acs annunciators. eia-485 specification overview rpt-485 - may extend the length 4,000 feet
Post on 29-Dec-2015
248 Views
Preview:
TRANSCRIPT
ACSAnnunciators
EIA-485 specification
Overview
RPT-485- May extend the length 4,000 feet
Control Button
CONTROL for:- SLC Relay - NAC Control Modules- Speaker Circuits - Software Zones
ACM-24AT and ACM-48A
ACM-24AT
- Visual Indication ONLY
ACM-48A
Rear View
Address Wheels
NFS-320 / NFS2-640MAP
NFS2-3030 / NCA-2MAP
KeylockSwitch
Key Lock Connection
Dip Switches
Receive & Transmit LED’s
End of Line Resistor
24V
Power Connection
ACS Connection
EIA-485 Circuits Power Circuits
RETROFIT CONSIDERATIONS
- A 64 point map exceeds physical points on an annunciator- So we add an expander
ACM-24ATAEM-24AT
Address Expansion
Note the differencein device population
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58
59
60
61
62
63
64
NOT
USED
ACM-24AT AEM-24AT AEM-24AT
Set AddressIntelligence
resides on board
Expansion annunciatorsconnect to communication bus
and receive information through host ACM
ACM-24AT with 64-Point Limit
123456789101112131415161718192021222324
ACM-48ASet AddressIntelligence
resides on board
AEM-48AExpansion annunciators connect to
communication bus and receiveinformation through host ACM
252627282930313233343536373839404142434445464748
495051525354555657585960616263646566676869707172
737475767778798081828384858687888990919293949596
NOT
USED
NOT
USED
NOT
USED
ACM-48A with 64-Point Limit
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
ACM-24AT AEM-24AT AEM-24AT
Set AddressIntelligence
resides on board
Expansion annunciatorsconnect to communication bus
and receive information through host ACM
ACM-24AT with 96-Point Limit
49
50
51
52
53
54
55
56
57
58
59
60
61
62
63
64
65
66
67
68
69
70
71
72
73
74
75
76
77
78
79
80
81
82
83
84
85
86
87
88
89
90
91
92
93
94
95
96
AEM-24AT
123456789101112131415161718192021222324
ACM-48ASet AddressIntelligence
resides on board
AEM-48AExpansion annunciators connect to
communication bus and receiveinformation through host ACM
252627282930313233343536373839404142434445464748
495051525354555657585960616263646566676869707172
737475767778798081828384858687888990919293949596
ACM-48A with 96-Point Limit
DOORS
CABINETRY
Address Wheel Relationship
NFS-320 / NFS2-640MAP
1 6
MAP Assignment
SETUP in the NFS-320 and NFS2-640
Pre-defined Maps:
ACS Group Annunciator DisplayA 8 System points & Zones 1 – 56B Zones 57 - 99, 9 F Zones, 8 R Zones, 4 NACsC Loop 1, Modules 1 – 64D Loop 2, Modules 1 – 64E Loop 1, Modules 65 – 128F Loop 2, Modules 65 – 128
G Loop 1, Modules 129 - 159 (1 unused point) Loop 2, Modules 129 - 159 (1 unused point)
H Loop 1, Detectors 1 – 64I Loop 2, Detectors 1 – 64J Loop 1, Detectors 65 – 128K Loop 2, Detectors 65 – 128
L Loop 1, Detectors 129 - 159 (1 unused point) Loop 2, Detectors 129 - 159 (1 unused point)
M For use with FireVoice NFV-25/50ZS N 8 System Points & Zones 1-56 O 8 System Points & Zones 1-56
MAP A 8 System points & Zones 1 – 56
Points 11 – 62 Zones 3 thru 54
SYSTEMPOINTS
POINT TYPE RED LED YELLOW LED SWITCH FUNCTION*1 Input System Alarm System Trouble Acknowledge2 Output Not Used Signal Silenced Alarm Silence3 Output Not Used Program Mode System Reset4 Output Not Used Supervisory Drill5 Output NAC #1 Active NAC Trouble Control NAC #16 Input Security P/A Maint Alert Not Used7 Input Not Used Low Battery Not Used8 Input Not Used AC Fail Not Used
* Pressing the switch button when the Switch Function is "Not Used" causes the associated LED to stop blinking. This is a local acknowledgement at the annunciator only: no message is sent to the panel.
SYSTEM POINTS
Pre-defined and USER MapsACS Group Annunciator Display
A 8 System points & Zones 1 – 56B Zones 57 - 99, 9 F Zones, 8 R Zones, 4 NACsC Loop 1, Modules 1 – 64D Loop 2, Modules 1 – 64E Loop 1, Modules 65 – 128F Loop 2, Modules 65 – 128
G Loop 1, Modules 129 - 159 (1 unused point) Loop 2, Modules 129 - 159 (1 unused point)
H Loop 1, Detectors 1 – 64I Loop 2, Detectors 1 – 64J Loop 1, Detectors 65 – 128K Loop 2, Detectors 65 – 128
L Loop 1, Detectors 129 - 159 (1 unused point) Loop 2, Detectors 129 - 159 (1 unused point)
M For use with FireVoice NFV-25/50ZS N 8 System Points & Zones 1-56 O 8 System Points & Zones 1-561 – 10 USER-DEFINED MAPS
SETUP in the NFS-320 and NFS2-640
ACS Group Annunciator Display1 Programmable Annunciator #12 Programmable Annunciator #23 Programmable Annunciator #34 Programmable Annunciator #45 Programmable Annunciator #56 Programmable Annunciator #67 Programmable Annunciator #78 Programmable Annunciator #89 Programmable Annunciator #9
10 Programmable Annunciator #10
User Defined Maps
User Map Programming
Select User Map #1
User Map Programming
Select a point TYPE
User Map Programming
When you choose the point, installed points appear
User Map Programming
Selecting the point will install it on the map
User Map Programming
You must decide what to DO with the point
User Map Programming
Monitor/Control or Enable/Disable
User Map Programming
Select MODIFY to install the point
Final ACS Addressing
When the User-Defined map is saved, it will appear in the list
CLICKACS1
Final ACS Addressing
When it’s added, ACS 1 is highlighted providing a quick-link
Final ACS Addressing
The quick-link brings you back to the User Map
ACS Map in VeriFire Tools
NFS-320 / NFS2-640MAP
Questions
top related