amendment no. 2 to tender documents tender no.: rites…€¦ · supply, installation, and testing...
Post on 28-Aug-2018
216 Views
Preview:
TRANSCRIPT
AMENDMENT No. 2 TO TENDER DOCUMENTS Tender No.: RITES/CO/B&A/EE/DTEH-Rohtak –Air Cooled Chiller System of HVAC work S.No. Clause of tender Page No. Description Amended & to be read as 1 Part –I Annexure
–I Similar work (a)
25 a) Similar works shall mean the work of: “Supply, Installation, and Testing & Commissioning of Air Cooled chiller System HVAC work for Fashion Design & Film & TV at Institutional Campus, Rohtak.”
a) Similar works shall mean the work of: “Supply, Installation, and Testing & Commissioning of HVAC work with air cooled/ water cooled chilled system.
2 Part-I Compressor Capacity Control
98 Microprocessor activated slide valve, controlled by external solenoid valves via micro-computer control panel, fully modulating control from 100% to 15% of the capacity for Chillers less than 70 TR capacity and 100% to 7.5% for Chillers more than 70 TR capacity.
Microprocessor activated slide valve, controlled by external solenoid valves via micro-computer control panel, fully modulating control from 100% to 25% of the capacity for Chillers
3 Part-I Part –II BOQ Item No. 1.a & 1.b
97-100 11-12
Technical Specifications A. HELICAL ROTARY SCREW TYPE WATER CHILLER
The technical specification of air cooled screw chiller machine / Scroll machine given in the tender are for the reference of the bidders. However the air cooled machine/scroll machine is acceptable as per manufacturer standard of approved make specified in the tender.
4 Part- I 7 2. Scope of work -Building Management System complete with Automatic controls and instruments.
2. Scope of work -All HVAC equipments shall be BMS compatible. Provision of BMS System is not covered in scope of work.
5 Part-II 11- 53 Bill of quantities Revised Bill of quantities as per Annexure –“A” to this amendment.
6 The following has been added to the tender:
1 . The several documents forming the contract are to be taken as mutually explanatory on one another, detailed drawings being followed in preference to small scale drawings.
1.1 In case of discrepancy between Bill of quantities , the specification and/ or the drawings, the following order of preference shall be observed: i) Description of Bill of Quantities ii) Specific Conditions and technical specifications and special condition if any iii) Drawings iv) CPWD specification v) Indian Standard Specification of BIS
7 As per
amendment No.1 Date of tender submission: 1400 Hrs. on
23.12.2010 Date of tender Opening : 1430 Hrs. on 23.12.2010
Date of tender submission: 1400 Hrs. on 10.01.2011 Date of tender Opening : 1430 Hrs. on 10.01.2011
Supply, Installation, and Testing & Commissioning of Air Cooled chiller System HVAC work for Fashion Design & Film & TV at Institutional Campus, Rohtak.SR. NO.
UNIT QUANTITY
AMOUNTIn Figures (Rs.) In Words (Rs.) In Figures(Rs.)
1.a
i)
ii)
iii)
QUOTED
UNIT RATE
Chiller CHW IN - 12.2 º C / 54.0 º F CHW OUT - 6.67 º C / 44.00 º F Fouling Factor - 0.0001 FPS
IkW/ TR of the Air cooled screw chiller at full loadshall not be more than 1.4
Condenser Air Temp. - 43.3º C./ 110.0 º F
Supply, installation, testing and commissioningof Air CooledScrew Water Chilling M/C following capacity at belowmentioned operating conditions with R-134a refrigerant,Multiple semihermetic/Open compressors & circuits, drivenby suitable KW Sq. Cage induction motor complete with aircooled condenser,Electronic ExpansionValve, insulated shelland tube flooded chiller with victaulic coupling, DP flowswitches in chiller, refrigerant piping, Refrigerant and gas andOil (First Charge), Microprocessor based control panel,factory mounted, motor starter & accessories etc. all mountedon M.S. frame. Motor shall be highly efficient and suitablefor 415 volts ± 10%,50Hz ± 5 %, three phase A.C. supply.
SUB HEAD 'A' MACHINERY
ITEM OF WORK
FASHION DESIGN
As the performance of the chillers mentioned hereindoes not fall under the ARI/Eurovent certificationprogram so the chiller shall be tested in the factors andthe performance test shall be witnessed byRITES/DTHrepresentatives as per procedure laid downby ARI/Eurovent at four point loads at tender designconditions.
The chiller shall be able to provide 25% to 100%stepless capacity control
SR. NO.
UNIT QUANTITY
AMOUNTIn Figures (Rs.) In Words (Rs.) In Figures(Rs.)
QUOTED
UNIT RATE
ITEM OF WORK
FASHION DESIGN
iv)
v)
vi)
Nos 3
1.b
i)
ii)
CHW OUT - 6.67 º C / 44.00 º F
Condenser Air Temp. - 43.3º C./ 110.0 º F Chiller CHW IN - 12.2 º C / 54.0 º F
a) 529200 Kcal/hr (175 TR) (2W + 1S)
The Chiller shall be able to provide mimimun 3 stepscapacity control.
The System should be compatible with the BMS systemand having the facility to perform the function thruBMS viz remote chiller start and stop, remote leavingchiller liquid temperature adjustment, remote currentlimit setpoint, remote ready to start contacts, safetyshutdown contacts, run contacts
Supply, installation, testing and commissioningof Air CooledScroll Water Chilling M/C following capacity at belowmentioned operating conditions with R410a refrigerant,hermetic, Multiple Scroll compressor unit(s), Air cooledcondenser, insulated evaporator, Electronic Expansion Valve,integral refrigerant piping and wiring, flow swtiches,accessories as required and called for, automatic and safetycontrols mounted in central control panel and all mounted onframe complete. Motor shall be suitable for 415±10% volts,50 cycles/second, 3 phase AC supply.
The chilling machine as described above shall be asper specifications.
(The system shall be complete in all respects vizlubrication sytem, evaporator, condenser coil,refrigerent sytem, controller, communication port forBMS).
Fouling Factor - 0.0001 FPSIkW/ TR of the Air cooled screw chiller at full loadshall not be more than 1.7.
SR. NO.
UNIT QUANTITY
AMOUNTIn Figures (Rs.) In Words (Rs.) In Figures(Rs.)
QUOTED
UNIT RATE
ITEM OF WORK
FASHION DESIGN
iii)
iv)
As the performance of the chillers mentioned hereindoes not fall under the ARI/Eurovent certificationprogram so the chiller shall be tested in the factors andthe performance test shall be witnessed by customersrepresentatives as per procedure laid down byARI/Eurovent at four point loads at tender designconditions.
The System should be compatible with the BMS systemand having the facility to perform the function thruBMS viz remote chiller start and stop, remote leavingchiller liquid temperature adjustment, remote currentlimit setpoint, remote ready to start contacts, safetyshutdown contacts, run contacts
SR. NO.
UNIT QUANTITY
AMOUNTIn Figures (Rs.) In Words (Rs.) In Figures(Rs.)
QUOTED
UNIT RATE
ITEM OF WORK
FASHION DESIGN
v)
vi)
Nos 2
2
i)
ii)
iii)
iv)
v)
vi)
Nos. 3
Nos. 2
b) 136080 Kcal/hr (45 TR) (1W + 1S)
(The system shall be complete in all respects vizlubrication sytem, evaporator, condenser coil,refrigerent sytem, controller, communication port forBMS).
The chilling machine as described above shall be asper specifications.
b) Flow rate 410 LPM/head 20 m (1W+1SB)
Supply, installation, testing and commissioning of chilled water pump set each capable of delivering the specified flow rate comprising the following and complete as per specifications.
Lot, thermal insulation on the pump.
a) Flow rate 1820 LPM/head 25 m (2W+1SB)
Lot, concrete foundation for the pump.
2 Nos. 150 mm dia dial type pressure gauges.
Lot, anti-vibration pads, channel base, coupling,coupling guard, suction guide, etc.
1 No. suitable HP TEFC induction motor with class `F'insulation operating on 415 + 10% volts, 3 phase, 50cycles AC supply.
1 No. end section, vertical split casing, centrifugalpump.
SR. NO.
UNIT QUANTITY
AMOUNTIn Figures (Rs.) In Words (Rs.) In Figures(Rs.)
QUOTED
UNIT RATE
ITEM OF WORK
FASHION DESIGN
2.A
a No. 3.00
b No. 2.00
Hot Water PumpsSupply, installation, testing and commissioning of Hotwater pump set each capable of delivering the specifiedflow rate comprising the following and complete as perspecifications.I) 1 No. monoblok pump.II) 1 No. suitable HP TEFC induction motor with class`F' insulation operating on 415 + 10% volts, 3 phase, 50cycles AC supply.III) Lot, thermal insulation on the pump.IV) 2 Nos. 150 mm dia dial type pressure gauges.V) Lot, anti-vibration pads, channel base, coupling,coupling guard, suction guide, etc.VI) Lot, concrete foundation for the pump.
Flow rate 100 LPM/head 20 m 2 Nos. (1W+1SB)
Flow rate 450 LPM/head 25 m 3 Nos. (2W+1SB)
SR. NO.
UNIT QUANTITY
AMOUNTIn Figures (Rs.) In Words (Rs.) In Figures(Rs.)
QUOTED
UNIT RATE
ITEM OF WORK
FASHION DESIGN
3.0
S.No. Tag No. Cooling Load (TR) Each De-humidified Air Qty. (CFM)
Chilled water coil (Row)
3.1 AHU-1.1-A&B 8.8 5000 4 Nos. 2
3.2 AHU-2.1-A&B 7.3 4050 4 Nos. 2
3.3 AHU-3.1-A&B 7.3 4050 4 Nos. 2
3.4 AHU-4.1-A&B 13.5 7000 4 Nos. 2
GROUND FLOOR
The face velocity across cooling coil shall be limited to 152MPM maxm. The capacity of Air-handlers shall be as follows:
Supply, installation, testing and commissioning offactory built, cabinet type, horizontal/vertical, floormounted/ceilingsuspendedbelt driven air handling unitsin double skin construction of following capacity atrequired static pressure of 40 mm complete with factoryfabricated independent sections, housing the variouscomponents e.g. blower, TEFC blower motor suitablefor operation on 415 + 10% volts, 3 phase, 50 Hz ACsupply, copper tube, aluminium finned chilled watercooling coil, thermostat and control wiring etc., prefilter sets, drain connections and concrete foundationwith anti-vibration mountingsetc. as required and as per"Schedule of equipment" and specifications.
SR. NO.
UNIT QUANTITY
AMOUNTIn Figures (Rs.) In Words (Rs.) In Figures(Rs.)
QUOTED
UNIT RATE
ITEM OF WORK
FASHION DESIGN
3.5 AHU-1.2-A&B 8.4 4700 4 Nos. 2
3.6 AHU-2.2-A&B 6.8 3700 4 Nos. 2
3.7 AHU-3.2-A&B 6.8 3700 4 Nos. 2
3.8 AHU-4.2-A&B 5.9 3200 4 Nos. 2
3.9 AHU-5.2-A&B 5.9 3200 4 Nos. 2
3.10 AHU-1.3-A&B 8.4 4700 4 Nos. 2
3.11 AHU-2.3-A&B 9.2 5125 4 Nos. 2
3.12 AHU-3.3-A&B 8.9 4925 4 Nos. 2
3.13 AHU-4.3-A&B 9.3 5225 4 Nos. 2
3.14 AHU-5.3-A&B 6.8 3700 4 Nos. 2
3.15 AHU-6.3-A&B 6.8 3700 4 Nos. 2
3.16 AHU-7.3-A&B 5.9 3200 4 Nos. 2
SECOND FLOOR
FIRST FLOOR
SR. NO.
UNIT QUANTITY
AMOUNTIn Figures (Rs.) In Words (Rs.) In Figures(Rs.)
QUOTED
UNIT RATE
ITEM OF WORK
FASHION DESIGN
3.17 AHU-8.3-A&B 5.9 3200 4 Nos. 2
3.18 AHU-9.3-A&B 6.1 3400 4 Nos. 2
3.19 AHU-1.4-A&B 21.6 12000 4 Nos. 2
3.20 AHU-2.4-A&B 7.9 4425 4 Nos. 2
3.21 AHU-3.4-A&B 8.5 4825 4 Nos. 2
3.22 AHU-4.4-A&B 8.3 4650 4 Nos. 24.0 Supply and installation and commissioning of ceiling
concealed fan coil units including air - filter ball valveset with strainer, 2 way diverting valve with snap actingheat-cool thermostat as per drawing flexible electricalwiring necessaryconnection for chilled hot water supplyand return line coling heating coil with mechanicallyexpanded copper tube and aluminiumfins statically anddynamically balanced centrifugal forward curvealuminium blower 3 speed mortor suitable for 220(±.)10% V supply complete with stainless steel drain panduly insulated sheet metal casing of heavy gauge steelincluding flanges canvas connection as required. FCU'sare to be powder coated and the noice level shall lessthan 40 Db at AC unit outlet and as per specification.
THIRD FLOOR
SR. NO.
UNIT QUANTITY
AMOUNTIn Figures (Rs.) In Words (Rs.) In Figures(Rs.)
QUOTED
UNIT RATE
ITEM OF WORK
FASHION DESIGN
S.No. TAG No. Cooling Load (TR) Each
4.1 FCU-1.1-6.1 1.5 Nos. 6
5.0
i) Nos. 24
6.0
a i) Nos. 1
b i) Nos. 1
Supply, installation, testing and commissioningof long casingtube axial fan with adjustable pitched aluminium alloyimpeller, TEFC squirrel cage induction motor with class 'H/F'insulation high temprature resistance and flame proof, directdrive arrangement, variable frequency drive, sheet metalcasing, rubber isolator mounts and other accessories as perspecified and of following capacities as per Schedule ofEquipment.
Smoke spill application (exhaust fans) suitable for 250ºCoperating temperature for 120 minutes as per standard BS7346 Part-II-1990, Class-B and tested by an independent firelaboratory.
Supply air fan with class 'F' insulation with PR-12 epoxycoating suitable for normal application and AMCA certifiedfor air and sound levels.
76500 CMH at SP at 20mm WG, 1440 rpm, (Forbasment Fr. Air supply)
76500 CMH at SP at 10mm WG, 1440 rpm,(Forbasment exhaust)
Supply, installation, testing and commissioning, of ductmounted Inline fans complete with direct driven centrifugalfan, TEFC squirrel cage induction motor, direct drivearrangement, heavy gauge sheet metal casing, rubber isolatormounts and other accessories. Inline fans shall be of followingcapacities:
400 CFM at SP of 20 mm WG
GROUND FLOOR
SR. NO.
UNIT QUANTITY
AMOUNTIn Figures (Rs.) In Words (Rs.) In Figures(Rs.)
QUOTED
UNIT RATE
ITEM OF WORK
FASHION DESIGN
ii) Nos. 1
7.0
a Nos. 3
bNos. 2
1.0
5100 CMH at SP at 10mm WG, 1440 rpm, (For lift wellpressurisation)
TOTAL OF SUB HEAD `A’ MACHINERY CARRIED OVER TO SUMMARY
SUB-HEAD 'B' PIPING
Capacity 35 KW 2 No. (1W+1SB)
Exposed Pipes
Supply, laying/fixing,testing and commissioning of followingsizes of chilled water MS ERW heavy class piping confirmingto IS code with necessary clamps, supports, anti-vibrationmountings, hangers and fittings such as bends, tees, reducersetc. (but excluding valves, strainers, gauges, etc.) dulyinsulated with factoryremoulded section of polyurethanefoamwith wire mesh and coated with sand and cement plaster as perspecifications.
Capacity 150 KW 3 Nos. (2W+1SB)
Supply, Installation, testing and commissioning of outdoor type Electric Hot Water Generator of following capacity conforming to BIS standards and hot water in let/ out let temperature of 45/50oC complete as per specifications with following accessories.i) Matching electrical immersion heater banks.ii) All automatic and safety controls such as manual reset, high temperature cut off, step controller and recycling relay, thermostats, pilot light, low water cut off and other controls.iii) Electrical panel mounted on generator frame complete with internal wiring, contractors, switches, etc.iv) Interconnecting cables between panel and heaterv) Concrete foundation for Hot Water Generatorvi) Water Temp. in °C 45 Water Temp. Out °C50
SR. NO.
UNIT QUANTITY
AMOUNTIn Figures (Rs.) In Words (Rs.) In Figures(Rs.)
QUOTED
UNIT RATE
ITEM OF WORK
FASHION DESIGN
i) 200 mm dia M 70
SR. NO.
UNIT QUANTITY
AMOUNTIn Figures (Rs.) In Words (Rs.) In Figures(Rs.)
QUOTED
UNIT RATE
ITEM OF WORK
FASHION DESIGN
ii) 150 mm dia M 35
iii) 125 mm dia M 50
iv) 100 mm dia M 150
v) 80 mm dia M 650
vi) 65 mm dia M 370
vii) 50 mm dia M 390
viii) 40 mm dia M 270
ix) 32 mm dia M 350
x) 25 mm dia M 50
xi) 20 mm dia M 70
2.0
a)
i) 125 mm dia No 3
Supply, installation, testing and commissioning of followingvalves, strainers, in the chilled water piping complete withcompanionflanges, nuts, bolts, gaskets, supports, etc. and dulyinsulated and painted as per specifications.
Motorised Butterfly Valve
SR. NO.
UNIT QUANTITY
AMOUNTIn Figures (Rs.) In Words (Rs.) In Figures(Rs.)
QUOTED
UNIT RATE
ITEM OF WORK
FASHION DESIGN
ii) 80 mm dia No 2
b)
i) 65 mm dia No 2
ii) 50 mm dia No 2
iii) 40 mm dia No 32
iv) 32 mm dia No 10
v) 20 mm dia No 6
c)
i) 200 mm dia No 2
ii) 125 mm dia No 12
iii) 80 mm dia No 8
iv) 65 mm dia No 4
v) 50 mm dia No 4
2 way Chilled water Dynamic cum modulating Valve
Butterfly Valves
SR. NO.
UNIT QUANTITY
AMOUNTIn Figures (Rs.) In Words (Rs.) In Figures(Rs.)
QUOTED
UNIT RATE
ITEM OF WORK
FASHION DESIGN
vi) 40 mm dia No 64
d)
i) 125 mm dia No 6i) 80 mm dia No 4
e)
i) 125 mm dia No 3ii) 80 mm dia No 2
f)
i) 65 mm dia No 2
ii) 50 mm dia No 2iii) 40 mm dia No 32
g)
i) 10 mm dia No 50
h)
i) 32 mm dia No 12
Balancing Valves
Non Return Valves
Y'-Strainer
Auto Air Vent Valves
G M Gate Valve
SR. NO.
UNIT QUANTITY
AMOUNTIn Figures (Rs.) In Words (Rs.) In Figures(Rs.)
QUOTED
UNIT RATE
ITEM OF WORK
FASHION DESIGN
ii) 25 mm dia No 30
i)
i) 32 mm dia No 10
ii) 20 mm dia No 6
j)
i) 32 mm dia No 10
ii) 20 mm dia No 6
k)
i) 9.4 mm Bulb Dia) No 108
l)
i) 100 mm dial No 108
Dial type pressure gauge Range: (0 - 7 Kg/cm2)
Ball Valve without Strainer
Stem typeTemperature gauge Range (0 - 500C)
Ball Valve with Strainer
SR. NO.
UNIT QUANTITY
AMOUNTIn Figures (Rs.) In Words (Rs.) In Figures(Rs.)
QUOTED
UNIT RATE
ITEM OF WORK
FASHION DESIGN
3.0 No 1
1.0
i) Sqm 25
ii) Sqm 30
iii) Sqm 272
iv) Sqm 1686
2.0 Sqm 175
Supply, installation, testing and balancing of factory fabricated rectangular GSS ducting of following thicknessincluding necessary supports, hangers, nut bolts, gaskets,splitter dampers, vanes, canvas connections etc. complete asper specifications.
Supply and fixing acoustic lining of 15 mm thick engineeredestastomeric open cell nitrile rubber slab on the inner side ofducting as per specifications for ducts are required.
0.63 mm
TOTAL OF SUB HEAD 'B' PIPING CARRIED OVER
1.25 mm
SUB-HEAD 'C' DUCTING AND GRILLES
0.8 mm
Supply, installation, testing and commissioning, of MSexpansion tank of size 1.2m x 1.2 m x 1.2 m height, made of3 mm thick mild steel sheet complete with insulation, vent andcontrol valves, air vent, manhole cover, final painting etc.
1.00 mm
SR. NO.
UNIT QUANTITY
AMOUNTIn Figures (Rs.) In Words (Rs.) In Figures(Rs.)
QUOTED
UNIT RATE
ITEM OF WORK
FASHION DESIGN
3.0 Sqm 2000
4.0 Sqm 7
5.0 Sqm 5
6.0 Sqm 4
7.0 Sqm 1
8.0 Sqm 160
9.0 Sqm 2
10.0 Sqm 2
11.0 Sqm 994
Supply, installation, testing and commissioning of powdercoated extruded aluminium supply air Continuous grilles ofvarious sizes, with vcd complete as per specifications .
Supply, installation, testing and commissioning of GI multi-leaf motorised fire dampers complete with chrome platedspindles in self lubricated bronze bushes, linkages, actuatormotor, limit switch, wiring etc. complete as per specifications.
Supply, installation, testing and commissioning ofsquare/rectangularpowder coated extruded aluminium supply air jet diffusers of various sizes with volume controldampers, and complete as per specifications.
Supply, installation, testing and balancing of box type GIvolume control damper complete as per specifications
Supply, installation, testing and commissioning of powdercoated extruded aluminium fresh air louvers with aluminiumbird screen and volume control damper as per specifications.
Supply and installation of powder coated extruded aluminiumlouvers complete with bird screen as per specifications.
Supply and fixing of underdeck roof insulation and thermalinsulation on wall with 40mm thick polyisocyanuratemachinecut shiplap joint slabs prelaminated with 0.05mm aluminiumfoil etc.as per specifications
Supply, installation, testing and commissioning ofsquare/rectangular powder coated extruded aluminiumreturn/exhaust air diffusers of various sizes completewithout volume control dampers, and as per specifications.
Supply and fixing of 15 mm thick chemically crosslinked,closed cell polyethylene FR-XPE retardant gradeinsulation on supply/return air duct as per specifications.
SR. NO.
UNIT QUANTITY
AMOUNTIn Figures (Rs.) In Words (Rs.) In Figures(Rs.)
QUOTED
UNIT RATE
ITEM OF WORK
FASHION DESIGN
TOTAL OF SUB HEAD `C’ DUCTING & GRILLES CARRIED OVER TO SUMMARY
Supply, Installation, and Testing & Commissioning of Air Cooled chiller System HVAC work for Fashion Design & Film & TV at Institutional Campus, Rohtak.SR. NO.
ITEM OF WORK UNIT QTY.
AMOUNT (In words)
In Figures (Rs.) In Words (Rs.) In Figures (Rs.)SUB-HEAD 'D' ELECTRICALS
1.0 CABLES1.1 Supply, storing, handling, laying, testing and commissioning
of 1100 Volt grade XLPE insulated and sheathed aluminiumconductor armoured cables including the cost of providingrequired gap between adjacent cables (minimum one cabledia.) and including the cost of providing identification tags inshaft/ cable trays etc. complete as per specification, asrequired (Low losses).
a 3.5 C x 240 Sq.mm cable RM 500
b 3.5 C x 150 Sq.mm cable RM 50
c 3.5 C x 120 Sq.mm cable RM 300
d 3.5 C x 35 Sq.mm cable RM 300
e 4C x 25 Sq.mm cable RM 300
f 4C x 16 Sq.mm cable RM 700
g 4c x 6 sqmm RM 50
h 4c x 4 sqmm RM 50
1.2 Cable Termination
QUOTED
UNIT RATE
Supply, Installation, and Testing & Commissioning of Air Cooled chiller System HVAC work for Fashion Design & Film & TV at Institutional Campus, Rohtak.SR. NO.
ITEM OF WORK UNIT QTY.
AMOUNT (In words)
In Figures (Rs.) In Words (Rs.) In Figures (Rs.)SUB-HEAD 'D' ELECTRICALS
QUOTED
UNIT RATE
Supply, storing, handling, laying, testing and commissioningof 1100 Volt grade PVC insulated and sheathed aluminiumconductor unarmoured cables including the cost of providingrequired gap between adjacent cables (minimum one cabledia.) and including the cost of providing identification tags inshaft/ cable trays etc. complete as per specification, asrequired (Low losses).
Supply, Installation, and Testing & Commissioning of Air Cooled chiller System HVAC work for Fashion Design & Film & TV at Institutional Campus, Rohtak.SR. NO.
ITEM OF WORK UNIT QTY.
AMOUNT (In words)
In Figures (Rs.) In Words (Rs.) In Figures (Rs.)SUB-HEAD 'D' ELECTRICALS
QUOTED
UNIT RATE
a 3.5 C x 240 Sq.mm cable Nos 16
b 3.5 C x 150 Sq.mm cable Nos 4
c 3.5 C x 120 Sq.mm cable Nos 12
d 3.5 C x 35 Sq.mm cable Nos 16
e 4C x 25 Sq.mm cable Nos 12
f 4C x 16 Sq.mm cable Nos 24
g 4c x 6 sqmm Nos 70
h 4c x 4 sqmm Nos 21.3 Control Cables :
Supplying, receiving, storing, laying, effecting proper
connections, testing and commissioning of the following
sizes of 1.1 KV grade PVC insulated and sheathed copper
conductor armoured stranded control cable complete with
saddles, clamps etc. as required and as per specifications.a 2 Core x 2.5 Sq.mm Cable RM 1500
b 4 Core x 2.5 Sq.mm Cable RM 200
Supply, Installation, and Testing & Commissioning of Air Cooled chiller System HVAC work for Fashion Design & Film & TV at Institutional Campus, Rohtak.SR. NO.
ITEM OF WORK UNIT QTY.
AMOUNT (In words)
In Figures (Rs.) In Words (Rs.) In Figures (Rs.)SUB-HEAD 'D' ELECTRICALS
QUOTED
UNIT RATE
c 7 Core x 2.5 Sq.mm Cable RM 100
Supply, Installation, and Testing & Commissioning of Air Cooled chiller System HVAC work for Fashion Design & Film & TV at Institutional Campus, Rohtak.SR. NO.
ITEM OF WORK UNIT QTY.
AMOUNT (In words)
In Figures (Rs.) In Words (Rs.) In Figures (Rs.)SUB-HEAD 'D' ELECTRICALS
QUOTED
UNIT RATE
1.4 Control Cables termination:Supplying and making of control cable terminations for
control cables as per item 8.0 above complete with brass
plated single compression glands, copper lugs etc. as
required:2 Core x 2.5 Sq.mm Cable Nos. 60
4 Core x 2.5 Sq.mm Cable Nos. 8
7 Core x 2.5 Sq.mm Cable Nos. 4
1.5 Cable Trays (Ladder Type):Supply, fabrication and installation of Hot dip galvanized factory fabricated ladder type cable trays complete with all fabricated bends, tees,nuts bolts ,dash fasteners, elbows, reducers, offsets etc & required hardware. with rungs at every250 mm spacing (c/c) of various width in two tier/three/five tier fashion either on one side of the wall or on two sides of the wall or at other places and paint afterward if required. (All bends & tees shall be of factory built-in of same make as that of tray)
a 75mm x 1200mm x 75mm x 3mm wide cable tray with rungs
of 20mm x 40mm x 20mm
RM 10
b 75mm x 750mm x 75mm x 3mm wide cable tray with rungs
of 20mm x 40mm x 20mm
RM 50
c 50mm x 600mm x 50mm x 2mm wide cable tray with rungs of 15mm x 30mm x 15mm
RM 200
d 50mm x 300mm x 50mm x 2mm wide cable tray with rungs of 15mm x 30mm x 15mm
RM 30
e 50mm x 150mm x 50mm x 2mm wide cable tray with rungs of 15mm x 30mm x 15mm
RM 50
1.6 Cable Trays (Perforated Type)
Supply, Installation, and Testing & Commissioning of Air Cooled chiller System HVAC work for Fashion Design & Film & TV at Institutional Campus, Rohtak.SR. NO.
ITEM OF WORK UNIT QTY.
AMOUNT (In words)
In Figures (Rs.) In Words (Rs.) In Figures (Rs.)SUB-HEAD 'D' ELECTRICALS
QUOTED
UNIT RATE
Supplying and fixing cable trays of the following sizes (in
one/two/ three tier fashion either on one side of the wall or on
two sides of the wall) of GI/MS perforated type including
grouting supports/hangers, nuts, bolts, dash fasteners and
required hardwares etc. as specified in the drawings.a 75mm x 1000mm x 75mm x 3mm wide cable tray RM 10b 50mm x 300mm x 50mm x 2mm wide cable tray RM 50c 50mm x 150mm x 50mm x 2mm wide cable tray RM 100
Supply, Installation, and Testing & Commissioning of Air Cooled chiller System HVAC work for Fashion Design & Film & TV at Institutional Campus, Rohtak.SR. NO.
ITEM OF WORK UNIT QTY.
AMOUNT (In words)
In Figures (Rs.) In Words (Rs.) In Figures (Rs.)SUB-HEAD 'D' ELECTRICALS
QUOTED
UNIT RATE
1.7 Steel SupportsSupplying and fixing of additional length of MS rod/angle
hangers duly painted with 2 coats of spray paint for
supporting the cable trays, complete for extension of the
supports.
Kgs. 2500
1.8 Providing and fixing 6 SWG dia GI wire on surface or inrecess for loop earthing as required.
Mtr 500
1.9 Providing and fixing 25mm x 5mm GI strip on surface or inrecess for connection etc. as required.
Mtr 1000
2.0 HVAC PANELS
Design, fabrication, Supply, Installation, loading, unloading as per site condition, Installation, testing and commissioning of HVAC Panels fabricated out of 2mm thick for structural members (Load bearing members) and 1.6mm thick for door and covers (Non load bearing members) CRCA sheet in cubicle compartmentalize free standing floor mounted, dust and vermin proof with reinforcement of suitable size angle iron, channel 'T' irons and / or flats wherever necessary, 16 gauge CRCA sheet steel shall be used for final distribution panels. Cable gland plates shall be provided on top as well as at the bottom of the panels. Panels shall be treated with all anticorrosive process before painting as per specifications with 2 coats of zinc chromate primer and final approved shade of enamelled paint. 2 Nos. earthing terminals shall be provided for all distribution panels. Panels shall be suitable for 415V, 3-phase, 4-wire, 50Hz supply system and with 15%spare space, lifting hooks shall also be provided in case of large panels. The Panel shall be suitable for installion in Outdoor conditions IP rating of panel shall be IP 54.
Supply, Installation, and Testing & Commissioning of Air Cooled chiller System HVAC work for Fashion Design & Film & TV at Institutional Campus, Rohtak.SR. NO.
ITEM OF WORK UNIT QTY.
AMOUNT (In words)
In Figures (Rs.) In Words (Rs.) In Figures (Rs.)SUB-HEAD 'D' ELECTRICALS
QUOTED
UNIT RATE
Approval shall be taken for each panel before fabrication.Galvanized hardwares with zinc passivation shall be used infabrication of panels. The panels to confirm to IP-43 forindoor & for IP-55 for outdoor installation.
2.1 AC PANEL-1
Incoming
Two (2) Nos. 1000 A, TPN EDO ACB, 50 KA
Metering, Indication and Protection
Two (2) Sets of (0-1000 Amps) 96 x 96mm CT operated Ammeter with 3 way selector switch and 1000/5A, CL-1, 10VA CT.
Two (2) Sets of (0-500 Volt) 96 x 96mm Voltmeter with control MCB and 3 way selector switch.
Two (2) Sets of phase indicating lamps with control MCBs.
Bus Bar:
1500A, TPN aluminium, colour coded bus bar suitable for 415V, 50Hz with heat shrinkable insulation sleeves.
Outgoing:
Three (3) Nos. 630 Amp TP MCCB (35 KA)Three (3) Nos. 400 Amp TP MCCB (35 KA)Four (4) Nos. 100 Amp TP MCCB (15 KA)Three (3) Nos. 40 Amp TP MCB ( 10 KA)Three (3) Nos. Star Delta starters for Chilled Water Pumpswith O/L relay suitable for 15 KW motor and single phasepreventor.
Supply, Installation, and Testing & Commissioning of Air Cooled chiller System HVAC work for Fashion Design & Film & TV at Institutional Campus, Rohtak.SR. NO.
ITEM OF WORK UNIT QTY.
AMOUNT (In words)
In Figures (Rs.) In Words (Rs.) In Figures (Rs.)SUB-HEAD 'D' ELECTRICALS
QUOTED
UNIT RATE
Three (3) Nos. DOL Starters for hot water pumps with overload relay suitable for 3.7 KW motor and single phasepreventor.
Set 1
2.2 AC PANEL-2
Incoming
One (1) Nos. 400A, TPN MCCB, 35 KA
Metering, Indication and Protection
One (1) Sets of (0-400 Amps) 96 x 96mm CT operated Ammeter with 3 way selector switch and 400/5A, CL-1, 10VA CT.
Supply, Installation, and Testing & Commissioning of Air Cooled chiller System HVAC work for Fashion Design & Film & TV at Institutional Campus, Rohtak.SR. NO.
ITEM OF WORK UNIT QTY.
AMOUNT (In words)
In Figures (Rs.) In Words (Rs.) In Figures (Rs.)SUB-HEAD 'D' ELECTRICALS
QUOTED
UNIT RATE
Two (2) Sets of (0-500 Volt) 96 x 96mm Voltmeter with control MCB and 3 way selector switch.
Two(2) Sets of phase indicating lamps with control MCBs.
Bus Bar:
600A, TPN aluminium, colour coded bus bar suitable for 415V, 50Hz with heat shrinkable insulation sleeves.
Outgoing:
Two(2) Nos. 250 Amp TP MCCB (25 KA)Two(2) Nos. 125 Amp TP MCCB (15 KA)Three (3) Nos. 40 Amp TP MCB ( 10 KA)Three (3) Nos. 25 Amp TP MCB ( 10 KA)Two (2) Nos. DOL starters for Chilled Water Pumps withO/L relay suitable for 5.5 KW motor and single phasepreventor.
Two (2) Nos. DOL starters for Hot Water Pumps with O/Lrelay suitable for 1.0 KW motor and single phase preventor.
Set 1
2.3 AHU AND VENTILATION PANELS
Supply, Installation, and Testing & Commissioning of Air Cooled chiller System HVAC work for Fashion Design & Film & TV at Institutional Campus, Rohtak.SR. NO.
ITEM OF WORK UNIT QTY.
AMOUNT (In words)
In Figures (Rs.) In Words (Rs.) In Figures (Rs.)SUB-HEAD 'D' ELECTRICALS
QUOTED
UNIT RATE
Incoming One (1) No. 1000A, EDO ACB, 50 KA Metering, Indication and Protection One (1) Set of (0-1000 Amps) 96 x 96mm CT operatedAmmeter with 3 way selector switch and 400/5A, CL-1,10VA CT. One (1) Set of (0-500 Volt) 96 x 96mm Voltmeter withcontrol MCB and 3 way selector switch. Two(2) Sets of phase indicating lamps with control MCBs. Bus Bar: 1200A, TPN aluminium, colour coded bus bar suitable for415V, 50Hz with heat shrinkable insulation sleeves. Outgoing:One (1) No. 630 Amp TP MCCB (35 KA)Two (2) Nos. 125 Amp TP MCCB (15 KA)Two (2) Nos. 63 Amp TP MCB ( 10 KA)Two (2) Nos. 40 Amp TP MCB ( 10 KA)Forty One (41) Nos. 25 Amp TP MCB ( 10 KA)
Set 1
3.0 AHU'S STARTER PANEL3.1 Supply, installation, testing and commissioning of One
no.63A TPN MPCB (10kA) with 5.5 KW DOL Starter
including single phasing prevention arrangement, O/L relays,
ammeters with CTs, ON/OFF / Trip indication lamps and
push buttons, potential free contacts for remote / local
operations, indication, interlocking. and Auto Manual
Selector Switch as required.
Set 2
Supply, Installation, and Testing & Commissioning of Air Cooled chiller System HVAC work for Fashion Design & Film & TV at Institutional Campus, Rohtak.SR. NO.
ITEM OF WORK UNIT QTY.
AMOUNT (In words)
In Figures (Rs.) In Words (Rs.) In Figures (Rs.)SUB-HEAD 'D' ELECTRICALS
QUOTED
UNIT RATE
3.2 Supply, installation, testing and commissioning of One no.
40A TPN MPCB (10kA) with 3.7 KW DOL Starter
including single phasing prevention arrangement, O/L relays,
ammeters with CTs, ON/OFF / Trip indication lamps and
push buttons, potential free contacts for remote / local
operations, indication, interlocking. and Auto Manual
Selector Switch as required.
Set 2
3.3 Supply, installation, testing and commissioning of One no.
25A TPN MPCB (10kA) with 2.2 KW DOL Starter
including single phasing prevention arrangement, O/L relays,
ammeters with CTs, ON/OFF / Trip indication lamps and
push buttons, potential free contacts for remote / local
operations, indication, interlocking. and Auto Manual
Selector Switch as required.
Set 40
4.0 LIFT WELL PRSSURIZATION AND BASEMENT VENTILATION STARTOR PANEL
4.1 Supply, installation, testing and commissioning of One no.
125 A TPN MPCB (10kA) with 30 KW Star Delta Starter
including single phasing prevention arrangement, O/L relays,
ammeters with CTs, ON/OFF / Trip indication lamps and
push buttons, potential free contacts for remote / local
operations, indication, interlocking. and Auto Manual
Selector Switch as required. (Basement Ventilation)
Set 2
Supply, Installation, and Testing & Commissioning of Air Cooled chiller System HVAC work for Fashion Design & Film & TV at Institutional Campus, Rohtak.SR. NO.
ITEM OF WORK UNIT QTY.
AMOUNT (In words)
In Figures (Rs.) In Words (Rs.) In Figures (Rs.)SUB-HEAD 'D' ELECTRICALS
QUOTED
UNIT RATE
4.2 Supply, installation, testing and commissioning of One no.
25A TPN MPCB (10kA) with 1.1 KW Direct-On-Line
Starter including single phasing prevention arrangement, O/L
relays, ammeters with CTs, ON/OFF / Trip indication lamps
and push buttons, potential free contacts for remote / local
operations, indication, interlocking. and Auto Manual
Selector Switch as required. (Lift Well Pressurization)
Set 1
TOTAL SUB-HEAD 'D' ELECTRICALS CARRIED OVER TO SUMMARY
Note : Qty. of cables or tentative, vendor should make the cable schedule and get it approved before procurement.
Supply, Installation, and Testing & Commissioning of Air Cooled chiller System HVAC work for Fashion Design & Film & TV at Institutional Campus, Rohtak.SR. NO.
UNIT QTY.
AMOUNT (in words)In Figures(Rs.) In Words(Rs.) In Figures(Rs.)
1.0
i)
ii)
iii)
Condenser Air Temp. - 43.3º C./ 110.0 º F
Supply, installation, testing and commissioning of Air CooledScrew Water Chilling M/C following capacity at below mentionedoperating conditions with R-134a refrigerant, Multiplesemihermetic/Open compressors & circuits, driven by suitable KWSq. Cage induction motor complete with air cooled condenser,Electronic Expansion Valve, insulated shell and tube floodedchiller with victaulic coupling, DP flow switches in chiller,refrigerant piping, Refrigerant and gas and Oil (First Charge),Microprocessor based control panel, factory mounted, motorstarter & accessories etc. all mounted on M.S. frame. Motor shallbe highly efficient and suitable for 415 volts ± 10%,50Hz ± 5%, three phase A.C. supply.
FILM & TV
ITEM OF WORK QUOTED
UNIT RATE
SUB HEAD 'A' MACHINERY
Chiller CHW IN - 12.2 º C / 54.0 º F CHW OUT - 6.67 º C / 44.00 º F Fouling Factor - 0.0001 FPS
As the performance of the chillers mentioned herein doesnot fall under the ARI/Eurovent certification program sothe chiller shall be tested in the factors and the performancetest shall be witnessed by customers representatives as perprocedure laid down by ARI/Eurovent at four point loads at tender design conditions.
IkW/ TR of the Air cooled screw chiller at full load shallnot be more than 1.3 at Std. Design Conditions
The Chiller shall be able to provide 25% to 100% steplesscapacity control.
Supply, Installation, and Testing & Commissioning of Air Cooled chiller System HVAC work for Fashion Design & Film & TV at Institutional Campus, Rohtak.SR. NO.
UNIT QTY.
AMOUNT (in words)In Figures(Rs.) In Words(Rs.) In Figures(Rs.)FILM & TV
ITEM OF WORK QUOTED
UNIT RATE
iv)
v)
vi)
Nos. 3
2
i)
ii)
iii)
iv)
v)
vi)
Chilled Water Pumps
(The system shall be complete in all respects viz Drive,lubrication sytem, evaporator, condenser coil, refrigerentsytem, controller, communication port for BMS).
The chilling machine as described above shall be as perspecifications.
The System should be compatible with the BMS systemand having the facility to perform the function thru BMSviz remote chiller start and stop, remote leaving chillerliquid temperature adjustment, remote current limitsetpoint, remote ready to start contacts, safety shutdowncontacts, run contacts
2 Nos. 150 mm dia dial type pressure gauges.
a) 302400 Kcal/hr (100 TR) (2W + 1S)
1 No. end section, vertical split casing, centrifugal pump.
1 No. suitable HP TEFC induction motor with class `F'insulation operating on 415 + 10% volts, 3 phase, 50 cyclesAC supply.
Supply, installation, testing and commissioning of chilled water pump set each capable of delivering the specified flow rate comprising the following and complete as per specifications.
Lot, thermal insulation on the pump.
Lot, anti-vibration pads, channel base, coupling, couplingguard, suction guide, etc.
Lot, concrete foundation for the pump.
Supply, Installation, and Testing & Commissioning of Air Cooled chiller System HVAC work for Fashion Design & Film & TV at Institutional Campus, Rohtak.SR. NO.
UNIT QTY.
AMOUNT (in words)In Figures(Rs.) In Words(Rs.) In Figures(Rs.)FILM & TV
ITEM OF WORK QUOTED
UNIT RATE
Nos. 3
2.A
3.0
a) Flow rate 910 LPM/head 25 m (2W+1SB)
Supply, installation, testing and commissioning of factorybuilt, cabinet type, horizontal/vertical, floor mounted/ceilingsuspended belt driven air handling units in double skinconstruction of following capacity at required static pressureof 40 mm complete with factory fabricated independentsections, housing the various components e.g. blower, TEFCblower motor suitable for operation on 415 + 10% volts, 3phase, 50 Hz AC supply, copper tube, aluminium finnedchilled water cooling coil, thermostat and control wiring etc.,pre filter sets, drain connections and concrete foundation withanti-vibrationmountings etc. as required and as per "Scheduleof equipment" and specifications.
Hot Water PumpsSupply, installation, testing and commissioning of Hot waterpump set each capable of delivering the specified flow ratecomprising the following and complete as per specifications.I) 1 No. monoblok pump.II) 1 No. suitable HP TEFC induction motor with class `F'insulation operating on 415 + 10% volts, 3 phase, 50 cyclesAC supply.III) Lot, thermal insulation on the pump.IV) 2 Nos. 150 mm dia dial type pressure gauges.V) Lot, anti-vibration pads, channel base, coupling, couplingguard, suction guide, etc.VI) Lot, concrete foundation for the pump.a) Flow rate 450 LPM/head 25 m 3 Nos. (2W+1SB)b) Flow rate 100 LPM/head 20 m 2 Nos. (1W+1SB)
Supply, Installation, and Testing & Commissioning of Air Cooled chiller System HVAC work for Fashion Design & Film & TV at Institutional Campus, Rohtak.SR. NO.
UNIT QTY.
AMOUNT (in words)In Figures(Rs.) In Words(Rs.) In Figures(Rs.)FILM & TV
ITEM OF WORK QUOTED
UNIT RATE
S.No. TAG No. Cooling Load (TR) Each
De-humidi-fied Air Qty. (CFM)
Chilled Water Coil (Row)
3.1 AHU-1.1 35.0 20000 4 No. 1
3.2 AHU-2.1 17.0 9500 4 No. 1
3.3 AHU-3.1 & 4.1 7.0 4000 4 Nos. 2
3.4 AHU-5.1 & 6.1 7.0 4000 4 Nos. 2
GROUND FLOOR
The face velocity across cooling coil shall be limited to 152 MPMmaxm. The capacity of Air-handlers shall be as follows:
Supply, Installation, and Testing & Commissioning of Air Cooled chiller System HVAC work for Fashion Design & Film & TV at Institutional Campus, Rohtak.SR. NO.
UNIT QTY.
AMOUNT (in words)In Figures(Rs.) In Words(Rs.) In Figures(Rs.)FILM & TV
ITEM OF WORK QUOTED
UNIT RATE
3.5 AHU-7.1 & 8.1 7.0 4000 4 Nos. 2
3.6 AHU-9.1 & 10.1 7.0 3500 4 Nos. 2
3.7 AHU-11.1 12.0 5800 4 No. 1
3.8 AHU-1.2 5.6 2800 4 Nos. 2
3.9 AHU-2.2 & 3.2 7.0 3500 4 Nos. 1
3.10 AHU-1.3 & 2.3 8.1 4650 4 Nos. 2
3.11 AHU-3.3 & 4.3 8.1 4650 4 Nos. 2
3.12 AHU-5.3 & 6.3 6.5 3500 4 Nos. 2
FIRST FLOOR
SECOND FLOOR
Supply, Installation, and Testing & Commissioning of Air Cooled chiller System HVAC work for Fashion Design & Film & TV at Institutional Campus, Rohtak.SR. NO.
UNIT QTY.
AMOUNT (in words)In Figures(Rs.) In Words(Rs.) In Figures(Rs.)FILM & TV
ITEM OF WORK QUOTED
UNIT RATE
4.0
S.No. TAG No. Cooling Load (TR) Each
4.1 FCU-1.1 1.5 No. 2
4.2 FCU-2.1 1.5 No. 2
5.0
Supply and installation and commissioning of ceilingconcealed fan coil units includingair - filter ball valve set withstrainer, 2 way diverting valve with snap acting heat-coolthermostat as per drawing flexible electrical wiring necessaryconnection for chilled hot water supply and return line colingheating coil with mechanically expanded copper tube andaluminium fins staticallyand dynamicallybalanced centrifugalforward curve aluminium blower 3 speed mortor suitable for220(±.) 10% V supply complete with stainlesssteel drain panduly insulated sheet metal casing of heavy gauge steelincluding flanges canvas connection as required. FCU's are tobe powder coated and the noice level shall less than 40 Db atAC unit outlet and as per specification.
De-humidi-fied Air Qty. (CFM)
600
GROUND FLOOR
Supply, installation, testing and commissioning, of duct mountedInline fans complete with direct driven centrifugal fan, TEFCsquirrel cage induction motor, direct drive arrangement, heavygauge sheet metal casing, rubber isolator mounts and otheraccessories. Inline fans shall be of following capacities:
600
Supply, Installation, and Testing & Commissioning of Air Cooled chiller System HVAC work for Fashion Design & Film & TV at Institutional Campus, Rohtak.SR. NO.
UNIT QTY.
AMOUNT (in words)In Figures(Rs.) In Words(Rs.) In Figures(Rs.)FILM & TV
ITEM OF WORK QUOTED
UNIT RATE
i) No. 12
6.0
i) No. 1
7.0
400 CFM at SP of 20 mm WG
Supply, installation, testing and commissioning of long casing tubeaxial fan with adjustable pitched aluminium alloy impeller, TEFCsquirrel cage induction motor with class 'F' insulation hightemprature resistance and flame proof, direct drive arrangement,variable frequency drive, sheet metal casing, rubber isolator mountsand other accessories as per specified and of following capacities asper Schedule of Equipment.
Supply air fan with class 'F' insulation with PR-12 epoxy coatingsuitable for normal application and AMCA certified for air andsound levels.
5100 CMH at SP at 10mm WG, 1440 rpm, (For lift wellpressurisation)
Supply, Installation, testing and commissioning of Electric Hot Water Generator of following capacity conforming to BIS standards and hot water in let/ out let temperature of 45/50oC complete as per specifications with following accessories.i) Matching electrical immersion heater banks.ii) All automatic and safety controls such as manual reset, high temperature cut off, step controller and recycling relay, thermostats, pilot light, low water cut off and other controls.iii) Electrical panel mounted on generator frame complete with internal wiring, contractors, switches, etc.iv) Interconnecting cables between panel and heaterv) Concrete foundation for Hot Water Generator vi) Water Temp. in °C 45 Water Temp. Out °C50
Capacity 70 KW 3 Nos. (2W+1SB)
TOTAL OF SUB HEAD `A’ MACHINERY CARRIED OVER TO SUMMARY
Supply, Installation, and Testing & Commissioning of Air Cooled chiller System HVAC work for Fashion Design & Film & TV at Institutional Campus, Rohtak.SR. NO.
UNIT QTY.
AMOUNT (in words)In Figures(Rs.) In Words(Rs.) In Figures(Rs.)FILM & TV
ITEM OF WORK QUOTED
UNIT RATE
1.0 A.
i) 150 mm dia M 20
ii) 125 mm dia M 100
iii) 100 mm dia M 25
iv) 80 mm dia M 275
v) 65 mm dia M 260
vi) 50 mm dia M 170
vii) 40 mm dia M 260
SUB-HEAD 'B' PIPING
Exposed Pipes
Supply, laying/fixing, testing and commissioning of following sizesof chilled water MS ERW heavy class piping with necessaryclamps, supports, anti-vibration mountings, hangers and fittingssuch as bends, tees, reducers etc. (but excluding valves, strainers,gauges, etc.) duly insulated with polyurethane foam pipe sectionprelaminated with aluminium foil and finally applying aluminiumtape at joints as per specifications.
Supply, Installation, and Testing & Commissioning of Air Cooled chiller System HVAC work for Fashion Design & Film & TV at Institutional Campus, Rohtak.SR. NO.
UNIT QTY.
AMOUNT (in words)In Figures(Rs.) In Words(Rs.) In Figures(Rs.)FILM & TV
ITEM OF WORK QUOTED
UNIT RATE
viii) 32 mm dia M 185
ix) 25 mm dia M 25
x) 20 mm dia M 20
2.0
a)
i) 125 mm dia Nos. 3
b)
i) 80 mm dia Nos. 1
ii) 50 mm dia Nos. 3
iii) 40 mm dia Nos. 16
iv) 25 mm dia Nos. 4
Supply, installation, testing and commissioning of followingvalves, strainers, in the chilled water piping complete withcompanion flanges, nuts, bolts, gaskets, supports, etc. and dulyinsulated and painted as per specifications.
Motorised Butterfly Valve
2 way Chilled water Dynamic cum modulating Valve
Supply, Installation, and Testing & Commissioning of Air Cooled chiller System HVAC work for Fashion Design & Film & TV at Institutional Campus, Rohtak.SR. NO.
UNIT QTY.
AMOUNT (in words)In Figures(Rs.) In Words(Rs.) In Figures(Rs.)FILM & TV
ITEM OF WORK QUOTED
UNIT RATE
c)
i) 150 mm dia Nos. 2
ii) 125 mm dia Nos. 18
iii) 80 mm dia Nos. 1
iv) 50 mm dia Nos. 6
v) 40 mm dia Nos. 32
d)
i) 125 mm dia Nos. 9
e)
i) 125 mm dia Nos. 3
f)
i) 80 mm dia Nos. 1
ii) 50 mm dia Nos. 3
Balancing Valves
Y'-Strainer
Non Return Valves
Butterfly Valves
Supply, Installation, and Testing & Commissioning of Air Cooled chiller System HVAC work for Fashion Design & Film & TV at Institutional Campus, Rohtak.SR. NO.
UNIT QTY.
AMOUNT (in words)In Figures(Rs.) In Words(Rs.) In Figures(Rs.)FILM & TV
ITEM OF WORK QUOTED
UNIT RATE
iii) 40 mm dia Nos. 16
g)
i) 10 mm dia Nos. 30
h)i) 32 mm dia Nos. 12
ii) 25 mm dia Nos. 30
i)
i) 25 mm dia Nos. 4
j)
i) 25 mm dia Nos. 4
k)
Ball Valve without Strainer
G M Gate Valve
Auto Air Vent Valves
Stem typeTemperature gauge Range (0 - 500C)
Ball Valve with Strainer
Supply, Installation, and Testing & Commissioning of Air Cooled chiller System HVAC work for Fashion Design & Film & TV at Institutional Campus, Rohtak.SR. NO.
UNIT QTY.
AMOUNT (in words)In Figures(Rs.) In Words(Rs.) In Figures(Rs.)FILM & TV
ITEM OF WORK QUOTED
UNIT RATE
i) 9.4 mm Bulb Dia) Nos. 60
l)
i) 100 mm dial Nos. 60
3.0 No. 1
1.0
i) Sqm. 20
ii) Sqm. 25
iii) Sqm. 190
iv) Sqm. 850
Supply, installation, testing and balancing of factory fabricatedrectangular GSS ducting of following thickness includingnecessary supports, hangers, nut bolts, gaskets, splitter dampers,vanes, canvas connections etc. complete as per specifications.
Dial type pressure gauge Range: (0 - 7 Kg/cm2)
TOTAL OF SUB HEAD 'B' PIPING CARRIED OVER TO SUMMARY
SUB-HEAD 'C' DUCTING AND GRILLES
Supply, installation, testing and commissioning, of MS expansiontank of size 1.2m x 1.2 m x 1.2 m height, made of 3 mm thickmild steel sheet complete with insulation, vent and control valves,air vent, manhole cover, final painting etc.
0.8 mm
0.63 mm
1.25 mm
1.00 mm
Supply, Installation, and Testing & Commissioning of Air Cooled chiller System HVAC work for Fashion Design & Film & TV at Institutional Campus, Rohtak.SR. NO.
UNIT QTY.
AMOUNT (in words)In Figures(Rs.) In Words(Rs.) In Figures(Rs.)FILM & TV
ITEM OF WORK QUOTED
UNIT RATE
2.0 Sqm. 150
3.0 Sqm. 950
4.0 Sqm. 7
5.0 Sqm. 5
6.0 Sqm. 1
7.0 Sqm. 85
8.0 Sqm. 1.5
9.0 Sqm. 1.5
10.0 Sqm. 550
Supply, installation, testing and commissioning of powder coatedextruded aluminium supply air Continuous grilles of various sizes,with vcd complete as per specifications .
Supply, installation, testing and commissioning ofsquare/rectangular powder coated extruded aluminiumreturn/exhaust air diffusers of various sizes complete withoutvolume control dampers, and as per specifications.
Supply, installation, testing and commissioning of GI multi-leafmotorised fire dampers complete with chrome plated spindles inself lubricated bronze bushes, linkages, actuator motor, limitswitch, wiring etc. complete as per specifications.
Supply, installation, testing and balancing of box type GI volumecontrol damper complete as per specifications
Supply and fixing of 15 mm thick chemically cross linked,closedcell polyethylene FR-XPE retardant grade insulation onsupply/return air duct as per specifications.
Supply and fixing acoustic lining of 15 mm thick engineeredestatomeric open cell nitrile rubber slab on the inner side ofducting as per specifications for ducts as required
TOTAL OF SUB HEAD `C’ DUCTING & GRILLES CARRIED OVER TO SUMMARY
Supply, installation, testing and commissioning of powder coatedextruded aluminium fresh air louvers with aluminium bird screenand volume control damper as per specifications.
Supply and installation of powder coated extruded aluminiumlouvers complete with bird screen as per specifications.
Supply and fixing of underdeck roof insulation and thermalinsulation on wall with 40mm thick polyisocyanurate machine cutshiplap joint slabs prelaminated with 0.05mm aluminium foil etc.asper specifications
Supply, Installation, and Testing & Commissioning of Air Cooled chiller System HVAC work for Fashion Design & Film & TV at Institutional Campus, Rohtak.
UNIT QTY. RATE (in Rs.)
AMOUNT
In Figures (Rs.) In Words (Rs.) In Figures (Rs.)
1.0 CABLES1.1
a RM 150
b RM 60
c RM 120
d RM 50
e RM 440
f RM 400
g RM 100
1.2 Cable Termination
3.5 C x 120 Sq.mm cable
4c x 6 sqmm
4C x 16 Sq.mm cable
4C x 25 Sq.mm cable
SR. NO.
ITEM OF WORK
SUB-HEAD 'D' ELECTRICALS
Supply, storing, handling, laying, testing and commissioningof1100 Volt grade XLPE insulated and sheathed aluminiumconductor armoured cables including the cost of providingrequired gap between adjacent cables (minimumone cable dia.)and including the cost of providing identification tags in shaft/cable trays etc. complete as per specification, as required (Lowlosses).
FILM & TV
3.5 C x 240 Sq.mm cable
3.5 C x 150 Sq.mm cable
4c x 4 sqmm
QUOTED
UNIT RATE
Supply, Installation, and Testing & Commissioning of Air Cooled chiller System HVAC work for Fashion Design & Film & TV at Institutional Campus, Rohtak.
UNIT QTY. RATE (in Rs.)
AMOUNT
In Figures (Rs.) In Words (Rs.) In Figures (Rs.)
SR. NO.
ITEM OF WORK
FILM & TV
QUOTED
UNIT RATE
a Nos 4
b Nos 6
c Nos 12
d Nos 2
e Nos 2
f Nos 40
g Nos 6
Supply, storing, handling, laying, testing and commissioningof1100 Volt grade PVC insulated and sheathed aluminiumconductor unarmoured cables including the cost of providingrequired gap between adjacent cables (minimumone cable dia.)and including the cost of providing identification tags in shaft/cable trays etc. complete as per specification, as required (Lowlosses).
3.5 C x 120 Sq.mm cable
3.5 C x 150 Sq.mm cable
4C x 16 Sq.mm cable
4c x 6 sqmm
4c x 4 sqmm
3.5 C x 240 Sq.mm cable
4C x 25 Sq.mm cable
Supply, Installation, and Testing & Commissioning of Air Cooled chiller System HVAC work for Fashion Design & Film & TV at Institutional Campus, Rohtak.
UNIT QTY. RATE (in Rs.)
AMOUNT
In Figures (Rs.) In Words (Rs.) In Figures (Rs.)
SR. NO.
ITEM OF WORK
FILM & TV
QUOTED
UNIT RATE
Control Cables :
RM 600
RM 200
RM 100
1.4
Nos. 30
7 Core x 2.5 Sq.mm Cable
Control Cables termination:
2 Core x 2.5 Sq.mm Cable
Supplying, receiving, storing, laying, effecting proper
connections, testing and commissioning of the following sizes of
1.1 KV grade PVC insulated and sheathed copper conductor
armoured stranded control cable complete with saddles, clamps
etc. as required and as per specifications.
4 Core x 2.5 Sq.mm Cable
Supplying and making of control cable terminations for control
cables as per item 8.0 above complete with brass plated single
compression glands, copper lugs etc. as required:2 Core x 2.5 Sq.mm Cable
Supply, Installation, and Testing & Commissioning of Air Cooled chiller System HVAC work for Fashion Design & Film & TV at Institutional Campus, Rohtak.
UNIT QTY. RATE (in Rs.)
AMOUNT
In Figures (Rs.) In Words (Rs.) In Figures (Rs.)
SR. NO.
ITEM OF WORK
FILM & TV
QUOTED
UNIT RATE
Nos. 8
Nos. 4
1.5
RM 10
RM 50
RM 50
4 Core x 2.5 Sq.mm Cable
7 Core x 2.5 Sq.mm Cable
Cable Trays (Ladder Type):Supply, fabrication and installation of Hot dip galvanized factoryfabricated ladder type cable trays complete with all fabricated bends, tees,nuts bolts ,dash fasteners, elbows, reducers, offsets et& required hardware. with rungs at every 250 mm spacing (c/c) of various width in two tier/three/five tier fashion either on one side of the wall or on two sides of the wall or at other places and paint afterward if required. (All bends & tees shall be of factory built-in of same make as that of tray)
75mm x 750mm x 75mm x 3mm wide cable tray with rungs of
20mm x 40mm x 20mm50mm x 600mm x 50mm x 2mm wide cable tray with rungs of
15mm x 30mm x 15mm
75mm x 1200mm x 75mm x 3mm wide cable tray with rungs of
20mm x 40mm x 20mm
Supply, Installation, and Testing & Commissioning of Air Cooled chiller System HVAC work for Fashion Design & Film & TV at Institutional Campus, Rohtak.
UNIT QTY. RATE (in Rs.)
AMOUNT
In Figures (Rs.) In Words (Rs.) In Figures (Rs.)
SR. NO.
ITEM OF WORK
FILM & TV
QUOTED
UNIT RATE
RM 150
RM 50
1.6
a RM 10b RM 50c RM 50
1.7Kgs. 1500
1.8 Mtr 500
1.9 Mtr 1000
2.0
50mm x 150mm x 50mm x 2mm wide cable tray with rungs of 15mm x 30mm x 15mm
Cable Trays (Perforated Type)Supplying and fixing cable trays of the following sizes (in one/two/ three tier fashion either on one side of the wall or on two sides of the wall) of GI/MS perforated type including grouting supports/hangers, nuts, bolts, dash fasteners and required hardwares etc. as specified in the drawings.
75mm x 1000mm x 75mm x 3mm wide cable tray
Steel SupportsSupplying and fixing of additional length of MS rod/angle
hangers duly painted with 2 coats of spray paint for supporting
the cable trays, complete for extension of the supports.
HVAC PANELS
Providing and fixing 25mm x 5mm GI strip on surface or inrecess for connection etc. as required.
Providing and fixing 6 SWG dia GI wire on surface or in recess for loop earthing as required.
50mm x 300mm x 50mm x 2mm wide cable tray with rungs of
15mm x 30mm x 15mm
50mm x 150mm x 50mm x 2mm wide cable tray50mm x 300mm x 50mm x 2mm wide cable tray
Supply, Installation, and Testing & Commissioning of Air Cooled chiller System HVAC work for Fashion Design & Film & TV at Institutional Campus, Rohtak.
UNIT QTY. RATE (in Rs.)
AMOUNT
In Figures (Rs.) In Words (Rs.) In Figures (Rs.)
SR. NO.
ITEM OF WORK
FILM & TV
QUOTED
UNIT RATE
Approval shall be taken for each panel before fabrication.Galvanized hardwares with zinc passivation shall be used infabrication of panels. The panels to confirm to IP-43 for indoor& for IP-55 for outdoor installation.
Design, fabrication, Supply, Installation, loading, unloading asper site condition, Installation, testing and commissioning ofHVAC Panels fabricated out of 2mm thick for structuralmembers (Load bearing members) and 1.6mm thick for door andcovers (Non load bearing members) CRCA sheet in cubiclecompartmentalize free standing floor mounted, dust and verminproof with reinforcement of suitable size angle iron, channel 'T'irons and / or flats wherever necessary, 16 gauge CRCA sheetsteel shall be used for final distribution panels. Cable glandplates shall be provided on top as well as at the bottom of thepanels. Panels shall be treated with all anticorrosive processbefore painting as per specifications with 2 coats of zincchromate primer and final approved shade of enamelled paint. 2Nos. earthing terminals shall be provided for all distributionpanels. Panels shall be suitable for 415V, 3-phase, 4-wire, 50Hzsupply systemand with 15% spare space, lifting hooks shall alsobe provided in case of large panels. The panel shall be suitablefor installation in outdoor conditions. IP rating of panel shall be I
Supply, Installation, and Testing & Commissioning of Air Cooled chiller System HVAC work for Fashion Design & Film & TV at Institutional Campus, Rohtak.
UNIT QTY. RATE (in Rs.)
AMOUNT
In Figures (Rs.) In Words (Rs.) In Figures (Rs.)
SR. NO.
ITEM OF WORK
FILM & TV
QUOTED
UNIT RATE
2.1
One (1) No. 800A, TPN EDO ACB, 35 KA
Three (3) Nos. 160 Amp TPN MCCB (25 KA)
Three (3) Nos. 25 Amp TPN MCB with motor duty (10 KA)
One(1) Set of phase indicating lamps with control MCBs.
One (1) Set of (0-500 Volt) 96 x 96mm Voltmeter with control MCB and 3 way selector switch.
Metering, Indication and Protection
AC PANEL
Incoming
Bus Bar:
Outgoing:
Three (3) Nos. star delta starters for Chilled Water Pumps withO/L relay suitable for 7.5 KW motor and single phase preventor.
Three (3) Nos. 400 Amp TPN MCCB (35 KA)
Five (5) Nos. 63 Amp TPN MCB with motor duty (10 KA)
1000A, TPN aluminium, colour coded bus bar suitable for 415V50Hz with heat shrinkable insulation sleeves.
One (1) Set of (0-800 Amps) 96 x 96mm CT operated Ammeter with 3 way selector switch and 800/5A, CL-1, 10VA CT.
Supply, Installation, and Testing & Commissioning of Air Cooled chiller System HVAC work for Fashion Design & Film & TV at Institutional Campus, Rohtak.
UNIT QTY. RATE (in Rs.)
AMOUNT
In Figures (Rs.) In Words (Rs.) In Figures (Rs.)
SR. NO.
ITEM OF WORK
FILM & TV
QUOTED
UNIT RATE
Set 1
3.03.1 Set 1
3.2 Set 1
Supply, installation, testing and commissioningof One no. 63A
TPN MPCB (10kA) with 7.5 KW Star Delta Starter including
single phasing prevention arrangement, O/L relays, ammeters
with CTs, ON/OFF / Trip indication lamps and push buttons,
potential free contacts for remote / local operations, indication,
interlocking. and Auto Manual Selector Switch as required.
Supply, installation, testing and commissioningof One no. 63A
TPN MPCB (10kA) with 5.5 KW DOL Starter including single
phasing prevention arrangement, O/L relays, ammeterswith CTs,
ON/OFF / Trip indication lamps and push buttons, potential free
contacts for remote / local operations, indication, interlocking.
and Auto Manual Selector Switch as required.
Three (3) Nos. DOLstarters for Chilled Water Pumps with O/Lrelay suitable for 1.5 kw motor and single phase preventor.
AHU'S STARTOR PANEL
Supply, Installation, and Testing & Commissioning of Air Cooled chiller System HVAC work for Fashion Design & Film & TV at Institutional Campus, Rohtak.
UNIT QTY. RATE (in Rs.)
AMOUNT
In Figures (Rs.) In Words (Rs.) In Figures (Rs.)
SR. NO.
ITEM OF WORK
FILM & TV
QUOTED
UNIT RATE
3.3 Set 2Supply, installation, testing and commissioningof One no. 40A
TPN MPCB (10kA) with 3.7 KW DOL Starter including single
phasing prevention arrangement, O/L relays, ammeterswith CTs,
ON/OFF / Trip indication lamps and push buttons, potential free
contacts for remote / local operations, indication, interlocking.
and Auto Manual Selector Switch as required.
Supply, Installation, and Testing & Commissioning of Air Cooled chiller System HVAC work for Fashion Design & Film & TV at Institutional Campus, Rohtak.
UNIT QTY. RATE (in Rs.)
AMOUNT
In Figures (Rs.) In Words (Rs.) In Figures (Rs.)
SR. NO.
ITEM OF WORK
FILM & TV
QUOTED
UNIT RATE
3.4 Set 9
3.5 Set 1
3.6 Set 1Supply, installation, testing and commissioningof One no. 16A
TPN MPCB (10kA) with 0.75 KW DOL Starter including
single phasing prevention arrangement, O/L relays, ammeters
with CTs, ON/OFF / Trip indication lamps and push buttons,
potential free contacts for remote / local operations, indication,
interlocking. and Auto Manual Selector Switch as required.
Supply, installation, testing and commissioningof One no. 16A
TPN MPCB (10kA) with 1.5 KW DOL Starter including single
phasing prevention arrangement, O/L relays, ammeterswith CTs,
ON/OFF / Trip indication lamps and push buttons, potential free
contacts for remote / local operations, indication, interlocking.
and Auto Manual Selector Switch as required.
Supply, installation, testing and commissioningof One no. 25A
TPN MPCB (10kA) with 2.2 KW DOL Starter including single
phasing prevention arrangement, O/L relays, ammeterswith CTs,
ON/OFF / Trip indication lamps and push buttons, potential free
contacts for remote / local operations, indication, interlocking.
and Auto Manual Selector Switch as required.
Supply, Installation, and Testing & Commissioning of Air Cooled chiller System HVAC work for Fashion Design & Film & TV at Institutional Campus, Rohtak.
UNIT QTY. RATE (in Rs.)
AMOUNT
In Figures (Rs.) In Words (Rs.) In Figures (Rs.)
SR. NO.
ITEM OF WORK
FILM & TV
QUOTED
UNIT RATE
4.0 LIFT WELL PRSSURIZATION STARTOR PANEL
Supply, Installation, and Testing & Commissioning of Air Cooled chiller System HVAC work for Fashion Design & Film & TV at Institutional Campus, Rohtak.
UNIT QTY. RATE (in Rs.)
AMOUNT
In Figures (Rs.) In Words (Rs.) In Figures (Rs.)
SR. NO.
ITEM OF WORK
FILM & TV
QUOTED
UNIT RATE
4.1 Set 1
Note : Qty. of cables or tentative, vendor should make the cable schedule and get it approved before procurement.
TOTAL OF SUB HEAD `D’ MACHINERY CARRIED OVER TO SUMMARY
Supply, installation, testing and commissioningof One no. 16A
TPN MPCB (10kA) with 0.75 KW Direct On Line Starter
including single phasing prevention arrangement, O/L relays,
ammeters with CTs, ON/OFF / Trip indication lamps and push
buttons, potential free contacts for remote / local operations,
indication, interlocking. and Auto Manual Selector Switch as
required.