    Air cooled water chillers

    Air cooled motocondensing unit

    ALZ HA 011.1 033.2

    ALP HA 011.1 033.2

    Cooling capacity from 38,5 to 104,9 kW

    50Hz Refrigerant: HFC 407C

    Scroll Compressors

    305 B 00/09 B

    Date:September 2000

    Supersedes:none

    Product Manual

  • 8/10/2019 ALZ HA .PDF

    2/16

    305 B 00/09 B page 2

    New McQuay Air cooled chillers and motocondensing unit ALZ/ALP HA

    McQuay International introduces their newest air cooled chillers ALZ HA equipped with scroll compressors andelectronic control system. McQuay have once again succeded in developing a high quality product withextraordinary performance which is able to satisfy HVAC applications.

    McQuay units are completely factory assembled, piped, wired and charged with refrigerant and shipped ready for

    the installation.Each unit consists of scroll compressors, condenser coils with independent subcooler circuits, multiple propellertype direct drive condenser fans with independent fan motors, heavy-gauge weatherproof casing and weatherproofelectrical control centre containing all necessary and operating controls and motor starting equipment.

    ALZ / ALP HA units are high thermodynamic engineering products, studied with high accuracy in balancingcompressors, condensers and evaporators in order to offer high performances and wide safety margins. Thechoose of the materials and the equipments adopted for the products has been made without any compromises,taking care of quality and long life purposes. The products meet ISO 9001 requirements, an assurance, beyondany doubts, of the high producing standards followed by McQuay.

    Code requirementsAll units are designed and manufactured in accordance with applicable selections of the following which areequivalent to American Air-conditioning industry applicable codes:

    Rating of chillers: UNI 9018.

    Construction of pressure vessel: TUV Standards (optional).

    Electrical codes: IEC 204-1 CEI 44-5 Elect. & Safety Codes.

    Safety Codes: CEI-EN 602041 Codes.

    Manufacturing Quality Stds: ISO 9001.

    Highly flexible designThe ALZ / ALP HA units are available in sizes covering a range from 38,5 to 104,9 kW nominal cooling capacity.Availability of many accessories, and the applications of high tech control and safety devices, give to theseproducts high flexibility for their installation in commercial, residential and industrial environments.

    RefrigerantAs the HCFC phase out will occur more quickly than currently legislated, the designers, owners and operatorsshould only evaluate equipment using chlorine free refrigerants. ALZ / ALP HA units are supplied with ecologicalrefrigerant HFC 407C. Studied and used by McQuay for several years, it offers the same garancies ofperformance, costs and reliability of refrigerant HCFC 22.

    Low installation costsThe complete assembly of the units and fuction testing at the factory reduces the cost of installation on site. A rigidsteel base distributes the weight of the unit to the support points and allows simple installation by an easy accessto the lifting points. The units are designed with a single point 400/3/50 + NEUTRAL. The ALZ HA units can alsoinclude a pumping set consisting of one or more water circulation pumps and buffer tank.

    Low maintenence costsThe microprocessor safety and control system allows the trouble shooting of any type of functional anomaly,enabling simpler, safer and timely intervention by the unit maintenance personnel. The oil heater on eachcompressor and a complete set of controls and safety devices protect the unit from abnormal operating conditions.The design of the ALZ HA unit, with two independent refrigerant circuits, increases the redudancy of the unit andallows maintenance while the other circuit is still running.

    Factory testingEach unit is pressure tested, vacuum tested, evacuated and charged with refrigerant requested. It is then tested atthe factorys test bench under the design conditions specified by the customer. Upon request, a second series oftests can be carried out witnessed by the customer. Before shipment, each unit is re-checked for pressure andrefrigerant charge control.

  • 8/10/2019 ALZ HA .PDF

    3/16

    305 B 00/09 A pag. 3

    General characteristics

    Cabinet and structureThe cabinet is made of galvanized steel sheet and painted to provide a high resistance to corrosion. The unit baseframe has holes to lift the unit with ropes for an easy installation. The weight is uniformly distributed along theprofiles of the base and this facilitates the arrangement of the units bases and the support structures. Theelectrical and control equipment is located inside a panel which can be accessed by key locked doors completewith door interlocking on the power cabinet.

    The unit cabinet can be sound insulated (as an option) in order to reduce the noise of the compressors.

    Scroll compressors

    The scroll compressors achieve a high volumetric efficiency, due to constant contact with the sides of the scroll

    spirals and the total absence of discharge and suction valves. This compressor is not only extremely reliable

    thanks to the reduced number of moving parts, but has an exceptionally low noise level because of the absence of

    suction and discharge valves and hence of the reduced pulsations of the discharge gas. The reduction in moving

    parts means a very low level of vibration. Each compressor is equipped with a check valve on the discharge to

    mantain the pump-down condition and hence avoid the migration of the refrigerating gas from the condenser to the

    evaporator.

    Evaporator (only ALZ HA units)The evaporator is a compact, efficient, dual circuit plate to plate type heat exchanger consisting of stainless steel

    brazed plates.

    The evaporator is wrapped with closed cell heat insulation and equipped with an heater for protection against

    freezing down to 29C.

    Condenser coils

    ALZ HA condenser coils are constructed with internally enhanced seamless copper tubes arranged in a staggered

    row pattern and mechanically expanded into McQuay lanced and rippled aluminium condenser fins with full fin

    collars.

    Condenser coil fansThe condenser fans are of the axial helical type with wing-profile blades to achieve a better performance. The

    direct coupling with the electrical motor eliminates any problems as regards the application of transmission devices

    and reduces the vibrations caused by the functioning. The motors are supplied as standard with IP54 protection

    and are of the mono-phase external rotor type; they are protected against overload and short circuits by circuit

    breakers located inside the electrical control panel.

    Electrical control panel and control devices

    The electrical components for both the power and the control are split into two sections on the main panel. The

    panel is manufactured to ensure protection in all weather conditions (IP 54). The power panel is fitted with a door

    interlocked mains isolator to prevent access. The electrical control panel complies with IEC204-1 safety norms.

    The power section includes: compressors contactors and fuses, fans contactors and fuses. Additional space isprovided for the installation of the various optional accessories provided to enhance the capabilities of the ALZ HA

    units.

    The control section includes the microprocessor regulator of the water temperature (ALZ HA) which carries out the

    following functions:

    - access password to prevent unauthorised access

    - water temperature control

    - regulation of temperature set points

    - start-up sequence delay device

    - compressor on-off control

    - fan on-off control

    - antifreeze control

    - antifreeze heater functioning

    - general alarm

  • 8/10/2019 ALZ HA .PDF

    4/16

    305 B 00/09 B page 4

    - differential pressure switch or pump failure alarm (opt.)

    The multifunctional microprocessor control device has contacts for remote on/off control and remote signal of

    general failure.

    On request, remote programming radio-control and remote PC board are available as option.

    Refrigerant circuitThe ALZ HA units are equipped with a complete refrigerant charge. The ALP HA units are equipped only by a

    holding charge to keep the circuit in pression and to avoid moisture infiltration.The ALZ HA circuits consist of insulated copper pipes on the suction line and is complete with suction shut-off

    valves, filter driers, moisture indicators, liquid sight glass, thermostatic expansion valves and drain valves.

    ALP HA motocondensing units are not equipped by liquid and suction lines. Customer will have to provide:

    antivibration isolators, filter driers, solenoid valves, moisture indicators, thermostatic expansion valves.

    Accessories and Options

    100% total heat recovery (R)(only for ALZ HA units) - Produced with plate heat exchangers to produce hot water

    up to +50C. The heat exchangers are mounted on the refrigerant circuits parallel to the condenser coils to remove

    all the heat rejection.Desuperheaters (D) (only for ALZ HA units) - Produced with plate heat exchangers installed between the

    compressor discharge and the condenser coil. These allow hot water to be produced up to a maximum

    temperature of +55C.

    Compressor thermal overload relays Safety devices against compressor motor overload.

    Fans thermal overload relays Safety devices against fans motor overload.

    Condenser power factor correction- Installed on the electrical control panel to ensure the conformance to the

    local rules.

    Condenser coil guards- Metal protection guards fixed on all the external surface of the condenser coils.

    Cu-Cu condensing coils -To give better protection against corrosion by aggressive environments.

    Alucoat condensing coils- Fins are protected by a special epoxy paint with a high resistance to corrosion.

    Suction line shut off valve Standard.Discharge line shut off valve Standard.

    Inertial tank (factory unit mounted)- Cooled water buffer tank to give to the hydraulic plant inertia and reduce

    excessive compressor starts and stops. The tank, supplied with one or two pumps has a 180 l capacity. The tank

    is complete with: automatic filling module, manual vent valve, drain tap and 150 W antifreeze heater. The tank is

    heat insulated with 20-mm thick PU and wrapped with PVC.

    Water circulation pump (factory unit mounted) - Pump unit, assembled and wired, consists of a water

    circulation pump (max. working pressure 6 bar) complete with safety valve and 8 litre expansion tank. The pump

    motor is protected by a circuit breaker.

    Two water circulation pumps (factory unit mounted) - Pump unit, assembled and wired, consisting of two

    water circulation pumps (max. working pressure 6 bars) complete with shut off valve, check valves, safety valve

    and 8 litre expansion tank. The pump motors are protected by circuit breakers and controlled by a two-position

    switch.

    NOTE: one and two pumps options always include inertial tank.

    Microprocessor program remote infrared-control Infrared-control to remote program data.

    Wooden box packing- Self-supporting wooden box internally insulated and suitable for shipment by sea.

    Open Cage packing - Protection with polythene and wooden cage for transport and protection before the

    installation.

    Rubber type antivibration mounts - Supplied separately, these will be positioned under the base of the unit

    during installation. Ideal to reduce the vibrations when the unit is floor mounted.

    Spring type antivibration mounts - Supplied separately, these will be positioned under the base of the unit

    during installation. Ideal for dampening vibrations for installation on roofs and metallic structures.

    Low noise version For this version internal side of the steel cabinet is covered by soundproof material to allow

    compressor sound insulation.

  • 8/10/2019 ALZ HA .PDF

    5/16

    305 B 00/09 A pag. 5

    Table 1 - Operating limitsEntering evaporatorwater temperature

    Leaving evap. watertemp.(without glycol)

    Evaporator water t Ambient temperatureALZ

    Min (C) Max (C) Min (C) Max (C) Min (C) Max (C) Min (C) Max (C)

    011.1 8 20 4 10 4 8 15 50

    013.1 8 20 4 10 4 8 15 49

    017.1 8 20 4 10 4 8 14 49

    020.1 8 20 4 10 4 8 12 48

    022.2 8 20 4 10 4 8 15 50025.2 8 20 4 10 4 8 13 48

    029.2 8 15 4 10 4 8 12 47

    033.2 8 15 4 10 4 8 10 47

    Table 2 - Altitude correction factorElevation above sea level (m) 0 300 600 900 1200 1500 1800

    Barometric pressure (mbar) 1013 977 942 908 875 843 812

    Cooling capacity correction factor 1,000 0,991 0,981 0,972 0,962 0,953 0,943

    Table 3 - Ethylene glycol and low ambient temperature correction factors

    Air ambient temperature C -3 -8 -15 -23 -35% of ethylene glycol correction factor 10 20 30 40 50

    Cooling capacity correction factor 0,986 0,980 0,973 0,966 0,960

    Flow rate correction factor 1,023 1,054 1,092 1,140 1,200

    Water pressure drops correction factor 1,061 1,114 1,190 1,244 1,310

    Table 4 - Low temperature operation performance factorsEthylene glycol/water leaving temperature C 2 0 -2 -6 -8

    Cooling capacity correction factor 0,942 0.783 0,725 0,615 0,562

    Power input compressors correction factor 0,950 0,934 0,918 0,870 0,845

    Min % of ethylene glycol 10 20 20 30 30

    Max air ambient temperature C 40 40 38 34 32

    Table 5 - Fouling factor

    Fouling factorm

    2C / kW

    Cooling capacitycorrection factor

    0,044 1,000

    0,132 0,986

    0,308 0,939

    Water content in cooling circuits

    The cooled water distribution circuits should have a minimum water content to avoid excessive compressors startand stop.

    In fact, each time the compressor starts up, an excessive quantity of oil goes from the compressors sump and

    simultaneously there is a rise in the temperature of the compressor motors stator due to the inrush current during

    the start-up. To prevent damage to the compressors, McQuay has envisaged the application of a device to limit

    frequent stops and restarts.

    During the span of one hour there will be no more than 6 starts of the compressor. The plant side should therefore

    ensure that the overall water content allows a more constant functioning of the unit and consequently greater

    environmental comfort. The minimum installation water content envisaged should be calculated with a certain

    approximation using this formula:

    (1) Q =25

    Pxp

  • 8/10/2019 ALZ HA .PDF

    6/16

    305 B 00/09 B page 6

    where:

    Q = minimum content of the plant expressed in litres.

    P = cooling capacity of the plant expressed in W

    p = minimum unloading capacity percentage

    For a more accurate determination of the quantity of water, it is advisable to contact the designer of the plant.

    When the sum of the water content of the evaporator, the pipes of the hydraulic circuit and the terminals (coils,

    exchangers, etc.) is lower than the value obtained, it would be better to opt for a ALZ/ALP HA McQuay cooling unit

    equipped with inertial tank (optional).

    Installation notes

    Handling

    All moving and handling may damage the unit if some conditions are not scrupulously observed. The units should

    be lifted with a crane using long ropes anchored to the holes on the frame of the units base and by using the

    upper spacer bars to prevent the ropes from damaging the condenser coils.

    LocationThe ALZ/ALP HA units are produced for outside installation on roofs, floors or below ground level on condition that

    the area is free from obstacles for the passage of the condensation air. The unit should be positioned on solid

    foundations and perfectly level; in the case of installation on roofs or floors, it may be advisable to arrange the use

    of suitable weight distribution beams. When the units are installed on the ground, a concrete base at least 250 mm

    wider and longer than the units footprint should be laid. Furthermore, this base should be sufficiently robust to

    withstand the unit weight mentioned in the technical data table. When the units are positioned in areas which are

    easily accessible by persons or animals, it is advisable to fit guards (option) to protect the condenser and the

    compressors.

  • 8/10/2019 ALZ HA .PDF

    7/16

    305 B 00/09 A pag. 7

    Space requirements

    The ALZ/ALP HA units are air-cooled, hence it is important to observe the minimum distances which guarantee the

    best ventilation of the condenser coils. Limitations of space reducing the air flow could cause significant reductions

    in cooling capacity, and increase in electricity consumption. The fans do not allow the use of ducts which have

    high flow resistance, hence is should be ensured that the output air cannot recycle itself inside the condenser

    coils. The units should be positioned such that there is sufficient distance between the coils and any obstacles to

    improve ventilation and also to facilitate inspection (fig.1).

    When two or more units are positioned side by side it is recommended that the condenser coils are at least 2500

    mm distance from one another (fig. 2). Smaller distances could cause the recirculation of hot air. If the units are

    positioned in places surrounded by walls or obstacles of the same height as the units, the units should be at least

    2000 mm from said obstacles (fig. 3). In the event the obstacles are higher than the units, the units should be at

    least 2500 mm from the obstacle (fig. 4). For other installation solutions, consult McQuay technicians.

    Acoustic protection

    The low noise levels of the ALZ/ALP HA units means that they meet most of the most restrictive regulations. When

    the noise level must meet special requirements it will be necessary to pay the maximum attention to ensure the

    perfect insulation of the unit from the support base by applying appropriate vibration-dampening devices, applying

    vibration-dampening mounts on the water pipes and on the electrical connections (by the customer).

    Nomenclature

    ALZ HA 025 . 2 407

    ALZ Air cooled chillerALP Air cooled motocondensing unit

    High ambient temperature

    011033 Unit size

    12 N of tandem scroll

    407 Refrigerant HFC 407C

  • 8/10/2019 ALZ HA .PDF

    8/16

    305 B 00/09 B page 8

    Physical data HFC 407C units

    ALZ HA unit size 011.1 013.1 017.1 020.1

    Cooling capacity (1) kW 38,5 43,8 54,3 65,2

    Power input (1) kW 17,2 20,8 26,3 31,8

    Cooling cap. in heat rec. condition (2) kW 46,6 54,5 65,6 82,4

    Heating capacity (2) kW 57,7 68,1 83,5 104,1

    Power input heat recovery cond. (2) kW 12,5 15,1 20,0 24,1Desuperheaters heating capacity (3) kW 11,0 12,8 15,7 17,1

    Desuperheaters pressure drops (3) kPa 14 18 15 20

    Scroll compressorsNo. of compressors / No of circuits 1 Tandem / 1 1 Tandem / 1 1 Tandem / 1 1 Tandem / 1

    Oil charge l 6,5 6,5 10,4 13,2

    No. of reduction steps 2 2 2 2

    Refrigerant charge kg 5,5 6 7 8,5

    Plate heat exchangersWater volume l 2,6 2,9 3,6 4,4

    Max. water pressure bar 30 30 30 30

    Condenser fans

    No. of fans / Diameter mm 2 / 630 2 / 630 2 / 630 2 / 630

    Motor power / rotation regime Kw / rpm 1,9 / 1360 1,9 / 1360 1,9 / 1360 1,9 / 1360Dimensions and weightsUnit length mm 2780 2780 2780 2780

    Unit width mm 1200 1200 1200 1200

    Unit height mm 1400 1400 1400 1400

    Standard unit shipping weight kg 400 520 530 560

    Unit with two pumps and tank weight kg 662 676 740 804

    ALZ HA unit size 022.2 025.2 029.2 033.2

    Cooling capacity (1) kW 76,1 85,9 98,8 105,9

    Power input (1) kW 35,2 42,9 47,9 54,9

    Cooling cap. in heat rec. condition (2) kW 91,6 106,5 125,1 134,9

    Heating capacity (2) kW 115,7 135,2 157,2 171,5

    Power input heat recovery cond. (2) kW 26,9 32,1 36,5 41,7

    Desuperheaters heating capacity (3) kW 21,4 24,4 28,1 30,0

    Desuperheaters pressure drops (3) kPa 18 20 19 24

    Scroll compressorsNo. of compressors / No of circuits 2 Tandem / 2 2 Tandem / 2 2 Tandem / 2 2 Tandem / 2

    Oil charge l 6,5+6,5 6,5+6,5 6,5+10,4 10,4+10,4

    No. of reduction steps 2 2 2 2

    Refrigerant charge kg 11 13 16 18

    Plate heat exchangeWater volume l 5,2 5,8 6,8 7,6

    Max. water pressure bar 30 30 30 30

    Condenser fans

    No. of fans / Diameter mm 3 / 630 3 / 630 3 / 630 3 / 630

    Motor power / rotation regime Kw / rpm 1,9 / 1360 1,9 / 1360 1,9 / 1360 1,9 / 1360

    Dimensions and weights

    Unit length mm 3530 3530 3530 3530

    Unit width mm 1200 1200 1200 1200

    Unit height mm 1400 1400 1400 1400

    Standard unit shipping weight kg 630 750 760 940

    Unit with two pumps and tank weight kg 834 958 992 1040

    Notes: (1) Nominal cooling capacity and power input are based on: 12/7 C entering/leaving evaporator water temperature;46C ambient temperature;

    (2) Nominal cooling capacity, power input and heating capacity are based on : 12/7 C entering/leaving evaporator

    water temperature; 45C leaving HR water temperature.(3) Desuperheaters heating capacity and pressure drops are based on: 12/7C entering/leaving evaporator water

    temperature; 40/45C entering/leaving desuperheater water temperature; 46C ambient temperature.

  • 8/10/2019 ALZ HA .PDF

    9/16

    305 B 00/09 A pag. 9

    Electrical data

    ALZ / ALP HA Unit size 011.1 013.1 017.1 020.1 022.2 025.2 029.2 033.2

    Standard voltage (1) 400 V - 3f 50 Hz + NEUTRAL

    Max tandem 1 absorbed current A 37,0 42,4 52,0 64,0 37,0 42,4 52,0 52,0

    Max tandem 1 absorbed current A - - - - 37,0 42,4 42,4 52,0

    Max total compressors abs. current A 37,0 42,4 52,0 64,0 74,0 84,8 94,4 104,0

    Max fans absorbed current A 6,8 6,8 6,8 6,8 10,2 10,2 10,2 10,2

    Max unit absorbed current A 43,8 49,2 58,8 70,8 84,2 95,0 104,6 114,2Max inrush current (2) A 134,5 148,2 185,0 224,0 171,5 190,6 227,4 237,0

    Note: (1) Allowed voltage tolerance 10%.Note: (2)1 Tandem units: absorbed current of compressor n1 at full load + inrush current of the second compressor.

    2 tandem units: absorbed current of Tandem n1 at full load + full load of compressor n1 (of the second Tandem) + inrushcurrent of the last compressor.

    Sound pressure level ALZ / ALP HA

    Sound pressure level at 1 m from the unit in free field ( rif. 2 x 10-5 )Unit size

    ALZ / ALP HA 63 Hz 125 Hz 250 Hz 500 Hz 1000 Hz 2000 Hz 4000 Hz 8000 Hz dBA

    011.1 75,0 75,0 72,0 71,5 71,0 65,5 58,0 50,5 74,5013.1 75,0 75,0 72,0 71,5 71,0 65,5 58,0 50,5 74,5

    017.1 75,0 75,0 72,0 71,5 71,0 65,5 58,0 50,5 74,5

    020.1 75,0 75,0 72,0 71,5 71,0 65,5 58,0 50,5 74,5

    022.2 77,0 76,5 73,5 73,0 72,5 67,0 59,5 52,0 76,0

    025.2 77,0 76,5 73,5 73,0 72,5 67,0 59,5 52,0 76,0

    029.2 77,0 76,5 73,5 73,0 72,5 67,0 59,5 52,0 76,0

    033.2 77,0 76,5 73,5 73,0 72,5 67,0 59,5 52,0 76,0

    Note:Average sound pressure level rated in accordance to ISO 3744, free field conditions.

    Sound pressure level ALZ / ALP HA with soundproof cabinet

    Sound pressure level at 1 m from the unit in free field ( rif. 2 x 10-5 )Unit size

    ALZ / ALP HA 63 Hz 125 Hz 250 Hz 500 Hz 1000 Hz 2000 Hz 4000 Hz 8000 Hz dBA011.1 72,5 72,5 69,5 69,0 68,5 63,0 55,5 48,0 72,0

    013.1 72,5 72,5 69,5 69,0 68,5 63,0 55,5 48,0 72,0

    017.1 72,5 72,5 69,5 69,0 68,5 63,0 55,5 48,0 72,0

    020.1 72,5 72,5 69,5 69,0 68,5 63,0 55,5 48,0 72,0

    022.2 74,5 74,0 71,0 70,5 70,0 64,5 57,0 49,5 73,5025.2 74,5 74,0 71,0 70,5 70,0 64,5 57,0 49,5 73,5

    029.2 74,5 74,0 71,0 70,5 70,0 64,5 57,0 49,5 73,5

    033.2 74,5 74,0 71,0 70,5 70,0 64,5 57,0 49,5 73,5

    Note:Average sound pressure level rated in accordance to ISO 3744, free field conditions.

    Table 6 Sound pressure level correction factor for different distances

    ALZ /ALP HA 011.1 020.1

    Distance (mt) 1 5 10 15 20 25

    dBA 0 -9 -14,1 -17,3 -19,7 -21,5

    ALZ /ALP HA 022.2 033.2

    Distance (mt) 1 5 10 15 20 25dBA 0 -8,7 -13,8 -16,9 -19,3 -21,1

  • 8/10/2019 ALZ HA .PDF

    10/16

    305 B 00/09 B page 10

    Standard ratings ALZ HA HFC 407C

    AMBIENT TEMPERATURE - C

    30 35 40 43 46ALZ HA

    unitsizeHFC407C E

    vaporator

    leaving

    temp.

    (C)

    Coolingcapacity

    (kW)

    Powerinput

    (kW)

    Coolingcapacity

    (kW)

    Powerinput

    (kW)

    Coolingcapacity

    (kW)

    Powerinput

    (kW)

    Coolingcapacity

    (kW)

    Powerinput

    (kW)

    Coolingcapacity

    (kW)

    Powerinput

    (kW)

    4 41,7 12,1 40,2 13,2 38,0 14,8 36,6 15,8 35,1 16,95 43,0 12,2 41,5 13,3 39,2 14,9 37,8 15,9 36,3 17,06 44,3 12,3 42,8 13,4 40,5 15,0 38,9 16,0 37,4 17,17 45,7 12,5 44,1 13,5 41,7 15,0 40,1 16,1 38,5 17,28 47,0 12,6 45,4 13,6 43,0 15,1 41,4 16,2 39,7 17,39 48,4 12,5 46,7 13,6 44,2 15,2 42,6 16,3 40,9 17,4

    011.1

    10 49,8 12,6 48,1 13,7 45,5 15,3 43,9 16,4 42,2 17,5

    4 47,8 14,6 46,0 15,9 43,3 17,9 41,6 19,2 39,9 20,45 49,2 14,7 47,4 16,0 44,7 18,0 42,9 19,3 41,2 20,66 50,7 14,9 48,8 16,2 46,0 18,1 44,2 19,4 42,5 20,77 52,2 15,0 50,3 16,3 47,4 18,2 45,5 19,5 43,8 20,88 53,8 15,1 51,8 16,4 48,8 18,3 46,9 19,6 45,2 20,99 55,1 15,2 53,2 16,5 50,3 18,5 48,3 19,8 46,5 21,1

    013.1

    10 56,9 15,3 54,8 16,6 51,7 18,6 49,7 19,9 47,8 21,2

    4 59,6 18,6 57,3 20,2 53,9 22,6 51,7 24,2 49,6 25,85 61,3 18,7 59,0 20,3 55,6 22,7 53,3 24,4 51,1 26,06 63,1 18,9 60,8 20,5 57,3 22,9 55,0 24,5 52,7 26,17 65,0 19,1 62,6 20,7 59,0 23,1 56,6 24,7 54,3 26,38 66,9 19,1 64,4 20,8 60,7 23,3 58,3 24,9 56,0 26,59 68,8 19,3 66,3 21,0 62,5 23,5 60,0 25,1 57,6 26,7

    017.1

    10 70,7 19,6 68,1 21,2 64,2 23,6 61,7 25,3 59,3 26,9

    4 71,2 22,7 68,5 24,6 64,5 27,5 61,9 29,4 59,5 31,05 73,3 23,0 70,6 24,9 66,5 27,7 63,8 29,6 61,4 31,36 75,5 23,2 72,7 25,1 68,5 27,9 65,7 29,8 63,3 31,57 77,7 23,4 74,8 25,3 70,5 28,2 67,7 30,1 65,2 31,88 80,0 23,6 77,0 25,5 72,5 28,4 69,6 30,3 67,1 32,09 82,1 23,8 79,1 25,7 74,6 28,6 71,7 30,6 69,1 32,3

    020.1

    10 84,4 23,9 81,3 25,9 76,7 28,9 73,7 30,9 71,0 32,6

    4 83,0 25,1 79,9 27,2 75,3 30,4 72,4 32,6 69,3 34,8

    5 85,5 25,3 82,4 27,4 77,7 30,6 74,6 32,8 71,5 35,06 88,1 25,5 84,9 27,6 80,1 30,8 77,0 33,0 73,8 35,27 90,8 25,7 87,5 27,8 82,6 31,0 79,4 33,2 76,1 35,58 93,5 25,9 90,1 28,0 85,0 31,2 81,8 33,4 78,4 35,79 96,1 26,0 92,7 28,2 87,6 31,5 84,2 33,7 80,8 35,9

    022.2

    10 98,9 26,2 95,4 28,4 90,1 31,7 86,7 33,9 83,2 36,1

    4 94,2 30,2 90,5 32,9 85,0 36,9 81,5 39,6 78,4 42,05 96,9 30,5 93,2 33,2 87,7 37,2 84,1 39,9 80,9 42,36 99,8 30,7 96,0 33,4 90,3 37,5 86,6 40,2 83,4 42,67 102,7 31,0 98,8 33,7 93,0 37,7 89,2 40,5 85,9 42,98 105,7 31,3 101,7 34,0 95,7 38,0 91,9 40,7 88,5 43,19 108,7 31,5 104,6 34,2 98,5 38,3 94,5 41,0 91,1 43,4

    025.2

    10 111,6 31,8 107,5 34,5 101,3 38,6 97,2 41,3 93,6 43,7

    4 108,0 34,2 103,8 37,1 97,5 41,5 93,4 44,5 90,1 46,9

    5 111,3 34,5 107,0 37,4 100,6 41,8 96,3 44,8 92,9 47,26 114,7 34,8 110,3 37,7 103,7 42,1 99,3 45,2 95,8 47,67 118,1 35,0 113,6 38,0 106,8 42,5 102,4 45,5 98,8 47,98 121,6 35,3 116,9 38,3 109,9 42,8 105,4 45,9 101,8 48,39 125,1 35,6 120,3 38,6 113,1 43,1 108,5 46,2 104,7 48,6

    029.2

    10 128,6 35,8 123,7 38,9 116,4 43,5 111,6 46,6 107,7 49,0

    4 116,8 39,1 112,1 42,4 105,1 47,4 100,5 50,8 96,8 53,55 120,3 39,3 115,5 42,7 108,3 47,8 103,6 51,2 99,7 53,96 123,8 39,7 118,9 43,1 111,5 48,2 106,7 51,6 102,8 54,47 127,3 40,1 122,3 43,5 114,8 48,6 109,9 52,1 105,9 54,98 130,9 40,4 125,8 43,9 118,1 49,1 113,1 52,5 109,0 55,39 134,7 40,8 129,4 44,3 121,5 49,5 116,3 53,0 112,2 55,8

    033.2

    10 138,4 41,2 133,0 44,7 124,9 49,9 119,6 53,4 115,3 56,3

    Notes: (1) Rating based on: evaporator fouling factor of 0,044 m2C/ kW, evaporator temperature drop of 5C and sea level altitude.

    (2) Interpolation is allowed, extrapolation is not permitted. Please contact McQuay for performance outside the standard ratings.(3) The power input values are referred to compressor only.(4) To know the units functioning maximum air ambient temperature consult the operating limits table.

  • 8/10/2019 ALZ HA .PDF

    11/16

    305 B 00/09 A pag. 11

    Total heat recovery ratings ALZ HA HFC 407C

    LEAVING HEAT RECOVERY CONDENSER WATER TEMPERATURE

    40 45 50ALZ HA

    unitsizeHFC407C E

    vaporator

    leaving

    temp.

    (C)

    Coolingcapacity

    (kW)

    Powerinput

    (kW)

    Heatingcapacity

    (kW)

    Coolingcapacity

    (kW)

    Powerinput

    (kW)

    Heatingcapacity

    (kW)

    Coolingcapacity

    (kW)

    Powerinput

    (kW)

    Heatingcapacity

    (kW)

    4 46,8 12,3 57,7 44,0 12,3 55,0 41,1 13,1 52,9

    5 48,2 12,3 59,2 45,3 12,4 56,4 42,4 13,1 54,3

    6 49,8 12,3 60,6 46,3 12,6 57,4 43,7 13,1 55,4

    7 52,4 12,2 63,1 46,6 12,5 57,7 44,9 13,0 56,6

    8 54,2 12,3 64,9 47,7 12,6 58,9 47,3 13,0 58,9

    9 56,5 12,3 67,2 48,9 12,8 60,3 48,8 13,1 60,5

    011.1

    10 58,3 12,2 68,5 52,4 12,8 63,3 50,0 13,1 61,3

    4 54,5 14,6 67,2 49,9 14,8 63,0 47,1 16,0 61,55 56,2 14,6 69,0 51,5 14,9 64,9 49,0 16,1 63,66 57,4 14,5 70,4 53,0 15,1 66,6 52,9 16,1 67,57 59,1 14,6 72,1 54,5 15,1 68,1 53,1 16,3 67,88 60,8 14,6 73,3 56,2 15,1 69,2 54,6 16,2 68,89 64,4 14,6 76,9 59,0 15,3 72,3 54,8 16,3 69,1

    013.1

    10 66,0 14,6 78,7 60,5 15,3 74,0 56,2 16,5 70,9

    4 65,2 18,4 81,5 60,0 19,6 77,6 57,1 20,6 75,85 67,3 18,4 83,7 62,0 19,7 79,7 59,0 20,8 77,8

    6 69,5 18,5 85,7 63,7 19,8 81,4 60,7 20,9 79,5

    7 71,3 18,6 87,6 65,6 20,0 83,5 62,5 21,0 81,4

    8 73,3 18,8 89,8 68,7 20,2 86,7 64,2 21,1 83,1

    9 75,7 19,0 92,2 70,9 20,3 88,8 67,6 21,2 86,4

    017.1

    10 77,6 19,0 96,3 72,7 20,3 92,7 69,3 21,3 90,2

    4 77,7 22,2 97,5 76,1 23,5 97,2 71,7 24,7 94,1

    5 80,2 22,3 100,0 78,5 23,7 99,7 76,2 24,9 98,7

    6 82,5 22,3 102,5 80,7 23,8 102,2 78,5 25,1 101,3

    7 85,0 22,6 105,1 82,4 24,1 104,1 77,3 25,9 100,9

    8 87,4 22,5 106,7 84,8 24,0 105,6 79,5 25,0 101,4

    9 89,8 22,6 109,4 87,1 24,2 108,3 81,8 25,3 104,1

    020.1

    10 92,3 22,6 112,1 89,5 24,2 110,9 85,6 24,9 107,8

    4 90,1 25,0 112,3 83,8 26,4 107,4 78,9 27,7 104,05 93,0 25,2 115,2 86,4 26,6 110,1 81,4 28,0 106,6

    6 95,6 25,4 117,9 88,8 26,8 112,7 83,7 28,2 109,0

    7 96,0 25,5 118,7 91,6 26,9 115,7 86,3 28,3 111,9

    8 98,6 25,7 120,9 96,4 27,1 120,2 90,9 28,2 115,9

    9 99,0 25,7 121,9 95,1 27,4 119,7 89,9 28,5 115,7

    022.2

    10 101,6 25,8 124,1 97,6 27,6 121,9 92,3 28,7 117,9

    4 100,2 32,2 129,1 96,2 31,6 124,6 89,0 33,3 119,25 103,4 32,2 132,3 100,5 31,9 129,1 93,0 33,5 123,46 106,4 32,5 135,4 103,4 32,1 132,2 95,7 33,5 126,07 109,5 32,4 138,6 106,5 32,1 135,2 99,6 33,7 130,18 113,8 32,5 142,3 108,1 32,3 136,6 99,1 33,7 129,39 115,9 32,6 145,2 110,1 32,2 139,1 101,1 33,9 131,9

    025.2

    10 117,2 32,5 145,9 111,3 32,5 140,2 104,2 33,9 134,6

    4 121,6 34,6 152,3 113,3 36,0 145,5 106,9 37,9 141,2

    5 125,4 34,7 156,2 116,7 36,2 149,1 112,4 38,1 146,7

    6 126,1 35,1 158,8 120,4 36,1 154,2 116,0 38,5 152,2

    7 129,4 35,4 160,3 125,1 36,5 157,2 119,3 38,5 153,4

    8 129,9 36,0 162,5 126,0 36,7 159,5 120,1 38,7 155,7

    9 133,6 36,3 164,4 129,6 36,6 160,8 120,2 38,6 153,6

    029.2

    10 147,5 36,7 178,6 137,4 36,7 168,8 128,4 39,0 162,4

    4 131,6 39,5 166,8 122,5 41,3 159,7 115,7 43,4 155,2

    5 135,4 39,8 170,9 126,1 41,5 163,4 119,2 43,7 158,8

    6 136,0 40,1 173,8 129,9 41,5 169,1 125,1 44,0 166,9

    7 139,9 40,7 175,3 134,9 41,7 171,5 128,9 44,1 167,9

    8 146,5 41,0 184,3 138,8 41,9 177,6 132,4 44,4 173,8

    9 154,6 41,6 190,0 144,1 41,7 179,9 135,0 44,4 173,7

    033.2

    10 159,0 42,0 194,5 148,2 42,1 184,2 138,7 44,8 177,5

  • 8/10/2019 ALZ HA .PDF

    12/16

    305 B 00/09 B page 12

    Standard ratings motocondensing units ALP HA HFC 407C

    AMBIENT TEMPERATURE - C

    30 35 40 43 46

    UnitSizeALPHA

    HFC407C E

    vaporation

    temperature

    C Coolingcapacity

    (kW)

    Power

    input

    (kW)

    Cooling

    capacity

    (kW)

    Power

    input

    (kW)

    Cooling

    capacity

    (kW)

    Power

    input

    (kW)

    Cooling

    capacity

    (kW)

    Power

    input

    (kW)

    Cooling

    capacity

    (kW)

    Power

    input

    (kW)

    0 42,3 13,3 39,4 13,7 37,6 14,1 36,3 14,4 35,1 14,8

    2 45,0 13,7 41,9 14,2 39,9 14,5 38,6 14,9 37,3 15,3

    4 47,8 14,2 44,5 14,6 42,4 15,0 41,0 15,4 39,7 15,8

    6 50,8 14,7 47,4 15,2 45,3 15,6 43,9 16,0 42,5 16,4

    8 53,9 15,1 50,4 15,6 48,4 16,0 47,2 16,4 46,0 16,8

    011.1

    10 56,8 15,5 53,2 16,1 51,1 16,5 49,9 16,9 48,7 17,3

    0 47,9 15,9 44,7 16,5 42,9 16,9 41,7 17,3 43,0 17,8

    2 50,9 16,4 47,6 17,0 45,6 17,5 44,4 17,9 45,7 18,4

    4 54,1 17,0 50,5 17,6 48,5 18,0 47,2 18,5 48,6 19,0

    6 57,5 17,5 53,7 18,2 51,5 18,6 50,1 19,1 50,2 19,6

    8 61,1 18,1 57,1 18,8 54,8 19,2 53,3 19,7 51,9 20,2

    013.1

    10 64,4 18,8 60,4 19,5 58,0 20,0 56,5 20,5 55,0 21,0

    0 60,0 20,3 55,9 20,9 53,2 21,5 51,4 22,0 49,7 22,6

    2 63,8 20,9 59,4 21,6 56,5 22,2 54,7 22,7 52,8 23,34 67,8 21,6 63,1 22,3 60,1 22,9 58,1 23,5 56,2 24,1

    6 72,0 22,3 67,2 23,1 64,2 23,7 62,3 24,3 60,4 24,9

    8 76,1 23,0 71,2 23,9 68,2 24,5 66,4 25,2 64,6 25,8

    017.1

    10 80,3 23,8 75,2 24,7 72,4 25,3 70,7 25,9 69,0 26,6

    0 71,3 24,9 66,4 25,7 63,2 26,4 61,1 27,0 59,0 27,7

    2 76,3 25,7 71,0 26,5 67,6 27,2 65,3 27,9 63,1 28,6

    4 81,0 26,5 75,4 27,4 71,8 28,1 69,4 28,8 67,1 29,5

    6 86,1 27,4 80,4 28,3 76,8 29,1 74,4 29,8 72,2 30,6

    8 91,2 28,2 85,2 29,3 81,7 30,0 79,5 30,8 77,4 31,6

    020.1

    10 96,3 29,2 90,3 30,3 86,8 31,1 84,7 31,9 82,6 32,7

    0 83,1 27,3 77,4 28,5 72,9 29,2 69,7 30,0 66,7 30,7

    2 88,9 28,2 82,8 29,4 78,0 30,2 74,5 30,9 71,3 31,74 94,5 29,1 88,0 30,4 82,9 31,2 79,2 32,0 75,7 32,8

    6 100,0 30,2 93,3 31,5 88,0 32,3 84,2 33,1 80,6 34,0

    8 105,5 31,1 98,7 32,7 92,9 33,5 88,7 34,3 84,6 35,2

    022.2

    10 111,3 32,2 104,1 33,8 98,1 34,6 93,8 35,5 89,7 36,4

    0 93,9 33,1 87,4 34,6 82,3 35,5 78,8 36,4 75,4 37,3

    2 100,4 34,2 93,4 35,7 88,0 36,6 84,2 37,6 80,6 38,5

    4 106,7 35,3 99,3 36,9 93,6 37,8 89,5 38,8 85,6 39,8

    6 112,9 36,7 105,4 38,4 99,3 39,4 95,0 40,4 90,8 41,4

    8 119,5 37,8 111,7 39,6 105,2 40,6 100,6 41,6 96,1 42,7

    025.2

    10 126,0 39,1 118,0 41,0 111,1 42,0 106,1 43,1 101,4 44,2

    0 108,2 37,4 100,7 39,2 94,9 40,2 90,8 41,2 86,9 42,2

    2 115,6 38,6 107,7 40,4 101,5 41,5 97,1 42,5 92,9 43,6

    4 122,9 39,9 114,4 41,8 107,9 42,8 103,2 43,9 98,7 45,0

    6 130,5 41,2 121,8 43,2 114,8 44,2 109,8 45,4 105,1 46,5

    8 136,5 42,2 129,0 43,9 121,2 45,0 115,5 46,1 110,2 47,3

    029.2

    10 143,3 43,0 136,7 44,6 127,3 45,7 120,3 46,9 113,8 48,1

    0 116,8 43,0 108,7 44,9 102,5 46,1 98,1 47,2 93,9 48,4

    2 124,8 44,4 116,2 46,4 109,6 47,6 104,9 48,8 100,4 50,0

    4 132,7 45,8 123,5 47,9 116,5 49,1 111,5 50,4 106,7 51,7

    6 140,6 47,3 131,2 49,5 123,7 50,8 118,4 52,0 113,3 53,4

    8 149,1 48,6 138,9 50,4 131,5 51,7 126,3 53,0 121,4 54,4

    033.2

    10 156,5 50,1 146,9 51,3 136,3 52,6 128,3 53,9 120,9 55,2

  • 8/10/2019 ALZ HA .PDF

    13/16

    305 B 00/09 A pag. 13

    Evaporator Pressure drops

    ALZ HA 011.1 - 020.1 HFC 407C

    011.1 013.1 017.1 020.1

    Flow rate(l/s)

    Pressuredrop (kPa)

    Flow rate(l/s)

    Pressuredrop (kPa)

    Flow rate(l/s)

    Pressuredrop (kPa)

    Flow rate(l/s)

    Pressuredrop (kPa)

    1,02 10 1,18 10 1,44 10 1,71 10

    1,31 15 1,45 15 1,61 14 2,02 14

    1,72 28 1,75 21 2,03 20 2,42 20

    2,02 36 2,12 30 2,51 31 3,10 34

    2,51 52 2,71 47 3,23 50 3,83 49

    2,94 74 3,20 72 4,00 78 4,50 70

    3,24 100 3,74 100 4,56 100 5,42 100

    ALZ HA 022.2 - 033.2 HFC 407C

    022.2 025.2 029.2 033.2

    Flow rate(l/s)

    Pressuredrop (kPa)

    Flow rate(l/s)

    Pressuredrop (kPa)

    Flow rate(l/s)

    Pressuredrop (kPa)

    Flow rate(l/s)

    Pressuredrop (kPa)

    2,13 10 2,38 10 2,94 10 2,94 10

    2,62 15 2,81 14 3,42 14 3,41 14

    3,21 2 3,23 18 4,13 19 4,12 193,83 32 4,11 30 5,09 29 5,02 29

    5,06 54 5,12 45 6,23 44 6,21 44

    6,02 78 6,42 72 7,65 68 7,62 68

    6,72 100 7,51 100 9,28 100 9,28 100

  • 8/10/2019 ALZ HA .PDF

    14/16

    305 B 00/09 B page 14

    Water pump diagrams

    Type A water pump

    Standard voltage 400/3/50 Motor power 0,75 kW Absorbed current 2,3 A IP 55

    Type B water pump

    Standard voltage 400/3/50 Motor power 1,5 kW Absorbed current 4,3 A IP 55

    N.B. In order to get the net hydraulic lift, subtract the evaporator pressure drop from diagram value.When you order the unit with the water pump and tank, you must specify the selected type: A or B.

    100

    110

    120

    130

    140

    150

    160

    170

    180

    190

    200

    0,50 1,00 1,50 2,00 2,50 3,00 3,50 4,00 4,50

    Water flow (l/s)

    Hydrauliclift(kPa)

    60

    70

    80

    90

    100

    110

    120

    130

    140

    150

    160

    170

    180

    190

    3,00 4,00 5,00 6,00 7,00 8,00 9,00 10,00

    Water flow (l/s)

    Hydrau

    liclift(kPa)

  • 8/10/2019 ALZ HA .PDF

    15/16

    305 B 00/09 A pag. 15

    ALZ/ALP HA Unit dimensions

    Fans Arrangement

    ALZ /ALP HA 011.1 020.1 ALZ /ALP HA 022.2 033.2

  • 8/10/2019 ALZ HA .PDF

    16/16

    We reserve the right to make changes in design and construction at any time without notice, thus the cover picture is not binding.

    McQuay Italia S P A