© ABB Group February 25, 2009 | Slide 1

ABB SACECommunication Capability PortfolioLow voltage Breakers

L.B.U. Breakers & Switches Product Management

© ABB Group February 25, 2009 | Slide 2

Dialogue - New Emax

NEW Emax releases series

The new concept of modularity

More functions and more flexibility

PR122/PR122/PP

PR123/PR123/PP

PR120/PR120/DD--MM

© ABB Group February 25, 2009 | Slide 3

������������� ���������� ������

���������������� �� �� ����������

� ���������������������������� �� ��������! ������������"���

� #$��%&�����'���!����

� ��������� �� �&�!��!�&�������!�'���!�

� #���%&����������!���

!�

© ABB Group February 25, 2009 | Slide 4

������������� ���������� ������

���������������� �� �� �����������(�������)

� ������)��������������*�������������������������������+��,

� ���������������������������� �� ��������! ������������"���

� #$��%&�����'���!����

� ��������� �� �&�!��!�&�������!�'���!�

� #���%&����������!���

!�

© ABB Group February 25, 2009 | Slide 5

������������� ���������� ������

���������������� �� �� �������+��

� ������)��������������*�������������������������������+��,

� ���������������������������� �� ��������! ������������"���

� #$��%&�����'���!����

� ��������� �� �&�!��!�&�������!�'���!�

� #���%&����������!���!�

© ABB Group February 25, 2009 | Slide 6

Dialogue - Modbus

PR122/P characteristicsCommunication functionsProtocol Modbus RTUPhysical layer RS485Maximum baud-rate 19200 bpsMeasuring functionsPhase currentsNeutral currentGround currentVoltage (phase-phase, phase-neutral, residual)Power (active, reactive, apparent)Power factorFrequency and peak factorEnergy (active, reactive, apparent)Signalling functionsLED: auxiliary power supply, warning, alarmTemperatureIndication for L, S, I, G and other protectionAvailable dataCircuit-breaker status (open, closed)Circuit-breaker position (racked-in, racked-out)Mode (local, remote)Protection parameters setLoad control parametersEventsStatus changes in circuit-breaker, protections and

all alarms

AlarmsProtection LProtection SProtection IProtection GProtection TFault release mechanism failureUndervoltage, overvoltage and residual voltage (timing

and trip) protectionReverse power protection (timing and trip)Directional protection (timing and trip)Underfrequency/overfrequency protection (timing and trip)MaintenanceTotal number of operationsTotal number of tripsNumber of trip testsNumber of manual operationsNumber of separate trips for each protection functionContact wear (%)Record data of last tripOperating mechanismsCircuit-breaker openi/closeAlarm resetSetting of curves and protection thresholdsSynchronize system time

© ABB Group February 25, 2009 | Slide 7

Dialogue - Modbus

PR123/P characteristicsCommunication functionsProtocol Modbus RTUPhysical layer RS485Maximum baud-rate 19200 bpsMeasuring functionsPhase currentsNeutral currentGround currentVoltage (phase-phase, phase-neutral, residual)Power (active, reactive, apparent)Power factorFrequency and peak factorEnergy (active, reactive, apparent)Harmonic analisys up to the 40th harmonicSignalling functionsLED: auxiliary power supply, warning, alarmTemperatureIndication for L, S, I, G and other protectionAvailable dataCircuit-breaker status (open, closed)Circuit-breaker position (racked-in, racked-out)Mode (local, remote)Protection parameters setLoad control parametersEventsStatus changes in circuit-breaker, protections and

all alarms

AlarmsProtection LProtection SProtection IProtection GProtection TFault release mechanism failureUndervoltage, overvoltage and residual voltage (timing

and trip) protectionReverse power protection (timing and trip)Directional protection (timing and trip)Underfrequency/overfrequency protection (timing and trip)Phases rotationMaintenanceTotal number of operationsTotal number of tripsNumber of trip testsNumber of manual operationsNumber of separate trips for each protection functionContact wear (%)Record data of last tripOperating mechanismsCircuit-breaker openi/closeAlarm reset Setting of curves and protection thresholdsSynchronize system time

© ABB Group February 25, 2009 | Slide 8

Dialogue – New Emax X1

NEW Emax X1 & Tmax T7 releases

The new concept of modularity

More functions and more flexibility

PR332/PR332/PP

PR333/PR333/PP

PR330/PR330/DD--MM

© ABB Group February 25, 2009 | Slide 9

������������� ���������� ������

���������������� ��-�����.��./����++���

���++������������������������ �� ��������! ��-�����.��./���������

� %$���%&�����'���!����

� ��������� �� �&�!��!�&�������!�'���!�

� %����%&����������!���

© ABB Group February 25, 2009 | Slide 10

������������� ���������� ������

���������������� ��-�����.��./����++����(���++��)

� ��++��)��������������*������������++���������������+++��,

� ��++������������������������ �� ��������! ��-�����.��./���������

� %$���%&�����'���!����

� ��������� �� �&�!��!�&�������!�'���!�

� %����%&����������!���

© ABB Group February 25, 2009 | Slide 11

������������� ���������� ������

���������������� ��-�����+++��

� ��++��)��������������*������������++���������������+++��,

� ��++������������������������ �� ��������! ��-�����.��./���������

� %$���%&�����'���!����

� ��������� �� �&�!��!�&�������!�'���!�

� %����%&����������!���

© ABB Group February 25, 2009 | Slide 12

Dialogue - Modbus

PR332/P characteristicsCommunication functionsProtocol Modbus RTUPhysical layer RS485Maximum baud-rate 19200 bpsMeasuring functionsPhase currentsNeutral currentGround currentVoltage (phase-phase, phase-neutral, residual)Power (active, reactive, apparent)Power factorFrequency and peak factorEnergy (active, reactive, apparent)Signalling functionsLED: auxiliary power supply, warning, alarmTemperatureIndication for L, S, I, G and other protectionAvailable dataCircuit-breaker status (open, closed)Circuit-breaker position (racked-in, racked-out)Mode (local, remote)Protection parameters setLoad control parametersEventsStatus changes in circuit-breaker, protections and

all alarms

AlarmsProtection LProtection SProtection IProtection GProtection TFault release mechanism failureUndervoltage, overvoltage and residual voltage (timing

and trip) protectionReverse power protection (timing and trip)Directional protection (timing and trip)Underfrequency/overfrequency protection (timing and trip)MaintenanceTotal number of operationsTotal number of tripsNumber of trip testsNumber of manual operationsNumber of separate trips for each protection functionContact wear (%)Record data of last tripOperating mechanismsCircuit-breaker openi/closeAlarm resetSetting of curves and protection thresholdsSynchronize system time

© ABB Group February 25, 2009 | Slide 13

Dialogue - Modbus

PR333/P characteristicsCommunication functionsProtocol Modbus RTUPhysical layer RS485Maximum baud-rate 19200 bpsMeasuring functionsPhase currentsNeutral currentGround currentVoltage (phase-phase, phase-neutral, residual)Power (active, reactive, apparent)Power factorFrequency and peak factorEnergy (active, reactive, apparent)Harmonic analisys up to the 40th harmonicSignalling functionsLED: auxiliary power supply, warning, alarmTemperatureIndication for L, S, I, G and other protectionAvailable dataCircuit-breaker status (open, closed)Circuit-breaker position (racked-in, racked-out)Mode (local, remote)Protection parameters setLoad control parametersEventsStatus changes in circuit-breaker, protections and

all alarms

AlarmsProtection LProtection SProtection IProtection GProtection TFault release mechanism failureUndervoltage, overvoltage and residual voltage (timing

and trip) protectionReverse power protection (timing and trip)Directional protection (timing and trip)Underfrequency/overfrequency protection (timing and trip)Phases rotationMaintenanceTotal number of operationsTotal number of tripsNumber of trip testsNumber of manual operationsNumber of separate trips for each protection functionContact wear (%)Record data of last tripOperating mechanismsCircuit-breaker openi/closeAlarm reset Setting of curves and protection thresholdsSynchronize system time

© ABB Group February 25, 2009 | Slide 14

Dialogue - Tmax

Tmax releases series

The evolution of supervision and control with Molded Case Circuit Breaker

The communication functions integrated with the release

PR222DS/PR222DS/PDPD

PR223DSPR223DS--EFEF

© ABB Group February 25, 2009 | Slide 15

������������� ���������� ������

��������������������.��.0�.1�.���������%���

� �2-� �� ���������������3�������

� -+�����������4�� ��������!.������������"���

� )�����������������

� �$ � ���������'�����"��&������������� �

!�

© ABB Group February 25, 2009 | Slide 16

������������� ���������� ������

��������������������.��.0�.1�.�������+ 4

� �2-� �� ���������������3�������

� -+�����������4�� ��������!.������������"���

� -0�����������4�� ��������!.����)����

� )�����������������

� �$ � ���������'�����"��&������������� �!�

© ABB Group February 25, 2009 | Slide 17

������������� ���������� ������

��������������������.��.0�.1�.�������+�%

� �2-� �� ���������������3�������

� -+�����������4�� ��������!.������������"���

� -0�����������4�� ��������!.����)����

� )�����������������

� �$ � ���������'�����"��&������������� �

!�

© ABB Group February 25, 2009 | Slide 18

Dialogue - Modbus

PR222DS/PD characteristicsCommunication functionsProtocol Modbus RTUPhysical layer RS485Maximum baud-rate 19200 bps

Measuring functionsPhase currentsNeutral currentGround current

Signalling functionsL pre-alarmL alarm LEDL alarm output contact

Available dataCircuit-breaker status (open, closed)Circuit-breaker position (racked-in, racked-out)Mode (local, remote)Protection parameters setLoad control parameters

EventsStatus changes in circuit-breaker, protections and

all alarms

AlarmsProtection LProtection SProtection IProtection GFault release mechanism failure

MaintenanceTotal number of operationsTotal number of tripsNumber of trip testsNumber of manual operationsNumber of separate trips for each protection functionRecord data of last trip

Operating mechanismsCircuit-breaker openi/closeAlarm resetCircuit-breaker resetSetting of curves and protection thresholds

© ABB Group February 25, 2009 | Slide 19

Dialogue - Modbus

PR223DS-EF/PD characteristicsCommunication functionsProtocol Modbus RTUPhysical layer RS485Maximum baud-rate 19200 bpsMeasuring functionsPhase currentsNeutral currentGround currentVoltage (phase-phase, phase-neutral, residual)Power (active, reactive, apparent)Power factorFrequency and peak factorEnergy (active, reactive, apparent)Signaling functionsL pre-alarmL alarm LEDL alarm output contactAvailable dataCircuit-breaker status (open, closed)Circuit-breaker position (racked-in, racked-out)Mode (local, remote)Protection parameters setEventsStatus changes in circuit-breaker, protections and

all alarmsEvent logger

AlarmsProtection LProtection SProtection IProtection GFault release mechanism failureEFDPMaintenanceTotal number of operationsTotal number of tripsNumber of trip testsNumber of manual operationsNumber of separate trips for each protection functionRecord data of last tripOperating mechanismsCircuit-breaker openi/closeAlarm resetCircuit-breaker resetSetting of curves and protection thresholds

BACK

© ABB Group February 25, 2009 | Slide 20

Dialogue - EP010

For all new series

the universal evolution

To be open to all the protocols

EP010EP010

© ABB Group February 25, 2009 | Slide 21

.&�45���������� �� ��� �����������6��7�

������������� ���������� ������

© ABB Group February 25, 2009 | Slide 22

������������� ���������� ������

���������������� �� �� �

� �������������4���5������!���� �

� �������45�����$4852%���� ���������� �

� �7�����45����6��7� ���������� �

© ABB Group February 25, 2009 | Slide 23

������������� ���������� ������

.��./�� ��-�

� �������������4���5������!���� �

� �������45�����$4852%���� ���������� �

� �7�����45����6��7� ���������� �

© ABB Group February 25, 2009 | Slide 24

������������� ���������� ������

.��������%���

� �������������4���5������!���� �

� �������45�����$4852%���� ���������� �

� �7�����45����6��7� ���������� �

© ABB Group February 25, 2009 | Slide 25

����������������������� ���������� ������

.������+ 4��%

� �������������4���5������!���� �

� �������45�����$4852%���� ���������� �

� �7�����45����6��7� ���������� �

© ABB Group February 25, 2009 | Slide 27

Dialogue – Bluetooth

� ABB SACE SpA is the only manufacturer on the market that can provide the wireless communication via Bluetooth for the electronic trip units.

� Two version of Bluetooth module available

- Internal module PR120/D-BT WL

- External module BT030

The Bluetooth Connection

© ABB Group February 25, 2009 | Slide 28

.&���������%��+��-� �� ������������9��''�"��&

� �&����!�������'������*:!:�.��;�.��,

� ������������'������"��&������������� ����� �� �"���&������������

������������� ���������� ������

!�