B J C D E F G H
FXFDN050B
15 – 50 4 5.50(139.7)
13.13(333.5)
14.13(358.9)
6.13(155.7)
10.75(273.1)
5.25(133.4)
10.63(270.0)
15.25(387.4)
8.88(225.6)
2.00(50.8)
1.50(38.1)
38 (17)
F �
XFDN100B 60 – 100 4 6.00
(152.4)18.00(457.2)
19.00(482.6)
6.50(165.1)
16.00(406.4)
5.50(139.7)
11.00(279.4)
20.50(520.7)
9.00(228.6)
2.31(58.7)
2.00(50.8)
57 (26)
F �XFDN225B
125 – 225 4 10.25(260.4)
22.63(574.8)
— 11.38(289.1)
20.00(508.0)
6.38(162.1)
16.38(416.1)
25.13(638.3)
9.63(244.6)
3.50(88.9)
2.50(63.5)
104 (47)
JXJDN225B
70 – 225 4 8.50(215.9)
27.13(689.1)
— 11.25(285.8)
29.88(759.0)
7.38(187.5)
16.00(406.4)
29.50(749.3)
12.31(312.7)
4.00(101.6)
3.00(76.2)
145 (66)
JXJDN250B
250 4 9.50(241.3)
27.25(692.2)
— 11.25(285.8)
29.88(759.0)
8.06(204.7)
16.38(416.1)
35.00(889.0)
12.38(314.5)
4.19(106.4)
4.00(101.6)
170 (77)
(2) 1/2-inch(12.7 mm)NPT
Figure 8. NEMA 4/4X, 5 Stainless Steel
EB
DA ON
OFF
C
September 2006
12
For more information visit: www.EatonElectrical.com PG.29C.02C.S.K
Assembled Enclosed Circuit Breakers & EnclosuresTechnical Data and Specifications
Technical Data and Specifications
NEMA 7/9 Cast Aluminum with Weather-Resistant Seals — 400 – 1200 Amperes (See Figure 9)
� Maximum wire size: 500 kcmil.� Power cables must enter and leave from opposite ends (through-feed).
Figure 9. NEMA 7/9 Cast Aluminum with Weather-Resistant Seals
Breaker Frame
Breaker Size Amperes
Dimensions in Inches (mm) WeightLbs. (kg)Overall
EnclosureEnclosureMounting
Conduit HingedCover
StandardConduit
A B C D E F G H I J Size Location
K �
XKDN400B 400 35.00
(889.0)16.38(416.1)
12.63(320.8)
7.13(181.1)
9.50(241.3)
27.25(692.2)
.50(12.7)
3.00(76.2)
4.19(106.4)
5.50(139.7)
4.00(101.6)
1, 3 & 6, 8 170 (77)
LXLDN600B
600 37.88(962.2)
23.88(606.6)
14.25(362.0)
8.25(209.6)
16.00(406.4)
45.38(1152.7)
.50(12.7)
4.00(101.6)
5.00(127.0)
6.00(152.4)
4.00(101.6)
1, 3 & 6, 8 419 (190)
MXMCN800B
800 47.88(1216.2)
13.63(346.2)
12.81(325.4)
6.81(173.0)
16.13(409.7)
40.75(1035.1)
.50(12.7)
4.00(101.6)
4.00(101.6)
6.00(152.4)
4.00(101.6)
1, 3 & 6, 8 228 (104)
N �
XNDN1200B1200 64.00
(1625.6)26.00(660.4)
21.38(543.1)
14.38(365.3)
27.56(700.0)
38.63(981.2)
.50(12.7)
6.50(165.1)
4.38(111.3)
7.00(177.8)
4.00(101.6)
1, 3 & 6, 8 567 (257)
CONDUIT POSITION NO.
1 2 3G-MTG.HOLES (4)
F-M
TG
.A
8 7 6
I D
C
J B
H H
Conduit OpeningsRefer to outline dimensions for size and location of standard conduit openings. In addition, 1/2-inch (12.7 mm) openings are drilled and tapped for breather and drain. Unless ordered with breather and drain, these openings are plugged. Refer to Eaton for price of breather and drain.
© Eaton Corporation, 2006All Rights ReservedPub. No. PG.29C.02C.S.KOctober 2006Printed in Canada
Eaton Electrical5050 MainwayBurlington, ON L7L 5Z1CanadaTel: 1-800-268-3578www.EatonElectrical.ca
Eaton Corporation is a diversified industrial manufacturer with 2005 sales of $11.1 billion. Eaton is a global leader in electrical systems and components for power quality, distribution and control; fluid power systems and services for industrial, mobile and aircraft equipment; intelligent truck drivetrain systems for safety and fuel economy; and automotive engine air management systems, powertrain solutions and specialty controls for performance, fuel economy and safety. Eaton has 60,000 employees and sells products to customers in more than 125 countries. For more information, visit www.eaton.com
Eaton's electrical business is a global leader in electrical control, powerdistribution, and industrial automation products and services. Through advanced product development, world-class manufacturing methods, and global engineering services and support, Eaton's electrical business provides customer-driven solutions under brand names such as Cutler-Hammer®,Powerware®, Durant®, Heinemann®, Holec® and MEM®, which globallyserve the changing needs of the industrial, utility, light commercial, residential,and OEM markets. For more information, visit www.eatonelectrical.ca.
top related