aritech master fire product catalogue (06.12.05)
Post on 21-Apr-2015
739 Views
Preview:
TRANSCRIPT
GESecurity
Aritech Fire Systems Products Catalogue
g
In this catalogue you will find a wide range of
Fire Protection equipment from GE Security.
GE Security is a global technology leader dedicated
to supporting the needs of the rapidly growing
electronic security industry and to expanding
current technologies, products and services that
create revenue growth opportunities for its
customers. As part of the GE family, GE Security
shares the spirit of innovation that has
distinguished GE for well over 100 years. GE
Security's commitment to the ongoing success of
its partners and affiliates means that we maintain
a sharp focus on product and service innovation,
world-class manufacturing practices and
operational excellence.
GE Security is a worldwide organisation with sales
and technical support operations in 27 countries,
and manufacturing and logistics operations in
Europe, the U.S. and China.
GE Security has expertise in all areas of electronic
security, including:
Intrusion and Fire Protection
Electronic Access and Facility Management
Key Management and Remote Access Systems
and Services
Fibre Optic Transmission and Reception
Equipment
CCTV, Digital Video and Surveillance Equipment
Video Multiplexing and Digital Storage
When you're looking for the finest in Fire
Protection products with leading-edge
technology and the backing of a world leader, you
need look no further than this catalogue.
GE Security,unrivalled expertise in Fire Protection
Perimeter detection
Page : 3
DI322IIonisation detector, conventional
The 300 Series conventional fire detectors are the ideal solution for anyconventional installation. They are built specifically for use with theAritech FP400, FP500, FP600 and FP700 series conventional fire panels,but can also be connected to most 3rd party industry standardconventional control panels.
Specifications
Operating voltage 18 to 28 VDC
Current consumption
Quiescent at 24 VDC 30 A
Alarm at 24 VDC < 100 mA
Radio-active source Americium 241
Average activity 0.33 +/-0.04 Ci (12.1 +/- 1.5 kBq)
Remote alarm output < 100 mA
Heat specification
Operating temperature -10 to +60 °C
Storage temperature -10 to +70 °C
Humidity (non-condensing) 0 - 95%
IP rating IP43
Number of detectors per zone 20
Recommended protectionresistor
300 ohm
Dimensions (h x Ø)
Head 45 mm x 99 mm
Base 24 mm x 103 mm
Approvals* EN54 (BOSEC)
* Check current status with localoffice
Ordering Information
Ionisation detector, conventionalDI322I Universal fire detector base KZ700Universal fire detector base with earth connectionKZ705Conventional fire detector base with diodeKZ705D Low current remote LED indicatorPA25/3L
Full line consisting of Optical, Ionisation and Heatdetectors
E
An ultra-fine grid prevents the ingress of dust andinsects in smoke detectors
E
Attractive, low-profile designE
EN54 approved *E
Innovative base compensates for uneven surfacesE
Page : 4
DP331IOptical detector, conventional, with field exchangeable optical block
The 300 Series conventional fire detectors are the ideal solution for anyconventional installation. They are built specifically for use with theAritech FP400, FP500, FP600 and FP700 series conventional fire panels,but can also be connected to most 3rd party industry standardconventional control panels.
Specifications
Operating voltage 9 to 28 VDC
Current consumption
Quiescent at 24 VDC 85 A
Alarm at 24 VDC < 100 mA
Radio-active source
Average activity
Remote alarm output < 100 mA
Heat specification
Operating temperature -10 °C to +70 °C
Storage temperature -10 °C to +70 °C
Humidity (non-condensing) 95%
IP rating IP43
Number of detectors per zone 20
Recommended protectionresistor
300 ohm
Dimensions (h x Ø)
Head 45 mm x 99 mm
Base 24 mm x 103 mm
Approvals* EN54 (BOSEC)
* Check current status with localoffice
Ordering Information
Optical detector, conventional, with field exchangeable optical blockDP331I Replacement Optical Chamber for KL731/A & DP331I/1561 detectorsKOB700 Universal fire detector base KZ700Universal fire detector base with earth connectionKZ705Conventional fire detector base with diodeKZ705DConventional 12 VDC fire detector base with relayKZ705R Low current remote LED indicatorPA25/3L
Full line consisting of Optical, Ionisation and Heatdetectors
E
An ultra-fine grid prevents the ingress of dust andinsects in smoke detectors
E
Attractive, low-profile designE
EN54 approved *E
Innovative base compensates for uneven surfacesE
Conventional Fire Systems
Page : 5
DT313ITemperature detector (fixed and rate-of-rise), conventional
The 300 Series conventional fire detectors are the ideal solution for anyconventional installation. They are built specifically for use with theAritech FP400, FP500, FP600 and FP700 series conventional fire panels,but can also be connected to most 3rd party industry standardconventional control panels.
Specifications
Operating voltage 18 to 28 VDC
Current consumption
Quiescent at 24 VDC 70 A
Alarm at 24 VDC < 100 mA
Radio-active source
Average activity
Remote alarm output < 100 mA
Heat specification Max. & ROR to EN54p5
Operating temperature -10 °C to +70 °C
Storage temperature -10 °C to +80 °C
Humidity (non-condensing) 95%
IP rating IP43
Number of detectors per zone 20
Recommended protectionresistor
300 ohm
Dimensions (h x Ø)
Head 45 mm x 99 mm
Base 24 mm x 103 mm
Approvals* EN54 (BOSEC)
* Check current status with localoffice
Ordering Information
Temperature detector (fixed and rate-of-rise), conventionalDT313I Universal fire detector base KZ700Universal fire detector base with earth connectionKZ705Conventional fire detector base with diodeKZ705D Low current remote LED indicatorPA25/3L
Full line consisting of Optical, Ionisation and Heatdetectors
E
An ultra-fine grid prevents the ingress of dust andinsects in smoke detectors
E
Attractive, low-profile designE
EN54 approved *E
Innovative base compensates for uneven surfacesE
Conventional Fire Systems
Page : 6
KCT731Calibration Tool for KL731/DP331I Fire Detectors
The KCT731 is a calibration tool to recalibrate the conventionaldetectors after replacement of the field exchangeable optical block.
Specifications
Supply 2 x 9 V batteries
Dimensions (w x h x d) 104 x 195 x 63 mm
Ordering Information
Calibration Tool for KL731/DP331I Fire DetectorsKCT731
Easy to useE
Simple "go/no-go" functionE
Battery operatedE
Detector Bases & Accessories
Page : 7
KZ700Universal fire detector base
The KZ700 is a 4 contact universal detector base. It has the ability tocompensate for uneven mounting surfaces. It is also available in blackfor special applications in false ceilings.
Specifications
Dimensions
Diameter 104 mm
Height 24 mm
Ordering Information
Universal fire detector base KZ700Universal fire detector base (for KL700/A and Dx300/1500) - BlackKZ700B
Polarity sensitiveE
Universal base fits conventional and analoguedetectors
E
Compensates for uneven surfacesE
Remote indicator contact availableE
EN54 approvedE
Variant in black also availableE
Detector Bases & Accessories
Page : 8
KZ705Universal fire detector base with earth connection
The KZ705 is a 5 contact universal detector base for use with theKL700/Dx300 and KL700A/Dx1500 series detectors from GE-Interlogix.In addition to the normal base and remote indication connectors, theKZ705 also has an additional earth terminal connector to allow foreasy terminations of a possible cable screen.
Specifications
Dimensions (Ø x h) 100 x 29 mm
Operating Voltage -
Current Consumption -
Isolation Current -
Isolation Resistance -
Sounder Frequency -
Sound Output
@ 3 mA -
@ 5 mA -
Environmental Characteristics
Operating Temperature -10 to 70 °C
Storage Temperature -10 to 70 °C
Relative Humidity (max) 95 % (non-cond.)
Ordering Information
Universal fire detector base with earth connectionKZ705
Polarity sensitiveE
Universal base fits conventional and analoguedetectors
E
Additional earth terminal availableE
Remote indicator contact availableE
Conventional Fire Systems
Page : 9
KZ705DConventional fire detector base with diode
The KZ705D is a 5 contact universal detector base for use with theKL700/Dx300 series detectors from GE-Interlogix. In addition to thenormal base and remote indication connectors, the KZ705D also hasan additional earth terminal connector to allow for easy terminationsof a possible cable screen. The built in diode is specifically targeted atsystems using active end-of-line devices.
Specifications
Dimensions (Ø x h) 100 x 29 mm
Operating Voltage -
Current Consumption -
Isolation Current -
Isolation Resistance -
Sounder Frequency -
Sound Output
@ 3 mA -
@ 5 mA -
Environmental Characteristics
Operating Temperature -10 to 70 °C
Storage Temperature -10 to 70 °C
Relative Humidity (max) 95 % (non-cond.)
Ordering Information
Conventional fire detector base with diodeKZ705D
Polarity sensitiveE
Universal base for conventional detectorsE
Additional earth terminal availableE
Remote indicator contact availableE
Built in diode for active end-of-line systemsE
EOL-ACTActive end-of-line device for use with FP400/KL700 fire panels
The EOL-ACT is designed for use with the NK700/FP400 fire panels fromGE-Interlogix. It is an active end-of-line device to allow the monitoringof a conventional zone through a diode base (such as the KZ705D).
Ordering Information
Active end-of-line device for use with FP400/KL700 fire panelsEOL-ACT
SmallE
Easy to installE
Conventional Fire Systems
Page : 10
KZ705RConventional 12 VDC fire detector base with relay
The KZ705R is a 5 contact detector base for use with the KL731/DP331Idetectors from GE-Interlogix. In addition to the normal base andremote indication connectors, the KZ705R also has an additional earthterminal connector to allow for easy terminations of a possible cablescreen. A built in 12 V relay makes it ideal for use on low voltageintrusion systems.
Specifications
Dimensions (Ø x h) 100 x 29 mm
Operating Voltage 12 V ± 10%
Current Consumption 12 A
Isolation Current -
Isolation Resistance -
Sounder Frequency -
Sound Output
@ 3 mA -
@ 5 mA -
Environmental Characteristics
Operating Temperature -10 °C to +70 °C
Storage Temperature -10 °C to +70 °C
Relative Humdity 95 % (non cond.)
Ordering Information
Conventional 12 VDC fire detector base with relayKZ705R
Polarity sensitiveE
12 V relay for 4 wire systemsE
Additional earth terminal availableE
Remote indicator contact availableE
Detector Bases & Accessories
Page : 11
S700Surface mount accessory for KZ700 and KZ705 series bases
The S700 is a base accessory designed for use with the KZ700 seriesdetector bases. It allows for a surface mount conduit and cable toenter the base from the side. The KZ700 series base fits on top of thisaccessory.
Specifications
Dimensions
Diameter 95 mm
Height 30 mm
Ordering Information
Surface mount accessory for KZ700 and KZ705 series basesS700
Surface mount accessory for KZ700 series basesE
Conventional Fire Systems
Page : 12
DP721IPhotoelectric smoke detector with remote alarm LED output
700 seriesThe smoke detector continually monitors its own sensitivity andoperational status. Once a day, it performs a full diagnostic test whichincludes dynamically testing the sensing chamber and internalelectronics.
Specifications
Operating voltage 8.5 - 33 V dc
Current consumption
Quiescent at 24 V dc 100 A; Max. 70 A average
In alarm at 24 V dc 60 mA
Alarm indication White LED (red alarm)
Fault indication Yellow LED
Remote alarm output 30 mA
RY contact rating
Relay models 2 A @ 30 V dc;1 A @ 120 V ac
Humidity 0 - 95%; Non-condensing
IP rating IP 43
Operating temperature -10°C - 60°C
Sensitivity 10%/m (+1.6%, -3.3%)
Reset voltage 2,5 V max
Reset time 1 sec
Dimensions 10 cm Ø, H = 5 cm
Ordering Information
Photoelectric smoke detector with remote alarm LED outputDP721IPhotoelectric smoke detector with C/O relay outputDP721R10 cm diameter base - 6 terminalsDB702
Automatic Self Diagnostics : Dynamic full detector test,Sensitivity test
E
Manual Self Diagnostic routine with visual sensitivityindication
E
Field sensitivity testing without external metersE
Field exchangeable and disposable optical chamberE
High false alarm immunityE
Floating background with drift compensationE
Separate fire and trouble LEDE
12 - 24 V dc operationE
Polarity insensitiveE
Full range : optical, heat and optical/heat multi criteriasensor
E
EN 54 approvedE
Conventional Fire Systems
Page : 13
DP721TPhotoelectric smoke and heat detector head with remote alarm LED
700 seriesFitted with a field-exchangeable optical block. The smoke detectorcontinually monitors its own sensitivity and operational status. Once aday, it performs a full diagnostic test which includes dynamicallytesting the sensing chamber and internal electronics.
Specifications
Operating voltage 8.5 - 33 V dc FWR
Current consumption
Quiescent at 24 V dc 100 A; Max. 70 A average
In alarm at 24 V dc 60 mA
Alarm indication White LED (red alarm)
Fault indication Yellow LED
Remote alarm output 30 mA
RY contact rating 2 A @ 30 V dc;1 A @ 120 V ac
Humidity 0 - 95%; Non-condensing
IP rating IP 43
Sensitivity 10%/m (+1.6%, -3.3%)
Reset voltage 2,5 V max
Reset time 1 sec
Dimensions 10 cm Ø, H = 5 cm
Ordering Information
Photoelectric smoke and heat detector head with remote alarm LEDDP721TPhotoelectric smoke and heat detector with relay outputDP721RTPhotoelectric smoke and heat detector with relay output, autoresetDP721RTA10 cm diameter base - 6 terminalsDB702
Automatic Self Diagnostics : Dynamic full detector test,Sensitivity test
E
Manual Self Diagnostic routine with visual sensitivityindication
E
Field sensitivity testing without external metersE
Field exchangeable and disposable optical chamberE
High false alarm immunityE
Floating background with drift compensationE
Separate fire and trouble LEDE
12 - 24 V dc operationE
Polarity insensitiveE
Full range : optical, heat and optical/heat multi criteriasensor
E
EN 54 approvedE
Conventional Fire Systems
Page : 14
DT713-557º C fixed and rate-of-rise heat detector
700 seriesThe smoke detector continually monitors its own sensitivity andoperational status. Once a day, it performs a full diagnostic test whichincludes dynamically testing the sensing chamber and internalelectronics.
Specifications
Operating voltage 8.5 - 33 V dc FWR
Current consumption
Quiescent at 24 V dc 100 A; Max. 70 A average
In alarm at 24 V dc 60 mA
Alarm indication Red LED
Fault indication Yellow LED
Remote alarm output 30 mA
RY contact rating 2 A @ 30 V dc;1 A @ 120 V ac
Humidity 0 - 95%; Non-condensing
IP rating IP 43
Heat specification
Max. 57º C ± 1.5º C
R.O.R. 8º C/min and > 40° C
Sensitivity
Reset voltage 2,5 V max
Reset time 1 sec
Dimensions 10 cm Ø, H = 5 cm
Ordering Information
57º C fixed and rate-of-rise heat detectorDT713-557º C and R.O.R. heat detector, with relay outputDT713-5R10 cm diameter base - 6 terminalsDB702
Automatic Self Diagnostics : Dynamic full detector test,Sensitivity test
E
Manual Self Diagnostic routine with visual sensitivityindication
E
Field sensitivity testing without external metersE
Field exchangeable and disposable optical chamberE
High false alarm immunityE
Floating background with drift compensationE
Separate fire and trouble LEDE
12 - 24 V dc operationE
Polarity insensitiveE
Full range : optical, heat and optical/heat multi criteriasensor
E
EN 54 approvedE
Conventional Fire Systems
Page : 15
DT713-770º C fixed and R.O.R. heat detector
700 seriesThe smoke detector continually monitors its own sensitivity andoperational status. Once a day, it performs a full diagnostic test whichincludes dynamically testing the sensing chamber and internalelectronics.
Specifications
Operating voltage 8.5 - 33 V dc FWR
Current consumption
Quiescent at 24 V dc 100 A; Max. 70 A average
In alarm at 24 V dc 60 mA
Alarm indication Red LED
Fault indication Yellow LED
Remote alarm output 30 mA
RY contact rating 2 A @ 30 V dc;1 A @ 120 V ac
Humidity 0 - 95%; Non-condensing
IP rating IP 43
Heat specification
Max. 70º C ± 1.5º C
R.O.R. 8º C/min and > 40° C
Reset voltage 2,5 V max
Reset time 1 sec
Dimensions 10 cm Ø, H = 5 cm
Ordering Information
70º C fixed and R.O.R. heat detectorDT713-710 cm diameter base - 6 terminalsDB702
Automatic Self Diagnostics : Dynamic full detector test,Sensitivity test
E
Manual Self Diagnostic routine with visual sensitivityindication
E
Field sensitivity testing without external metersE
Field exchangeable and disposable optical chamberE
High false alarm immunityE
Floating background with drift compensationE
Separate fire and trouble LEDE
12 - 24 V dc operationE
Polarity insensitiveE
Full range : optical, heat and optical/heat multi criteriasensor
E
EN 54 approvedE
Conventional Fire Systems
Page : 16
DB70210 cm diameter base - 6 terminals
700 seriesDetector base for 700 series detectors
Ordering Information
10 cm diameter base - 6 terminalsDB70215 cm diameter base - 6 terminalsDB702U
Automatic Self Diagnostics : Dynamic full detector test,Sensitivity test
E
Manual Self Diagnostic routine with visual sensitivityindication
E
Field sensitivity testing without external metersE
Field exchangeable and disposable optical chamberE
High false alarm immunityE
Floating background with drift compensationE
Separate fire and trouble LEDE
12 - 24 V dc operationE
Polarity insensitiveE
Full range : optical, heat and optical/heat multi criteriasensor
E
EN 54 approvedE
Conventional Fire Systems
Page : 17
DI650Ionisation smoke detector
650 seriesThis elegant slim-line ionisation detector offers high performance andwide operating voltage
Specifications
Size of detector (mm)
Height 42
Diameter 100
Size of detector + base (mm)
Height 50
Diameter 100
Supply voltage 9 - 33 V dc
Quiescent Current at 24 V(typical)
28 A
Alarm indication LED
Normal operating temp. range(no icing)
-20 to + 60°C
Humidity (no condensation) 0-95% RH
Max. wind 10m/s
Remote alarm output current 17 mA
IP Rating 43
Ordering Information
Ionisation smoke detectorDI650Integrating ionisation smoke dectectorDI651Standard BaseDB860
Wide operating voltageE
Advanced electronic technologyE
Flashing LED optionE
Polarity insensitiveE
Common baseE
Elegant slim-line designE
EN54 approvedE
Magnetic test switch optionE
Proven detection performanceE
Conventional Fire Systems
Page : 18
DP652Optical smoke detector
650 seriesThis elegant slim-line optical sensor provides high performance andwide operating range.
Specifications
Size of detector (mm)
Height 42
Diameter 100
Size of detector + base (mm)
Height 50
Diameter 100
Supply voltage 9 - 33 V dc
Quiescent Current at 24 V(typical)
40 A
Alarm indication LED
Normal operating temp. range(no icing)
-20 to + 60°C
Humidity (no condensation) 0-95% RH
Max. wind Not affected
Remote alarm output current 17 mA
IP Rating 43
Ordering Information
Optical smoke detectorDP652Standard BaseDB860
Polarity insensitiveE
Common baseE
Elegant slim-line designE
EN 54 approvedE
Wide operating voltageE
Conventional Fire Systems
Page : 19
DT654Heat detector, R.O.R., 57º C A1R
650 seriesThis elegant slim-line heat sensor has a wide operating temperatureand is available in four ranges
Specifications
Size of detector (mm)
Height 42
Diameter 100
Size of detector + base (mm)
Height 50
Diameter 100
Supply voltage 9 - 33 V dc
Quiescent Current at 24 V(typical)
45 A
Alarm indication LED
Normal operating temp. range(no icing)
-20 to + 60°C
Humidity (no condensation) 0-95% RH
Max. wind Not affected
Remote alarm output current 17 mA
IP Rating 54
Ordering Information
Heat detector, R.O.R., 57º C A1RDT654Heat detector, 75º C BRDT655Heat detector, 95º C CRDT656Heat detector, 90º C CSDT657Standard BaseDB860
Wide operating voltageE
Advanced electronic technologyE
Flashing LED optionE
Polarity insensitiveE
Common baseE
Elegant slim-line designE
EN54 approvedE
Magnetic test switch optionE
Proven detection performanceE
Conventional Fire Systems
Page : 20
DB860Standard Base
650 seriesThe base has been designed to enable detectors to be plugged inwithout any need for force - particularly useful when fitting tosuspended ceilings.
Ordering Information
Standard BaseDB860Standard base 15 cm diameterDB860U
860 series Conventional fire detectorsE
Polarity insensitiveE
Common baseE
Elegant slim-line designE
EN 54 approvedE
DB861Backplate for Ingress Protection 860-950
Ordering Information
Backplate for Ingress Protection 860-950DB861
Can prevent most ingress into the base and detectorE
Conventional Fire Systems
Page : 21
DB806Conduit box for 860 / 950 series bases
An inexpensive and versatile accessory for surface mounting 860 and950 series bases
Ordering Information
Conduit box for 860 / 950 series basesDB806
DB650650 series relay base
650 seriesThe relay base provides a volt-free contact for use in 4 wire controlsystems, and other applications
Ordering Information
650 series relay baseDB650
DB650E
For use with 4 wire control systemsE
Automatic door closersE
Volt-free relay contactsE
Addressable Fire Systems
Page : 22
DI1552Ionisation Sensor
The 1500 Series uses a microprocessor for measurement andcommunication. An enhanced protocol ensures the overall integrityand error free operation of the system, without compromisingdetection speed. All sensors are compatible with a standard base thatmakes them easily interchangeable and support the connection of aremote indicator.
Specifications
Operating voltage 22 to 38 VDC
Current consumption
Quiescent @ 38 VDC 200 A
In Alarm < 11 mA
Alarm indication (Dual LED) White OFF - Red ON
Remote Alarm Output Available
Environment
Storage Temperature -10 to +70 °C
Operating Temperature -10 to +60 °C
Humidity (non-condensing) 0-95%
IP rating IP42
Radioactive Source 0.33 ± 0.04 Ci Am 241
Dimensions (h x Ø) 45 x 99 mm
Ordering Information
Ionisation SensorDI1552 Universal fire detector base KZ700Universal fire detector base with earth connectionKZ705Analogue fire detector base with sounderKZ705ASAnalogue fire detector base with isolatorKZ705IAnalogue fire detector base with isolator and sounderKZ705IAS Low current remote LED indicatorPA25/3L
Remote signalling capabilitiesE
Optical sensor with field exchangeable optical chamberE
Easy soft addressing (1-125)E
SMD technologyE
Reliable communication protocolE
Full diagnostic self testingE
Full range: Ionisation, Optical and Heat and Dualsensors (optical/heat)
E
Full range of supporting I/O units and accessoriesE
EN54 ApprovedE
Addressable Fire Systems
Page : 23
DP1561Optical sensor with field exchangeable optical block
The 1500 series detectors use a microprocessor for measurement andcommunication. An enhanced protocol ensures the overall integrityand error free operation of the system, without compromisingdetection speed.
All sensors are compatible with a standard base that makes themeasily interchangeable and support the connection of the PA25/3Lremote indicator.
Specifications
Operating voltage 22 to 38 VDC
Current consumption
Quiescent @ 38 VDC 350 A
In Alarm < 11 mA
Alarm indication (Dual LED) Red
Remote Alarm Output Available
Environment
Storage Temperature -10 to +70 °C
Operating Temperature -10 to +60 °C
Humidity (non-condensing) 0-95%
IP rating IP42
Radioactive Source NA
Dimensions (h x Ø) 45 x 99 mm
Ordering Information
Optical sensor with field exchangeable optical blockDP1561 Replacement Optical Chamber for KL731/A & DP331I/1561 detectorsKOB700 Universal fire detector base KZ700Universal fire detector base with earth connectionKZ705Analogue fire detector base with sounderKZ705ASAnalogue fire detector base with isolatorKZ705IAnalogue fire detector base with isolator and sounderKZ705IAS Low current remote LED indicatorPA25/3L
Remote signalling capabilitiesE
Optical sensor with field exchangeable optical chamberE
Easy soft addressing (1-125)E
SMD technologyE
Reliable communication protocolE
Full diagnostic self testingE
Full range: Ionisation, Optical and Heat and Dualsensors (optical/heat)
E
Full range of supporting I/O units and accessoriesE
EN54 ApprovedE
Addressable Fire Systems
Page : 24
DP1551TDual Sensor (Optical/Heat)
The 1500 Series uses a microprocessor for measurement andcommunication. An enhanced protocol ensures the overall integrityand error free operation of the system, without compromisingdetection speed. All sensors are compatible with a standard base thatmakes them easily interchangeable and support the connection ofaremote indicator.
Specifications
Operating voltage 22 to 38 VDC
Current consumption
Quiescent @ 38 VDC 350 A
In Alarm < 5 mA
Alarm indication (Dual LED) Red
Remote Alarm Output Available
Environment
Storage Temperature -10 to +70 °C
Operating Temperature -10 to +70 °C
Humidity (non-condensing) 0-95%
IP rating IP42
Radioactive Source NA
Dimensions (h x Ø) 51 x 99 mm
Ordering Information
Dual Sensor (Optical/Heat)DP1551T Universal fire detector base KZ700Universal fire detector base with earth connectionKZ705Analogue fire detector base with sounderKZ705ASAnalogue fire detector base with isolatorKZ705IAnalogue fire detector base with isolator and sounderKZ705IAS Low current remote LED indicatorPA25/3L
Remote signalling capabilitiesE
Optical sensor with field exchangeable optical chamberE
Easy soft addressing (1-125)E
SMD technologyE
Reliable communication protocolE
Full diagnostic self testingE
Full range: Ionisation, Optical and Heat and Dualsensors (optical/heat)
E
Full range of supporting I/O units and accessoriesE
EN54 ApprovedE
Addressable Fire Systems
Page : 25
DT1553Heat Sensor
The 1500 Series uses a microprocessor for measurement andcommunication. An enhanced protocol ensures the overall integrityand error free operation of the system, without compromisingdetection speed. All sensors are compatible with a standard base thatmakes them easily interchangeable and support the connection ofaremote indicator.
Specifications
Operating voltage 22 to 38 VDC
Current consumption
Quiescent @ 38 VDC 250 A
In Alarm < 11 mA
Alarm indication (Dual LED) White OFF - Red ON
Remote Alarm Output Available
Environment
Storage Temperature -10 to +80 °C
Operating Temperature -10 to +70 °C
Humidity (non-condensing) 0-95%
IP rating IP42
Radioactive Source NA
Dimensions (h x Ø) 45 x 99 mm
Ordering Information
Heat SensorDT1553 Universal fire detector base KZ700Universal fire detector base with earth connectionKZ705Analogue fire detector base with sounderKZ705ASAnalogue fire detector base with isolatorKZ705IAnalogue fire detector base with isolator and sounderKZ705IAS Low current remote LED indicatorPA25/3L
Remote signalling capabilitiesE
Optical sensor with field exchangeable optical chamberE
Easy soft addressing (1-125)E
SMD technologyE
Reliable communication protocolE
Full diagnostic self testingE
Full range: Ionisation, Optical and Heat and Dualsensors (optical/heat)
E
Full range of supporting I/O units and accessoriesE
EN54 ApprovedE
Addressable Fire Systems
Page : 26
PG700Fire sensor programmer
The PG700 is a handheld device programmer and tester for theKL700A/Dx1500 series detectors. It is battery operated and allows theinstaller to perform installation tasks (such as device addressing) andmaintenance tasks (such as device calibration) in the field withoutexternal assistance.
Specifications
Supply 2 x 9 V batteries
Dimensions (w x h x d) 104 x 195 x 63 mm
Ordering Information
Fire sensor programmerPG700
Easy to useE
Battery operatedE
4 User selectable programs-Device analogue value-Change Device Address-Sequential device addressing-KL731A Calibration
E
Addressable Fire Systems
Page : 27
KZ705IAnalogue fire detector base with isolator
The KZ705I is a detector base with built in isolator for use with theKL700A/Dx1500 series detectors from GE-Interlogix. The isolatorprotects the loop from short circuit conditions. A LED on the side of thebase indicates the status of the isolator.
Specifications
Dimensions (Ø x h) 100 x 29 mm
Operating Voltage 17 - 34 V
Current Consumption 50 A
Isolation Current 6 mA
Isolation Resistance 140 Mohm
Sounder Frequency -
Sound Output
@ 3 mA -
@ 5 mA -
Environmental Characteristics
Operating Temperature -10 °C to +70 °C
Storage Temperature -10 °C to +70 °C
Relative Humidity (max) 95 % (non cond.)
Ordering Information
Analogue fire detector base with isolatorKZ705I
Polarity sensitiveE
Universal base for analogue detectorsE
Additional earth terminal availableE
Remote indicator contact availableE
Built in isolatorE
Addressable Fire Systems
Page : 28
KZ705ASAnalogue fire detector base with sounder
The KZ705AS is a detector base with built in analogue addressablesounder for use with the KL700A/Dx1500 series detectors fromGE-Interlogix. The sounder has its own address on the fire panel loopand works independent of the detector. It is fully controlled from thefire panel.
Specifications
Dimensions (Ø x h) 120 x 58 mm
Operating Voltage 22 - 38 V
Current Consumption 300 A Quiescent
Isolation Current -
Isolation Resistance -
Sounder Frequency 1 kHz (Continuous)
Sound Output
@ 3 mA 85 dBA
@ 5 mA 90 dBA
Environmental Characteristics
Operating Temperature -10 °C to +70 °C
Storage Temperature -10 °C to +70 °C
Relative Humidity (max) 95 % (non cond.)
IP Rating IP21c
Ordering Information
Analogue fire detector base with sounderKZ705AS
Polarity sensitiveE
Universal base for analogue detectorsE
Additional earth terminal availableE
Remote indicator contact availableE
Built in sounderE
Up to 90 dBA sound outputE
Low current consumptionE
Addressable Fire Systems
Page : 29
KZ705IASAnalogue fire detector base with isolator and sounder
The KZ705IAS is a detector base with built in analogue addressablesounder and isolator for use with the KL700A/Dx1500 series detectorsfrom GE-Interlogix. The sounder has its own address on the fire panelloop and works independent of the detector. It is fully controlled fromthe fire panel. The isolator protects the loop from short circuitconditions.
Specifications
Dimensions (Ø x h) 120 x 58 mm
Operating Voltage 22 - 38 V
Current Consumption 350 A Quiescent
Isolation Current 6 mA
Isolation Resistance 140 Mohm
Sounder Frequency 1 kHz (Continuous)
Sound Output
@ 3 mA 85 dBA
@ 5 mA 90 dBA
Environmental Characteristics
Operating Temperature -10 °C to +70 °C
Storage Temperature -10 °C to +70 °C
Relative Humidity (max) 95 % (non cond.)
IP Rating IP21c
Ordering Information
Analogue fire detector base with isolator and sounderKZ705IAS
Polarity sensitiveE
Universal base for analogue detectorsE
Additional earth terminal availableE
Remote indicator contact availableE
Built in sounderE
Up to 90 dBA sound outputE
Low current consumptionE
Built in isolatorE
Addressable Fire Systems
Page : 30
KAL410Conventional Zone Monitor Unit - 1 Zone
Allows the connection of one conventional zone to the analogue firesystem loop. This zone is constantly monitored. Up to 20 conventionaldevices may be connected to this zone.
Specifications
Supply voltage 22-38 VDC
Current consumption
Quiescent @ 24 V 90 A
Quiescent @ 35 V 105 A
Alarm < 3 mA
Aux. supply (24 VDC)quiescent
200 A + equip
Aux. supply (24 VDC) alarm < 85 mA
End-of-line resistor 4.7 kohm
Relay contact rating NA
Environmental
Storage temperature -10 °C to +50°C
Operating temperature -10 °C to +70°C
Relative humidity 95 % (non condensing)
Dimensions (L x W x H) 117 x 80 x 44 mm
Ordering Information
Conventional Zone Monitor Unit - 1 ZoneKAL410
Easy numeric addressingE
Continuous supervision of the conventional zonesE
Surface mountE
Local alarm indicationE
Externally or loop poweredE
Aesthetically pleasingE
Part of family of I/O modules consisting of:-Conventional Zone Monitors-Digital Input Modules-Extinguishing Control Modules-Isolator Modules-Manual Call Points-Output Units-Retention Units-Supervised Output Units for sounder control
E
Addressable Fire Systems
Page : 31
KAL414CConventional Zone Monitor Unit - 4 Zones
Allows the connection of four conventional zones to the analogue firesystem loop. These zones are constantly monitored. Up to 20conventional devices may be connected to any zone.
Specifications
Supply voltage 22-38 VDC
Current consumption
Quiescent @ 24 V 110 A
Quiescent @ 35 V 135 A
Alarm < 5 mA
Aux. Supply (24V DC)Quiescent
200 A + equip
Aux. Supply (24V DC) Alarm < 360 mA
End-of-line resistor 4.7 kOhm
Relay contact rating NA
Environmental
Storage temperature -10 to +50°C
Operating temperature -10 to +70°C
Relative humidity(non-condensing)
0-95 %
Dimensions (l x w x h) 163 x 107 x 36 mm
Ordering Information
Conventional Zone Monitor Unit - 4 ZonesKAL414C
Easy numeric addressingE
Continuous supervision of the conventional zonesE
Surface mountE
Local alarm indicationE
Externally poweredE
Aesthetically pleasingE
Part of a family of I/O modules consisting of:E
- Conventional Zone MonitorsE
- Digital Input ModulesE
- Extinguishing Control ModulesE
- Isolator ModulesE
- Manual Call PointsE
- Output UnitsE
- Retention UnitsE
- Supervised Output Units for sounder controlE
Addressable Fire Systems
Page : 32
KAL426CExtinguishing Control Module
The 400 Series modules consists of a complete range of interfacesdeveloped for input/output control in the KSA700/FP1500 analogue firesystems from GE Interlogix. The KAL426 allows for the connection andcontrol of one extinguishing area to the addressable fire panel loop.
Specifications
Supply voltage 22-38 VDC
Current consumption
Quiescent @ 24 V 110 A
Quiescent @ 35 V 210 A
Alarm < 10 mA
Aux. supply (24 VDC)quiescent
120 mA
Aux. supply (24 VDC) alarm < 1 A
End-of-line resistor 4.7 kOhm
Relay contact rating 2½ A
Environmental
Storage temperature -10 °C to +50°C
Operating temperature -10 °C to +70°C
Relative humidity 95 % (non condensing)
Dimensions (L x W x H) 163 x 107 x 36 mm
Ordering Information
Extinguishing Control ModuleKAL426C
Aesthetically pleasingE
Easy numeric addressingE
Externally poweredE
Supervised I/OE
Surface mountE
Part of family of I/O modules consisting of:-Conventional Zone Monitors-Digital Input Modules-Extinguishing Control Modules-Isolator Modules-Manual Call Points-Output Units-Retention Units-Supervised Output Units for sounder control
E
Addressable Fire Systems
Page : 33
KAL430Relay Module - 1 Relay
Provides for one potential free relay output for the fire system loop.Each relay allows for COMMON, NORMALLY OPEN and NORMALLYCLOSED contacts. The output may be used to activate ventilationcontrols, warning signs, activation of other alarm devices etc. duringfire situations.
Specifications
Supply voltage 22-38 VDC
Current consumption
Quiescent @ 24 V 70 A
Quiescent @ 35 V 100 A
Alarm < 3.5 mA
Aux. 24 VDC quiescent 22 mA
Aux. 24 VDC alarm < 50 mA
End-of-line resistor NA
Relay contact rating 2½A @ 250 VAC
Environmental
Storage temperature -10 °C to +50°C
Operating temperature -10 °C to +70°C
Relative humidity 95 % (non condensing)
Dimensions (L x W x H) 117 x 80 x 44 mm
Ordering Information
Relay Module - 1 RelayKAL430
Easy numeric addressingE
Externally or loop poweredE
Normally open / normally closed operation for I/OE
Surface mountE
Aesthetically pleasingE
Local status indicationE
Part of family of I/O modules consisting of:-Conventional Zone Monitors-Digital Input Modules-Extinguishing Control Modules-Isolator Modules-Manual Call Points-Output Units-Retention Units-Supervised Output Units for sounder control
E
Addressable Fire Systems
Page : 34
KAL434CAddressable Relay Module - 4 Relays
Provides for four potential free relay outputs for the fire system loop.Each relay allows for COMMON, NORMALLY OPEN and NORMALLYCLOSED contacts. The outputs may be used to activate ventilationcontrols, warning signs, activation of other alarm devices etc. duringfire situations.
Specifications
Supply voltage 22-38 VDC
Current consumption
Quiescent @ 24 V 110 A
Quiescent @ 35 V 135 A
Alarm 10 mA
Aux. 24VDC Quiescent 100 A
Aux. 24VDC Alarm 10 mA
End-of-line resistor NA
Relay contact rating 2½A @ 250 VAC
Environmental
Storage temperature -10 to +50°C
Operating temperature -10 to +70°C
Relative humidity (non-cond.) 0-95 %
Dimensions (l x w x h) 163 x 107 x 36 mm
Ordering Information
Addressable Relay Module - 4 RelaysKAL434C
Easy numeric addressingE
Externally poweredE
Normally open / normally closed operation for I/OE
Surface mountE
Aesthetically pleasingE
Local status indicationE
Part of a family of I/O modules consiting of:E
- Conventional Zone MonitorsE
- Digital Input ModulesE
- Extinguishing Control ModulesE
- Isolator ModulesE
- Manual Call PointsE
- Output UnitsE
- Retention UnitsE
- Supervised Output Units for sounder controlE
Addressable Fire Systems
Page : 35
KAL440Supervised Relay Module
Allows for the supervision of a single, 24 Volt powered output contacton the fire system loop. This unit may be used to control for e.g.sounders in case of fire conditions, but may also be used to switch anyoutput considered crucial enough to have the cable integrity betweenthe unit and the switch point monitored.
Specifications
Supply voltage 22-38 VDC
Current consumption
Quiescent @ 24 V 110 A
Quiescent @ 35 V 135 A
Alarm < 3.6 mA
Aux. 24 VDC quiescent 23 mA
Aux. 24 VDC alarm 23 mA + equip
End-of-line resistor 4.7 kohm
Relay contact rating 1¼ A @ 250 VAC
Environmental
Storage temperature -10 °C to +50°C
Operating temperature -10 °C to +70°C
Relative humidity 95 % (non condensing)
Dimensions (L x W x H) 117 x 80 x 44 mm
Ordering Information
Supervised Relay ModuleKAL440
Easy numeric addressingE
Externally poweredE
Supervised 24 VDC Output E
Surface mountE
Aesthetically pleasingE
Local status indicationE
Part of family of I/O modules consisting of:-Conventional Zone Monitors-Digital Input Modules-Extinguishing Control Modules-Isolator Modules-Manual Call Points-Output Units-Retention Units-Supervised Output Units for sounder control
E
Addressable Fire Systems
Page : 36
KAL450Addressable Manual Call Point
The 400 Series modules consists of a complete range of interfacesdeveloped for input/output control in the KSA700/FP1500 analogue firesystems from GE Interlogix. The KAL450 is an addressable manual callpoint for manual fire activation.
Specifications
Supply voltage 22-38 VDC
Current consumption
Quiescent @ 24 V 90 A
Quiescent @ 35 V 120 A
Alarm < 3.5 mA
Aux. supply (24 VDC)quiescent
NA
Aux. supply (24 VDC) alarm NA
End-of-line resistor NA
Relay contact rating NA
Environmental
Storage temperature -10 °C to +70°C
Operating temperature -10 °C to +50°C
Relative humidity 95 % (non condensing)
Ingress Protection IP20
Dimensions (L x W x H) 87 x 87 x 20 mm
Weight 98 g
Ordering Information
Addressable Manual Call PointKAL450EN54 universal glass for manual call pointDM715Terminal tray for MCPDM780GS cardDM781Hinged transparent MCP protection coverDM782BZB black bezelDM783Test keyDM784Spacer box, redDM785Surface mounting box with connectors, redDM787Surface mount box without connectors, redDM788Flush mount cradle with connectorsDM790Flush mount cradle, connectors & forkgripsDM795Breakable seal for MCPDM798Terminal tray ETT/3 with bezel 3DM799Resettable element for MCP DM700/KAL450DM800
Easy numeric addressingE
Loop poweredE
Local test facilityE
Surface or flush mountE
Aesthetically pleasingE
Local status indicationE
Part of family of I/O modules consisting of:-Conventional Zone Monitors-Digital Input Modules-Extinguishing Control Modules-Isolator Modules-Manual Call Points-Output Units-Retention Units-Supervised Output Units for sounder control
E
Wide range of accessoriesE
Addressable Fire Systems
Page : 37
KAL460Digital Input Module
Provides a remote input to the fire system loop. The input is constantlymonitored and its status communicated to the fire control panel. Theinput may be activated by closing or opening a potential free contact,depending on the module configuration.
This module may be used to monitor any contact by showing its statusthrough the fire control panel e.g. the monitoring of pressureequipment and closure fire break doors.
Specifications
Supply voltage 22-38 VDC
Current consumption
Quiescent @ 24 V 110 A
Quiescent @ 35 V 135 A
Alarm < 10 mA
Aux. 24 VDC quiescent 200 A
Aux. 24 VDC alarm < 50 mA
End-of-line resistor NA
Relay contact rating NA
Environmental
Storage temperature -10 °C to +50°C
Operating temperature -10 °C to +70°C
Relative humidity 95 % (non condensing)
Dimensions (L x W x H) 117 x 80 x 44 mm
Ordering Information
Digital Input ModuleKAL460
Easy numeric addressingE
Externally or loop poweredE
Normally open / normally closed operation for I/OE
Surface mountE
Aesthetically pleasingE
Local status indicationE
Part of family of I/O modules consisting of:-Conventional Zone Monitors-Digital Input Modules-Extinguishing Control Modules-Isolator Modules-Manual Call Points-Output Units-Retention Units-Supervised Output Units for sounder control
E
Addressable Fire Systems
Page : 38
KAL470Isolator Module
The 400 series modules consist of a complete range of interfacesdeveloped for input/output control in the KSA700/FP1500 analogue firesystems from GE Interlogix. The KAL470 is an isolator module in thisseries that isolates the faulty zone on a fire panel loop during shortcircuit conditions. The KAL470 does not use an address on the loop.
Specifications
Supply voltage 22-38 VDC
Current consumption
Quiescent @ 24 V 110 A
Quiescent @ 35 V 135 A
Alarm 10 mA
Aux. supply (24 VDC)quiescent
NA
Aux. supply (24 VDC) alarm NA
End-of-line resistor NA
Relay contact rating NA
Environmental
Storage temperature -10 °C to +50°C
Operating temperature -10 °C to +50°C
Relative humidity 95 % (non condensing)
Dimensions (L x W x H) 75 x 45 x 28 mm
Ordering Information
Isolator ModuleKAL470
Requires no device addressE
Automatic resetE
Local status indicationE
Surface mountE
Part of family of I/O modules consisting of:-Conventional Zone Monitors-Digital Input Modules-Extinguishing Control Modules-Isolator Modules-Manual Call Points-Output Units-Retention Units-Supervised Output Units for sounder control
E
Addressable Fire Systems
Page : 39
KAL490Retention Module - 1 Input / 1 Output
Provides a remote input and a potential free voltage relay output tothe fire system loop. The input signal is constantly monitored and itsstatus displayed on the control panel, whilst the output is fail-to-safe.Auxiliary supply monitoring is also included.
The module is used to for e.g. control and monitor doors such as firebreak doors. The relay provides the door activation and the inputmonitors the door status.
Specifications
Supply voltage 22-38 VDC
Current consumption
Quiescent @ 24 V 110 A
Quiescent @ 35 V 135 A
Alarm 10 mA
Aux. 24 VDC quiescent 200 A
Aux. 24 VDC alarm < 50 mA
End-of-line resistor NA
Relay contact rating 1A @ 30 VAC/VDC
Environmental
Storage temperature -10 °C to +50°C
Operating temperature -10 °C to +70°C
Relative humidity 95 % (non condensing)
Dimensions (L x W x H) 117 x 80 x 44 mm
Ordering Information
Retention Module - 1 Input / 1 OutputKAL490
Easy numeric addressingE
Externally or loop poweredE
Normally open / normally closed operation for I/OE
Surface mountE
Aesthetically pleasingE
Local status indicationE
Part of family of I/O modules consisting of:-Conventional Zone Monitors-Digital Input Modules-Extinguishing Control Modules-Isolator Modules-Manual Call Points-Output Units-Retention Units-Supervised Output Units for sounder control
E
Addressable Fire Systems
Page : 40
DP2051Optical Sensor
2000 SeriesEquipped with a field-exchangeable optical block and has fullcertification, this optical sensor provides good looks as well as topfeatures
Specifications
Operating voltage 17 - 28 V dc
Current consumption at 24 V dc
Quiescent < 150 A
Alarm LED: 2 mA - 7-segment: 2 mA
Alarm indication White LED (red alarm)
Remote alarm output
DP2051 / DT2053 -
DP2061 / DT2063 4 mA
DP2071 / DT2073 4 mA
Humidity 0 - 95% non condensing
Operating temperature -10°C - 70°C
IP rating IP43
Dimensions
Height 5 cm
Diameter 10 cm
Ordering Information
Optical SensorDP20512000 series base, 2 terminalsDB2001Isolating baseDB2016
Remote test capabilitiesE
Remote signalling capabilitiesE
Optical sensor with field exchangeable optical chamberE
Easy numeric addressing (1-128)E
Enhanced communication protocolE
Full diagnostic self testingE
Polarity insensitiveE
Full range: optical and heatE
Full range of I/0 units and accessoriesE
Isolator baseE
EN54 approvedE
VdS approvedE
Addressable Fire Systems
Page : 41
DP2061Optical Sensor with remote LED output
The DP2061 is equipped with a field-exchangeable optical block andhas full certification. This optical sensor combines good looks withalarm and fault LEDs as well as a remote output.
Specifications
Operating voltage 17 - 28 VDC
Current consumption @ 24 VDC
Quiescent < 150 A
Alarm 2 mA
Alarm indication White LED (Red alarm)
Remote alarm output 4 mA
Humidity 0 - 95% non condensing
Operating temperature -10 to +70°C
IP rating IP43
Dimensions
Height 5 cm
Diameter 10 cm
Ordering Information
Optical Sensor with remote LED outputDP2061 2000 series base, 4 terminalsDB2002Standard Base 15 cm, 4 TerminalsDB2002UIsolating baseDB2016
Remote test capabilitiesE
Remote signalling capabilitiesE
Optical sensor with field exchangeable optical chamberE
Easy numeric addressing (1-128)E
Enhanced communication protocolE
Full diagnostic self testingE
Polarity insensitiveE
Full range of detectors availableE
Full range of I/0 units and accessoriesE
Isolator baseE
EN54 approvedE
VdS approvedE
Addressable Fire Systems
Page : 42
DP2061TOptical and heat multi-sensor with remote LED output
The DP2061T multi-sensor combines the smoke sensitivity of an opticalsmoke detector with the enhancement of heat sensing. Being able tooperate in five modes, the DP2061T multi sensor can operate as anoptical smoke sensor enhanced by heat detection (with two differentsmoke sensitivities), as a dual smoke and heat detector, each sensoroperating independently, an optical sensor only, or a heat detectoronly.
Specifications
Operating voltage 17 to 28 VDC
Current consumption @ 24 VDC
Quiescent < 150 uA
Alarm 2 mA
Alarm indication White LED (Red alarm)
Remote alarm output 4mA
Humidity 0 - 95% non condensing
Operating temperature -10°C to 70°C
IP rating IP43
Dimensions
Height 5 cm
Diameter 10 cm
Ordering Information
Optical and heat multi-sensor with remote LED outputDP2061T 2000 series base, 2 terminalsDB20012000 series base, 4 terminalsDB2002Standard Base 15 cm, 4 TerminalsDB2002U2000 series deep base, 4 terminalsDB2004Isolating baseDB2016 Optical Remote IndicatorAI672Optical and Accustical Remote IndicatorAI673
Optical smoke and heat detectionE
Five modes of operation: multisensor (2 sensitivities) ,dual sensor, or independant smoke and heat
E
Independant control of detector modesE
Optical sensor with field exchangeable optical chamberE
Easy numeric addressing (1-128)E
Enhanced communication protocolE
Full diagnostic self testingE
Remote test capabilitiesE
Remote signalling capabilitiesE
Polarity insensitiveE
Full range of sensors: optical and heatE
Full range of I/0 units, MCPs and accessoriesE
Isolator base optionE
Addressable Fire Systems
Page : 43
DP2071Optical Sensor with 7-segment display
2000 SeriesEquipped with a field-exchangeable optical block and with fullcertification, this optical sensor provides good looks as well as topfeatures. Fitted with an exclusive 7-segment display, the sensorprovides comprehensive information. In addition to alarm signalling,information such as Fault, Pre-alarm, Maintenance Alarm (Clean me),Disabled Sensor, Sensor in Test, Error (double address, wrong sensortype) and Sensor Polled is provided.
Specifications
Operating voltage 17 - 28 V dc
Current consumption at 24 V dc
Quiescent < 150 A
Alarm LED: 2 mA - 7-segment: 2 mA
Alarm indication White LED (red alarm)
Remote alarm output 4 mA
DP2051 / DT2053 -
DP2061 / DT2063 4 mA
DP2071 / DT2073 4 mA
Humidity 0 - 95% non condensing
Operating temperature -10°C - 70°C
IP rating IP43
Dimensions
Height 5 cm
Diameter 10 cm
Ordering Information
Optical Sensor with 7-segment displayDP20712000 series base, 4 terminalsDB2002Standard Base 15 cm, 4 TerminalsDB2002UIsolating baseDB2016
7-segment displayE
Remote test capabilitiesE
Remote signalling capabilitiesE
Optical sensor with field exchangeable optical chamberE
Easy numeric addressing (1-128)E
Enhanced communication protocolE
Full diagnostic self testingE
Polarity insensitiveE
Full range: optical and heatE
Full range of I/0 units and accessoriesE
Addressable Fire Systems
Page : 44
DT20532000 Series heat sensor
2000 seriesFully certified, this heat sensor provides good looks as well as topfeatures.
Specifications
Operating voltage 17 - 28 V dc
Current consumption at 24 V dc
Quiescent < 150 A
Alarm LED: 2 mA - 7-segment: 2 mA
Alarm indication Red LED
Remote alarm output
DP2051 / DT2053 -
DP2061 / DT2063 4 mA
DP2071 / DT2073 4 mA
Humidity 0 - 95% non condensing
Operating temperature -10°C - 70°C
IP rating IP43
Dimensions
Height 5 cm
Diameter 10 cm
Ordering Information
2000 Series heat sensorDT20532000 series base, 2 terminalsDB2001Isolating baseDB2016
Remote test capabilitiesE
Remote signalling capabilitiesE
Optical sensor with field exchangeable optical chamberE
Available in one LED, two LED and seven segmentdisplay
E
Easy numeric addressing (1-128)E
Enhanced communication protocolE
Full diagnostic self testingE
Polarity insensitiveE
Full range: optical and heatE
Full range of I/0 units and accessoriesE
Isolator baseE
EN54 approvedE
VdS approvedE
Addressable Fire Systems
Page : 45
DT20632000 series heat sensor with remote LED output
2000 SeriesFully certified, this heat sensor provides good looks as well as topfeatures. Dual LED's indicate both alarm and fault. A remote output isalso provided.
Specifications
Operating voltage 17 - 28 VDC
Current consumption @ 24 VDC
Quiescent < 150 A
Alarm LED: 2 mA - 7-segment: 2 mA
Alarm indication Red LED
Remote alarm output 4 mA
Humidity 0 - 95% non condensing
Operating temperature -10 to +70°C
IP rating IP43
Dimensions
Height 5 cm
Diameter 10 cm
Ordering Information
2000 series heat sensor with remote LED outputDT2063 2000 series base, 4 terminalsDB2002Standard Base 15 cm, 4 TerminalsDB2002UIsolating baseDB2016
Remote test capabilitiesE
Remote signalling capabilitiesE
Optical sensor with field exchangeable optical chamberE
Available in one LED, two LED and seven segmentdisplay
E
Easy numeric addressing (1-128)E
Enhanced communication protocolE
Full diagnostic self testingE
Polarity insensitiveE
Full range: optical and heatE
Full range of I/0 units and accessoriesE
Isolator baseE
EN54 approvedE
VdS approvedE
Addressable Fire Systems
Page : 46
DT2073Heat Sensor with 7-segment Display and Remote LED Output
2000 SeriesFitted with an exclusive 7-segment display, this detector providescomprehensive, on the spot information. In addition to alarm signalling,information such as Fault, Pre-alarm, Maintenance Alarm (Clean me),Disabled Sensor, Sensor in Test, Error (double address, wrong sensortype) and Sensor Polled is provided.
Specifications
Operating voltage 17 - 28 V dc
Current consumption at 24 V dc
Quiescent < 150 A
Alarm LED: 2 mA - 7-segment: 2 mA
Alarm indication Red LED
Remote alarm output
DP2051 / DT2053 -
DP2061 / DT2063 4 mA
DP2071 / DT2073 4 mA
Humidity 0 - 95% non condensing
Operating temperature -10°C - 70°C
IP rating IP43
Dimensions
Height 5 cm
Diameter 10 cm
Ordering Information
Heat Sensor with 7-segment Display and Remote LED OutputDT20732000 series base, 4 terminalsDB2002Standard Base 15 cm, 4 TerminalsDB2002UIsolating baseDB2016
Remote test capabilitiesE
Remote signalling capabilitiesE
Optical sensor with field exchangeable optical chamberE
Available in one LED, two LED and seven segmentdisplay
E
Easy numeric addressing (1-128)E
Enhanced communication protocolE
Full diagnostic self testingE
Polarity insensitiveE
Full range: optical and heatE
Full range of I/0 units and accessoriesE
Isolator baseE
EN54 approvedE
VdS approvedE
Addressable Fire Systems
Page : 47
DB20012000 series base, 2 terminals
2000 series2 terminal base for DP2051 and DT2053
Ordering Information
2000 series base, 2 terminalsDB2001
Remote test capabilitiesE
Remote signalling capabilitiesE
Optical sensor with field exchangeable optical chamberE
Available in one LED, two LED and seven segmentdisplay
E
Easy numeric addressing (1-128)E
Enhanced communication protocolE
Full diagnostic self testingE
Polarity insensitiveE
Full range: optical and heatE
Full range of I/0 units and accessoriesE
Isolator baseE
EN54 approvedE
VdS approvedE
Addressable Fire Systems
Page : 48
DB20022000 series base, 4 terminals
2000 seriesA four terminal base for all 2000 series detectors
Ordering Information
2000 series base, 4 terminalsDB2002Standard Base 15 cm, 4 TerminalsDB2002U
Remote test capabilitiesE
Remote signalling capabilitiesE
Optical sensor with field exchangeable optical chamberE
Available in one LED, two LED and seven segmentdisplay
E
Easy numeric addressing (1-128)E
Enhanced communication protocolE
Full diagnostic self testingE
Polarity insensitiveE
Full range: optical and heatE
Full range of I/0 units and accessoriesE
Isolator baseE
EN54 approvedE
VdS approvedE
Addressable Fire Systems
Page : 49
DB2016Isolating base
The DB2016 isolator base senses and isolates short circuit faults. Ayellow LED indicates a short circuit condition. The detector in the basewill still receive power in the event of a single short circuit. If everydetector is fitted with an isolator base then no device will be lost in theevent of a single short circuit.
Ordering Information
Isolating baseDB2016
Remote test capabilitiesE
Remote signalling capabilitiesE
Optical sensor with field exchangeable optical chamberE
Available in one LED, two LED and seven segmentdisplay
E
Easy numeric addressing (1-128)E
Enhanced communication protocolE
Full diagnostic self testingE
Polarity insensitiveE
Full range: optical and heatE
Full range of I/0 units and accessoriesE
Isolator baseE
EN54 approvedE
VdS approvedE
Addressable Fire Systems
Page : 50
IU2016Loop Isolator
2000 seriesThe Aritech Loop Isolator is designed to prevent an entirecommunication loop from being disabled in the event of a short circuit.The IU 2016 isolates that part of the loop containing the short from theremainder of the circuit.
Specifications
Operating voltage 17 - 28 V, comm. loop terminals
Total standby current < 250 A
Isolated current
Average < 1.6 mA
Transition pulse < 36 mA (5 ms duration)
Operating temperature -10º C to 70º C
Operating humidity range 0 - 95%; Non-condensing
Line resistance
Normal 0.55 Ohms
Isolated > 33K Ohms
Switching voltage
Normal to isolated 13.8 V dc
Isolated to normal 2.5 V dc
Switching time
Normal to isolated < 5 ms
Isolated to normal < 0.5 ms (after fault correction)
Ordering Information
Loop IsolatorIU2016Base for the IU2016 isolatorDB2003
Complete isolation of loop short circuitE
Automatic restore when fault is correctedE
Module LED indicates location of faultE
Addressable Fire Systems
Page : 51
DB2003Base for the IU2016 isolator
Ordering Information
Base for the IU2016 isolatorDB2003
Addressable Fire Systems
Page : 52
DM2000Manual call point, flying leads
2000 seriesThe DM 2000 is a break glass design call point with a high strengthplastic housing. The LED indicator provides visual confirmation of alarminitiation. The test key (included with each unit) facilitates functionaltesting of the call point.
Specifications
Operating voltage 17 - 28 V, @ comm.loop terminals
Voltage modulation 4 - 9 V dc
Standby current < 250 A
LED indicator current 2.5 mA maximum
Operating temperature -10º C to 70º C
Operating humidity 0 - 95%; Non-condensing
Dimensions (L x W x H)
Flush mount 87 x 87 x 24 mm
Surface mount 87 x 87 x 56 mm
Ordering Information
Manual call point, flying leadsDM2000Manual call point flying leads - YellowDM2000YManual call point flying leads - BlueDM2000BBreak glass, EN54, Aritech logoDM711EN54 universal glass for manual call pointDM715
Analogue addressable manual call pointE
LED alarm indicatorE
Tamper resistant break glass designE
Easy to test with self resetE
Fast responseE
IP67 waterproof model availableE
Addressable Fire Systems
Page : 53
DM2000EManual call point - Red IP67 waterproof, including backbox
2000 seriesThe DM 2000E is a break glass design call point with a high strengthplastic housing and IP67 waterproof. The LED indicator provides visualconfirmation of alarm initiation. The test key (included with each unit)facilitates functional testing of the call point.
Specifications
Operating voltage 17 - 28 V, @ comm.loop terminals
Voltage modulation 4 - 9 V dc
Standby current < 250 A
LED indicator current 2.5 mA maximum
Operating temperature -10º C to 70º C
Operating humidity 0 - 95%; Non-condensing
Dimensions (L x W x H)
Flush mount 87 x 87 x 24 mm
Surface mount 87 x 87 x 56 mm
Ordering Information
Manual call point - Red IP67 waterproof, including backboxDM2000EBreak glass, EN54, Aritech logoDM711EN54 universal glass for manual call pointDM715 Analogue addressable manual call pointE
LED alarm indicatorE
Tamper resistant break glass designE
Easy to test with self resetE
Fast responseE
IP67 waterproof model availableE
Addressable Fire Systems
Page : 54
IO2014Input Output unit - 4 inputs
The 2000 Series loop powered Input/Output modules are designed toprovide unlimited applications to input monitoring and outputswitching. These modules, combined with the powerful features of the2000/1200 Series fire panels gives the user total versatility.
The IO2014 is a unit that provides 4 inputs with selectable linesupervision.
Specifications
Operating voltage 17 - 39 VDC
Total standby current < 420 A
Typical standby current < 350 A
Operating temperature -10°C to +70°C
Operating humidity range 0 - 95%, Non-condensing
Outputs NA
Inputs 4 Supervision Selectable
33 k resistor in series withswitch
Normal, Active, Open, Short
No resistor in series withswitch
Open, Short
EOL resistor 150 k , ¼ W, 5%
Ordering Information
Input Output unit - 4 inputsIO2014
Wide range of I/O Modules : 2 input-1 output / 2 input-2output / 4 input / 4 input - 4 output
E
Versatile input structureE
Supervised inputsE
Normally Open/Normally Closed operationE
Magnetic latched output relaysE
Loop poweredE
No external power requiredE
Easy numeric addressingE
Addressable Fire Systems
Page : 55
IU2050Single Input Module
2000 seriesThe Aritech Analogue Addressable Single Input Module is designed foruse with the FP 2000 Fire Panel to monitor normally open or normallyclosedcontacts. It can typically be connected to conventional Manual CallPoints, Pull Stations or Door Monitors and will report actuation within 1seconddepending on the programming of the fire panel.
Specifications
Operating voltage 17 - 28 V, @ comm. loop terminals
Voltage modulation 4-9 V dc
Standby current < 250 A
Operating temperature -20° C to 70° C
Operating humidity 0 - 95%; Non-condensing
EOL resistor 150 K, 1/4 W, 5%
Ordering Information
Single Input ModuleIU2050
Analogue Addressable Single Input ModuleE
Loop PoweredE
Supervised InputE
Addressable Fire Systems
Page : 56
IU2055Conventional Zone Monitor
The IU2055 two-wire zone monitor is designed to provide an interfacebetween conventional smoke detectors and the addressable series2000/1200 fire panels. The IU2055 enables the adressable panel tomonitor the presence and operation of up to 30 conventional detectorsin standard operation mode, or up to 20 intrinsically safe series 870conventional detectors in intrinscally safe configurations.
Specifications
Operating voltage
At loop terminals 18 - 39 VDC
At zone output terminals 14 - 18.5 VDC
Operating current
Standby < 15 mA
Alarm < 35 mA
Remote LED 4.5 mA
Maximum zone load current 3.5 mA
Maximum zone capacitance < 1 F
Maximum zone resistance < 30 Ohm
Operating temperature -10° C to +70° C
Operating humidity range 0 - 95%; Non-condensing
End of line resistance 4.3 k Ohm, ¼ W, 5 %
Zone impedances @ 24 V
Short circuit < 30 Ohms
Fire 180 - 300 Ohms
Quiescent 2.7 - 4.3 K Ohms
Open > 15 K Ohms
Ordering Information
Conventional Zone MonitorIU2055
Monitors up to 30 conventional smoke detectorsE
Zone supervised for open and short circuitsE
Supports alarm verification and reset functionsE
Loop poweredE
Easy numeric addressingE
Supports intrinsically safe applications for up to 20series 870 detectors
E
Addressable Fire Systems
Page : 57
GBX2000Galvanic barrier
2000 seriesA Galvanic barrier used with IU2055 zone monitor unit in intrinsic safeapplications
Ordering Information
Galvanic barrierGBX2000
Approved with the IU2055 zone monitor unitE
Intrinsic safe operation when correctly installedE
IU2080Indicating Circuit Controller
2000 seriesThe Aritech Indicating Circuit Controller is designed for efficient,addressable control of sounders, bells and strobes in a fire detectionsystem. The 3 A of output power available from the IU 2080 assuresmeeting all requirements for signaling devices on a fire alarm system.
Specifications
Operating voltage 17-28 V, at comm. loop terminals
Total standby current <350 A, <200 A typical
Maximum alarm current <3.5 mA at comm. loop
Operating temperature -10º C to 70º C
Operating humidity range 0 - 95%; Non-condensing
Circuit impedance at 24 V
Short circuit <3.3 K
Quiescent 3.3 K - 13 K
Open circuit <13 K
Power supply low voltagedetection
24 V; <20.4 V
Standby current <11 mA @ 24 V dc
Alarm current <72 mA @ 24 V dc (plus output circuit loadcurrent from ext. power supply)
Supervisory voltage 2.2 V dc, inverted
Circuit voltage in alarm 24 V dc
Alarm current (fuse rating) 3 A
End of line resistor value 10 K, 1/4W, 5%
Ordering Information
Indicating Circuit ControllerIU2080
Versatile, addressable control for sounders, bells andstrobes
E
Supervised output circuitE
Programmable outputE
24 V external power supplyE
Addressable Fire Systems
Page : 58
FD2705R2000 series addressable reflective beam detector 5 - 50m
2000 seriesThe FD 2705R and FD 2710R provides an integral, loop poweredanalogue addressable reflective beam detector up to 100m distance. It operates with 2000 series protocol with the FP1200 / 2000 Firepanels
Specifications
Supply voltage 17 - 30 V dc
Range
FD 2705R 5 - 50 m
FD 2710R 50 - 100 m
Lateral detection 7.5 m
Current consumption
Quiescent 5 mA
Alarm 9 mA
Fault 5 mA
Optical wave length 880 nm
Operating temperature -30°C to 55°C
Size 210 x 130 x 120 mm
IP rating IP50
Construction Flame retardent ABS
Colour Gray-black
Ordering Information
2000 series addressable reflective beam detector 5 - 50mFD2705R2000 series addressable reflective beam detector 50 - 100mFD2710R
Loop PoweredE
2000 series protocolE
Area coverage up to 600 m 2 per unitE
Range from 5 - 50 m and 50 - 100 mE
Up to ceiling heights of 25 mE
Low current consumptionE
3 selectable alarm thresholdsE
Self check and automatic contamination compensationE
Automatic discrimination between fire and faultE
Retro operation through prismE
Vertical or horizontal mountE
Easy wiring and unique alignmentE
Microprocessor controlledE
Conforms to BS 5839 part 5 and EN54E
Warning Device
Page : 59
AS20152000 series loop powered sounder
2000 seriesThe AS2015 is a 2000 series addressable loop powered sounder for theFP1200 and FP2000 range of fire panels. The unit has a built in isolatorand can be synchronized.
Specifications
Operating voltage 17-39 VDC
Supply current
not activated 240 A
activated 3mA
Sound output @ 1 meter 100 dB(A)
Continuous tone 990 Hz
Intermittent tone 990 Hz, On Off @ 1 Hz
Two tone 990 Hz / 650 Hz @ 1 Hz
Ordering Information
2000 series loop powered sounderAS20152000 series loop powered sounder - whiteAS2015W
Loop poweredE
Low currentE
High outputE
Built in isolatorsE
3 tonesE
FP1200 / 2000 fire panel operationE
Addressable Fire Systems
Page : 60
DI950Analogue addressable ionisation sensor
950 seriesThis elegant slim-line ionisation sensor provides high-performancesmoke detection
Specifications
Supply voltage (V dc) 17-28
Quiescent current 280 A
Alarm indication Red LED
Alarm LED current 2 mA
Normal operating temperature(no icing)
-20º to +60º C
Rel. humidity (no condensation) 0-95 %
Max. wind (continuous) 10 m/s
Size of device in base (H x Ø mm) 50 x 100
Ordering Information
Analogue addressable ionisation sensorDI950
Passive base addressE
Programmable slide-in address cardE
Aesthetic designE
EN 54,BOSEC,VdS,CNBOP approvedE
DP951Optical sensor
950 seriesThis elegant slim-line optical sensor provides high performanceanalogue addressable features
Specifications
Supply voltage (V dc) 17-28
Quiescent current 340 A
Alarm indication Clear LED (red in alarm)
Alarm LED current 4 mA
Normal operating temperature(no icing)
-20º to +60º C
Rel. humidity (no condensation) 0-95 %
Max. wind (continuous) Not affected
Size of device in base (H x Ø mm) 50 x 100
Ordering Information
Optical sensorDP951950 series standard baseDB950
Passive base addressE
Programmable slide-in address cardE
Aesthetic designE
EN 54,BOSEC,VdS,CNBOP approvedE
Addressable Fire Systems
Page : 61
DT952Analogue addressable temperature sensor
950 seriesThis elegant slim-line analogue addressable heat sensor providesexact temperature information to the fire panel.
Specifications
Supply voltage (V dc) 17-28
Quiescent current 250 A
Alarm indication Red LED
Alarm LED current 2 mA
Normal operating temperature(no icing)
-20º to +60º C
Rel. humidity (no condensation) 0-95 %
Max. wind (continuous) Not affected in fixed temp. use
Size of device in base (H x Ø mm) 50 x 100
Ordering Information
Analogue addressable temperature sensorDT952950 series standard baseDB950
Passive base addressE
Programmable slide-in address cardE
Aesthetic designE
EN 54,BOSEC,VdS,CNBOP approvedE
DM960950 series analogue addressable manual callpoint
950 seriesA manual call point operating with 950 series protocol.
Ordering Information
950 series analogue addressable manual callpointDM960
Addressable Fire Systems
Page : 62
DI970Intrinsic safe analogue addressable ionisation detector
970 seriesAn intrinsic safe ionisation detector, when used with the PT971/2protocol simulator and GBX70 barrier
Ordering Information
Intrinsic safe analogue addressable ionisation detectorDI970Intrinsic safe protocol translatorPT971Dual channel IS protocol translatorPT972Galvanic barrier (single channel)GBX70Detector base for 970 series intrinsic safe sensorsDB970
Passive base addressE
Programmable slide-in address cardE
Aesthetic designE
EN 54,BOSEC,VdS,CNBOP approvedE
DP971Intrinsic safe optical detector
970 seriesAn intrinsic safe optical detector, when used with the PT971/2 protocoltranslator and GBX70 barrier
Ordering Information
Intrisic safe optical detectorDP971Intrinsic safe protocol translatorPT971Dual channel IS protocol translatorPT972Galvanic barrier (single channel)GBX70Detector base for 970 series intrinsic safe sensorsDB970
Passive base addressE
Programmable slide-in address cardE
Aesthetic designE
EN 54,BOSEC,VdS,CNBOP approvedE
Addressable Fire Systems
Page : 63
DT972Intrinsic safe heat detector
970 seriesAn intrinsic safe heat detector, when used with the PT971/2 protocoltranslator and GBX70 barrier
Ordering Information
Intrinsic safe heat detectorDT972Intrinsic safe protocol translatorPT971Dual channel IS protocol translatorPT972Galvanic barrier (single channel)GBX70Detector base for 970 series intrinsic safe sensorsDB970
Passive base addressE
Programmable slide-in address cardE
Aesthetic designE
EN 54,BOSEC,VdS,CNBOP approvedE
DM970Intrinsic safe manual call point
970 seriesAn intrinsic safe manual call point, when used with the PT971/2protocol translator and GBX70 barrier.
Ordering Information
Intrinsic safe manual call pointDM970
Addressable Fire Systems
Page : 64
PT971Intrinsic safe protocol translator
970 seriesA protocol translator for the 970 series analogue addressable intrinsicsafe sensors. This must be used with the GBX70 barrier
Ordering Information
Intrinsic safe protocol translatorPT971Dual channel IS protocol translatorPT972
GBX70Galvanic barrier (single channel)
970 serisA galvanic barrier used in 970 series intrinsic safe applications. TheGBX70 is used in conjuntion with the PT971 and PT972 protocoltranslators.
Ordering Information
Galvanic barrier (single channel)GBX70
Addressable Fire Systems
Page : 65
II950950 series mini switch monitor unit
950 seriesThis unit is designed to monitor the state of one or more single poleswitches connected on a single pair of cables.
Specifications
Supply voltage 14-28 Vdc
Current consumption
Quiescent (20kOhm) 1 mA
Alarm -
Led /relay on 3.5 mA
Switch on surge 3 mA
Switch monitoring 9-11 Vdc
Relay contact rating -
Operating temperature -20/+70°C
Relative humidity 0-95%
Ingress protection IP54
Ordering Information
950 series mini switch monitor unitII950II950I
Loop poweredE
Full line: Switch monitors, Zone monitors, Input/outputunit, Output unit, Sounder circuit controller
E
LEDs for signalling of I/O and fault conditionE
Aesthetically pleasingE
II952950 series switch monitor unit - surface mount
950 seriesThis unit is designed to monitor the state of one or more single poleswitches connected on a single pair of cables. The circuit will reportopen and short-circuit faults.
Specifications
Supply voltage 14-28 Vdc
Current consumption
Quiescent (20kOhm) 730 A
Alarm
Led /relay on 5.6 mA
Switch on surge 2.5 mA
Switch monitoring 9-11 Vdc
Relay contact rating -
Operating temperature -20/+70°C
Relative humidity 0-95%
Ingress protection IP54
Ordering Information
950 series switch monitor unit - surface mountII952Switch monitor unit plus - surface mountII953
Loop poweredE
Full line: Switch monitors, Zone monitors, Input/outputunit, Output unit, Sounder circuit controller
E
LEDs for signalling of I/O and fault conditionE
Aesthetically pleasingE
Addressable Fire Systems
Page : 66
II955950 series zone monitor unit - surface mount
950 seriesThe zone monitor powers and controls the operation of a zone ofconventional detectors.
Specifications
Supply voltage 14-28 Vdc
Current consumption
Quiescent (20kOhm) 4 mA
Alarm 11-19 mA
Led /relay on -
Switch on surge 2.8 mA
Switch monitoring -
Relay contact rating -
Operating temperature -20/+70°C
Relative humidity 0-95%
Ingress protection IP54
Ordering Information
950 series zone monitor unit - surface mountII955
Loop poweredE
Full line: Switch monitors, Zone monitors, Input/outputunit, Output unit, Sounder circuit controller
E
LEDs for signalling of I/O and fault conditionE
Aesthetically pleasingE
IO950950 series single channel IO - surface mount
950 seriesThis unit provides a loop-powered relay output, a monitored input andan un-monitored opto-coupled input. It can report fault, switch openand switch closed condition. It uses the standard housing.
Specifications
Supply voltage 14-28 Vdc
Current consumption
Quiescent (20kOhm) 1.2 mA
Alarm -
Led /relay on 6 mA
Switch on surge 3.5 mA
Switch monitoring 9-11 Vdc
Relay contact rating 1A@30 Vac/dc
Operating temperature -20/+70°C
Relative humidity 0-95%
Ingress protection IP54
Ordering Information
950 series single channel IO - surface mountIO950
Loop poweredE
Full line: Switch monitors, Zone monitors, Input/outputunit, Output unit, Sounder circuit controller
E
LEDs for signalling of I/O and fault conditionE
Aesthetically pleasingE
Addressable Fire Systems
Page : 67
IO955950 series output unit - surface mount
950 seriesThis unit provides a loop-powered relay output
Specifications
Supply voltage 14-28 Vdc
Current consumption
Quiescent (20kOhm) 720 A
Alarm -
Led /relay on 3.3 mA
Switch on surge 3 mA
Switch monitoring -
Relay contact rating 1A@30 Vac/dc
Operating temperature -20/+70°C
Relative humidity 0-95%
Ingress protection IP54
Ordering Information
950 series output unit - surface mountIO955
Loop poweredE
Full line: Switch monitors, Zone monitors, Input/outputunit, Output unit, Sounder circuit controller
E
LEDs for signalling of I/O and fault conditionE
Aesthetically pleasingE
IO956950 series sounder circuit controller - surface mount
950 seriesThis unit is designed to control a zone of sounders powered by anexternal DC supply.
Specifications
Supply voltage 14-28 Vdc
Current consumption
Quiescent (20kOhm) 1.9 mA
Alarm -
Led /relay on 1.7 mA
Switch on surge 2.6 mA
Switch monitoring 9-11 Vdc
Relay contact rating -
Operating temperature -20/+70°C
Relative humidity 0-95%
Ingress protection IP54
Ordering Information
950 series sounder circuit controller - surface mountIO956
Loop poweredE
Full line: Switch monitors, Zone monitors, Input/outputunit, Output unit, Sounder circuit controller
E
LEDs for signalling of I/O and fault conditionE
Aesthetically pleasingE
Addressable Fire Systems
Page : 68
IU950950 series loop isolator
Ordering Information
950 series loop isolatorIU950
Addressable Fire Systems
Page : 69
AS950950 series loop powered sounder
950 SeriesDesigned to operate with the 950 series analogue sensors andmonitors, the AS950 loop sounders are addressed and utilise the sameprotocol using a very low current.
Specifications
Supply voltage 14 - 28 V dc
Current consumption
Quiescent 140 A at 24 V dc
Switch on surge 1.24 mA for 3 sec.
Operated at 85 dBA 3 mA +/- 0.25 mA
Operated at 92 dBA 8 mA +/- 0.25 mA
Drive frequency 500 - 550 Hz (continuous mode)
Ingress protection IP43
Operating temperature -20 to 60 °C
Dimension (dia. x depth) 115 x 25 mm (sounder only)
115 x 33 mm (sounder with cap)Weight 140 g (sounder only)
145 g (sounder with cap)
Ordering Information
950 series loop powered sounderAS950Loop powered sounder, for use with isolator baseAS950ILoop powered sounder, white capAS950W
Loop poweredE
Low current consumptionE
Aritech 950 and Apollo protocol compatibleE
Continuous or pulsed toneE
Sound output 85 - 92 dBA at 1 metreE
Reduces wiring and installation costE
Addressable Fire Systems
Page : 70
AS955950 series high output loop powered sounder
950 SeriesDesigned to operate with the 950 series analogue sensors andmonitors, the AS955 high output loop sounders are addressed andutilise the same protocol using a very low current.
Specifications
Supply voltage 14 - 28 V dc
Current consumption
Quiescent 140 A at 24 V dc
Switch on surge 1.24 mA for 3 sec.
Operated 4.5 mA +/- 0.25 mA
Drive frequency 500 - 550 Hz (continuous mode)
Ingress protection IP43
Operating temperature -20 to 60 °C
Sound output 100 dB(A)
Ordering Information
950 series high output loop powered sounderAS955
Loop poweredE
Low current consumptionE
950 series protocolE
Continuous or pulsed toneE
Sound output 100 dB(A) at 1 metreE
Reduces wiring and installation costE
Addressable Fire Systems
Page : 71
FD950950 series loop-powered beam detector
950 SeriesA 950 series loop-powered beam detector with a range of up to 100mlong and 15m wide.
Ordering Information
950 series loop-powered beam detectorFD950
Loop-poweredE
950 series compatible with FP1200 and FP2000E
Four selectable alarm levelsE
Drift compensationE
Remote interfaceE
Simple wiringE
Simple alignmentE
Addressable Fire Systems
Page : 72
DB950950 series standard base
950 seriesA unique, patented addressing method provides simple, user-friendlyand accurate identification of monitor location whereby a coded card,inserted in the base, is read by any monitor as it is plugged in.
Ordering Information
950 series standard baseDB950
Passive base addressE
Programmable slide-in address cardE
Aesthetic designE
EN 54,BOSEC,VdS,CNBOP approvedE
DB951Base for IU 950
950 seriesThis base is required for the IU950 isolator
Ordering Information
Base for IU 950DB951
Passive base addressE
Programmable slide-in address cardE
Aesthetic designE
EN 54,BOSEC,VdS,CNBOP approvedE
Addressable Fire Systems
Page : 73
DB961Isolating base (20 devices)
The isolating base senses and isolates short circuit faults on 950 seriesloops and spurs. Up to 20 devices may be placed between any twoisolator bases.
Ordering Information
Isolating base (20 devices)DB961
Passive base addressE
Programmable slide-in address cardE
Aesthetic designE
EN 54,BOSEC,VdS,CNBOP approvedE
DB970Detector base for 970 series intrinsic safe sensors
Ordering Information
Detector base for 970 series intrinsic safe sensorsDB970
Passive base addressE
Programmable slide-in address cardE
Aesthetic designE
EN 54,BOSEC,VdS,CNBOP approvedE
Addressable Fire Systems
Page : 74
IU980Coded cards, addresses 1 - 18
950 seriesPrecoded Xpert address cards for use in DB9xx bases
Ordering Information
Coded cards, addresses 1 - 18IU980Coded cards, addresses 19 - 36IU981Coded cards addresses 37 - 54IU982Coded cards, addresses 55 - 72IU983Coded cards, addresses 73 - 90IU984Coded cards, addresses 91- 108IU985Coded cards, addresses 109 - 126IU986
Conventional Fire Systems
Page : 75
FP202Conventional fire alarm panel with 2 zones
The FP200 Series microprocessor controlled, conventional fire panelsincorporate state of the art technology, reliability, ease of installationand maintenance in a basic package. They are compatible withconventional detectors such as the Aritech Series 300, Series 650 andSeries 700 devices. The FP202 has 2 conventional zones.
Specifications
Supply Voltage 125/230 VAC @ 50/60 Hz
Mains fuse (Type 5x20 mm) 0.5/0.25 A
Total consumption < 20 W
Nominal Output Voltage 24 VDC
Batteries
Recommended batteries 2 off 1.9 Ah, 12 V
Fuse Rating 1 A
Maximum load current < 100 mA
Zone
Maximum Load 72 mA
Maximum number ofdetectors
20
Ouput voltage 22 to 28 VDC
End-of-line resitance 4k7 Ohm
Manual call point resistance 100 Ohm, 2 W
Outputs
Fire alarm 24 VDC ± 15%, 300 mA
Fault alarm (Fail-to-safe) 24 VDC ± 15%, 100 mA
Environmental
Working temperature +5 to +40°C
Storage temperature -10 to +70°C
Relative humidity 95 % (non-condencing)
Physical Characteristics
Size (w x h x d) 305 x 295 x 100 mm
Weight without batteries 3 kg
Ordering Information
Conventional fire alarm panel with 2 zonesFP202
Modern, elegant designE
Compact models for 2, 4 and 6 zonesE
Microprocessor controlledE
Multilingual keyboardE
2 Access levelsE
Differentiation between alarms from manual call pointsand automatic detectors in the same zone
E
Acoustic indications for fire and faultE
Optical indications for fire and fault by zoneE
Low maintenanceE
Compatible with all ranges of ARITECH conventionaldetectors
E
Conventional Fire Systems
Page : 76
FP204Conventional fire alarm panel with 4 zones
The FP200 Series microprocessor controlled, conventional fire panelsincorporate state of the art technology, reliability, ease of installationand maintenance in a basic package. They are compatible withconventional detectors such as the Aritech Series 300, Series 650 andSeries 700 devices. The FP204 has 4 conventional zones.
Specifications
Supply Voltage 125/230 VAC @ 50/60 Hz
Mains fuse (Type 5x20 mm) 0.5/0.25 A
Total consumption < 20 W
Nominal Output Voltage 24 VDC
Batteries
Recommended batteries 2 off 1.9 Ah, 12 V
Fuse Rating 1 A
Maximum load current < 100 mA
Zone
Maximum Load 72 mA
Maximum number ofdetectors
20
Ouput voltage 22 to 28 VDC
End-of-line resitance 4k7 Ohm
Manual call point resistance 100 Ohm, 2 W
Outputs
Fire alarm 24 VDC ± 15%, 300 mA
Fault alarm (Fail-to-safe) 24 VDC ± 15%, 100 mA
Environmental
Working temperature +5 to +40°C
Storage temperature -10 to +70°C
Relative humidity 95 % (non-condencing)
Physical Characteristics
Size (w x h x d) 305 x 295 x 100 mm
Weight without batteries 3 kg
Ordering Information
Conventional fire alarm panel with 4 zonesFP204
Modern, elegant designE
Compact models for 2, 4 and 6 zonesE
Microprocessor controlledE
Multilingual keyboardE
2 Access levelsE
Differentiation between alarms from manual call pointsand automatic detectors in the same zone
E
Acoustic indications for fire and faultE
Optical indications for fire and fault by zoneE
Low maintenanceE
Compatible with all ranges of ARITECH conventionaldetectors
E
Conventional Fire Systems
Page : 77
FP206Conventional fire alarm panel with 6 zones
The FP200 Series microprocessor controlled, conventional fire panelsincorporate state of the art technology, reliability, ease of installationand maintenance in a basic package. They are compatible withconventional detectors such as the Aritech Series 300, Series 650 andSeries 700 devices. The FP206 has 6 conventional zones.
Specifications
Supply Voltage 125/230 VAC @ 50/60 Hz
Mains fuse (Type 5x20 mm) 0.5/0.25 A
Total consumption < 20 W
Nominal Output Voltage 24 VDC
Batteries
Recommended batteries 2 off 1.9 Ah, 12 V
Fuse Rating 1 A
Maximum load current < 100 mA
Zone
Maximum Load 72 mA
Maximum number ofdetectors
20
Ouput voltage 22 to 28 VDC
End-of-line resitance 4k7 Ohm
Manual call point resistance 100 Ohm, 2 W
Outputs
Fire alarm 24 VDC ± 15%, 300 mA
Fault alarm (Fail-to-safe) 24 VDC ± 15%, 100 mA
Environmental
Working temperature +5 to +40°C
Storage temperature -10 to +70°C
Relative humidity 95 % (non-condencing)
Physical Characteristics
Size (w x h x d) 305 x 295 x 100 mm
Weight without batteries 3 kg
Ordering Information
Conventional fire alarm panel with 6 zonesFP206
Modern, elegant designE
Compact models for 2, 4 and 6 zonesE
Microprocessor controlledE
Multilingual keyboardE
2 Access levelsE
Differentiation between alarms from manual call pointsand automatic detectors in the same zone
E
Acoustic indications for fire and faultE
Optical indications for fire and fault by zoneE
Low maintenanceE
Compatible with all ranges of ARITECH conventionaldetectors
E
Conventional Fire Systems
Page : 78
FP402Conventional fire alarm panel with 2 zones
The FP400 series of conventional fire alarm and extinguishing controlpanels is the ideal solution for small to medium-sized installations. Verypowerful and cost-effective, they are extremely simple to install anduse due to their ergonomic, advanced design. The panels come inelegant, high-quality, conveniently sized, heavy-duty metal enclosureswith space for batteries and finished in high-gloss paint. All panelshave a high-quality keyboard with audible metallic click and goodtravel
Specifications
Supply Voltage (+10% - 15%) 230 / 110 VAC @ 50 / 60 Hz
Current Consumption (panel only)
Quiescent 75 mA
Alarm 162 mA
Batteries
Capacity 2 x 2.3 Ah
Fuse rating 2 A
Zone
Nominal Voltage 24 VDC
Maximum load 94 mA
Max. number of detectors perzone
20
Maximum zone resistance 44 ohm
Sounders
Maximum load 250 mA
Delay Selectable 0 - 9 min
Relay Outputs (excludingsounders)
1 A @ 30 VDC
Auxilliary Output 250 mA
24 VDC Resetable Output
Maximum load 100 mA
Reset time 3 s
Environment
Working temperature -5°C to +40°C
Relative humidity (noncondencing)
95 %
IP rating IP30
Physical Characteristics
Size (mm) 297 (w) x 307 (h) x 105 (d)
Weight (without batteries) 3.6 kg
Expansion Module Slots 1
Ordering Information
Conventional fire alarm panel with 2 zonesFP402 Relay module, 4 potential free relays for NK700/Fx400 fire panelsRB404Relay module, 4 supervised relays for NK700/Fx400 fire panelsSB404 Active end-of-line device for use with FP400/KL700 fire panelsEOL-ACTSealed Lead-Acid Battery - 12V 2.2AhBS122N
Modern, attractive designE
Microprocessor controlledE
From 2 up to 16 zonesE
EN54 compliant with approvals pendingE
2 Access levelsE
2 Monitored sounder outputsE
One-man test capabilityE
24 Volt resetable outputE
External 'class change' facilityE
Alarm output with potential free relayE
General fault output with potential free relay E
External watchdogE
Conventional Fire Systems
Page : 79
FP408Conventional fire alarm panel with 8 zones
The FP400 series of conventional fire alarm and extinguishing controlpanels is the ideal solution for small to medium-sized installations. Verypowerful and cost-effective, they are extremely simple to install anduse due to their ergonomic, advanced design. The panels come inelegant, high-quality, conveniently sized, heavy-duty metal enclosureswith space for batteries and finished in high-gloss paint. All panelshave a high-quality keyboard with audible metallic click and goodtravel
Specifications
Supply Voltage (+10% - 15%) 230 / 110 VAC @ 50 / 60 Hz
Current Consumption (panel only)
Quiescent 137 mA
Alarm 247 mA
Batteries
Capacity 2 x 7.5 Ah
Fuse rating 5 A
Zone
Nominal Voltage 24 VDC
Maximum load 94 mA
Max. number of detectors perzone
20
Maximum zone resistance 44 ohm
Sounders
Maximum load 250 mA
Delay Selectable 0 - 9 min
Relay Outputs (excludingsounders)
1 A @ 30 VDC
Auxilliary Output 250 mA
24 VDC Resetable Output
Maximum load 100 mA
Reset time 3 s
Environment
Working temperature -5°C to +40°C
Relative humidity (noncondencing)
95 %
IP rating IP30
Physical Characteristics
Size (mm) 420 (w) x 335 (h) x 110 (d)
Weight (without batteries) 6.2 kg
Expansion Module Slots 4
Ordering Information
Conventional fire alarm panel with 8 zonesFP408 Relay module, 4 potential free relays for NK700/Fx400 fire panelsRB404Relay module, 4 supervised relays for NK700/Fx400 fire panelsSB404 Active end-of-line device for use with FP400/KL700 fire panelsEOL-ACTSealed Lead-Acid Battery - 12V 7.2AhBS127N
Modern, attractive designE
Microprocessor controlledE
From 2 up to 16 zonesE
EN54 compliant with approvals pendingE
2 Access levelsE
2 Monitored sounder outputsE
One-man test capabilityE
24 Volt resetable outputE
External 'class change' facilityE
Alarm output with potential free relayE
General fault output with potential free relay E
External watchdogE
Conventional Fire Systems
Page : 80
FP412Conventional fire alarm panel with 12 zones
The FP400 series of conventional fire alarm and extinguishing controlpanels is the ideal solution for small to medium-sized installations. Verypowerful and cost-effective, they are extremely simple to install anduse due to their ergonomic, advanced design. The panels come inelegant, high-quality, conveniently sized, heavy-duty metal enclosureswith space for batteries and finished in high-gloss paint. All panelshave a high-quality keyboard with audible metallic click and goodtravel
Specifications
Supply Voltage (+10% - 15%) 230 / 110 VAC @ 50 / 60 Hz
Current Consumption (panel only)
Quiescent 137 mA
Alarm 247 mA
Batteries
Capacity 2 x 7.5 Ah
Fuse rating 5 A
Zone
Nominal Voltage 24 VDC
Maximum load 94 mA
Max. number of detectors perzone
20
Maximum zone resistance 44 ohm
Sounders
Maximum load 250 mA
Delay Selectable 0 - 9 min
Relay Outputs (excludingsounders)
1 A @ 30 VDC
Auxilliary Output 250 mA
24 VDC Resetable Output
Maximum load 100 mA
Reset time 3 s
Environment
Working temperature -5°C to +40°C
Relative humidity (noncondencing)
95 %
IP rating IP30
Physical Characteristics
Size (mm) 420 (w) x 335 (h) x 110 (d)
Weight (without batteries) 6.2 kg
Expansion Module Slots 4
Ordering Information
Conventional fire alarm panel with 12 zonesFP412
Modern, attractive designE
Microprocessor controlledE
From 2 up to 16 zonesE
EN54 compliant with approvals pendingE
2 Access levelsE
2 Monitored sounder outputsE
One-man test capabilityE
24 Volt resetable outputE
External 'class change' facilityE
Alarm output with potential free relayE
General fault output with potential free relay E
External watchdogE
Conventional Fire Systems
Page : 81
FP416Conventional fire alarm panel with 16 zones
The FP400 series of conventional fire alarm and extinguishing controlpanels is the ideal solution for small to medium-sized installations. Verypowerful and cost-effective, they are extremely simple to install anduse due to their ergonomic, advanced design. The panels come inelegant, high-quality, conveniently sized, heavy-duty metal enclosureswith space for batteries and finished in high-gloss paint. All panelshave a high-quality keyboard with audible metallic click and goodtravel
Specifications
Supply Voltage (+10% - 15%) 230 / 110 VAC @ 50 / 60 Hz
Current Consumption (panel only)
Quiescent 137 mA
Alarm 247 mA
Batteries
Capacity 2 x 7.5 Ah
Fuse rating 5 A
Zone
Nominal Voltage 24 VDC
Maximum load 94 mA
Max. number of detectors perzone
20
Maximum zone resistance 44 ohm
Sounders
Maximum load 250 mA
Delay Selectable 0 - 9 min
Relay Outputs (excludingsounders)
1 A @ 30 VDC
Auxilliary Output 250 mA
24 VDC Resetable Output
Maximum load 100 mA
Reset time 3 s
Environment
Working temperature -5°C to +40°C
Relative humidity (noncondencing)
95 %
IP rating IP30
Physical Characteristics
Size (mm) 420 (w) x 335 (h) x 110 (d)
Weight (without batteries) 6.2 kg
Expansion Module Slots 4
Ordering Information
Conventional fire alarm panel with 16 zonesFP416
Modern, attractive designE
Microprocessor controlledE
From 2 up to 16 zonesE
EN54 compliant with approvals pendingE
2 Access levelsE
2 Monitored sounder outputsE
One-man test capabilityE
24 Volt resetable outputE
External 'class change' facilityE
Alarm output with potential free relayE
General fault output with potential free relay E
External watchdogE
Conventional Fire Systems
Page : 82
RB404Relay module, 4 potential free relays for NK700/Fx400 fire panels
The RB404 relay expander module provides 4 additional voltage freerelays on the GE Security NK700/FP400/FEC400 conventional firepanels ranges. It allows for these relays to be allocated to individualdetection zones, or for programming the activation of different relaysdepending on the status of one or more zones. Up to 4 of thesemodules may be used on every fire panel.
Specifications
Relay rating
Voltage 250 VAC / 30 VDC
Current 10 A
Delay setting 0 to 9 minutes
Ordering Information
Relay module, 4 potential free relays for NK700/Fx400 fire panelsRB404
4 Potential free relaysE
Up to 4 modules may be housed inside the fire panelcabinet
E
Programmable with basic boolen functionsE
Power supplied from fire panel busE
Output delay setting per relayE
Conventional Fire Systems
Page : 83
SB404Relay module, 4 supervised relays for NK700/Fx400 fire panels
The SB404 expander module provides 4 additional supervised relaysthat provide 24 VDC outputs on the GE Security NK700/FP400/FEC400conventional fire panels ranges. These relays may be configured topower sounders or as standard 24 VDC supervised outputs for otherdevices. Relays may be allocated to individual detection zones, or forprogramming the activation of different relays depending on the statusof one or more zones. Up to 4 of these modulesmay be used on every fire panel.
Specifications
Auxiliary supply 24 VDC
Relay Rating
Voltage 250 VAC / 30 VDC
Current 5 A
Delay setting 0 to 9 minutes
Ordering Information
Relay module, 4 supervised relays for NK700/Fx400 fire panelsSB404
4 Supervised relaysE
Up to 4 modules may be housed inside the fire panelcabinet
E
Programmable with basic boolen functionsE
Output delay setting per relayE
Configurable for sounder control or as supervisedoutputs
E
Conventional Fire Systems
Page : 84
FEC403Conventional extinguishing control panel with 3 zones
The FP400 series of conventional fire alarm and extinguishing controlpanels is the ideal solution for small to medium-sized installations. Verypowerful and cost-effective, they are extremely simple to install anduse due to their ergonomic, advanced design. The panels come inelegant, high-quality, conveniently sized, heavy-duty metal enclosureswith space for batteries and finished in high-gloss paint. All panelshave a high-quality keyboard with audible metallic click and goodtravel
Specifications
Supply Voltage (+10% - 15%) 230 / 110 VAC @ 50 / 60 Hz
Batteries
Capacity 2 x 7 Ah
Fuse rating 2 A
Zone
Maximum load 94 mA
Max. number of detectors perzone
20
Maximum zone resistance 44 ohm
Sounders
Maximum load 250 mA
Delay Selectable 0 - 9 min
Relay Outputs (excludingsounders)
1 A @ 30 VDC
Extinguishing Relay Outputs
Maximum load 350 mA
Fuse rating 1 A
Auxilliary Output 250 mA
24 VDC Resetable Output
Maximum Load 100 mA
Reset time 3 s
Environment
Working temperature -5°C to +40°C
Relative humidity (noncondencing)
95 %
IP rating IP30
Physical Characteristics
Size (mm) 420 (w) x 335 (h) x 110 (d)
Weight (without batteries) 6.2 kg
Ordering Information
Conventional extinguishing control panel with 3 zonesFEC403
Modern, attractive designE
Microprocessor controlledE
3 zone (1 ext. area) and 6 zone (2 ext. areas) availableE
Automatic extinguishing agent release controlE
2 Access levelsE
Supervised general sounder outputE
Supervised extinguishing inputs and outputsE
One-man test capabilityE
24 Volt resetable outputE
External 'class change' facilityE
Alarm output with potential free relayE
General fault output with potential free relay E
External watchdogE
Conventional Fire Systems
Page : 85
FEC406Conventional extinguishing control panel with 6 zones
The FP400 series of conventional fire alarm and extinguishing controlpanels is the ideal solution for small to medium-sized installations. Verypowerful and cost-effective, they are extremely simple to install anduse due to their ergonomic, advanced design. The panels come inelegant, high-quality, conveniently sized, heavy-duty metal enclosureswith space for batteries and finished in high-gloss paint. All panelshave a high-quality keyboard with audible metallic click and goodtravel
Specifications
Supply Voltage (+10% - 15%) 230 / 110 VAC @ 50 / 60 Hz
Batteries
Capacity 2 x 7 Ah
Fuse rating 2 A
Zone
Maximum load 94 mA
Max. number of detectors perzone
20
Maximum zone resistance 44 ohm
Sounders
Maximum load 250 mA
Delay Selectable 0 - 9 min
Relay Outputs (excludingsounders)
1 A @ 30 VDC
Extinguishing Relay Outputs
Maximum load 350 mA
Fuse rating 1 A
Auxilliary Output 250 mA
24 VDC Resetable Output
Maximum Load 100 mA
Reset time 3 s
Environment
Working temperature -5°C to +40°C
Relative humidity (noncondencing)
95 %
IP rating IP30
Physical Characteristics
Size (mm) 420 (w) x 335 (h) x 110 (d)
Weight (without batteries) 6.2 kg
Ordering Information
Conventional extinguishing control panel with 6 zonesFEC406
Modern, attractive designE
Microprocessor controlledE
3 zone (1 ext. area) and 6 zone (2 ext. areas) availableE
Automatic extinguishing agent release controlE
2 Access levelsE
Supervised general sounder outputE
Supervised extinguishing inputs and outputsE
One-man test capabilityE
24 Volt resetable outputE
External 'class change' facilityE
Alarm output with potential free relayE
General fault output with potential free relay E
External watchdogE
Conventional Fire Systems
Page : 86
FP6044-zone Conventional Fire Panel
The FP 604 fire panel is designed using the latest technologies and iscompatible with most brands of conventional fire detectors. The FP 604is a 4-zone panel which is extendable up to 6 zones.
Specifications
Supply voltage 230 V (± 10% - 50 Hz ± 5%)
Total current 12 V dc (no charge),quiescent
80 mA
Total current 24 V dc (no charge),quiescent
90 mA
Auxiliary output 100 mA - 12 V dc
Battery back-up for 72 hrs 1 x 12 V - 7.2 Ah battery
Battery charger fuse 2 A
Battery charger voltage 13.8 V
Bells - Fire Brigade fuse 315 mA
Dimensions 390 x 315 x 85 mm
Ordering Information
4-zone Conventional Fire PanelFP604Two zone extension board, including 6 outputsZI602Set of 6 bi-stable magnetic latch relaysRC606 One man maintenanceE
Alarm verificationE
Individual zone alarm outputsE
One 12 V back-up batteryE
12 V dc auxiliary outputE
4 - 6 zonesE
Mixed zone capabilityE
Head removal optionE
Sirens output 12 or 24 V dcE
Microprocessor basedE
EN 54 p2/4 approvedE
LPCB certifiedE
Optional third sourceE
Optional digital diallerE
Conventional Fire Systems
Page : 87
ZI602Two zone extension board, including 6 outputs
This board extends the FP604 from 4 zones to 6 zones. It also provides6 outputs for the 6 zones.
Ordering Information
Two zone extension board, including 6 outputsZI602
RC606Set of 6 bi-stable magnetic latch relays
A set of 6 relays for the ZI602 zone extension board
Ordering Information
Set of 6 bi-stable magnetic latch relaysRC606
Conventional Fire Systems
Page : 88
FP708Fire panel equipped with 8 zones
FP700 seriesA set of four conventional fire panels. The FP708 and FP708C are 8zone non-expandable fire panels. The FP740 and FP740C are 8 zoneexpandable to 40 zones. The FP708C and FP740C have an alarmcounter. All panels can use the full range of LON700 output boards.
Specifications
Dimensions (W x H x D) 444 x 340 x110 mm
Weight (no batteries) 5.5 kg
Supply voltage (see engineeringguide)
230 V ac; 1,5 A; 50 Hz
Quiescent current @20devices/zone
210 mA (8 zones)
Batteries for 24 hrs (in housing) 7.2 Ah
Batteries for 72 hrs 17 Ah
Battery charger rating 1.4 A max
Nominal battery charger voltage@ 25°C
27,6 V
Auxiliary output 1 21 - 29,4 V dc; 1.2 A max.
Auxiliary output 2 11.5 - 12.5 V dc; 0.4 A max.
Total 24 V output (no charging) 3,5 A max
Sounder/warning 0,5 A, 19-31 V dc, polarity reversal
Evacuation/Fire brigade 0,5 A, 19-31 V dc, polarity reversal
Fault and Fire protection relayrating
2 A, @ 42 V
RS 232 port 19200 baud, DB9, 1 start, 8 data, 1 stop, no parity
Ordering Information
Fire panel equipped with 8 zonesFP708Fire panel equipped with 8 zones including alarm counterFP708CFire panel equipped with 8 zones expandable up to 40 zonesFP740Fire panel equipped with 8 zones exp. to 40 including alarm counterFP740C
Fully modularE
LON based networkE
One-man maintenanceE
Alarm verificationE
700 series detectors Clean Me® detectionE
Various output boardsE
EN54 approved and BOSEC certifiedE
Modular up to 40 zonesE
Full line of repeatersE
Microprocessor basedE
Local and remote controlE
Conventional Fire Systems
Page : 89
FR708Repeater 8 zones, 24 VDC input
FR700 seriesThe repeaters provide different solutions - 24 volt input and 230 voltinput using the PS700 power supply. The FR708 is 8 zones nonexpandable and the FR740 is 8 zones expandable to 40 zones. TheFR700 repeaters connect to the FP700 fire panel with the LON 700 bus. The FR708V230 and FR740V230 include a card cage for LON boardexpansion and have a PS700 power supply.
Ordering Information
Repeater 8 zones, 24 VDC inputFR708Repeater 8 zones with card cage and PS700 PSU (230V input)FR708V230Repeater 8 zones, expandable up to 40 zones, 24 VDC inputFR740Repeater 8 zones, exp to 40 zones with card cage and PS700 PSU (230V)FR740V230
Fully modularE
Echelon based networkE
Various output boardsE
Modular up to 40 zonesE
Full line of repeatersE
Microprocessor basedE
Local and remote controlE
Conventional Fire Systems
Page : 90
ZE7088 zone indicator LED extension board fire/fault
FP700 seriesThis zone indicator extension board is used to expand the FP740 andFR740 front panel indications.
Ordering Information
8 zone indicator LED extension board fire/faultZE708
LON700 Devices
Page : 91
ZI7088 zone input extension board
The ZI708 is an eight zone input expansion board for LON700compatible systems. It allows for the connection of up to 8conventional fire detector zones and is compatible with most industrystandard conventional detectors.
Ordering Information
8 zone input extension boardZI708
Conventional Fire Systems
Page : 92
FM740Synoptic driver for 80 LEDs and common signals
LON 700 seriesA LON700 output board to display LED's. It can be self-standing as wellas plugging into a card cage.
Specifications
Dimensions mm (L x W x D) 150x30x60
Weight 200 g
Operating temp °C -5°C - +40
Operating voltage Vdc 19 - 30
Current consumption
max quiesent mA 30
power consumption per LED(mW)
40
Bus Connection
FP1200/FP2000 (withLON2000)
***
FP700 (direct connection) ***
Bus Cable Cat 5
Total number of repeaters
FP1200/FP2000 15
FP700 8
Ordering Information
Synoptic driver for 80 LEDs and common signalsFM740
LON700 Devices
Page : 93
OCB724LON700 output board with 24 open collector outputs
The OCB724 is a 24 way open collector board used in a LON700system.
Ordering Information
LON700 output board with 24 open collector outputsOCB724
RB708LON700 output board with 8 relays
The RB708 is an eight way relay board used in LON700 systems.
Specifications
Number of outputs 8
Relay contact rating
Switching current 2A
Switching volage 42V ac/dc
Switching power 60W
Ordering Information
LON700 output board with 8 relaysRB708
LON700 Devices
Page : 94
SOB708LON700 output board with 8 supervised outputs
The SOB708 provides eight supervised outputs that can be used inLON700 systems.
Specifications
Number of outputs 8
Output type polarity reversal
End of line resistor 5.6 Kohm
Output current per output 500mA
Total current for all outputs 2A
Open circuit >27 Kohm
Normal 1.2 - 18 Kohm
Short circuit < 470 ohm
Ordering Information
LON700 output board with 8 supervised outputsSOB708
Conventional Fire Systems
Page : 95
FB708FP700 black box with 7 slot card cage
LON700 seriesThe FB708 and FB740 'black boxes' allow for the distribution of LON700input / output units. When used with the NC700 or FM740, the FB7xx isconnected to the FP700 / FP2000 firepanels with the LON700 bus.
Ordering Information
FP700 black box with 7 slot card cageFB708FP700 black box with 11 slot card cage and PS700FB740LON700 interface boardNC700
Fully modularE
Echelon based networkE
Various output boardsE
Microprocessor basedE
Local and remote controlE
For fire panel distributed systemsE
7 slot card cage or 11 slot card cage with power supplyE
LON700 Devices
Page : 96
NC700LON700 interface board
The NC700 is an interface board to connect a LON700 bus from a firepanel to a FB7xx 'black box'.
Ordering Information
LON700 interface boardNC700
PS700Plug-in power supply 3.5 A
The PS700 power supply can be used to extend the power output inLON700 systems.
Ordering Information
Plug-in power supply 3.5 APS700
Addressable Fire Systems
Page : 97
FP1501Analogue addressable fire detection panel - 1 loop
The FP1501 1 loop analogue addressable fire alarm control panel is theideal solution for small to medium-sized installations. Very powerfuland cost-effective, it is extremely simple to install and use due to isergonomic, advanced design. The panel is supplied in an elegant,high-quality, conveniently sized, heavy-duty enclosure. It has ahigh-quality keyboard with audible metallic click and good travel.
Specifications
Supply Voltage 110 VAC @ 50 Hz or 230 VAC @ 50 Hz (+10% -15%)
Current Consumption 175 mA Quiescent / 241 mA in alarm with no devicesconnected
Batteries
Capacity 2 x 12 V - 7 AH (SLA type)
Fuse Rating 3 A
Charger Rating 350 mA @ 27.6 VDC @ 20 °C (Temperaturecompensated -3 V / °C)
Loop characteristics per loop
Capacity 250 addresses per loop
Maximum Load 400 mA / 26 VDC to 32 VDC
Maximum ElectricalCharacteristics
44 Ohm / 500 nF approximately 2 km of 1.5 mm2diameter cable
Sounders (reverse polaritysupervision)
Maximum Load 250 mA each (2 Sounder outputs available) / 18 VDCto 24 VDC
Delays 10 seconds to 600 seconds, software adjustable in 10second intervals
Relay Outputs (potential free) 1 A @ 30 VDC
24 V Auxiliary Output
Maximum Load 250 mA @ 18 VDC to 28 VDC
Environment
Working Temperature -5°C to +40 °C
Relative Humidity 0-95% non-condensing
IP Rating IP30
Physical Characteristics
Size 420 mm (w) x 335 (h) x 110 (d)
Weight 6.2 kg without batteries / 10.7 kg with 2 x 7 Ahbatteries
Ordering Information
Analogue addressable fire detection panel - 1 loopFP1501
One and two loop control panelsE
4 x 40 characters LCD displayE
20 Display zonesE
EN54 approvedE
2 User access levelsE
2 Monitored sounder outputsE
2 Programmable voltage free relaysE
24 Volt auxiliary outputE
I/O programming capabilities with Boolean functionsE
Day/night sensitivity settingsE
Coincidence within zonesE
Installation test capabilityE
Full networking capabilities up to 10 nodesE
2-wire RS485 communications networkE
Industry standard RS232 communications portE
Easy up/download programming from a standard PCE
Graphic PC softwareE
Addressable Fire Systems
Page : 98
FP1502Analogue addressable fire detection panel - 2 loops
The FP1500 series analogue addressable fire alarm control panels isthe ideal solution for small to medium-sized installations. Very powerfuland cost-effective, they are extremely simple to install and use due totheir ergonomic, advanced design.
The panels are supplied in an elegant, high-quality, conveniently sized,heavy-duty metal enclosure and are finished in a high-gloss paint. Allpanels have a high-quality keyboard with audible metallic click andgood travel.
The batteries for the system may be housed inside the cabinet.
Specifications
Supply Voltage 110 VAC @ 50 Hz or 230 VAC @ 50 Hz (+10% -15%)
Current Consumption 175 mA Quiescent / 241 mA in alarm with no devicesconnected
Batteries
Capacity 2 x 12 V - 7 AH (SLA type)
Fuse Rating 3 A
Charger Rating 350 mA @ 27.6 VDC @ 20 °C (Temperaturecompensated -3 V / °C)
Loop characteristics per loop
Capacity 250 addresses per loop
Maximum Load 400 mA / 26 VDC to 32 VDC
Maximum ElectricalCharacteristics
44 Ohm / 500 nF approximately 2 km of 1.5 mm2diameter cable
Sounders (reverse polaritysupervision)
Maximum Load 250 mA each (2 Sounder outputs available) / 18 VDCto 24 VDC
Delays 10 seconds to 600 seconds, software adjustable in 10second intervals
Relay Outputs (potential free) 1 A @ 30 VDC
24 V Auxiliary Output
Maximum Load 250 mA @ 18 VDC to 28 VDC
Environment
Working Temperature -5°C to +40 °C
Relative Humidity 0-95% non-condensing
IP Rating IP30
Physical Characteristics
Size 420 mm (w) x 335 (h) x 110 (d)
Weight 6.2 kg without batteries / 10.7 kg with 2 x 7 Ahbatteries
Ordering Information
Analogue addressable fire detection panel - 2 loopsFP1502
One and two loop control panelsE
4 x 40 characters LCD displayE
20 Display zonesE
EN54 approvedE
2 User access levelsE
2 Monitored sounder outputsE
2 Programmable voltage free relaysE
24 Volt auxiliary outputE
I/O programming capabilities with Boolean functionsE
Day/night sensitivity settingsE
Coincidence within zonesE
Installation test capabilityE
Full networking capabilities up to 10 nodesE
2-wire RS485 communications networkE
Industry standard RS232 communications portE
Easy up/download programming from a standard PCE
Graphic PC softwareE
Addressable Fire Systems
Page : 99
NC785RS485 expansion kit for KSA701/FP1500 fire panels
The NC785 RS485 expander allows for an easy upgrade to theKSA701/FP1500 series addressable fire panels. Each module adds anadditional industry standard RS485 communication port to the panel.This port could be used for communications with other network nodesin the fire panel network.
Specifications
Number of ports 1
Communications medium RS485
Technical specifications
Maximum cable length 1200 m
Communication speed 9600 baud
Cable CAT5 - twisted with screen
Termination resistance 150 Ohm
Ordering Information
RS485 expansion kit for KSA701/FP1500 fire panelsNC785
Industry standard RS485 communicationsE
No hardware configuration requiredE
Addressable Fire Systems
Page : 100
FR1500Analogue addressable LCD Repeater/Emulator (AC Powered)
The FP1500 Series analogue addressable fire alarm panels are theideal solution for small to medium-sized installations. Very powerfuland cost-effective, they are easy to install and use due to theirergonomic, advanced design. The FR1500 LCD repeater is supplied inthe same enclosure as the FP1500.
Specifications
Supply Voltage
AC Version 110 VAC @ 50 Hz or 230 VAC @ 50 Hz (+10% -15%)
DC Version 24 VDC
Current Consumption 175 mA Quiescent / 200 mA in alarm
Battery Charger (AC Version only)
Capacity 2 x 12 V - 7 AH (SLA type)
Fuse Rating 3 A
Charger Rating 350 mA @ 27.6 VDC @ 20 °C (Temperaturecompensated -3 V / °C)
Environment
Working Temperature -5°C to +40 °C
Relative Humidity 0-95% non-condensing
IP Rating IP30
Physical Characteristics
Size 420 mm (w) x 335 (h) x 110 (d)
Weight 6.2 kg without batteries / 10.7 kg with 2 x 7 Ahbatteries
Communication Ports RS232 and RS485 standard
Ordering Information
Analogue addressable LCD Repeater/Emulator (AC Powered)FR1500
Modern, attractive designE
4 x 40 characters LCD displayE
20 Display zonesE
EN54 compliant with approvals pendingE
3 User access levelsE
24 VDC or 230 VAC models availableE
Panel networkingE
Full system controlE
Addressable Fire Systems
Page : 101
MODGSMGSM Modem for KSA700/FP1500 Series Fire Panels
The MODGSM modem may be used in KSA701/FP1500, KSA702 andKSA705 fire panel from GE-Interlogix. It is ideal for use as a standardmodem for making and receiving calls from and to the fire panel, butmay also be used for GSM messaging.
Specifications
GSM Band 900/1800 MHz
Services Data, SMS, Voice and Fax
AT Commands GSM 07.07 and 07.05
Output Power (max)
GSM900 2 W
GSM1800 1 W
Input Voltage 5 to 32 V
Current @ 5V
Avarage 330 mA
Peak 1.8 A
SIM Interface 3V / 5V
Dimensions (h x w x d) 98 x 54 x 25 mm
Weight 130 g
Environmental Temperature
Storage - 25 °C to + 70 °C
Operating - 20 °C to + 55 °C
Ordering Information
GSM Modem for KSA700/FP1500 Series Fire PanelsMODGSM
Dual-Band 900/1800 MHzE
Data and SMS servicesE
Remote control by AT commandsE
Wide input voltage rangeE
Addressable Fire Systems
Page : 102
PCG-Graphic102Graphic Software for KSA700/FP1500 Fire Systems (1 panel-2 loops)
The PCG-Config series consists of 3 software applications. Theindividual software formats allows the graphic package to grow withthe installation. PCG-Config102 operates with a single panel and allowsfor the configuration of all devices up to a maximum of two loops.
Specifications
Hardware requirements
Communication RS232, modem and/or TCP/IP
Display SVGA or higher resolution
Hard disk 2 Gb with 650 Mb free space
Keyboard Required
Pointing device Required
Printer System printer required for printing
Processor 1 GHz or higher Pentium III-compatible CPU
RAM 256 Mb or more
Removable media 1.44 Mb stiffy and CD-ROM or DVD drive
Software requirements
Operating system Windows '98 or Windows 2000
Ordering Information
Graphic Software for KSA700/FP1500 Fire Systems (1 panel-2 loops)PCG-Graphic102
Bi-directional communication with single panels andnetworked fire systems
E
Local or remote connection via modem or TCP/IPE
Large selection of user configurable iconsE
Visualises device alarms and status of in- and outputsE
Event texts retrieval from the panelE
Configurator and operator contol levelsE
Navigation buttons allowedE
Event logs with reporting facilitiesE
Basic drawing package includedE
Imports bmp & drw format graphicsE
Addressable Fire Systems
Page : 103
PCG-GraphicNWGraphic Software for KSA700/FP1500 Fire Systems (multi-panel)
The PCG-Config series consists of 3 software applications. Theindividual software formats allows the graphic package to grow withthe installation. PCG-ConfigNW allows for monitoring on networkedsystems with multiple panels.
Specifications
Hardware requirements
Communication RS232, modem and/or TCP/IP
Display SVGA or higher resolution
Hard disk 2 Gb with 650 Mb free space
Keyboard Required
Pointing device Required
Printer System printer required for printing
Processor 1 GHz or higher Pentium III-compatible CPU
RAM 256 Mb or more
Removable media 1.44 Mb stiffy and CD-ROM or DVD drive
Software requirements
Operating system Windows '98 or Windows 2000
Ordering Information
Graphic Software for KSA700/FP1500 Fire Systems (multi-panel)PCG-GraphicNW
Bi-directional communication with single panels andnetworked fire systems
E
Local or remote connection via modem or TCP/IPE
Large selection of user configurable iconsE
Visualises device alarms and status of in- and outputsE
Event texts retrieval from the panelE
Configurator and operator contol levelsE
Navigation buttons allowedE
Event logs with reporting facilitiesE
Basic drawing package includedE
Imports bmp & drw format graphicsE
Addressable Fire Systems
Page : 104
FP1216ENAnalogue addressable fire panel 2 - 4 loops, 16 zones
The FP1216EN is a versatile, cost effective analogue addressable firepanel with 2 to 4 loops and powerfull I/O features. It supports all theLON700 devices and repeaters, and can be optionally upgraded toprovide full networking. The FP1216EN is truly user friendly andprovides a generous 8 x 40 graphic, backlit display. I/O control is donevia the powerful FP2000/FP1200 series boolean I/O programingmodule. Extensive maintenance features are provided standard. TheFP1216EN supports both 2000 and 900 series sensors and I/O units.
Specifications
Supply voltage 230 V ac (+10/-15%)
50 Hz220 VA
Min. supply current @ 24 VDC 0.2 A
Battery charger rating @ 27.6VDC
1.6 A
Total supply rating @ 27.6 VDC 4 A
Relay rating @ 24 VDC 2 A
Weight (no batteries) 7.5 kg
Dimensions (h x w x d) 440 x 444 x 125 mm
Ordering Information
Analogue addressable fire panel 2 - 4 loops, 16 zonesFP1216EN LCD repeater with emulator functionsFR2000 Rim surround for the 780 and 1200N series fire panel boxesFP-RIM12702-loop extension board for FP1200 / FP2000 fire panelsLC2002LON700 driver for FP1200 / FP2000LON2000Modem kitMOD2000ARCNET RS485 network card with single RS485 interfaceNC2011ARCNET network card with single optical interface boardNC2051RS485 network extension boardNE2011Fibre optic network extension boardNE2051 Graphics package network application with copy protection keyPCG-NGraphics package with copy protection keyPCG-SProgramming and configuration softwarePCC2000Maintenance and support software with copy protection keyPCM2000
One man maintenanceE
Soak testE
On-line diagnostics and statisticsE
Power supply for 72 hour autonomyE
Floating background for 2000 series sensorsE
Coincidence within and in between zonesE
Start-up default modeE
Upload/download, remote maintenance and graphic PCsoftware
E
I/O programming including Boolean functionsE
EN 54 p2 & 4 approvedE
Bosec certifiedE
2 or 4 class A loopsE
Full range of LON700 devicesE
Addressable Fire Systems
Page : 105
FP2416Analogue addressable fire panel 2 - 4 loops, 16 zones
FP2000 SeriesA versatile, powerful analogue addressable fire panel, 2 to 4 loops, 16displayed zones with extensive I/O features. The fire panel can operatewithin a 31 panel network and can communicate with global repeatersand PC grahics. It also supports all the LON700 devices and repeatersusing a seperate two wire bus. The FP2000 series is truly user-friendly,and provides a generous 8 x 40 backlit graphic display. I/O control isdone via the powerful FP2000/FP1200 series boolean I/O programingmodule. Extensive maintenance features are provided standard. TheFP2000 series supports both 2000 and 900 series sensors and I/O units.
Specifications
Supply voltage 1 190 - 270 V ac
40- 60 Hz160 VA max.
Supply voltage 2 21 - 27 V dc
Current consumption
Quiescent @ 24 V dc (equippedloop)
500 mA
Alarm current @ 24 V dc 600 mA
Available auxiliary current inalarm
3.4 A
Battery charger rating @ 27.5 Vdc
3 A
Total supply rating @ 27.5 V dc 4 A
Relay rating @ 24 V dc 2 A
Weight (no batteries) 11 kg
Dimensions (mm) (H x W x D) 609 x 441 x 109
Ordering Information
Analogue addressable fire panel 2 - 4 loops, 16 zonesFP2416LCD repeater with emulator functionsFR20002-loop extension board for FP1200 / FP2000 fire panelsLC2002ARCNET RS485 network card with single RS485 interfaceNC2011ARCNET network card with single optical interface boardNC2051RS485 network extension boardNE2011Fibre optic network extension boardNE2051LON700 driver for FP1200 / FP2000LON20002 wire repeatersLON700LCD repeaterFRL700Modem kitMOD2000Maintenance and support software with copy protection keyPCM2000Programming and configuration softwarePCC2000PC Graphic Software Packages for Aritech Fire SytemsPCG SeriesInternal printerPR2000
One man maintenanceE
Graphic maintenanceE
Maintenance warningE
Service reminder signalE
Soak testE
On-line diagnostics and statisticsE
Floating backgroundE
Day/night sensitivity settingE
Coincidence within and in between zonesE
Automatic timed and manual on/off zonesE
Start-up default modeE
Service switchE
Upload/download, remote maintenance and graphic PCsoftware
E
I/O programming including Boolean functionsE
ARCNET panel networkingE
EN54 approved, certified Bosec, VdS, NFA2PE
Networkable "black box" and "global zone" systemE
Full range of repeater panelsE
Full range of LON700 devicesE
Addressable Fire Systems
Page : 106
FP2432Analogue addressable fire panel 2 - 4 loops, 16 - 32 zones
FP2000 SeriesA versatile, powerful analogue addressable fire panel, 2 to 4 loops, 16to 32 displayed zones with extensive I/O features. The fire panel canoperate within a 31 panel network and can communicate with globalrepeaters and PC grahics. It also supports all the LON700 devices andrepeaters using a seperate two wire bus. The FP2000 series is trulyuser-friendly, and provides a generous 8 x 40 backlit graphic display. I/O control is done via the powerful FP2000/FP1200 series boolean I/Oprograming module. Extensive maintenance features are providedstandard. The FP2000 series supports both 2000 and 900 seriessensors and I/O units.
Specifications
Supply voltage 1 190 - 270 V ac
40- 60 Hz160 VA max.
Supply voltage 2 21 - 27 V dc
Current consumption
Quiescent @ 24 V dc (equippedloop)
500 mA
Alarm current @ 24 V dc 600 mA
Available auxiliary current inalarm
3.4 A
Battery charger rating @ 27.5 Vdc
3 A
Total supply rating @ 27.5 V dc 4 A
Relay rating @ 24 V dc 2 A
Weight (no batteries) 11 kg
Dimensions (mm H x W x D) 609 x 441 x 109
Ordering Information
Analogue addressable fire panel 2 - 4 loops, 16 - 32 zonesFP2432LCD repeater with emulator functionsFR20002-loop extension board for FP1200 / FP2000 fire panelsLC200216-zone LED extension fire and fault LEDZE2016ARCNET RS485 network card with single RS485 interfaceNC2011ARCNET network card with single optical interface boardNC2051RS485 network extension boardNE2011Fibre optic network extension boardNE2051LON700 driver for FP1200 / FP2000LON20002 wire repeatersLON700LCD repeaterFRL700Modem kitMOD2000Maintenance and support software with copy protection keyPCM2000Programming and configuration softwarePCC2000PC Graphic Software Packages for Aritech Fire SytemsPCG Series
One man maintenanceE
Graphic maintenanceE
Maintenance warningE
Service reminder signalE
Soak testE
On-line diagnostics and statisticsE
Floating backgroundE
Day/night sensitivity settingE
Coincidence within and in between zonesE
Automatic timed and manual on/off zonesE
Start-up default modeE
Service switchE
Upload/download, remote maintenance and graphic PCsoftware
E
I/O programming including Boolean functionsE
ARCNET panel networkingE
EN54 approved, certified Bosec, VdS, NFA2PE
Networkable "black box" and "global zone" systemE
Full range of repeater panelsE
Full range of LON700 devicesE
Addressable Fire Systems
Page : 107
FP2864Analogue addressable fire panel, 2 - 8 loops, 16 - 64 zones
The FP2864 is a versatile, powerful analogue addressable fire panel, 2to 8 loops, 16 to 64 displayed zones with extensive I/O features. It canoperate within a 31 panel network and can communicate with globalrepeaters and PC grahics. It also supports all the LON700 devices andrepeaters using a seperate two wire bus.The panel is trulyuser-friendly, and provides a generous 8 x 40 backlit graphic display.I/O control is done via the powerful 2000/1200 series boolean I/Oprograming module. Extensive maintenance features are providedstandard. The FP2864 supports 2000, 1500 and 900 series sensors andI/O units.
Specifications
Supply voltage 1 190 - 270 VAC
40 - 60 Hz160 VA max.
Supply voltage 2 21 - 27 VDC
Current consumption
Quiescent @ 24 VDC(equipped loop)
800 mA
Alarm current @ 24 VDC 1 A
Available auxiliary current inalarm
3 A
Battery charger rating @ 27.5VDC
3 A
Total supply rating @ 27.5 VDC 4 A
Relay rating @ 24 VDC 2 A
Weight (no batteries) 15 kg
Dimensions (H x W x D) 804 x 441 x 109 mm
Ordering Information
Analogue addressable fire panel, 2 - 8 loops, 16 - 64 zonesFP2864 2000 Series bus termination boardBUS2000ESPA protocol hardware keyESPA20002-loop extension board for 1200/2000 series fire panelsLC1502LON700 driver for FP1200 / FP2000LON2000LON driver for FP1200/2000 - closed loop systemsLON2000RModem kitMOD2000ARCNET RS485 network card with single RS485 interfaceNC2011ARCNET network card with single optical interface boardNC2051RS485 network extension boardNE2011Fibre optic network extension boardNE2051Internal printerPR2000Relay extension board for 1200/2000 series fire panelsRB20162000 Series Memory Expansion KitRE200416-zone LED extension fire and fault LEDZE2016 Maintenance and support software with copy protection keyPCM2000Programming and configuration softwarePCC2000 Graphics package network application with copy protection keyPCG-NGraphics package with copy protection keyPCG-S
One man maintenanceE
Graphic maintenanceE
Maintenance warningE
Service reminder signalE
Soak testE
On-line diagnostics and statisticsE
Floating backgroundE
Day/night sensitivity settingE
Coincidence within and in between zonesE
Automatic timed and manual on/off zonesE
Start-up default modeE
Service switchE
Upload/download, remote maintenance and graphic PCsoftware
E
I/O programming including Boolean functionsE
ARCNET panel networkingE
EN54 approved, certified Bosec, VdS, NFA2PE
Networkable "black box" and "global zone" systemE
Full range of repeater panelsE
Full range of LON700 devicesE
Addressable Fire Systems
Page : 108
FB2400Analogue addressable fire panel 2 - 4 loops, 'black box'
FP2000 seriesThe FB2400 / FB2800 'black box' system allows a cost-effectivenetwork of fire panels to be interconnected to a global repeater usingthe FP2000 series arcnet network. The FB black boxes have all thefeatures of the FP2000 series of fire panels, but have no display /keyboard. All controls and display is done via the global repeater.
Specifications
Supply voltage 1 190 - 270 V ac
40- 60 Hz160 VA max.
Supply voltage 2 21 - 27 V dc
Current consumption
Quiescent @ 24 V dc (equippedloop)
500 mA
Alarm current @ 24 V dc 600 mA
Available auxiliary current inalarm
3.4 A
Battery charger rating @ 27.5 Vdc
3 A
Total supply rating @ 27.5 V dc 4 A
Relay rating @ 24 V dc 2 A
Weight (no batteries) 11 kg
Dimensions (mm) (H x W x D) 609 x 441 x 109
Ordering Information
Analogue addressable fire panel 2 - 4 loops, 'black box'FB2400Analogue addressable fire panel 2 - 8 loops, 'black box'FB2800
One man maintenanceE
Graphic maintenanceE
Maintenance warningE
Service reminder signalE
Soak testE
On-line diagnostics and statisticsE
Floating backgroundE
Day/night sensitivity settingE
Coincidence within and in between zonesE
Automatic timed and manual on/off zonesE
Start-up default modeE
Service switchE
Upload/download, remote maintenance and graphic PCsoftware
E
I/O programming including Boolean functionsE
ARCNET panel networkingE
Networkable "black box" and "global zone" systemE
Full range of repeater panelsE
Addressable Fire Systems
Page : 109
LC20022-loop extension board for FP1200 / FP2000 fire panels
FP1200 / FP2000 series
Specifications
Current consumption
Quiescent @ 24 V dc (Fullyequipped loop)
+ 150 mA (252 detectors)
Ordering Information
2-loop extension board for FP1200 / FP2000 fire panelsLC2002
ZE201616-zone LED extension fire and fault LED
The ZE2016 allows the extension of the zones of the Fx2x32 andFx2x64 fire panels and repeaters by 16 additional zones.
Ordering Information
16-zone LED extension fire and fault LEDZE2016
Addressable Fire Systems
Page : 110
LON2000LON700 driver for FP1200 / FP2000
FP1200 / FP2000 seriesA LON700 driver that connects FP1200 / FP2000 fire panels to LON700devices
Ordering Information
LON700 driver for FP1200 / FP2000LON2000
NC2011ARCNET RS485 network card with single RS485 interface
The NC2011 is an interface board to connect an RS485 copper networkdirectly into the 1200/2000 series fire panels. It is supplied with oneNE2011 pre installed.
Ordering Information
ARCNET RS485 network card with single RS485 interfaceNC2011RS485 network extension boardNE2011
Addressable Fire Systems
Page : 111
NC2051ARCNET network card with single optical interface board
The NC2051 is an interface board to connect a fiber optic networkdirectly into the 1200/2000 series fire panels. It is supplied with oneNE2051 pre installed.
Ordering Information
ARCNET network card with single optical interface boardNC2051Fibre optic network extension boardNE2051
NE2011RS485 network extension board
The NE2011 is a RS485 network extension board for the NC2011 toallow dual bus and closed ring networks.
Ordering Information
RS485 network extension boardNE2011
Addressable Fire Systems
Page : 112
NE2051Fibre optic network extension board
FP1200 / FP2000 seriesAn extension board for the NC2051 to allow a fibre optic ring bus
Ordering Information
Fibre optic network extension boardNE2051
LON700 Devices
Page : 113
FRL700LCD repeater
The LON700 LCD repeater is a smart and compact, cost-effectivesolution for fire panel repeaters. It is also available as an FBP700 firebrigade panel for Dutch and Scandinavian norms.
Specifications
Dimensions (l x w x d) 240 x 320 x 60 mm
Weight 1.5 kg
Operating temp °C -5°C to +40°C
Operating voltage 15 - 30 VDC
Current consumption
Max. quiesent 100 mA
Bus Connection two wire LON700
Bus Cable CAT 5
Total number of repeaters
700/1200/2000 Series 15
Ordering Information
LCD repeaterFRL700
2 wire connection between fire panel and repeatersE
Up to 1500 metre bus lengthE
24 Volt power supplyE
Cost effective repeater solutionsE
Easily installed, simple operationE
4 x 20 charater LCD display, common LED's, pushbutton control
E
LON700 moduleE
Addressable Fire Systems
Page : 114
FR2000LCD repeater with emulator functions
FP1200 / FP2000 seriesA powerful LCD repeater that can be used as a local or global repeateron a FP1200 / FP2000 fire panel network. Fire panels can be emulatedfrom the FR2000. An 80 x 40 backlit graphic display and full indicationand control keyboard is provided standard.
Specifications
Supply voltage 230 V ac (+10/-15%)
50 Hz50 VA
Min. supply current @ 24 V dc 0.15 A
Battery charger rating @ 27.6 Vdc
0.3 A
Total supply rating @ 27.6 V dc 1 A
Relay rating @ 24 V dc 2 A
Weight (no batteries) 7.5 kg
Dimensions (mm H x W x D) 365 x 444 x 111
Ordering Information
LCD repeater with emulator functionsFR2000RS485 network extension boardNE2011Fibre optic network extension boardNE2051Rim surround for the 780 and 1200N series fire panel boxesFP-RIM1270
8 x 40 character graphic displayE
Arcnet network connection to FP1200/FP2000 seriesfirepanels
E
Global repeater functionE
Comprehensive control and display functionsE
Fire panel emulation functionE
Dual RS232 portsE
Addressable Fire Systems
Page : 115
FR2032Repeater / emulator 16 - 32 zones or panels
FP1200 / FP2000 seriesA repeater / emulator with 16, expandable to 32, displayed fire andfault zones, used in FP1200 / FP2000 networked systems. The repeateris connected on the arcnet network and can operate in a local orglobal repeater mode. An 80 x 40 backlit graphic display and fullindication and control keyboard is provided standard.
Specifications
Supply voltage 21 - 28 V dc
Current consumption 300 mA max
Weight 11 kg
Dimensions (mm H x W x D) 609 x 441 x 109
Ordering Information
Repeater / emulator 16 - 32 zones or panelsFR2032RS485 network extension boardNE2011Fibre optic network extension boardNE205116-zone LED extension fire and fault LEDZE2016
8 x 40 character graphic displayE
Arcnet network connection to FP1200 / FP2000 seriesfirepanels
E
Global repeater functionE
Comprehensive control and display functionsE
16 zones fire and fault expandable to 32 zonesE
24 Volt operationE
Emulation functionsE
Addressable Fire Systems
Page : 116
FR2064Repeater/emulator 16 - 64 zones or panels
A repeater/emulator with 16 fire and fault zones, expandable to 64,used in 1200/2000 series networked systems. The repeater isconnected on the arcnet network and can operate in a local or globalrepeater mode. An 80 x 40 character, backlit graphic display and fullindication and control keyboard is provided standard.
Specifications
Supply voltage 1
160 VA max.Supply voltage 2 21 - 27 VDC
Current consumption
Quiescent @ 24 VDC(equipped loop)
300 mA
Alarm current @ 24 VDC
Available auxiliary current inalarm
Battery charger rating @ 27.5VDC
Total supply rating @ 27.5 VDC
Relay rating @ 24 VDC
Weight (no batteries) 15 kg
Dimensions (H x W x D) 804 x 441 x 109 mm
Ordering Information
Repeater/emulator 16 - 64 zones or panelsFR2064 2000 Series bus termination boardBUS2000ESPA protocol hardware keyESPA2000LON700 driver for FP1200 / FP2000LON2000LON driver for FP1200/2000 - closed loop systemsLON2000RModem kitMOD2000RS485 network extension boardNE2011Fibre optic network extension boardNE2051Internal printerPR200016-zone LED extension fire and fault LEDZE2016
8 x 40 character graphic displayE
Arcnet network connection to FP1200 / FP2000 seriesfirepanels
E
Global repeater functionE
Comprehensive control and display functionsE
Emulation functionE
16 to 64 zones fire and fault displayedE
24 volt operationE
Addressable Fire Systems
Page : 117
UN2011FP1200 / FP2000 arcnet to RS232 converter
FP1200 / FP2000 seriesThe unversal node allows the fire panel arcnet network to be extendedto computer software applications either locally with the RS232interface, or remotely using the MOD2000. It has a 230 volt powersupply and battery charger self contained in the unit.
Specifications
Input voltage 230 V ac, 50 Hz, 10 VA
Battery type 12 V 1,2 Ah
Fault relay 2 A @ 24 V dc, 50 W dc
Weight 5 kg
Dimensions mm (H x W x D) 400 x 300 x 65
Operating remperature 0 - 40 °C
Ordering Information
FP1200 / FP2000 arcnet to RS232 converterUN2011Modem kitMOD2000
FP1200 / FP2000 arcnet to RS232 interfaceE
Allows computer applications to operate on the firepanel network
E
230V operation and battery chargerE
Can be extended with MOD2000 for remote operationE
'Black box' operationE
Addressable Fire Systems
Page : 118
MOD2000Modem kit
FP1200 / FP2000 seriesAn internal modem for the FP1200 / FP2000 fire panels or a UN2011universal node. The modem has the autonomy of the fire panel powersupply, and has extended telephone line protectection. The MOD2000can also be used with a computer.
Ordering Information
Modem kitMOD2000
MOD2000E
For fire panel and universal node operationE
Internal installationE
Autonomous power supplyE
Addressable Fire Systems
Page : 119
PCC2000Programming and configuration software
PCC2000 allows easy, menu driven, programming of all the panel'sfeatures and settings. Common texts can be easily copied whilesensors, zones and areas increment or follow automatically. Booleanlogic programming becomes simple as inputs and outputs arecontinuously displayed for the programmer's convenience.
Specifications
Processor 486 66 MHz
RAM 12 Mb
Display adapter VGA
Hard disk space 20 MB
Pointing device MS Mouse
Graphical environment Windows 98, 2000, XP
Communications ports 1 x RS232
1 x Parallel
Ordering Information
Programming and configuration softwarePCC2000
Provide communication with single fire panels andnetworked fire systems, both locally or remote viamodem
E
Windows 98, 2000 and XP compatibleE
For use with 2000/1200 series panelsE
Menu drivenE
Full or partial up- and downloadE
Addressable Fire Systems
Page : 120
PCM2000Maintenance and support software with copy protection key
PCM2000 allows local and remote maintenance facilities for 1200/2000series fire panels. Amongst others, it allows for full panel emulation,data retrieval and central alarm monitoring.
Specifications
Processor Pentium 133Mhz (or better)
RAM 32 Mb (or more)
Display Adapter VGA
Hard Disk Space 20 MB
Pointing Device Bus or P/S2 Mouse
Graphical Environment Windows 98, NT or 2000
Communications ports Depending on Drivers Printer port (for key)
1 Parallel
Ordering Information
Maintenance and support software with copy protection keyPCM2000
Provide communication with single fire panels andnetworked fire systems, both locally or remote viamodem
E
Windows 95, 98 and NT compatibleE
For use with FP2000, FP1200E
Full panel emulationE
Data retrievalE
Central stationE
History logE
Address bookE
Dynamic Link Library (DLL) for third party integrationE
Addressable Fire Systems
Page : 121
PCG-SGraphics package with copy protection key
2 Packages allow the graphic package to grow with the installation.The basic version PCG-S operates with a single panel, while the PCG-Nsupports a network. Upgrades do not require rework on the existingdatabase, drawings, etc.
Specifications
Item Recommended
Processor Pentium II 266 MHz (or better)
RAM 64 Mb (or more)
Display adapter SVGA or better
Hard disk space 200 MB
Pointing device MS Mouse, Bus or P/S2
Graphical environment Windows NT
Communication ports 1 x RS-232 - Depending on drivers
1 x Parallel - Printer port (for key)
Ordering Information
Graphics package with copy protection keyPCG-S
Provide bi-directional communication with single firepanels and networked fire systems, both locally andremote via modem
E
Windows 2000 and NT compatibleE
For use with FP2000, FP1200, FP1100 and FP700E
Constructed around Sybase SQL AnywhereE
Large selection of iconsE
Visualises inputs & outputsE
Information page per pointE
Get texts from panelE
Several operator levels and passwordsE
Operator configurableE
Multiple navigation buttonsE
Event logsE
Basic drawing package includedE
Imports .bmp & .wmf drawings from virtually anypackage
E
Hardware key protectedE
Content
DI322I Ionisation detector, conventional Page : 3
DP331I Optical detector, conventional, with field exchangeable optical block Page : 4
DT313I Temperature detector (fixed and rate-of-rise), conventional Page : 5
KCT731 Calibration Tool for KL731/DP331I Fire Detectors Page : 6
KZ700 Universal fire detector base Page : 7
KZ705 Universal fire detector base with earth connection Page : 8
KZ705D Conventional fire detector base with diode Page : 9
EOL-ACT Active end-of-line device for use with FP400/KL700 fire panels Page : 9
KZ705R Conventional 12 VDC fire detector base with relay Page : 10
S700 Surface mount accessory for KZ700 and KZ705 series bases Page : 11
DP721I Photoelectric smoke detector with remote alarm LED output Page : 12
DP721T Photoelectric smoke and heat detector head with remote alarm LED Page : 13
DT713-5 57º C fixed and rate-of-rise heat detector Page : 14
DT713-7 70º C fixed and R.O.R. heat detector Page : 15
DB702 10 cm diameter base - 6 terminals Page : 16
DI650 Ionisation smoke detector Page : 17
DP652 Optical smoke detector Page : 18
DT654 Heat detector, R.O.R., 57º C A1R Page : 19
DB860 Standard Base Page : 20
DB861 Backplate for Ingress Protection 860-950 Page : 20
DB806 Conduit box for 860 / 950 series bases Page : 21
DB650 650 series relay base Page : 21
DI1552 Ionisation Sensor Page : 22
DP1561 Optical sensor with field exchangeable optical block Page : 23
DP1551T Dual Sensor (Optical/Heat) Page : 24
DT1553 Heat Sensor Page : 25
PG700 Fire sensor programmer Page : 26
KZ705I Analogue fire detector base with isolator Page : 27
KZ705AS Analogue fire detector base with sounder Page : 28
KZ705IAS Analogue fire detector base with isolator and sounder Page : 29
KAL410 Conventional Zone Monitor Unit - 1 Zone Page : 30
KAL414C Conventional Zone Monitor Unit - 4 Zones Page : 31
KAL426C Extinguishing Control Module Page : 32
KAL430 Relay Module - 1 Relay Page : 33
KAL434C Addressable Relay Module - 4 Relays Page : 34
KAL440 Supervised Relay Module Page : 35
KAL450 Addressable Manual Call Point Page : 36
KAL460 Digital Input Module Page : 37
KAL470 Isolator Module Page : 38
KAL490 Retention Module - 1 Input / 1 Output Page : 39
DP2051 Optical Sensor Page : 40
DP2061 Optical Sensor with remote LED output Page : 41
DP2061T Optical and heat multi-sensor with remote LED output Page : 42
DP2071 Optical Sensor with 7-segment display Page : 43
DT2053 2000 Series heat sensor Page : 44
DT2063 2000 series heat sensor with remote LED output Page : 45
DT2073 Heat Sensor with 7-segment Display and Remote LED Output Page : 46
DB2001 2000 series base, 2 terminals Page : 47
DB2002 2000 series base, 4 terminals Page : 48
DB2016 Isolating base Page : 49
IU2016 Loop Isolator Page : 50
DB2003 Base for the IU2016 isolator Page : 51
DM2000 Manual call point, flying leads Page : 52
DM2000E Manual call point - Red IP67 waterproof, including backbox Page : 53
IO2014 Input Output unit - 4 inputs Page : 54
IU2050 Single Input Module Page : 55
IU2055 Conventional Zone Monitor Page : 56
GBX2000 Galvanic barrier Page : 57
IU2080 Indicating Circuit Controller Page : 57
FD2705R 2000 series addressable reflective beam detector 5 - 50m Page : 58
AS2015 2000 series loop powered sounder Page : 59
DI950 Analogue addressable ionisation sensor Page : 60
DP951 Optical sensor Page : 60
DT952 Analogue addressable temperature sensor Page : 61
DM960 950 series analogue addressable manual callpoint Page : 61
DI970 Intrinsic safe analogue addressable ionisation detector Page : 62
DP971 Intrisic safe optical detector Page : 62
DT972 Intrinsic safe heat detector Page : 63
DM970 Intrinsic safe manual call point Page : 63
PT971 Intrinsic safe protocol translator Page : 64
GBX70 Galvanic barrier (single channel) Page : 64
II950 950 series mini switch monitor unit Page : 65
II952 950 series switch monitor unit - surface mount Page : 65
II955 950 series zone monitor unit - surface mount Page : 66
IO950 950 series single channel IO - surface mount Page : 66
IO955 950 series output unit - surface mount Page : 67
IO956 950 series sounder circuit controller - surface mount Page : 67
IU950 950 series loop isolator Page : 68
AS950 950 series loop powered sounder Page : 69
AS955 950 series high output loop powered sounder Page : 70
FD950 950 series loop-powered beam detector Page : 71
DB950 950 series standard base Page : 72
DB951 Base for IU 950 Page : 72
DB961 Isolating base (20 devices) Page : 73
DB970 Detector base for 970 series intrinsic safe sensors Page : 73
IU980 Coded cards, addresses 1 - 18 Page : 74
FP202 Conventional fire alarm panel with 2 zones Page : 75
FP204 Conventional fire alarm panel with 4 zones Page : 76
FP206 Conventional fire alarm panel with 6 zones Page : 77
FP402 Conventional fire alarm panel with 2 zones Page : 78
FP408 Conventional fire alarm panel with 8 zones Page : 79
FP412 Conventional fire alarm panel with 12 zones Page : 80
FP416 Conventional fire alarm panel with 16 zones Page : 81
RB404 Relay module, 4 potential free relays for NK700/Fx400 fire panels Page : 82
SB404 Relay module, 4 supervised relays for NK700/Fx400 fire panels Page : 83
FEC403 Conventional extinguishing control panel with 3 zones Page : 84
FEC406 Conventional extinguishing control panel with 6 zones Page : 85
FP604 4-zone Conventional Fire Panel Page : 86
ZI602 Two zone extension board, including 6 outputs Page : 87
RC606 Set of 6 bi-stable magnetic latch relays Page : 87
FP708 Fire panel equipped with 8 zones Page : 88
FR708 Repeater 8 zones, 24 VDC input Page : 89
ZE708 8 zone indicator LED extension board fire/fault Page : 90
ZI708 8 zone input extension board Page : 91
FM740 Synoptic driver for 80 LEDs and common signals Page : 92
OCB724 LON700 output board with 24 open collector outputs Page : 93
RB708 LON700 output board with 8 relays Page : 93
SOB708 LON700 output board with 8 supervised outputs Page : 94
FB708 FP700 black box with 7 slot card cage Page : 95
NC700 LON700 interface board Page : 96
PS700 Plug-in power supply 3.5 A Page : 96
FP1501 Analogue addressable fire detection panel - 1 loop Page : 97
FP1502 Analogue addressable fire detection panel - 2 loops Page : 98
NC785 RS485 expansion kit for KSA701/FP1500 fire panels Page : 99
FR1500 Analogue addressable LCD Repeater/Emulator (AC Powered) Page : 100
MODGSM GSM Modem for KSA700/FP1500 Series Fire Panels Page : 101
PCG-Graphic102 Graphic Software for KSA700/FP1500 Fire Systems (1 panel-2 loops) Page : 102
PCG-GraphicNW Graphic Software for KSA700/FP1500 Fire Systems (multi-panel) Page : 103
FP1216EN Analogue addressable fire panel 2 - 4 loops, 16 zones Page : 104
FP2416 Analogue addressable fire panel 2 - 4 loops, 16 zones Page : 105
FP2432 Analogue addressable fire panel 2 - 4 loops, 16 - 32 zones Page : 106
FP2864 Analogue addressable fire panel, 2 - 8 loops, 16 - 64 zones Page : 107
FB2400 Analogue addressable fire panel 2 - 4 loops, 'black box' Page : 108
LC2002 2-loop extension board for FP1200 / FP2000 fire panels Page : 109
ZE2016 16-zone LED extension fire and fault LED Page : 109
LON2000 LON700 driver for FP1200 / FP2000 Page : 110
NC2011 ARCNET RS485 network card with single RS485 interface Page : 110
NC2051 ARCNET network card with single optical interface board Page : 111
NE2011 RS485 network extension board Page : 111
NE2051 Fibre optic network extension board Page : 112
FRL700 LCD repeater Page : 113
FR2000 LCD repeater with emulator functions Page : 114
FR2032 Repeater / emulator 16 - 32 zones or panels Page : 115
FR2064 Repeater/emulator 16 - 64 zones or panels Page : 116
UN2011 FP1200 / FP2000 arcnet to RS232 converter Page : 117
MOD2000 Modem kit Page : 118
PCC2000 Programming and configuration software Page : 119
PCM2000 Maintenance and support software with copy protection key Page : 120
PCG-S Graphics package with copy protection key Page : 121
www.gesecurity.netAs a company of innovation, GE Security reserves the right to change product specifications without notice. For the latest productspecifications, visit GE Security online or contact your GE Security sales representative.
IPSCAT-2005-12-6 15:44:32
top related