aluminium cables paper
TRANSCRIPT
-
7/24/2019 Aluminium Cables Paper
1/6
Aluminium conductors and cables are extensively used by utilities throughout the world for both medium
and low voltage applications, whereas building and industrial cabling has been predominantly being
carried out with copper conductors. The recent (5 years) meteoric rises in copper prices have forced
manufacturers and engineers in all sphere of industry and construction work to look at alternative
materials.
This paper investigates the use of aluminium conductor for industrial and building cabling, as on an
average there is a potential of saving of around 50% of power cabling costs in a project.
1.
Aluminium as an electrical conductor
The earliest applications of aluminium as an electrical conductor were:
1895 Stranded aluminium bare conductor for overhead lines in America and France
1908 Stranded steel-reinforced aluminium bare conductor (ACSR) for overhead lines
1910 Underground lead-sheathed cable with paper-insulated aluminium conductor at Boston and
Ealing
1912 Aluminium bus-bars in a ship named AQUITANA
1917 Aluminium transformer coils
1920 Aluminium squirrel-cage rotor for induction motors
2. Properties comparison with copper
The table below shows the comparative physical properties of E-Cu copper, E-Al aluminium, and AlMgSi
aluminium alloy (used in some OH conductors and cables)
Properties UnitE-Cu
Copper
E-Al
Aluminium
AIMgSi Al
Alloy
Density kg/dm3 8.9 2.7 2.7
Tensile strength (hard annealed) N/mm2 450240 18080 310
Elongation at break (hardannealed) % 135 235 3
Modulus of elasticity kN/mm2 120 70 70
Melting point C 1083 658 658
Coef. of thermal expansion 10-6/ C 16.6 23.8 23.0
Temperature coef. of resistance @ +20C 1/ C 0.0039 0.0040 0.0036
Conductivity @ +20C IACS % 97100 6162 53
Resistivity @ +20C mm2/m 0,01786 0,02857 0,03280
Table-1: Physical properties of aluminium & copper
Use of Aluminium Cables
in Buildings & Industries
Naveed Jabbar, AMIEEEP
-
7/24/2019 Aluminium Cables Paper
2/6
With 60% of the conductivity of copper, and 30% of its density, an aluminium conductor would be 60%
larger and 50% lighter than the equivalent copper conductor (which would have the same voltage drop
and I2R losses).
Use of aluminium conductors would require larger raceways (conduits, trunking, ladders), but would be
much lighter to pull and install. The weight advantage is a major reason aluminium conductor is used in
overhead transmission (lighter poles/structures) and underground distributions.
3. Price comparison with copper
-
1,000
2,000
3,000
4,000
5,000
6,000
7,000
8,000
9,000
1978
1979
1980
1981
1982
1983
1984
1985
1986
1987
1988
1989
1990
1991
1992
1993
1994
1995
1996
1997
1998
1999
2000
2001
2002
2003
2004
2005
2006
2007
2008
Ye
ar
UK
pertonne
0
0.5
1
1.5
2
2.5
3
Copper/Aluminium
Pri
ceRatioCu/Al
Cu
Al
Fig 1: Trends in LME prices of copper and aluminium
Electrical metals costs vary over time, and in recent years have shown a marked upwards trend. The graph
above shows the pattern over the past thirty years, based on London Metal Exchange prices.
4. Current-carrying capacity
The table below shows roughly equivalent
sizes of copper and aluminium cable based
on IEE Wiring Regulations current-carrying
capacity tables.
In each case, the aluminium cable size is
about 60% greater than the corresponding
copper cable size.
It will be noticed that the voltage drop / amp
/ m is approximately equal for equivalent
sizes, and, consequently, the I2R losses are
the same.
Table-2: Comparative electrical
characteristics of copper & aluminium
cables
Current
capacity
Copper
conductor
Aluminium
conductor
Amperes Size
(mm2)
Volt drop
(mV/A/m)
Size
(mm2)
Volt drop
(mV/A/m)
64 16 2.4 25 2.5
80 25 1.5 35 1.8
100 35 1.1 50 1.35
120 50 0.81 70 0.92
150 70 0.57 95 0.68
190 95 0.43 150 0.44
220 120 0.35 185 0.37
250 150 0.29 240 0.3
300 185 0.25 300 0.25
350 240 0.21 400 0.24
400 300 0.185 500 0.22
-
7/24/2019 Aluminium Cables Paper
3/6
5. Cost advantageCurrent
capacity
Copper
conductor
Aluminium
conductor
Saving
AmperesSize
(mm2)
Rate
(Rs./m)
Size
(mm2)
Rate
(Rs./m)(Rs./m)
64 16 532 25 160 372
80 25 771 35 189 582
100 35 1056 50 253
Based on Table-2 above, a
comparative is given in the table
below of approximate current prices
of equivalent copper and aluminium
cables.
803
120 50 1427 70 373 1054
150 70 2045 95 472 1573
190 95 2831 150 713 2118
220
Aluminium conductor cable costs60% less; if the cost of the larger
raceway and special terminations is
included, the price saving is still
around 50%.
120 3561 185 884 2677
250 150 4376 240 1145 3231
300 185 5479 300 1485 3994
350 240 7188 400 1810 5378
400 300 9013 500 2220 6793
In a typical office building the cost of
power cabling is around 8% to 10% of
the cost of the electrical works. By
carefully substituting aluminium
conductors in place of copper about
50% of the power cabling costs (4%
to 5% of the total electrical costs) canbe saved. In industrial projects,
depending upon their nature, this
saving can be much higher.
Table-3: Comparative prices of equivalent copper& aluminium cables
6. Additional factors
Changing over from copper to aluminium, despite the price and weight advantages, can only be done
when the following factors have been taken into account:
a)
Connectivity Issues
Three phenomena are encountered: Oxidation in the presence of moistureAll metals when exposed to air (oxygen) in the presence of moisture form metal oxides with varying
degree of severity and characteristics. Aluminium oxide is a bad conductor as compared to copper oxide.
Hence if not correctly made, any electrical connection between aluminium or other metal degrades.
Various sealant formations have been developed to provide improved electrical and mechanical
performance. These when applied immediately after scratch brushing seals the exposed surface to prevent
re-oxidation thus excluding future ingress of air and moisture.
Galvanic corrosion of dissimilar materials
Galvanic action results in corrosion when two dissimilar
materials are in contact with each other. In most situations, it is
necessary to connect aluminium conductors to copper terminalsas the majority of equipment (circuit breakers, fuse holders,
switches) has copper terminals. When using aluminium
conductors with such equipment, special bimetallic accessories
(ferrules and lugs) must be used to avoid the connection
corroding. In a (aluminium/copper) bi-metallic lug, the barrel is
aluminium into which an aluminium conductor is crimped, and
the head (or palm) is of copper. The contact between cable to bi-
metallic terminal lug is aluminium, and the contact between bi-
metallic lug to copper equipment terminal is copper. The bi-metallic lug manufacturers generally supply
these lugs filled with anti-oxidation sealant compounds.
Al
Cu
Fig-2: Bi-metallic lug
-
7/24/2019 Aluminium Cables Paper
4/6
In addition the lug crimping tools (dies) must be compatible with the lug. When crimping aluminium
ferrules or lugs, deep indent crimping is preferable in order to break the aluminium oxide layer which will
have formed on the conductor.
Looseness of contact with thermal cycling
Aluminium has a high coefficient of expansion, and with cyclic loading, a connection between two
terminals can become loose, resulting in a higher resistance connection. This is generally overcome using
appropriate spring cone washers.
Solutions to the above issues have been detailed in Annexure-1. However, point wiring is not done with
aluminium cable because terminals on switches, accessories, luminaries, etc are generally copper.
b)
Brittleness
Aluminium is more susceptible to vibration cracking than copper, especially when solid aluminium
conductors are used. Consequently, aluminium cables should not be used for final connections to motors,
transformer, generators or other equipment subject to movement.
7. Conclusion
Many utilities in world use aluminium conductor cables for MV and LV distribution, and as service drops
from overhead lines 11kV and 400/230V systems, including to meters.
Ex-WAPDA DISCOS and uses aluminium conductor cables for all of their LV cable requirements i.e.
from overhead conductor to meter, from transformer to meter, breaker, etc. The problems reported are all
at overhead joints. No appreciable complaints have been observed at connections to meter or other
locations.
Today, KESC is working on converting copper OH low-voltage distribution lines in Karachi to
aluminium bundled conductors, and expects to finance 50 - 60% of the cost from the sale of the old
copper.
Aluminium, instead of copper is also used in other areas of electrical equipment. Some examples are bus-
bar trunking, dry-type transformers, and squirrel-cage rotors.
References:
4. Electric Power Systems in Commercial Buildings, IEEE, USA.
5. Tyco Connectors & Fittings
6. Connector Theory & Application FCI Brundy Products
(Engr Roland deSouza is Principal Electrical Engineer, and Engr Naveed Jabbar is General Manager
[Electrical] with Fahim, Nanji & deSouza, a multi-disciplinary firm in the field of building services. This
paper was presented at the '23rd Multi-Topic International Symposium 2008'of the IEEEP, Karachi
Centre.)
-
7/24/2019 Aluminium Cables Paper
5/6
Annexure-1
Connectors for Aluminium
Aluminium conductors are different from copper in several ways, and these property differences should be considered in
specifying and using connectors for Aluminium conductors. The normal oxide coating on Aluminium has a relatively high
electrical resistance. Aluminium has a coefficient of thermal expansion that is greater than copper. The ultimate, the yield
strength properties, and the resistance to creep of Aluminium are different from the corresponding properties of copper.
Corrosion is possible under some conditions because Aluminium is anodic to other commonly used metals, including
copper, when electrolytes from even humid air are present.
1) Mechanical Properties and Resistance to Creep Creep has been defined as the continued deformation of material
under stress. The effect of excessive creep resulting from the use of an inadequate connector that applies excessive
stress could be the relaxation of contact pressure within the connector, and a resulting deterioration and failure of the
electrical connection. In mechanical connectors for Aluminium, as for copper, proper design can limit residual unit
bearing loads to reasonable values, with a resulting minimum plastic deformation and creep subsequent to that
initially experienced upon installation. Connectors for Aluminium wire can accommodate a range of conductor sizes,
provided that the design takes into account the residual pressure on both minimum and maximum conductors.
2) Oxide Film The surface oxide film on aluminium, though very thin and quite brittle, has a high electrical resistance
and, therefore, should be removed or penetrated to ensure a satisfactory electric joint. This film can be removed by
abrading with a wire brush, steel wool, emery cloth, or similar abrasive tool or material. A plated surface, whether on
the connector or bus, should never be abraded; it can be cleaned with a solvent or other means that will not remove
the plating. Some aluminium fittings are factory filled with a connection aid compound, usually containing particles
that aid in obtaining low contact resistance. These compounds act to seal connections against oxidation and corrosion
by preventing air and moisture from reaching contact surfaces. Connection to the inner strands of a conductor requires
deformation of these strands in the presence of the sealing compound to prevent the formation of an oxide film.
3) Thermal Expansion The linear coefficient of thermal expansion of aluminium is greater than that of copper and is
important in the design of connectors for aluminium conductors. Unless provided for in the connector, the use of
metals with coefficients of expansion that are less than that of aluminium can result in high stresses in the aluminium
during heat cycles, causing additional plastic deformation and significant creep. Stresses can be significant, not only
because of the differences in coefficients of expansion, but also because the connector may operate at an appreciably
lower temperature than the conductor. The condition will be aggravated by the use of bolts that are of a dissimilar
metal or have different thermal expansion characteristics from those of the terminal.
4) Corrosion Direct corrosion from chemical agents affects aluminium no more severely than it does copper and, in
most cases, less. However, since aluminium is more anodic than other common conductor metals, the opportunity
exists for galvanic corrosion in the presence of moisture and a more cathodic metal. For this to occur, a wetted path
should exist between external surfaces of the two metals in contact to set up an electric cell through the electrolyte
(moisture), resulting in corrosion of the more anodic of the two, which, in this instance, is the aluminium. Galvanic
corrosion can be minimized by the proper use of a joint compound to keep moisture away from the points of contact
between dissimilar metals. The use of relatively large aluminium anodic areas and masses minimizes the effects of
galvanic corrosion. Plated aluminium connectors should be protected by taping or other sealing means.
5) Types of Connectors for Aluminium Conductors UL has listed connectors approved for use on aluminium, which
have successfully withstood UL performance tests that are contained in ANSI/UL 486B-1982, Wire Connectors for
Aluminium Conductors. Both mechanical and compression connectors are available. The most satisfactory connectorsare specifically designed for aluminium conductors to prevent any possible troubles from creep, the presence of oxide
film, and the differences of coefficients of expansion between Aluminium and other metals. These connectors are
usually satisfactory for use on copper conductors in non-corrosive locations. The connection of an aluminium
connector to a copper or aluminium pad is similar to the connection of bus bars. When both the pad and the connector
are plated and the connection is made indoors, few precautions are necessary. The contact surfaces should be clean; if
not, a solvent should be used. Abrasive cleaners are undesirable since the plating may be removed. In normal
application, steel, aluminium, or copper alloy bolts, nuts, and flat washers may be used. A light film of a joint
compound is acceptable, but not mandatory. When either of the contact surfaces is not plated, the bare surface should
be cleaned by wire brushing and then coated with a joint compound. Belleville washers are suggested for heavy-duty
applications where cold flow or creep may occur, or where bare contact surfaces are involved. Flat washers should be
used wherever Belleville washers or other load concentrating elements are employed. The flat washer should be
located between the aluminium lug, pad, or bolt and the outside edge of the Belleville washer with the neck or crown
of the Belleville against the bolting nut to obtain satisfactory operation. In outdoor or corrosive atmospheres, the
-
7/24/2019 Aluminium Cables Paper
6/6
above applies with the additional requirement that the joint be protected. A non-plated aluminium -to- aluminium
connection can be protected by the liberal use of a non-oxide compound. In an aluminium -to-copper connection, a
large aluminium volume compared to the copper is important as is the placement of the aluminium above the copper.
Again, coating with a joint compound is the minimum protection; painting with a zinc chromate primer or thoroughly
sealing with a mastic or tape is even more desirable. Plated aluminium should be completely sealed against the
elements.
6) Welded Aluminium Terminals For Aluminium cables 250 kcmil and larger, which carry large currents, excellent
terminations can be made by welding special terminals to the cable. This is best done by the inert gas shielded metal
arc method. The use of inert gas eliminates the need for any flux to be used in making the weld. The welded terminal
is shorter than a compression terminal because the barrel for holding the cable can be very short. It has the advantage
of requiring less room in junction or equipment terminal boxes. Another advantage is the reduced resistance of the
connection. Each strand of the cable is bonded to the terminal, resulting in a continuous metal path for the current
from every strand of the cable to the terminal. Welding of these terminals to the conductors may also be achieved by
using the tungsten electrode type of ac welding equipment. The tungsten arc method is slower, but, for small work,
gives somewhat better control. The tongues or pads of the welded terminals, such as the large compression
connectors, are available with bolt holes to conform to NEMA Standards for terminals to be used on equipment.
7) Procedure for Connecting Aluminium Conductors.
(i) When cutting cable, avoid nicking the strands. Nicking makes
the cable subject to easy breakage.
(ii)
Contact surfaces should be cleaned. The abrasion of contact
surfaces is helpful even with new surfaces. . Do not abrade
plated surfaces.
(iii) Apply joint compound to the conductor if the connector does
not already have it.
(iv) Only use connectors specifically tested and approved for use
on aluminium conductors.
(v) On mechanical connectors, tighten the connector with a
screwdriver or wrench to the required torque. Remove excess
compound
(vi) On compression connectors, crimp the connector using the
proper tool and die. Remove excess compound.(vii) Always use a joint compound that is compatible with the
insulation and as recommended by the manufacturer. The
oxide films penetrating or removing properties of some
compounds aids in obtaining good initial conductivity. The
corrosion inhibiting and sealing properties of some
compounds help ensure the maintenance of continued good
conductivity and the prevention of corrosion.
(viii) When making an aluminium-to-copper connection that is
exposed to moisture, place the Aluminium conductor above
the copper. This prevents soluble copper salts from reaching
the aluminium conductor, which could result in corrosion. If
there is no exposure to moisture, the relative position of the
two metals is not important.(ix) When using insulated conductors outdoors, extend the
conductor insulation or covering as close to the connector as
possible to minimize weathering of the joint. Outdoors,
whenever possible, joints should be completely protected by
tape or heat-shrink insulation. When outdoor joints are
covered or protected, the protection should completely
exclude moisture, as the retention of moisture could lead tosevere corrosion.