alternators ppt
DESCRIPTION
presentation for alternatorsTRANSCRIPT
In the name of ALLAH, the
most Beneficent, the most
Merciful
MUHAMMAD SHAHID SHAUAKAT Project Engineer
ORIENT ENERGY SYSTEMS PVT LTD LAHORE
Introduction
Alternator Construction
Excitation
Speed of rotation of a synchronous generator
Internal Generated Voltages
Equivalent Circuit of Synchronous Generator
Phasor Diagrams of Synchronous Generator in case of
load
Power in Synchronous Generator
Synchronous Generator operating alone:
Effect of load change on a synchronous generator:
With unity power factor
With lagging power factor
With leading power factor
Voltage Regulation
Parallel Operation of Alternator with Large Power
System
Parallel Operation of Alternator with another Generator
Alternators are synchronous machines used to convert
mechanical energy to ac electric power.
Alternators generate electricity using the principle, when the
magnetic field around a conductor changes, a current is
induced in the conductor.
Typically, a rotating magnet, called the rotor turns within a
stationary set of conductors wound in coils on an iron core,
called the stator. The field cuts across the conductors,
generating an induced EMF (electromotive force)
The rotor's magnetic field may be produced by induction (as
in a "brushless" alternator), by permanent magnets (as in very
small machines), or by a rotor winding energized with direct
current through slip rings and brushes.
In a synchronous generator, a dc current is applied to the rotor winding, which produces a rotor magnetic field.
The rotor of the alternator is then turned by a prime mover, producing a rotating magnetic field within the machine.
This rotating magnetic field then induces a three phase set of voltages within the stator windings of the generator.
An electric generator or electric motor that uses field coils
rather than permanent magnets requires a current to be
present in the field coils for the device to be able to work.
If the field coils are not powered, the rotor in a generator can
spin without producing any usable electrical energy, while the
rotor of a motor may not spin at all.
The process of generating a magnetic field by means of an
electric current is called excitation.
Since the rotor is rotating, there are common two approaches to
supply dc current to rotor winding.
1. Supply dc power from an external source to the rotor by
means of slip rings and brushes.
2. Supply dc power from a special dc power source mounted
directly on the shaft of alternator (brushless supply).
A brushless exciter is a small ac generator with its field circuit
mounted on the stator and its armature circuit mounted on the
rotor shaft. Then the three phase output of this generator is
rectified to supply the dc power to rotor field.
A brushless exciter circuit
Brushless exciter including a pilot exciter
In synchronous generators the electrical frequency is locked in or synchronizes with the mechanical rate of rotation of the generator.
The rate of rotation of the magnetic field in the machine is related to the stator electrical frequency as,
𝒇𝒆 =𝒏𝒎𝑷
𝟏𝟐𝟎
Where
› 𝑓𝑒= electrical frequency, in Hz
› 𝑛𝑚= mechanical speed of magnetic field in r/min
› 𝑃= number of poles
The magnitude of the internally generated stator
voltage is as follows.
𝑬𝑨 = √𝟐𝝅𝑵𝒄𝝓𝒇,
› NC= number of stator coils
This voltage depends on the flux in the machine,
the frequency or speed of rotor, and the
machine’s construction.
EA is the internally generated voltage in on phase of the
synchronous generated.
However this voltage is not usually the voltage that appears at
the terminals Vϕ of the generator.
There are number of factors that cause the difference between
EA and Vϕ.
1. The distortion of the air-gap magnetic field by the current
flowing in the stator, called “armature reaction”.
2. The self-inductance of the armature coils.
3. The resistance of the armature coils.
So, the phase voltage will be expressed as,
𝑽∅ = 𝑬𝑨 + 𝑬𝒔𝒕𝒂𝒕𝒐𝒓
Here 𝑬𝑺𝒕𝒂𝒕𝒐𝒓 is the voltage induced due to the armature
reaction, which is,
𝑬𝑺𝒕𝒂𝒕𝒐𝒓 = −𝒋𝑿𝑰𝑨
So,
𝑽∅ = 𝑬𝑨 − 𝒋𝑿𝑰𝑨
In addition to the armature reaction, the stator coils have a
self-inductance LA (and reactance XA) and the resistance RA,
then the terminal voltages are,
𝑽∅ = 𝑬𝑨 − 𝒋𝑿𝑰𝑨 − 𝒋𝑿𝑨𝑰𝑨 − 𝑹𝑨𝑰𝑨
If
XS= XA+ X= synchronous reactance
Then,
𝑽∅ = 𝑬𝑨 − 𝑹𝑨𝑰𝑨 − 𝒋𝑿𝑺𝑰𝑨
Phasor Diagram of alternator is the graphical
representation of the voltage drops occur in the
generator.
It shows the relation of Internally generated
voltage EA, terminal voltage Vϕ and the voltage
drops.
Phasor diagram of an alternator at unity power factor
IA
EA
IARA
jXSIA
VΦ
Phasor diagram of alternator at lagging power factor
IA
EA
IARA
jXSIA
VΦ
Phasor diagram of alternator at leading power factor
IA
EA
IARA
jXSIA
VΦ
For a given phase voltage and armature current, a larger
internally generated voltage EA is needed for lagging loads
than for leading loads.
Therefore a larger field current is needed with lagging loads
to get same terminal voltages, as
EA=Kϕω
And ω must be constant to keep a constant frequency.
In other words, for a given field current and magnitude of
load current, the terminal voltage is lower for lagging loads
and higher for leading loads.
In real synchronous machines, the synchronous reactance is
much larger than the winding resistance RA, so RA is often
neglected in the qualitative study of voltage variations.
Pconverted
Pout
=√ τindωm
Pin=τ
appω
m
I2R losses
Copper losses Core losses
Frictional
& windage
losses
Stray
losse
s
a b
O θ
γ
δ
EAsinδ
=XSIAcosθ θ
Vϕ
The input mechanical power is the shaft power in the generator
Pin=τappωm.
The power converted from mechanical power to electrical power is
given by,
Pconverted=τindωm =3EAIAcosγ
Where “γ” is the angle between EA and IA. The real electrical power
of the synchronous generator is
Pout = √𝟑𝐕𝐓𝐈𝐋 𝐜𝐨𝐬 𝛉=3VϕIAcosθ
and the reactive power is
Qout =√𝟑𝐕𝐓𝐈𝐋 𝐬𝐢𝐧 𝛉.
In the figure shown above the vertical segment “bc” can be
expressed as EAsinδ or XSIAcosθ. So,
𝑰𝑨 𝐜𝐨𝐬 𝜽 =𝑬𝑨𝒔𝒊𝒏𝜹
𝑿𝑺
So, the output power will be
𝑷𝒐𝒖𝒕 =𝟑𝑽∅𝑬𝑨𝒔𝒊𝒏𝜹
𝑿𝑺
The behavior of synchronous generator under load varies
greatly depending on the power factor of the load and on
whether the generator is operating alone or in parallel with
other synchronous generators.
Generator Load
An increase in the load is an increase in the real and/or reactive power drawn from the generator.
Such a load increase increases the load current drawn from the generator. Because the field resistor has not been changed, the field current is same as earlier, and therefore the flux ϕ is constant.
Since the prime mover also keeps a constant speed ω, the magnitude of the internal generated voltage EA=Kϕω is constant.
The effect of changing the load of generator in this case the behavior of generator will be changed for different power factors.
In the case of lagging power factor when more load is added
at the same power factor, then |IA| increases but remaining at
the same angle as earlier.
Therefore, the armature reaction voltage jXSIA is larger than
before but at the same angle. As,
𝑬𝑨 = 𝑽∅ + 𝒋𝑿𝑺𝑰𝑨
or
𝑽∅ = 𝑬𝑨 − 𝒋𝑿𝑰𝑨
So, Vϕ will decrease in the case of load adding with lagging
power factor.
jXSI’
A
I’A VΦ
E’A
IA
EA
jXS I
A
V’Φ
V’Φ
E’A
IA
EA
VΦ
I’A
A conventional way to compare the voltage behavior
of two generators is by their voltage regulation. The
voltage regulation of a generator is defined by the
equation,
𝑽𝑹 =𝑽𝒏𝒍 − 𝑽𝒇𝒍
𝑽𝒇𝒍 𝒙 𝟏𝟎𝟎%
Where Vnl is the no load voltage and Vfl is the full load
voltage of the generator.
A generator operating at a lagging power factor has a
large positive voltage regulation.
A generator operating at a unity power factor has a
small positive voltage regulation.
A generator operating at leading power factor often
has a negative voltage regulation.
It is desired to keep the voltage supplied to a load
constant, even though the load varies. The obvious
approach is to vary the magnitude of EA to
compromise for the change in load.
As EA=Kϕω, since the frequency should not be
changed in a normal system; EA must be controlled
by varying the flux in the machine.
The idea to regulate the terminal voltages can be
summarized as follows:
By changing the field resistance RF, field current can
be changed IF.
Change in field current IF will change the flux ϕ in
the machine.
Change in flux ϕ will change the internal generated
voltages EA.
This process will change the output voltage Vϕ as,
𝑽∅ = 𝑬𝑨 − 𝑹𝑨𝑰𝑨 − 𝒋𝑿𝑺𝑰𝑨
More than one generator operating in parallel to
supply the power demand to the load is called
parallel operation of alternators.
Several generators can supply a bigger load
than single generator.
Having many generators increases the
reliability of the power system.
Having many generators operating in parallel
allows one or more generators to be removed
in case of failure of preventive maintenance.
RMS line voltages of the generators must be
equal.
Generators must have the same phase sequence.
Phase angles of the two “a” phases must be
equal.
The frequency of the oncoming generator must
be slightly higher than the frequency of running
system.
As the power drawn from prime movers increases, the speed at which they turn decreases.
Whatever the governor mechanism is present, it will always be adjusted to provide a slight drooping characteristics with increasing load,
𝑺𝒑𝒆𝒆𝒅 𝑫𝒓𝒐𝒑 = 𝑺𝑫 =𝒏𝒏𝒍 − 𝒏𝒇𝒍
𝒏𝒇𝒍𝒙 𝟏𝟎𝟎%
nnl= no-load prime mover speed
nfl= full-load prime mover speed
Most generators prime movers have a speed drop of 2 to 4 percent.
nnl
Me
ch
an
ica
l Sp
ee
d r
/min
nfl
Pfl Power KW E
lec
tric
al Fre
qu
en
cy
Hz
ffl
Pfl Power KW
fnl
P = sp(fnl - fsys) › sp = slop of curve in kW/Hz
› fsys=operating frequency of system
fe= nmP/120
› fe=electrical frequency
› nm=mechanical speed
VTnl
Te
rmin
al V
olta
ge
s V
T
VTfl
Qfl Reactive Power kVAR
Q = sp(VTnl - VTsys) › sp = slop of curve in kVAR/V
› VTsys=operating voltage of system
For any given real power, the governor set points
control the generator’s operating frequency fc.
For any given reactive power, the field current
controls the generator’s terminal voltages VT
When an alternator is connected to a power system,
the power system is often so large that nothing the
operator of the generator does will have much of an
effect on the power system.
A large power system is the system
› Terminal voltages are constant
› Electrical frequency is constant
Ter
min
al
Vo
lta
ges
VT
VT
Reactive Power kVAR Q
Ele
ctri
cal
freq
uen
cy
fe
Active Power kW P
PG PInfinite bus
fnl
P kW
fe
Pload
If Oncoming generator’s frequency
is greater than the frequency of
running system
PG < 0 +P kW
fe
-P kW
If Oncoming generator’s frequency is
less than the frequency of running
system
For the increase in the real power sharing the
governor’s set point of the generator is increased.
For the increase in the reactive power sharing the
field current of the generator is increased.
PG1 PB1
fnl
PG kW
fe
Pload= PG+PB
PG2 PG3 PB2 PB3 PB kW
When a generator is operating in parallel with a
larger system (infinite bus):
The frequency and terminal voltages of generator are
controlled by the system to which it is connected.
The governor set point of the generator control the
real power supplied by the generator.
The field current in the generator controls the
reactive power supplied by the generator
If a generator is connected in parallel with
another generator then the basic constraint is that
the sum of real and reactive power supplied by
the generators must be equal the demand by load.
Pload= PG1+PG2+PG3
Qload= QG1+QG2+QG3
System frequency and power supplied by a single
generator is not constant.
When two generators are operating in parallel, an
increase in governor set points on anyone of them,
Increases the system frequency.
Increases the power supplied by that generator ,
while reducing the power supplied by the other
generator.
PG2 PG1
f1
kW
fe
Pload= PG1+PG2
kW
f2
Effect of change of Governor’s set point
When two generators are operating in parallel, an
increase in field current of anyone of them,
Increases the system terminal voltages.
Increases the reactive power supplied by that
generator , while reducing the reactive power
supplied by the other generator.
QG2 QG1
V1
kVAR2
VT
Qload= QG1+QG2
kVAR1
V2
Effect of change of Field Current
An increase in governor’s set point increases the system
frequency and the power supplied of that machine.
To adjust the power sharing without changing the system
frequency, increase the governor set points of one generator
and simultaneously decrease the governor set points of other
generator.
PG2 PG1 kW
fe
Pload= PG1+PG2
kW
fsys
An increase in field current increases the system voltage and
the reactive power supplied of that machine.
To adjust the power sharing without changing the system
voltages, increase the field current of one generator and
simultaneously decrease the field current of other generator.
QG2 QG1 kVAR 2
VT
Qload= QG1+QG2
kVAR
1
Vsys
In the case of two generators operating in parallel,
The system is constrained in that the total power supplied by
the two generators must be equal to the load demand.
System frequency fsys and terminal voltages VT are not
constant in this system.
To adjust the real power sharing between generators without
changing system frequency, simultaneously increase the
governor set point of one generator and decrease governor set
points of other generator.
To adjust the system frequency without changing the power
sharing simultaneously increase or decrease the governor set
points of both generators.
To adjust the reactive power sharing without changing the
system voltage simultaneously increase the field current of
one generator and decrease the field current of other
generator.
To adjust the system voltage without changing the reactive
power sharing simultaneously increase or decrease the field
current of both generators.