03 - air quality
Post on 01-Jun-2018
216 Views
Preview:
TRANSCRIPT
-
8/9/2019 03 - Air Quality
1/17
1
Indoor Air Quality (IAQ)
Qualidade do Ar Interior QAI
Sources of pollutants
Effect on health and limits
Pollutant emission from persons
olf and decipol units
Mass balance to pollutantsUse of recirculation with filters
RSECE‐QAI Flow rates and limits
Internal Air Quality (IAQ)
• For comfort, indoor air quality may be said to be acceptable
if not more than
– 50% of the occupants can detect any odour
– 20% experience discomfort
– 10% suffer from mucosal irritation
– 5% experience annoyance
for less than 2% of the time.
• To guarantee air quality
– Maximum concentration of certain pollutants are defined
– Minimum flow rate of fresh air are defined per occupant
Values depend on human activity and building materials
-
8/9/2019 03 - Air Quality
2/17
2
Sick Buildings
• sick building defined as a building in which a significant number (more than 20 percent) of occupants report illness perceived as being building related.
, , , , and throat irritation, dryness of mucous membranes and skin, nose bleeds, skin rash, mental fatigue, headache, cough, hoarseness, wheezing, nausea, and dizziness.
• Identification of main causes of sick buildings in 80s (why?):
Table from S. Wang – Handbook of Air Conditioning
Reference ventilation rate
• Due to oil shock crisis the reference values were
lowered leading in the 80’s to health problems
Since 1989
Untill when? w
r a t e ( m 3 / h /
p e r s o n )
How is the ventilation rate
related to energy consumption?
F r e s h a i r f l o
From José Luís Alexandre, FEUP
-
8/9/2019 03 - Air Quality
3/17
3
Sources of pollutants
• Occupants (CO2, moisture, particles, odours)
• Smoking (CO2, CO, particles, PAHs, VOC, odours)
• Building materials (furniture coatings, adhesives,
carpets, dusts, house mites) ácaros
• Equipments (printers, copiers, computers, burners
and boilers) (gas and solid emissions and odours)
, • HVAC equipment (VOC (Refrig.), dust, legionella)
• Land and water (Radon, Chlorine)
Particulate Classification
• Dusts, fumes and smokes – Mainly solid
• Mists fo s and smo s – Mainl li uid smaller
• Bioaerosols – Viruses, bacteria, fungal spores
• Acording to the size can be:
– Visible or invisible
– Macroscopic, microscopic or submicroscopic or
– .
– Nowadays classified by mean diameter: PM10; PM2.5; etc.
• Accoding to the interaction with persons:
– Inhalable (
-
8/9/2019 03 - Air Quality
4/17
4
Limits and Health Effects• Particulates – Limit of 50 μg/m3 (1 year) and 150
μg/m3 (1 day). Main problem with diameters from 1
to 10 μm retained on body.
• CO (Carbon Monoxide) – Colorless and odorless
affects O2 distribution in body (35/9 ppm @ 8/1h)
• VOC (Volatile Organic Compounds) – Irritation of
. • Radon ‐ colorless, odorless, inert radiative gas widely
found in soil, rocks, and water, created by the decay of
the radium and uranium. Fix in lung and give cancer.
Legislation for air quality
• There are several sources of information for limits of
pollutants for human occupation:
• Laboral legislation: NP 1796‐1988 Higiene e segurança no trabalho: valores limites de exposição para substâncias nocivas
existentes no ar dos locais de trabalho• World Health Organization
• HVAC regulations/Regulations
e.g. CO limits are established in ppm for short (1h)
and long (8h) exposure.
Values in ppm can be converted to mg/m3 (@25oC) by:
5.24)()/( 3 iii M
ppm X mmgC
-
8/9/2019 03 - Air Quality
5/17
5
CO/CO2 Limits (From José Luis Alexandre, FEUP)
WHO(mg/m3)
NP
(mg/m3)
ASHRAE 62‐2001
-
8/9/2019 03 - Air Quality
6/17
6
r i s o n
A E C o m p
A S H
ASHRAE Fundamentals 2009; Ch. 10
RSECE ‐ QAI
Indicado em tabela que é PM10
UFC – Unidades Formadoras
de Colónias
Pesquisa obrigatória apenas em edifícios construídos em zonas
graníticas, nomeadamente nos
distritos de Braga, Vila Real, Porto,
Guarda, Viseu e Castelo Branco
Bq ‐ Becquerel corresponde
a uma desintegração de um
núcleo por segundo
9—Em edifícios com sistemas de climatização em que haja produção de aerossóis,
nomeadamente onde haja torres de arrefecimento ou humidificadores por água líquida,
ou com sistemas de água quente para chuveiros onde a temperatura de armazenamento
seja inferior a 60oC as auditorias da QAI incluem também a pesquisa da presença de
colónias de Legionella em amostras de água recolhidas nos locais de maior risco,
nomeadamente tanques das torres de arrefecimento, depósitos de água quente e
tabuleiros de condensação, não devendo ser excedido um número superior a 100 UFC.
-
8/9/2019 03 - Air Quality
7/17
7
Emissions from occupants I
• CO2 and H2O release depend on person and activity
Tabela extraída de José Luis Alexandre, FEUP
Emissions from occupants II
ASHRAE A08: Ch. 45 – Control of Gaseous Indoor Air Contaminants
-
8/9/2019 03 - Air Quality
8/17
-
8/9/2019 03 - Air Quality
9/17
9
Mass balance to pollutant• Volumetric flows ( ) for new air (n), insuflation (i ),
infiltration from outside (o), extracted by ventilation (e)
•
V
.
• Pollutant concentration (C ) with values in the room space (s), outside environment (o) and in the insuflation (i ) inlet.
• For a room of volume V and air recirculation R:
oso C C V onC V
iiC V seC V
s
se C RV )1( se RC V
The insulation and extraction are not always similar and in that case the
infiltration is not a direct exchange with the outside ambient.
If there is no balance between all the streams the concentration in the room
may change along time (accumulation or decrease along time).
Dilution with new air
sC V
sC V G
as C C V
sC V G
oC V
• Considering a global ventilation flow rate ( ) either forced or natural the concentration in the room may be obtained as:
so C V GC V V GC C os
• Based on the person production of 19 L/h CO2 and with the limit of 1800 m m3 or 1000 m and with 400 m in the
V
environment we can define the required new air flow rate:
persson/3166710)4001000(
196 h L
X X
GV
os
Volumetric
m3
h pers.32The Oxygen requirement is lower and therefore is satisfied.CO2 limits from other sources are in general >2500 ppm !
For CO limit with 40% smokers (calculate the value) + 2 m3/h pers.
-
8/9/2019 03 - Air Quality
10/17
10
Odours• Outdoor – Automotive exhaust, waste or sewage plants .
• Indoor – tobacco, bathrooms, building materials, consumer products, humans.
• There are two important limits of concentration:
– Threshold limit value (TLV) – Value with adverse health consequences for exposure for 8h periods.
– Odor detection threshold (ODT) – Concentration detected by olfact
When the ratio between the two (TLV/ODT) is low there is higher risk.
• Other properties of odours are:
–
– Character (e.g. fishy, ,flowery). Level of unpleasant or pleasant
• The detailed characterisation of odour sources can only be done by mass spectrometry and gas chromatography but in general is not necessary and only a global relative value is used.
Pollutants quantification• The olf unit is defined as the emission of air pollutants (bio‐
effluents) generated by a standard person in thermal comfort
• The decipol is the resultant erceived oluttion level when the emission is ventilated with 10 L/s of unpolluted air.
• The percentage of dissatisfied persons is related with the
ventilation rate q
in (L/s)/olf by:
• The ventilation rate for a given value of sources and pollution
25.085.1exp395 qPPDO PPDo=100 % for q 14000 ppm (1,4%)
][
10/ DecipolC C
s LV OS
][/ olf Gs LV q
-
8/9/2019 03 - Air Quality
11/17
11
OLF Emission sources
Emission (olf)
olf emissions per occupant Aditional olf emissions
from room type
Offices 0.3 0 – 1
Class rooms 0.3 0.1 – 0.6
Auditory 0.5 0.1 – 1.3
Room with carpets 1.5 0.1 – 4
House 0.1 0 – 1
Ventilation 0.2 0 – 0.4
Outside polutant level in Decipol
Pure Air (Mountain) 0 DecipolAir in city 0.05 to 0.3 Decipol
If the volume of air per person decreases from 10
m3 to 1 m3 the emissoin in olf is almost the double.
Table and values from José Luis Alexandre, FEUP
Definition of new air flow rate• For Cs=1.4 Decipol the PPDO for IAQ is 20%.
• Based on this value of decipol and from outside 0.3: – .
– Office as before with + 20% smokers: 23 L/s pers.
– Office as before with + carpet: 36 L/s pers.
Recomended values from W.P. Jones – Air Conditioning Engineering
-
8/9/2019 03 - Air Quality
12/17
12
ASHRAE 62‐2001
Exigências de
caudais de ar
novo (RSECE)
RPH
nexo
Legislação anterior (98) exprimia valores em renovações por hora (2ª coluna) e duplicava valores na presença de fumadores.
Nova legislação exige valores superiores a 60 m3/h ocupante com extracção directa para exterior e pressão na zona de fumo inferior à restante Art 29 RSECE.
-
8/9/2019 03 - Air Quality
13/17
13
Pollutant Removal• The removal of most pollutants is made by air renewal.
• The removal or articulates includin bioaerosols ma
also be achieved by filtering recirculated air.
• Microorganisms can also be removed by UV radiation
or using biocides or antimicrobials.
• VOCs and non‐organic gases (CO2, CO, etc) can also
be adsorbed in activated carbon or otassium
permanganate‐impregnated alumina and VOCs can be
converted in a catalytic surface using UV radiation.
Mass Balance to Pollutant
Scheme from ASHRAE
• The use of local
filters or collection
of pollutants is just
deduced from the
generation term.
Figura de ASHRAE HVAC Applications 07: Ch 45
-
8/9/2019 03 - Air Quality
14/17
14
ASHRAE 62‐2001
• Air renewal may start some
• This norm includes the possibility of treating transient cases.
.
• After utilization air renewal
should also operate to lower
pollutants.
• For transient situations:
V
t V
V
o
V Initialss
eV GC
eC C
1
,
Mass Balance with Recirculation
iC V
sC
V
se C RV )1(
G
mC V
• The new air and extraction can be expressed as a fraction of the
insuflation flow rate and the recirculation ratio R as indicated.
•
seC V on
se RC V
o
C RV 1 s RC V
m
so
som RC C R
V
RC V C RV C
1
1
naasV
GC
RV
GC C
1
Without filters C i =C m
The balance is the same as considering only the new air supply
-
8/9/2019 03 - Air Quality
15/17
15
Mass balance with filters
• Filters can be installed in the recirculation line or in
the insuflation line after the mixture.
• Considering the efficiencies of these filters as εr ; εm:
• Or expressing the total flow:
r mmo
s R
V G RC C
111
11
• The new air flow rate is
RC RC V
mar ms 11111
RV V n 1
Impingement panel filters
• Made of coarse highly porous fibers coated with a viscous substance to stick particles. Thickness from 13 to 100 mm and section up to 610x610 mm. Design at velocity from 1 to 4 m/s low De taP up to 125 Pa in operation , Low cost goo e iciency use before higher efficiency filters.
• Renewable‐media filters are panels where the medium is replaced
from a roll and they may be viscous or dry panel.• Dry extended‐surface filters (mangas) are supported by a wire
frame forming pocket. Media velocities range from 0.03 to 0.5 m/s, although approach velocities run to 4 m/s. Depth indirection of a r ow var es rom o mm. ommerc a es gns yp ca y have an initial resistance from 25 to 250 Pa. It is customary to replace the media when the final resistance of 125 Pa is reached for low‐resistance units and 500 Pa for the highest‐resistance units.
-
8/9/2019 03 - Air Quality
16/17
16
Electrostatic filters• Electret filters are composed of electrostatically charged fibers.
The electrical charges are loaded during the filter production. The
chages on the fibers augment collection of smaller particles by
interception and diffusion (Brownian motion) with Coulomb forces
caused by the charges. There are three types of these filters: resin
wool, electret, and an electrostatically sprayed polymer.
• Electronic air cleaners can be highly efficient filters using
electrostatic precipitation to remove and collect particulate
, , .
air cleaner denotes a precipitator for HVAC air filtration. The filter
consists of an ionization section and a collecting plate section.
Charges of 6 to 25 kV are given to the dust and the particles are
later collected in grounded plates.
High efficiency filters
• Very high‐efficiency dry filters, HEPA (high‐efficiency particulate air) filters, and ULPA (ultralow‐penetration air) i ters exten e ‐sur ace con gurat on o eep space o s
of submicrometre glass fiber paper. These filters operate at duct velocities near 1.3 m/s, with resistance rising from 120
to more than 500 Pa over their service life. These filters are the standard for cleanroom
• Membrane filters are used mainly for air sampling and specialized small‐scale applications where their particular
, resistance, and high cost. They are available in many pore diameters and resistances and in flatsheet and pleated forms.
-
8/9/2019 03 - Air Quality
17/17
Efficiencies for different sizes• Arrestance test – Measures the mass that
is retained in the filter but it does not
show any influence of the smaller dust.
• Dust spot – Is a test that measures the
opacity of a sample in a filter that
characterises the retention of finer
particles.
• DOP Penetration Test – For high efficiency filters is based on
the measuerement of the rate of droplets passing the filter
compared with upstream, with mean particle diamenter 0.3
μm !
Typical filter efficiencies
• Panel‐type or automatic roll (70 to 85% arrestance)
•
arrestance and 25 to 50% dust spot
• Extended surface, cartridge, bag, or electronic
(manually cleaned or replaceable media) 50 to 65% dust spot
• Use of prefilter (75 to 85% and 25 to 40%) and e ectron c ter or ot er w t to ust spot.
• Higher quality has second filter with 80 to 95% and further a high efficiency filter with DOP from 95 to 99.97% with a disposable cell.