SECONDARYCLARIFIER 2
SECONDARYCLARIFIER 3
SECONDARYCLARIFIER 1
BIOREACTORS
PRIMARY SLUDGEFERMENTERS
PRIMARY CLARIFIERS
UTILITYBUILDING ADMINISTRATION
DAFHEADWORKS
As of January 3, 2009,EarthTech became AECOM
Canada Ltd.
Certificate of Authorization
AECOM Canada Ltd.
No. 4671 Date:_____________Original dated on:
2006/04/26
LOAD BKR CCT A B C CCT BKR LOAD DESCRIPTION2 15A 1 * 2 15 Glycol Feed Tank S776-GFT2 15 3 * 4 20 Natural Gas Blower S660-GH3 15 5 * 6 20 Natural Gas Blower S665-GH3 15 7 * 8 15 Supply Fan S690-SF
15 9 * 10 15 Flow Transmitter S720-FIT15 11 * 12 15 Flow Transmitter S710-FIT15 13 * 14 15 Flow Transmitter S750-FIT15 15 * 16 - Flow Transmitter S530 FIT15 17 * 18 - Chem Scan15 19 * 20 - Chem Scan Pump15 21 * 22 - Receptacle by Chem Scan15 23 * 24 - Space15 25 * 26 - Space15 27 * 28 - Space15 29 * 30 - Space- 31 * 32 - Space- 33 * 34 - Space- 35 * 36 - Space- 37 * 38 - Space- 39 * 40 - Space- 41 * 42 - Space
Voltage:
Mains:
Location:
Mounting:
Spare to 12x12 in Mechanical Rm
PANEL SCHEDULEPanel SB
SpaceSpace
SpaceSpaceSpace
Space
Receptacles Clairifier#3SpareSpaceSpace
DESCRIPTIONReceptacles Mech RoomReceptacles Mech RoomReceptacles Clairifier#3
4/C#3 TECK
SpaceSpaceControl Pnl for S622-AHUUnit Heater S770SpaceSpace
Feeder:
Transfromer XFMR-SB
N/A
Power Source:
Main Breaker:
Surface
Secondary Clarifier Electrical Room
120/208V/3Ø/4 wire
225A
BIOREACTORS
SECONDARYCLARIFIER 3
SECONDARYCLARIFIER 2
SECONDARYCLARIFIER 1
ADMINISTRATION
PRIMARY CLARIFIERS
PRIMARY SLUDGEFERMENTERS
UTILITYBUILDING
HEADWORKS DAF
As of January 3, 2009,EarthTech became AECOM
Canada Ltd.
Certificate of Authorization
AECOM Canada Ltd.
No. 4671 Date:_____________Original dated on:
2006/04/26
BIOREACTORS
SECONDARYCLARIFIER 3
SECONDARYCLARIFIER 2
SECONDARYCLARIFIER 1
ADMINISTRATION
PRIMARY CLARIFIERS
PRIMARY SLUDGEFERMENTERS
UTILITYBUILDING
HEADWORKS DAF
As of January 3, 2009,EarthTech became AECOM
Canada Ltd.
Certificate of Authorization
AECOM Canada Ltd.
No. 4671 Date:_____________Original dated on:
2006/04/26
DAF
BIOREACTORS
SECONDARYCLARIFIER 3
SECONDARYCLARIFIER 2
SECONDARYCLARIFIER 1
ADMINISTRATION
PRIMARY CLARIFIERS
PRIMARY SLUDGEFERMENTERS
UTILITYBUILDING
HEADWORKS
As of January 3, 2009,EarthTech became AECOM
Canada Ltd.
Certificate of Authorization
AECOM Canada Ltd.
No. 4671 Date:_____________Original dated on:
2006/04/26
BIOREACTORS
SECONDARYCLARIFIER 3
SECONDARYCLARIFIER 2
SECONDARYCLARIFIER 1
ADMINISTRATION
PRIMARY CLARIFIERS
PRIMARY SLUDGEFERMENTERS
UTILITYBUILDING
HEADWORKS DAF
Certificate of Authorization
AECOM Canada Ltd.
No. 4671 Date:_____________Original dated on:
2006/04/26
As of January 3, 2009,EarthTech became AECOM
Canada Ltd.
BIOREACTORS
SECONDARYCLARIFIER 3
SECONDARYCLARIFIER 2
SECONDARYCLARIFIER 1
ADMINISTRATION
PRIMARY CLARIFIERS
PRIMARY SLUDGEFERMENTERS
UTILITYBUILDING
HEADWORKS DAF
Certificate of Authorization
AECOM Canada Ltd.
No. 4671 Date:_____________Original dated on:
2006/04/26
As of January 3, 2009,EarthTech became AECOM
Canada Ltd.
BIOREACTORS
SECONDARYCLARIFIER 3
SECONDARYCLARIFIER 2
SECONDARYCLARIFIER 1
ADMINISTRATION
PRIMARY CLARIFIERS
PRIMARY SLUDGEFERMENTERS
UTILITYBUILDING
HEADWORKS DAF
Certificate of Authorization
AECOM Canada Ltd.
No. 4671 Date:_____________Original dated on:
2006/04/26
As of January 3, 2009,EarthTech became AECOM
Canada Ltd.
BIOREACTORS
SECONDARYCLARIFIER 3
SECONDARYCLARIFIER 2
SECONDARYCLARIFIER 1
ADMINISTRATION
PRIMARY CLARIFIERS
PRIMARY SLUDGEFERMENTERS
UTILITYBUILDING
HEADWORKS DAF
------------ --------- ---------
E,-------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------1 E
...<Xl
X
"' "' " ,...: "' 0 8 I
f;) 0
0 I
/ 0 ., w /
"'
12.6kV FEEDER 12.6kV FEEDER FROM RANNOCK SUBSTATION FROM HEADINGLEY SUBSTATION
I --{]ILTI-1----i) (>----, I Jl
L__-{]IC::TI-1~) C>----, I Jl
M UTILITY MffiRING
UTILITY M METERING (_
MANITOBA HYDRO ---------------------~----------------------------------------------------------------------------------------
~.rr~-~----
~t TO EFFLUENT ~ MONITORING STATION ~ • SEE DRAWING ~~~Z001
~R~Um1 ______________________ _
I I I
I I I I I I I
I I I I
I I
49
63
I
GANG OPERATED SWITCH
GANG OPERATED FUSED SWITCH
0 lit
1- SMU-20 1- 80E
XFMR-U701 l J. J. PADMOUNT TRANSFORMER
2500/3300kVA fY [Yl12.6kV:600/347V
3~. 4W, 6.5%Z
-t---- --1 ¢>-----6-0-0/-1-2-0V------ ~O~~g~~~~~v;~~Oc;s~CM, 1-1/0 AWG NEUTRAL, AND 1-1/0 AWG
I [0]----j r GND IN EACH, ALL RW90 XPLE I .__ : ~>--..., 5 DUCTS SPARE I ~ 2-50mm PVC DUCTS: 1 1 DUCT WITH 4-1 0 AWG RW90 XLPE TO CONTROL PANEL FROM 30A, 1 ~ 3¢ BREAKER IN PANEL UA TO FEED TRANSFORMER COOLING FANS 1 27 1 DUCT WITH 4-14 AWG FROM TRANSFORMER TEMPERATURE SENSOR
47 AND SUDDEN PRESSURE RELAY CONTACTS. L ___ _ -------, I r-- __ ___j
27 47
L __
CB-U701 52-A
4000AF )- TRIP-~ --~ [[}-- ---------------------r--------------------
( ~ 5QL?1 C~ 51G
~~
cr OMS
I TVSS I
1 I I I I I I I
[J I TVSS I
49
63
I
GANG OPERATED FUSED SWITCH
0 lit
1- SMU-20 ;-- 80E
XFMR-U702 l J. J. PADMOUNT TRANSFORMER
2500/3300kVA ( Y Y 12.6kV:600/347V
3~. 4W, 6.5%Z
-·- ---1-- -·-·- ·- - -·-·- -I 10-100mm PVC DUCTS:
CilY OF WINNIPEG
600/120V I 5 DUCTS WITH 3-500 MCM, 1-1/0 AWG NEUTRAL, AND 1-1/0 AWG ) (L--01-{]DJ--1 GND IN EACH, ALL RW90 XPLE
l I I 5 DUCTS SPARE ) l I 2-50mm PVC DUCTS:
I 1 DUCT WITH 4-1 0 AWG RW90 XLPE TO CONTROL PANEL FROM 30A, 1 ~ ~ 3¢ BREAKER IN PANEL UA TO FEED TRANSFORMER COOLING FANS I 1 DUCT WITH 4-14 AWG FROM TRANSFORMER TEMPERATURE SENSOR I AND SUDDEN PRESSURE RELAY CONTACTS.
I
= --j :I~ _TRIP __ 'J ~t~702 Y J 4000AF
5QL?1 1------K! 51G J
OMS )
r;'\ ( - 4000:5 (1-
4000:5 -h CD ,------.--------.-------.-------~-~---------r---~---r--<~ ~~ :<; I I
~ ~~-~ I 0~----~»~)--,,-----~---------,----------------~.--------------------,---------------r-----------------r-------------,
-SGR-U702l I I I I I I I I I I I I I I I I I I I I I
--
I 1~ ) CB-U703 \..:.) 1 600AF I
I
I ~~ L_
5Q81 51G
) CB-U730 2000AF
(- 50..1?1 (_ 51G
~
) CB-U710 800AF
5QL?1 51G
) 800AF
5QL?1 51G
) 800AF
(>t---t 5QL? 1 ( 51G
¢>-- 1350A, 600V, BUS DUCT
¢>--1600A, 600V, ¢>--- 2 SETS OF 3-1C, ¢>--- 3-1C, 250 MCM, ¢>--- 3-1 C, 500 MCM, TECK90
PFC-U703 AUTOMATIC POWER
FACTOR CORRECTION 450 KVAR DETUNED
1x50 KVAR 4x100 KVAR
FEEDER BUS DUCT 3 AWG, TECK90 TECK90
1Mcc:..u730 - - l j (WAS MCC-8)
I I
I I L _____ j
(LOCATED IN UTILITY BUILDING)
I MCC:_U710- - l j (WAS MCC-1U) I
I I I I L _____ j
(LOCATED IN UTILITY BUILDING}
TO MCC-1SB LOCATED IN BIOREACTOR
TO MCC-1S LOCATED IN SECONDARY CLARIFIERS
) 800AF
5QL?1 51G
¢>--- 3-1 C, 500 MCM, TECK90
TO MCC-1H LOCATED IN HEADWORKS
BUILDING
5QL?1 51G
) 800AF [[]-----------[EJ
5QL?1 51G
) 800AF
(>1----1 5QL? 1 ( 51G
) CB-U740 2000AF
(>1----1 5QL? 1 ( 51G
) 800AF
5QL?1 51G
¢>--- 4-500 MCM, RW90, IN 100mm CONDUIT
¢>--- 4-500 MCM, RW90, IN 1 OOmm CONDUIT
c:p--- 1600A, 600V, FEEDER BUS DUCT
¢--- 3-1 C, 500 MCM, TECK90
r+------1h ATS TRANSFER SWITCH 400A, 3¢
L--+----'
4-500 MCM, -----<1~ RW90, IN 1 OOmm
CONDUIT
fMcc..:.u74o - I I (WAS MCC-A) I
I I I I L ____ _j
(LOCATED IN UTILITY BUILDING)
TO MCC-2H LOCATED IN HEADWORKS
BUILDING
REVISION 02 CHANGES THE ENGINEER'S DESIGN RESPONSIBILITIES ARE LIMITED TO THE CHANGES INDICATED
IN THE CLOUDED WORK
DESIGNED BY: J. A. BOUCHARD CHECKED BY: 1)t::t./
) 800AF
(>1----1 5QL? 1 ( 51G
) 800AF
(- 5QL?1 (_ 51G
~~
) CB-U720 800AF
( 1- 5QL?1 lr- 51 G
'~ -·-· !-·-·-·-
) CB-U704 1600AF
c 5QL?1 (_ 51G
~
I
I I I I I I
_j
¢--- 3-1 C, 500 MCM, TECK90
c:p-- 3-1C, 250 MCM, TECK90
c:p-- 2 SETS OF 3-1 C, c >--- 1350A, 600V, BUS 3 AWG, TECK90 DUCT
TO MCC-2S LOCATED IN SECONDARY CLARIFIERS
TO MCC-2SB LOCATED IN BIOREACTOR
CONSTRUCTION NOTES
I Mcc:..uno - - l I (WAS MCC-2U) I
I I I I L _____ J
(LOCATED IN UTILITY BUILDING)
I PFC-U704
AUTOMATIC POWER FACTOR CORRECTION
450 KVAR DETUNED
1x50 KVAR 4x100 KVAR
TO CDP-2UAA LOCATED IN UTILITY
BUILDING
ORA WN BY: S. GUSE APPROVED BY:l".A. 6oGKHMO
r.'l RE-USE EXISTING CT. CT IS NOT EASILY ACCESSIBLE WITHIN SWITCHGEAR. MANUFACTURER AND ~ MODEL NUMBER ARE NOT KNOWN. DETERMINE RATIO VIA METERING.
DATE: 2016/08/31 RELEASED FOR CONSlR. DATE: G) CHANGE PROTECTION RELAY SETTINGS AS SHOWN ON DRAWING 1-0103V-E0028.
"'~------------~------------------------------------------~ 9- ENGINEER'S SEAL
'" E'f a.,-... 00 "'~ ··o "'t I~ ~--' o"' --.....~ 0>0 o"' --.....--' <D2l
NOTES: 1. THIS DRAWING IS BASED ON 1-01 03A-E0003-002. ACTUAL CONFIGURATION MAY NOT BE EXACTLY AS SHOWN.
DESIGNED BY: 1-+-------------+----+-+--1 T. CHURCH
DRAWN BY:
S. FUNK
CHECKED BY:
C. REIMER APPROVED BY:
C. REIMER
~ 0
~ -~ 02 ISSUED FOR CONSTRUCTION ~
lj;! !?.- 01 AS-BUILT. BID OP. 419-2013
SCALE: RELEASED FOR CONSTRUCTim
j..::::---t-:::::::::=~::....::~:.::::~----------+2=0.:.:16'!..:/0:_:;9/-.::.0.:.2iCIY1f~<~~15~)t»J~;;rr.---N-T_S ____ -jBY: M. PAETKAU 2014/06/06 - TMC DATE: 2013/01/08 DAlE: 2013/06/26
;;) a.. 1-0103V-E0028 SGR-U701 AND SGR-U702 PROTECTION SETTINGS 00 ISSUED FOR TENDER (BID OP. 419 2013) 2013/06/26 TMC CJR CONSULTANT NO.: DATE DESIGN CHECK
ORIGINAL DRAWING SEALED BY:
T. M. CHURCH SNC-LAVALIN
MEMBER # 32682 2013/06/26
REV. 00
~ THE CITY OF WINNIPEG Wmni¢g WATER AND WASTE DEPARlMS'IT
WEST END WATER POLLUTION CONTROL CENTRE POWER FACTOR CORREC]ON
SINGLE LINE DIAGRAM SWITCHGEAR SGR-U701 AND SGR-U702
CllY DRAWING NUMBER SHEET REV. SIZE
1-01 03V-E0027 001 02 ~ ~ DRAWING NUMBER REFERENCE DRAWINGS NO. REVISIONS ~a..L-~~~~~~-L----------------~~~~~~--------------~--------------------------------------------------------------------------------------~~--------------------------~----~--~--~------------------------~~--------------~--------------------~~~~~~~--~ 1-01 03V E0027.dwg