all-glass balustradeEN
Table of contents
Litefront - all-glass balustrades in perfection Page 3Application examples - without handrail Page 4Technology Page 6Profiles and accessories Page 8Application notes Page 10Connection / application possibilities Page 11Selection of glass panel type Page 14Detailing of bracket supports Page 17Declaration of Performance Page 27Installation Page 29Order form Page 38
all-glass balustrades in perfection
2
Litefront – all-glass balustrades in perfection
Litefront, the tried-and-trusted all-glass balustrade system, can be connected to the structure in a variety of ways thanks to its sophisticated height-adjustable design. The system provides excellent protection against falling without obstructing views.
As required by the European Construction Products Regulation, this document contains a Declaration of Performance template, and also various load-dependent glass and bracket pre-dimensioning tables, enabling design proposals to be quickly and easily developed.
Advantages:
• Unrestricted view• Extremely flexible• Quick, uncomplicated installation• Multifunctional brackets with adjustable height• Optimal integration in the structure’s thermal insulation• Drainage feature possible• Maximum safety due to linear mounting• No glass tension• Glass is easy to replace
Compliant with standards*:
• EN 1090• EN 1999-1-1• DIN 18008• Etag 001
German “General Appraisal Certificates” (allgemeine bauaufsichtliche Prüfzeugnisse, AbP) available:
• AbP No. BAY 40-003-12-3• AbP No. BAY 40-002-13-1• AbP No. BAY 40-002-15-1
* Country-specific deviations must be taken into consideration
3
www.litefront.com
3
97
280
62
LF'15_Anwendung-03 (1:4)
25
97
280
62
LF'15_Anwendung-03 (1:4)
25
25
217
54
LF'15_Anwendung-02 (1:4)
170
Outdoors, connected to top of slab (at edge)
Outdoors, connected to inside of concrete upstand
Outdoors, connected to edge of slab
Application examples - without handrail
4
www.litefront.com
25
LF'15_Anwendung-07q (1:4-quer)
62
LF'15_Anwendung-08q (1:4-quer)
62
25
25
67
LF'15_Anwendung-06++('16) (1:4)
102
Outdoors, connected to the top (at edge), water level above roof, integrated in cladding
Outdoors, connected to top of concrete slab (at edge), integrated in cladding
Outdoors, connected to top of concrete slab (not at edge), integrated in cladding
Application examples - without handrail
5
www.litefront.com
25
168
9
100 60
Litefront_Konsole+_STATIK++++DE'16 (1:2)
25mm
Gla
sein
span
nung
150
mm
13
10
Glas-Toleranzen:
Glas d=
21mm
max.
21
Trockenverglasung:
168
100
9
100 60
LF'15_00_NASS (1:2)
13
10
min. 10
10
!
16
ArialArial
Arial
Technology - wet glazing (with silicone seals)
The tried-and-trusted wet glazing solution can be supplied with the top surface of the glass panels exposed, or covered by a customer-supplied protective strip, or covered by a handrail (AbP No. BAY 40-003-12-3).
Glass tolerances:
thickness max.
21.5mm
25.5mm
+0.2-0.5
13
168
100
10
9
±0.000
60
25.5
21.5 +0.2 -0.5
L-Bracket
Flexibly insertablefixing brackets
L-Bracket
Gla
ss c
lam
ping
150
mm
Customer-supplied:Connecting sheets(not copper)
Support
incl. self-adhesiverubber insert
Litefront filler compound
Litefront silicone seal
Glass surface treatment:sanded + polished
With handrail, tested and AbP-certified:
Top surface exposed(without handrail)
Customer-supplied protective stripCNS (1.5 mm), polished
Versions without handrails:
L-Bracket (heavy)
U-Bracket
+0.2 -0.5
6
www.litefront.com
54
LF'16_00_TROCKEN+ (1:2)
60
VSG 21-4
VSG 25-4
VSG 21-4
VSG 25-4?
62
ArialArial
Arial
Gh
168
100
9
100 60
LF'15_00_NASS (1:2)
13
10
min. 10
10
!
16
ArialArial
Arial
54
LF'15_00_TROCKEN (1:2)
60
VSG 21-4
VSG 25-4
VSG 21-4
VSG 25-4?
62
ArialArial
Arial
Technology - dry glazing (with rubber seals)
Litefront smooth profile (optional)
±0.000 ±0.000
21.521.5Version with
U-shaped handrail LSG 21-4
Laminated glass
LSG 25-4Laminated glass
25.5 25.5
Filler string (soft)
Filler rod (hard)
Alignment insert
If the top of the glass panels is exposed (not covered by a protective strip or a handrail - where appropriately certified), the filler string and filler rod are replaced by a special alignment insert (AbP No. BAY 40-002-15-1).
Falling direction(impact side)
not painted
60 54
62
Glass surfacetreatment:sanded + polished
Glass tolerances:
21.5mm
25.5mm
+0.2-0.5
The alignment insert makes it possible to align the glass panels accurately relative to each other (± 5 mm for Gh = 1 m).
Rubber seal(dry glazing)
Rubber seal(dry glazing)
The dry glazing solution with the quickly installed filler string and filler rod is only to be installed with a handrail profile (AbP No. BAY 40-002-13-1).
+0.2 -0.5+0.2 -0.5
+0.2 -0.5 +0.2 -0.5
thickness max.
7
www.litefront.com
LF'15_Teil01 (1:2)Litefront - Einzelteile1
60
168
57
164
LF'15_Teil02 (1:2)
57
164
LF'15_Teil02 (1:2)
57
164
LF'15_Teil02 (1:2)
L-Bracket
L-Bracket (heavy)
1 x 6 m section
Standard: 61.8 kg/sectionSmooth: 57 kg/section
Litefront profile: Standard / Smooth
Profiles and accessories
Art. No. 860070
Art. No. 860216
Standard: Art. No. 860032
1 packet of 10 pieces
incl. M10 threaded pin with clamping plate
1 piece
Smooth: Art. No. 860315
not painted
8
www.litefront.com
Litefront - Einzelteile2
LF'15_Teil04 (1:2)
30 40 30
44.821
.423
.4
100
Ø10
16
19.2
73
168
1080
5
5
Ø5
60
2 2
5
56
505
LF'15_Teil08 (1:2)
4 3
120
146
148
10861
63
5 6.5
7
148
30.5
108
30.5
16 251
LF'15_Teil09 (1:2)
LF'15_Teil08b (1:2)
LF'15_Teil09b (1:2)
Profiles and accessories
U-Bracket
1 packet of 10 pieces
Art. No. 860063
End plate (stainless steel)
Drainage profile (stainless steel)
Art. No. 860117
Art. No. 860094
1 packet of 2 piecesincl. 12 screws
1 pieceL = 120 mm
(not suitable for use with the smooth Litefront profile)
(not suitable for use with the smooth Litefront profile)
9
www.litefront.com
LF'15_00_DILASPALT (1:2)S
LL
T
L
± L
± L
T
L
54
LF'15_00_TROCKEN (1:2)
60
VSG 21-4
VSG 25-4
VSG 21-4
VSG 25-4?
62Arial
ArialArial
168
100
9
100 60
LF'15_00_NASS (1:2)
13
10
min. 10
10
!
16
ArialArial
Arial
54
LF'15_00_TROCKEN (1:2)
60
VSG 21-4
VSG 25-4
VSG 21-4
VSG 25-4?
62
ArialArial
Arial
168
100
9
100 60
LF'15_00_NASS (1:2)
13
10
min. 10
10
!
16
ArialArial
Arial
Application notes
Long profiles must be equipped with dilatation joints to accommodate thermal expansion and contraction.
The following dilatation joint widths (“S” = gap between the profiles) must be adhered to depending on the installation temperature.
Working joints and connection joints with a suitable expansion detail (e.g. membrane sealing system).
Dilatation joints:
L = 3 m L = 6 m
+ 30 °C 3.5 mm 7 mm
+ 20 °C 4 mm 8 mm
+ 10 °C 4.5 mm 9 mm
0 °C 5 mm 10 mm
- 10 °C 5.5 mm 11 mm
Dilatationsstoss-Breite "S"
bei Profillänge:
Einbau-
Lufttemperatur:
empfohlene
Structure connection sheeting and rubber seal:
Dry glazing rubber seal for 21 mm glass
Dry glazing rubber seal for 25 mm glass
Recommended thickness:- Splice plate: t = 1 mm- Cover plate: t = 1.5 mm
Removable rubber strip (to be removed when rubber seal is applied to structure connection sheeting as shown)
* Recommended gap = 8 mm (according to DIN 18008)
8*
Splice plate
If structure connection sheeting (as shown below) is used in combination with the dry glazing solution with rubber seals, it must be ensured that the downturn in the sheeting is exactly 10 mm (to suit the dimensions of the rubber seal strip).
Dilation joints must be provided for longer connecting plates.
Same rubber seal can be used whether or not there is structure connection sheet-ing to connect to:
Installation temperature:
Recommended dilatation joint width “S”
for profile length:
LSG 21-4 LSG 21-4
LSG 25-4 LSG 25-4
10
www.litefront.com
25
LF'15_Anwendung-01 (1:4)
6890
64
280
100
97
280
62
LF'15_Anwendung-03 (1:4)
25
25
217
54
LF'15_Anwendung-02 (1:4)
170
Connection / application possibilities
(page 19)
(page 18)
(page 23)
(page 24)
11
www.litefront.com
25
67
LF'15_Anwendung-06++('16) (1:4)
102
LF'16_Anwendung-07q (1:4-quer)
62
25
Connection / application possibilities
Counter-sunk screw M10x30(ISO 10642)
Membrane connection in accordance with applicable standard
(see page 26 and documentation "Litefront Sealing Connections")
12
www.litefront.com
25
68
64
280
LF'15_Anwendung-10 (1:4)
97
168
20
3067
Replacer lecouverclepréalablement
Copertina inprecedenza
Fitcoverbeforehand
LF'15_Anwendung-08q (1:4-quer)
62
25
Litefront_Det-1.5-Ans+DE (1:8)
Connection / application possibilities
Fitcoverin advance
• Upper screw connection (through holes) at each step• Lower screw connection (L-bracket) at every other step• Adapt lower part of cover on site
Stairs
(see documentation: "Litefront Sealing Connections")
13
www.litefront.com
Bestimmung Einspannmoment Md,G (Glas)(Innen) Windlast Wk [kN/m2]Wk=0 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0 2.2 2.4 2.6 2.8 3.0 3.5
0.5 0.8 1.2 1.3 1.5 1.7 1.8 2.0 2.2 2.4 2.6 2.8 2.9 3.1 3.3 3.80.8 1.3 1.6 1.8 1.9 2.0 2.2 2.4 2.6 2.7 2.9 3.1 3.3 3.5 3.6 4.11.0 1.7 2.0 2.1 2.2 2.3 2.4 2.6 2.8 3.0 3.2 3.3 3.5 3.7 3.9 4.31.6 2.6 3.0 3.1 3.2 3.3 3.4 3.5 3.6 3.7 3.8 4.0 4.2 4.4 4.6 5.02.0 3.3 3.6 3.7 3.8 4.0 4.1 4.2 4.3 4.4 4.5 4.6 4.7 4.9 5.0 5.53.0 5.0 5.3 5.4 5.5 5.6 5.7 5.8 5.9 6.0 6.1 6.3 6.4 6.5 6.6 6.9
Md,G [kNm/m]
Holm
last Hk
[kN/m
]
Bestimmung Kontrollmoment Md,Gk (Glas‐Kontrolle: "Ausfall einer Scheibe der VSG‐Schicht")(Innen) Windlast Wk [kN/m2]wk=0 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0 2.2 2.4 2.6 2.8 3.0 3.5
0.5 0.4 0.4 0.4 0.5 0.5 0.5 0.5 0.6 0.6 0.6 0.6 0.6 0.7 0.7 0.80.8 0.6 0.6 0.6 0.7 0.7 0.7 0.7 0.8 0.8 0.8 0.8 0.8 0.9 0.9 1.01.0 0.8 0.8 0.8 0.8 0.8 0.8 0.9 0.9 0.9 0.9 1.0 1.0 1.0 1.0 1.11.6 1.2 1.2 1.2 1.2 1.2 1.2 1.3 1.3 1.3 1.3 1.4 1.4 1.4 1.4 1.52.0 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.6 1.6 1.6 1.6 1.7 1.7 1.73.0 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.4
Holm
last Hk
[kN/m
]
Md,Gk [kNm/m]
Kontrolle "Ausfall einer Scheibe der VSG‐Schicht"min.
Gl.Breite 0.4 0.8 1.1 1.4 1.7 1.810 TVG 0.5 m ok ok ‐ ‐ ‐ ‐ ‐ ‐12 TVG 0.5 m ok ok ok ‐ ‐ ‐ ‐ ‐10 ESG 0.5 m ok ok ok ok ‐ ‐ ‐ ‐12 ESG 0.5 m ok ok ok ok ok ‐ ‐ ‐
Aussergewöhnlicher Lastfall "Ausfall einer Scheibe"
Einzelglastyp: Kontrollmoment Md,Gk [kNm/m]
TVG
ESG
Glasauswahl "mit Handlaufprofil" (AbP)min.
Gl.Breite 0.8 1.6 2.4 2.8 4.0 4.1 4.9 6.910 TVG / 1,52 PVB / 10 TVG 0.5 m ok ok ‐ ‐ ‐ ‐ ‐ ‐12 TVG / 1,52 PVB / 12 TVG 0.5 m ok ok ok ‐ ‐ ‐ ‐ ‐10 TVG / 0,9 SG / 10 TVG 0.5 m ok ok ok ok ‐ ‐ ‐ ‐12 TVG / 0,9 SG / 12 TVG 0.5 m ok ok ok ok ok ok ‐ ‐10 ESG / 1,52 PVB / 10 ESG 0.5 m ok ok ok ok ‐ ‐ ‐ ‐12 ESG / 1,52 PVB / 12 ESG 0.5 m ok ok ok ok ok ‐ ‐ ‐10 ESG / 0,9 SG / 10 ESG 0.5 m ok ok ok ok ok ok ok ‐12 ESG / 0,9 SG / 12 ESG 0.5 m ok ok ok ok ok ok ok ok
geregelt nach AbP Nr. BAY 40‐003‐12‐2 (Pendelschlagversuche + statisch berechnet)
Einspannmoment Md,G [kNm/m]Glasaufbau:
TVG
ESG
Glasauswahl "mit Handlaufprofil" (AbP)min.
Gl.Breite 0.8 1.6 2.4 2.8 4.0 4.1 4.9 6.910 TVG / 1,52 PVB / 10 TVG 0.5 m ok ok ‐ ‐ ‐ ‐ ‐ ‐12 TVG / 1,52 PVB / 12 TVG 0.5 m ok ok ok ‐ ‐ ‐ ‐ ‐10 TVG / 0,9 SG / 10 TVG 0.5 m ok ok ok ok ‐ ‐ ‐ ‐12 TVG / 0,9 SG / 12 TVG 0.5 m ok ok ok ok ok ok ‐ ‐10 ESG / 1,52 PVB / 10 ESG 0.5 m ok ok ok ok ‐ ‐ ‐ ‐12 ESG / 1,52 PVB / 12 ESG 0.5 m ok ok ok ok ok ‐ ‐ ‐10 ESG / 0,9 SG / 10 ESG 0.5 m ok ok ok ok ok ok ok ‐12 ESG / 0,9 SG / 12 ESG 0.5 m ok ok ok ok ok ok ok ok
geregelt nach AbP Nr. BAY 40‐003‐12‐2 (Pendelschlagversuche + statisch berechnet)
Einspannmoment Md,G [kNm/m]Glasaufbau:
TVG
ESG
Glasauswahl "mit Handlaufprofil" (AbP)min.
Gl.Breite 0.8 1.6 2.4 2.8 4.0 4.1 4.9 6.910 TVG / 1,52 PVB / 10 TVG 0.5 m ok ok ‐ ‐ ‐ ‐ ‐ ‐12 TVG / 1,52 PVB / 12 TVG 0.5 m ok ok ok ‐ ‐ ‐ ‐ ‐10 TVG / 0,9 SG / 10 TVG 0.5 m ok ok ok ok ‐ ‐ ‐ ‐12 TVG / 0,9 SG / 12 TVG 0.5 m ok ok ok ok ok ok ‐ ‐10 ESG / 1,52 PVB / 10 ESG 0.5 m ok ok ok ok ‐ ‐ ‐ ‐12 ESG / 1,52 PVB / 12 ESG 0.5 m ok ok ok ok ok ‐ ‐ ‐10 ESG / 0,9 SG / 10 ESG 0.5 m ok ok ok ok ok ok ok ‐12 ESG / 0,9 SG / 12 ESG 0.5 m ok ok ok ok ok ok ok ok
geregelt nach AbP Nr. BAY 40‐003‐12‐2 (Pendelschlagversuche + statisch berechnet)
Einspannmoment Md,G [kNm/m]Glasaufbau:
TVG
ESG
Balustrade with load-dispersing handrail (AbP-certified) 1.) First, the clamping moment Md,G (glass) is determined, based on the combined loads (wind and rail-level loads) arising:
2.) The permissible type of glass can now be selected on the basis of the calculated clamping moment Md,G:
3.) Now the exceptional load case combination of "Failure of an LSG layer" must be verified with the selected glass type. The reduced check moment Md, Gk is determined with the same loads (wind and rail-level load) when doing this:
4.) The previously selected type of glass must be checked on the basis of the calculated check moment Md,Gk. Only 1 pane of the LSG laminated glass is considered when doing this:
5.) The bracket spacing can be determined now that the type of glass is known. -> "Detailing of bracket supports" (page 17)
Selection of glass panel type
(Gh = 1.1m)
Glasauswahl "mit lastabtragendem Handlauf" (AbP)
min.
Gl.Breite 0.8 1.6 2.4 2.8 4.0 4.1 4.9 6.9
10 TVG / 1,52 PVB / 10 TVG 0.5 m ok ok - - - - - -
12 TVG / 1,52 PVB / 12 TVG 0.5 m ok ok ok - - - - -
10 TVG / 0,9 SG / 10 TVG 0.5 m ok ok ok ok - - - -
12 TVG / 0,9 SG / 12 TVG 0.5 m ok ok ok ok ok ok - -
10 ESG / 1,52 PVB / 10 ESG 0.5 m ok ok ok ok - - - -
12 ESG / 1,52 PVB / 12 ESG 0.5 m ok ok ok ok ok - - -
10 ESG / 0,9 SG / 10 ESG 0.5 m ok ok ok ok ok ok ok -
12 ESG / 0,9 SG / 12 ESG 0.5 m ok ok ok ok ok ok ok ok
geregelt nach AbP Nr. BAY 40-003-12-2 (Pendelschlagversuche + statisch berechnet)
Einspannmoment Md,G [kNm/m]
Glasaufbau:
TVG
ESG
Table 1a: Determination of clamping moment Md,G (Gh = 1.1m)
Table 1c: Determination of reduced check moment Md,Gk (“Failure of an LSG layer”)
Table 1d: Check “Complete failure of an LSG pane”
Table 1b: Glass selection “with load-dispersing handrail (AbP-certified)”
fram
e lo
ad H
k
Wind load Wk [kN/m2](indoors)
HSG
Glass structure: Clamping moment Md,G [kNm/m]min.Gl.width
According to AbP (pendulum impact test + static calculations)
Rai
l-lev
el lo
ad
Hk
[kN
/m]
Wind load Wk [kN/m2]
Single glass structure: min.Gl.width
Check moment Md,Gk [kNm/m]
Exceptional load case: “Complete failure of one LSG pane”
(Indoors)
Rai
l-lev
el lo
ad
Hk
[kN
/m]
10 HSG / 1.52 PVB / 10 HSG12 HSG / 1.52 PVB / 12 HSG10 HSG / 0.9 SG / 10 HSG12 HSG / 0.9 SG / 12 HSG
TSG
10 TSG / 1.52 PVB / 10 TSG12 TSG / 1.52 PVB / 12 TSG10 TSG / 0.9 SG / 10 TSG12 TSG / 0.9 SG / 12 TSG
Designations:
LSG = laminated safety glass HSG = heat-strenghened glass TSG = toughened safety glass PVB = polyvinyl butyral SG = SentryGlass
HSG
TSG
10 HSG12 HSG10 TSG12 TSG
14
www.litefront.com
Bestimmung Einspannmoment Md,G (Glas)(Innen) Windlast Wk [kN/m2]Wk=0 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0 2.2 2.4 2.6 2.8 3.0 3.5
0.5 0.8 1.2 1.3 1.5 1.7 1.8 2.0 2.2 2.4 2.6 2.8 2.9 3.1 3.3 3.80.8 1.3 1.6 1.8 1.9 2.0 2.2 2.4 2.6 2.7 2.9 3.1 3.3 3.5 3.6 4.11.0 1.7 2.0 2.1 2.2 2.3 2.4 2.6 2.8 3.0 3.2 3.3 3.5 3.7 3.9 4.31.6 2.6 3.0 3.1 3.2 3.3 3.4 3.5 3.6 3.7 3.8 4.0 4.2 4.4 4.6 5.02.0 3.3 3.6 3.7 3.8 4.0 4.1 4.2 4.3 4.4 4.5 4.6 4.7 4.9 5.0 5.53.0 5.0 5.3 5.4 5.5 5.6 5.7 5.8 5.9 6.0 6.1 6.3 6.4 6.5 6.6 6.9
Md,G [kNm/m]
Holm
last Hk
[kN/m
]
Glasauswahl "ohne Handlaufprofil, mit Kantenschutz"*min.
Gl.Breite 0.8 1.2 1.6 2.4 2.8 4.0 4.1 4.9 6.910 FG / 1,52 SG / 10 FG 1 m ok ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐12 FG / 1,52 SG / 12 FG 1 m ok ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐10 TVG / 1,52 PVB / 10 TVG 0.5 m ok ok ok ‐ ‐ ‐ ‐ ‐ ‐12 TVG / 1,52 PVB / 12 TVG 0.5 m ok ok ok ok ‐ ‐ ‐ ‐ ‐10 TVG / 0,9 SG / 10 TVG 0.5 m ok ok ok ok ok ‐ ‐ ‐ ‐12 TVG / 0,9 SG / 12 TVG 0.5 m ok ok ok ok ok ok ok ‐ ‐10 ESG / 1,52 PVB / 10 ESG 0.5 m ok ok ok ok ok ‐ ‐ ‐ ‐12 ESG / 1,52 PVB / 12 ESG 0.5 m ok ok ok ok ok ok ‐ ‐ ‐10 ESG / 0,9 SG / 10 ESG 0.5 m ok ok ok ok ok ok ok ok ‐12 ESG / 0,9 SG / 12 ESG 0.5 m ok ok ok ok ok ok ok ok ok
* Zustimmung im Einzelfall (ZiE) notwendig
Floa
t
Glasaufbau*: Einspannmoment Md,G [kNm/m]
TVG
ESG
Selection of glass panel type
Balustrade without handrail, with protective strip 1.) First, the clamping moment Md,G (glass) is determined, based on the combined loads (wind and rail-level loads) arising:
2.) The permissible type of glass can now be selected on the basis of the calculated clamping moment Md,G:
3.) The bracket spacing can be determined now that the type of glass is known. -> “Detailing of bracket supports” (page 17)
Notes:
For all-glass balustrades without handrail (with edge protection), the two exceptional load cases “Failure of an LSG layer" and "Complete failure of an LSG pane" can NOT be mathematically proven. The verification is carried out by means of tests.
Float glass (FG) corresponds to plate glassSG = “SentryGlass SGP5000” safety sheet (technical approval Z-70.3-170)
Protective strip applied in accordance with installation instructions.
The above design tables are not a substitute for project-specific design calculations.The tables apply only to rectangular glass panels. Design in accordance with DIN 18008. Country-specific deviations must be taken into consideration.
Table 2a:
Table 2b:
(Gh = 1.1m)Wind load Wk [kN/m2](inside)
fram
e lo
ad H
k
Glass structure: Clamping moment Md,G [kNm/m]min.Gl.width
Table 2a: Determination of clamping moment Md,G (Gh = 1.1m)
Table 2b: Glass selection “without handrail, with protective strip”
(indoors)
Rai
l-lev
el lo
ad
Hk
[kN
/m]
HSG
TSG
10 HSG / 1.52 PVB / 10 HSG12 HSG / 1.52 PVB / 12 HSG10 HSG / 0.9 SG / 10 HSG12 HSG / 0.9 SG / 12 HSG10 TSG / 1.52 PVB / 10 TSG12 TSG / 1.52 PVB / 12 TSG10 TSG / 0.9 SG / 10 TSG12 TSG / 0.9 SG / 12 TSG
10 FG / 1.52 SG / 10 FG12 FG / 1.52 SG / 12 FG
15
www.litefront.com
Bestimmung Einspannmoment Md,G (Glas)(Innen) Windlast Wk [kN/m2]Wk=0 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0 2.2 2.4 2.6 2.8 3.0 3.5
0.5 0.8 1.2 1.3 1.5 1.7 1.8 2.0 2.2 2.4 2.6 2.8 2.9 3.1 3.3 3.80.8 1.3 1.6 1.8 1.9 2.0 2.2 2.4 2.6 2.7 2.9 3.1 3.3 3.5 3.6 4.11.0 1.7 2.0 2.1 2.2 2.3 2.4 2.6 2.8 3.0 3.2 3.3 3.5 3.7 3.9 4.31.6 2.6 3.0 3.1 3.2 3.3 3.4 3.5 3.6 3.7 3.8 4.0 4.2 4.4 4.6 5.02.0 3.3 3.6 3.7 3.8 4.0 4.1 4.2 4.3 4.4 4.5 4.6 4.7 4.9 5.0 5.53.0 5.0 5.3 5.4 5.5 5.6 5.7 5.8 5.9 6.0 6.1 6.3 6.4 6.5 6.6 6.9
Md,G [kNm/m]
Holm
last Hk
[kN/m
]
Glasauswahl "ohne Handlaufprofil, freie Kante"**min.
Gl.Breite 0.8 1.2 1.6 2.4 2.8 4.0 4.1 4.9 6.910 TVG / 1,52 SG / 10 TVG 1 m ok ok ok ok ok ‐ ‐ ‐ ‐12 TVG / 1,52 SG / 12 TVG 1 m ok ok ok ok ok ok ok ‐ ‐
** Zustimmung im Einzelfall (ZiE) notwendig, sowie verbundlose Klebung (Antihaftband)
TVG
Einspannmoment Md,G [kNm/m]Glasaufbau**:
Selection of glass panel type
Balustrade without handrail, top surface exposed 1.) First, the clamping moment Md,G (glass) is determined, based on the combined loads (wind and rail-level loads) arising:
2.) The permissible type of glass can now be selected on the basis of the calculated clamping moment Md,G:
3.) The bracket spacing can be determined now that the type of glass is known. -> “Detailing of bracket supports” (page 17)
Notes:
For all-glass balustrades without handrail (top surface exposed), the two exceptional load cases “Failure of an LSG layer” and “Complete failure of an LSG pane” can NOT be mathematically proven. The verification is carried out by means of tests.
SG = “SentryGlass SGP5000” safety sheet (technical approval Z-70.3-170)
The above design tables are not a substitute for project-specific design calculations.The tables apply only to rectangular glass panels. Design in accordance with DIN 18008. Country-specific deviations must be taken into consideration.
Table 3a:
Table 3b:
(Gh = 1.1m) Table 3a: Determination of clamping moment Md,G (Gh = 1.1m)
Wind load Wk [kN/m2](inside)
Table 3b: Glass selection “without handrail, free edge”
Glass structure: Clamping moment Md,G [kNm/m]min.Gl.width
(indoors)
HSG
Rai
l-lev
el lo
ad
Hk
[kN
/m]
10 HSG / 1.52 SG / 10 HSG12 HSG / 1.52 SG / 12 HSG
16
www.litefront.com
Bestimmung Einspannmoment Md,K (Konsolen)(Innen) Windlast Wk [kN/m2]wk=0 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0 2.2 2.4 2.6 2.8 3.0 3.5
0.5 0.8 1.2 1.3 1.5 1.7 1.8 2.0 2.2 2.4 2.6 2.8 2.9 3.1 3.3 3.80.8 1.3 1.6 1.8 1.9 2.0 2.2 2.4 2.6 2.7 2.9 3.1 3.3 3.5 3.6 4.11.0 1.7 2.0 2.1 2.2 2.3 2.4 2.6 2.8 3.0 3.2 3.3 3.5 3.7 3.9 4.31.6 2.6 3.0 3.1 3.2 3.3 3.4 3.5 3.6 3.7 3.8 4.0 4.2 4.4 4.6 5.02.0 3.3 3.6 3.7 3.8 4.0 4.1 4.2 4.3 4.4 4.5 4.6 4.7 4.9 5.0 5.53.0 5.0 5.3 5.4 5.5 5.6 5.7 5.8 5.9 6.0 6.1 6.3 6.4 6.5 6.6 6.9
Md,K [kNm/m]
Holm
last Hk
[kN/m
]
42.4 x 1.5 V2A (K320)
48.3 x 1.5 V2A (K320)
LF'15_Statik-Typ1 (1:4)21
111
78
min
.70
1580
15
24 54
max
.10
min.75
Typ 1:
110
max.10
X X X 0.25m0.25m
110 110
= keine Dübel setzen
21
102
399
Md 2.0
6099
29
15 63 21
Ø11
Winkel-Konsole
vollflächige Unterfütterungoder druckfeste Unterlagen
2x HST-R M10
2x HST-R M10
Bracket spacing, X 1.) First, the clamping moment Md,K (bracket) is determined, based on the combined loads (wind and rail-level loads) arising:
2.) The spacing between bracket axes, X - which depends on the type of bracket (1-9, see following pages) - can be read from the appropriate table on the basis of the calculated clamping moment, Md,K.
Notes:
Design according to EN 1999-1-1. Country-specific deviations must be taken into consideration.
Such a design is not a substitute for project-specific design calculations.
Detailing of bracket supports
Table 4:(Gh = 1.1m)
Design example:
Balustrade type: With load-dispersing handrailSupport design: Type 1
Rail-level load: Hk = 0.8 kN/m Wind load: Wk = 1.2 kN/m2 Balustrade height: Gh = 1.1 m
Glass: -> Clamping moment: Md,G = 2.0 kNm/m (Tab. 1a) -> Glass selection: 12 HSG / 1.52 PVB / 12 HSG (Tab. 1b)-> Check moment: Md,Gk = 0.7 kNm/m (Tab. 1c)-> Check: 12 HSG: 0.7 < 0.8 = ok (Tab. 1d) -> Selection of load- dispersing handrail: 2x12 HSG -> Ø 48.3 x 1.5 V2A
Bracket: -> Clamping moment: Md,K = 2.0 kNm/m (Tab. 4)-> Axis spacing (Type 1): X = 360mm
Table 4: Determination of clamping moment Md,G (Gh = 1.1m)
Wind load Wk [kN/m2](inside)
fram
e lo
ad H
k
Continuous lining or pres-sure-resistant underlayers
(indoors)
Rai
l-lev
el lo
ad
Hk
[kN
/m]
17
www.litefront.com
LF'15_Statik-Typ1 (1:4)
21
111
78
min
.70
1580
15
24 54
max
.10
min.75
Typ 1:
110
max.10
X X X 0.25m0.25m
110 110
= keine Dübel setzen
21
102
399
Md 2.0
6099
29
15 63 21
Ø11
Winkel-Konsole
vollflächige Unterfütterungoder druckfeste Unterlagen
2x HST-R M10
2x HST-R M10
Md,K [kNm/m]
AbstandX [mm]
0.8 9600.9 8551.1 7001.3 5901.5 5101.6 4801.7 4501.8 4252.0 3602.2 ‐
Typ 1
LF'15_Statik-Typ1 (1:4)
21
111
78
min
.70
1580
15
24 54
max
.10
min.75
Typ 1:
110
max.10
X X X 0.25m0.25m
110 110
= keine Dübel setzen
21
102
399
Md 2.0
6099
29
15 63 21
Ø11
Winkel-Konsole
vollflächige Unterfütterungoder druckfeste Unterlagen
2x HST-R M10
2x HST-R M10
Detailing of bracket supports
Bracket layout (plan view):
For Type 1 fixing, the bracket spacing (X), according to design calculations, is as follows:
Notes: Only Hilti anchors of type HST-R M10 in accordance with European tech-nical approval ETA-98/0001 [12], or equivalent, may be used to fix the brackets to the structure. The requirements of this European technical approval must be adhered to. Concrete quality at least C20/25 (cracked concrete).
At least two bracket pairs. Two anchors per bracket.Brackets in each pair offset from each other as shown.
do not place anchors
Such a design is not a substitute for project-specific design calculations.
Continuous lining or pres-sure-resistant underlayers
Type 1:
Type 1:Spacing
L-bracket
18
www.litefront.com
LF'15_Statik-Typ2 (1:4)
X X X 0.25m0.25m
110 110
21
65
min.75
max
.10
max.10
118
Typ 2:
= keine Dübel setzen
6099
78
1580
15
24 54
110 21
102
399
29
15 63 21
Ø11
Winkel-Konsole
Md 1.6
min
.70
vollflächige Unterfütterungoder druckfeste Unterlagen
2x HST-R M10
2x HST-R M10
Md,K [kNm/m]
AbstandX [mm]
0.8 6200.9 5501.1 4501.3 3801.5 3301.6 3101.7 ‐
Typ 2
LF'15_Statik-Typ1 (1:4)
21
111
78
min
.70
1580
15
24 54
max
.10
min.75
Typ 1:
110
max.10
X X X 0.25m0.25m
110 110
= keine Dübel setzen
21
102
399
Md 2.0
6099
29
15 63 21
Ø11
Winkel-Konsole
vollflächige Unterfütterungoder druckfeste Unterlagen
2x HST-R M10
2x HST-R M10
Detailing of bracket supports
At least two bracket pairs. Two anchors per bracket.Brackets in each pair offset from each other as shown.
For Type 2 fixing, the bracket spacing (X), according to design calculations, is as follows:
Notes: Only Hilti anchors of type HST-R M10 in accordance with European tech-nical approval ETA-98/0001 [12], or equivalent, may be used to fix the brackets to the structure. The requirements of this European technical approval must be adhered to. Concrete quality at least C20/25 (cracked concrete).
do not place anchors
Bracket layout (plan view):
Such a design is not a substitute for project-specific design calculations.
Continuous lining or pres-sure-resistant underlayers
Type 2:
Type 2:Spacing
L-bracket
19
www.litefront.com
LF'16_Statik-Typ3 (1:4)
ISO 4017 M10x30Sechskantschraube4 Stk.
304030
100
73
2148
100
31
10
11040
35
35
15
15
80110 10050
50
Typ 3:
X X X 0.25m0.25m
Ø10
168
min
.120
6013
U-Konsole
Md ≤ 2.2
max
. 10
St.Winkel 100x100x10 - 110
8
vollflächige Unterfütterungnur mit geeignetem Vergussmörtel(zB. Hilti CB-G PG1)oder druckfeste Unterlagen
2x HST-R M10
100
min.75
Md,K [kNm/m]
AbstandX [mm]
0.8 1'5000.9 1'5001.1 1'3751.3 1'1751.5 9851.6 9401.7 8751.8 8302.0 7382.2 6902.4 ‐
Typ 3
LF'15_Statik-Typ1 (1:4)
21
111
78
min
.70
1580
15
24 54
max
.10
min.75
Typ 1:
110
max.10
X X X 0.25m0.25m
110 110
= keine Dübel setzen
21
102
399
Md 2.0
6099
29
15 63 21
Ø11
Winkel-Konsole
vollflächige Unterfütterungoder druckfeste Unterlagen
2x HST-R M10
2x HST-R M10
Detailing of bracket supports
At least two bracket pairs. Two anchors and four bolts per bracket.
For Type 3 fixing, the bracket spacing (X), according to design calculations, is as follows:
Notes: Only Hilti anchors of type HST-R M10 in accordance with European tech-nical approval ETA-98/0001 [12], or equivalent, may be used to fix the brackets to the structure. The requirements of this European technical approval must be adhered to. Concrete quality at least C20/25 (cracked concrete).
Bracket layout (plan view):
Such a design is not a substitute for project-specific design calculations.
Continuous liningonly with suitable grout(e.g. Hilti CB-G PG1)or pressure-resistant underlayers
U-Bracket Steel angle 100x100x10 - 110mm
4 pcs.Hexagon boltISO 4017 M10x30
Type 3:
Type 3:Spacing
20
www.litefront.com
78
LF'15_Statik-Typ4 (1:4)
Typ 4:
15
15
112
2215 58
24
168
X
77
X X0.25m 0.25m
110 110
= keine Schrauben setzen
60
6099
max
.10
max
.10
1580
15
24 54
110 21
102
399
29
15 63 21
Ø11
unverschieblicheUnterfütterung(aufgeschweisst)
unverschieblicheUnterfütterung(aufgeschweisst)
Winkel-Konsole
Md 2.0ISO 4014 M10x45Sechskantschraube4 Stk.
Md,K [kNm/m]
AbstandX [mm]
0.8 1'5100.9 1'3901.1 1'1701.3 9901.5 8601.6 7801.7 6601.8 5402.0 3502.2 ‐
Typ 4
LF'15_Statik-Typ1 (1:4)
21
111
78
min
.70
1580
15
24 54
max
.10
min.75
Typ 1:
110
max.10
X X X 0.25m0.25m
110 110
= keine Dübel setzen
21
102
399
Md 2.0
6099
29
15 63 21
Ø11
Winkel-Konsole
vollflächige Unterfütterungoder druckfeste Unterlagen
2x HST-R M10
2x HST-R M10
Detailing of bracket supports
At least two bracket pairs. Two bolts per bracket.Brackets in each pair offset from each other as shown.
For Type 4 fixing, the bracket spacing (X), according to design calculations, is as follows:
do not place screws
Bracket layout (plan view):
Such a design is not a substitute for project-specific design calculations.
4 pcs.Hexagon boltISO 4014 M10x45
Permanently fixed packing plate (welded on)
Type 4:
Type 4:Spacing
L-bracket
21
www.litefront.com
LF'15_Statik-Typ5 (1:4)
Typ 5:
15
78
58
84
X X X 0.25m0.25m
110 110
= keine Schrauben setzen22
168
77
min.30
6099
max
.10
max
.10
1580
15
24 54
110 21
102
399
29
15 63 21
Ø11
LeimbinderKlotz 200x120
Winkel-Konsole
min
.30
Md 2.0Sk.H.Schr.DIN 571 10x100
Md,K [kNm/m]
AbstandX [mm]
0.8 7200.9 6401.1 5301.3 4401.5 3901.6 3601.7 3401.8 3202.0 2902.2 ‐
Typ 5
LF'15_Statik-Typ1 (1:4)
21
111
78
min
.70
1580
15
24 54
max
.10
min.75
Typ 1:
110
max.10
X X X 0.25m0.25m
110 110
= keine Dübel setzen
21
102
399
Md 2.0
6099
29
15 63 21
Ø11
Winkel-Konsole
vollflächige Unterfütterungoder druckfeste Unterlagen
2x HST-R M10
2x HST-R M10
Detailing of bracket supports
For Type 5 fixing, the bracket spacing (X), according to design calculations, is as follows:
At least two bracket pairs. Two screws per bracket.Brackets in each pair offset from each other as shown.
do not place screws
Bracket layout (plan view):
Such a design is not a substitute for project-specific design calculations.
Hexagonalwood screwDIN 571 10x100
Glued laminated timber(200 x 100)
Type 5:
Type 5:Spacing
L-bracket
22
www.litefront.com
167
LF'15_Statik-Typ6 (1:4)
Typ 6:
X X X
15
0.25m0.25m
135
7065
10
70
max
.10
= keine Dübel setzen
20 60 40
163
Ø11
1515
110
40
18
3160
60
min
.120
10
11
15 65 45 38
80
A
B
A / B
mit KlemmblechISO 4026 M10x16inkl. Gewindestift
muss
A oder B
Winkel-Konsole massiv
min. 70
Md 1.5vollflächige Unterfütterungmit Vergussmörtel d,max = 10mmoder druckfeste Unterlagen
2x HST-R M10
167
LF'15_Statik-Typ6 (1:4)
Typ 6:
X X X
15
0.25m0.25m
135
7065
10
70
max
.10
= keine Dübel setzen
20 60 40
163
Ø11
1515
110
40
18
3160
60
min
.120
10
11
15 65 45 38
80
A
B
A / B
mit KlemmblechISO 4026 M10x16inkl. Gewindestift
muss
A oder B
Winkel-Konsole massiv
min. 70
Md 1.5vollflächige Unterfütterungmit Vergussmörtel d,max = 10mmoder druckfeste Unterlagen
2x HST-R M10
167
LF'15_Statik-Typ6 (1:4)
Typ 6:
X X X
15
0.25m0.25m
135
7065
10
70
max
.10
= keine Dübel setzen
20 60 40
163
Ø11
1515
110
40
18
3160
60
min
.120
10
11
15 65 45 38
80
A
B
A / B
mit KlemmblechISO 4026 M10x16inkl. Gewindestift
muss
A oder B
Winkel-Konsole massiv
min. 70
Md 1.5vollflächige Unterfütterungmit Vergussmörtel d,max = 10mmoder druckfeste Unterlagen
2x HST-R M10
Md,K [kNm/m]
AbstandX [mm]
0.8 5500.9 4801.1 4001.3 3301.5 2901.6 ‐
Typ 6
LF'15_Statik-Typ1 (1:4)
21
111
78
min
.70
1580
15
24 54
max
.10
min.75
Typ 1:
110
max.10
X X X 0.25m0.25m
110 110
= keine Dübel setzen
21
102
399
Md 2.0
6099
29
15 63 21
Ø11
Winkel-Konsole
vollflächige Unterfütterungoder druckfeste Unterlagen
2x HST-R M10
2x HST-R M10
Detailing of bracket supports
At least two brackets. Two anchors per bracket.One anchor in the front row of holes, one in the back row, as indicated in the sketch.
For Type 6 fixing, the bracket spacing (X), according to design calculations, is as follows:
Notes: Only Hilti anchors of type HST-R M10 in accordance with European tech-nical approval ETA-98/0001 [12], or equivalent, may be used to fix the brackets to the structure. The requirements of this European technical approval must be adhered to. Concrete quality at least C20/25 (cracked concrete).
do not place anchorsBracket layout (plan view):
Such a design is not a substitute for project-specific design calculations.
Continuous lining with grout, max. thickness = 10 mmor pressure-resistant underlayers
incl. threaded boltISO 4026 M10x16with clamping plate
incl. threaded boltISO 4026 M10x16with clamping plate
incl. threaded boltISO 4026 M10x16with clamping plateType 6:
Type 6:Spacing
L-bracket (heavy)
23
www.litefront.com
LF'15_Statik-Typ7 (1:4)
0.25m
Typ 7:
X X X 0.25m
3511
015
max. 10
110
= keine Dübel setzen
59
133
168
60
20 60 40
163
Ø11
1515
110
40
3160
10
11
15 65 45 38
8018
A B
BA
Winkel-Konsole massiv
min
.70
min
.70
min
.250
Md 1.6
mit KlemmblechISO 4026 M10x16inkl. Gewindestift
vollflächige Unterfütterungmit Vergussmörtel d,max = 10mmoder druckfeste Unterlagen
2x HST-R M10
167
LF'15_Statik-Typ6 (1:4)
Typ 6:
X X X
15
0.25m0.25m
135
7065
10
70
max
.10
= keine Dübel setzen
20 60 40
163
Ø11
1515
110
40
18
3160
60
min
.120
10
11
15 65 45 38
80
A
B
A / B
mit KlemmblechISO 4026 M10x16inkl. Gewindestift
muss
A oder B
Winkel-Konsole massiv
min. 70
Md 1.5vollflächige Unterfütterungmit Vergussmörtel d,max = 10mmoder druckfeste Unterlagen
2x HST-R M10
167
LF'15_Statik-Typ6 (1:4)
Typ 6:
X X X
15
0.25m0.25m
135
7065
10
70
max
.10
= keine Dübel setzen
20 60 40
163
Ø11
1515
110
40
18
3160
60
min
.120
10
11
15 65 45 38
80
A
B
A / B
mit KlemmblechISO 4026 M10x16inkl. Gewindestift
muss
A oder B
Winkel-Konsole massiv
min. 70
Md 1.5vollflächige Unterfütterungmit Vergussmörtel d,max = 10mmoder druckfeste Unterlagen
2x HST-R M10
Md,K [kNm/m]
AbstandX [mm]
0.8 5600.9 5001.1 4201.3 3501.5 3001.6 2801.7 ‐
Typ 7
LF'15_Statik-Typ1 (1:4)
21
111
78
min
.70
1580
15
24 54
max
.10
min.75
Typ 1:
110
max.10
X X X 0.25m0.25m
110 110
= keine Dübel setzen
21
102
399
Md 2.0
6099
29
15 63 21
Ø11
Winkel-Konsole
vollflächige Unterfütterungoder druckfeste Unterlagen
2x HST-R M10
2x HST-R M10
Detailing of bracket supports
For Type 7 fixing, the bracket spacing (X), according to design calculations, is as follows:
At least two brackets. Two anchors per bracket.One anchor in the lower row of holes, one in the upper row, as indicated in the sketch.
Notes: Only Hilti anchors of type HST-R M10 in accordance with European tech-nical approval ETA-98/0001 [12], or equivalent, may be used to fix the brackets to the structure. The requirements of this European technical approval must be adhered to. Concrete quality at least C20/25 (cracked concrete).
do not place anchors
Bracket layout (plan view):
Such a design is not a substitute for project-specific design calculations.
Continuous lining with grout, max. thickness = 10 mmor pressure-resistant underlayers
incl. threaded boltISO 4026 M10x16with clamping plateType 7:
Type 7:Spacing
L-bracket (heavy)
24
www.litefront.com
20
LF'16_Statik-Typ8 (1:4)
Typ 8:
14018020
2272
51
1214
520
6
1360
340
max
. 10
X X X 0.25m0.25m
200
min
.120
150x20Flachstahl
Absturzrichtung
Md ≤ 5.0ISO 4017 M10x30Sechskantschraube4 Stk.
6 150
10 150
vollflächige Unterfütterungmit Vergussmörtel d,max = 10mmoder druckfeste Unterlagen
HST-R M10
20 180 140
Ø11
2011
020
150
360
5540
55
304030
100
Ø10Ø
11
20
x2LF'15_Statik-Typ8b (1:4)
AnzahlDübel:
Md,K [kNm/m]
0.8 1'160 1'3000.9 1'000 1'3001.1 840 1'2501.3 710 1'0061.5 620 9201.6 580 8601.7 540 8101.8 510 7702.0 460 6902.2 420 6302.4 380 5702.5 370 5502.6 350 5302.7 340 5103.2 290 4303.3 280 4205.0 ‐ 280
Belastung inAbsturzrichtung
AbstandX [mm]
2 Stk. 4 Stk.
Typ 8a
AnzahlDübel:
Md,K [kNm/m]
0.8 510 ‐0.9 460 ‐1.1 370 ‐1.3 320 ‐1.5 270 ‐1.6 260 ‐1.7 ‐ ‐
Belastung gegenAbsturzrichtung
AbstandX [mm]
2 Stk. 4 Stk.
Typ 8b
LF'15_Statik-Typ1 (1:4)
21
111
78
min
.70
1580
15
24 54
max
.10
min.75
Typ 1:
110
max.10
X X X 0.25m0.25m
110 110
= keine Dübel setzen
21
102
399
Md 2.0
6099
29
15 63 21
Ø11
Winkel-Konsole
vollflächige Unterfütterungoder druckfeste Unterlagen
2x HST-R M10
2x HST-R M10
Detailing of bracket supports
At least two brackets. Two/four anchors and four bolts per bracket. At least one anchor in the front row of holes, at least one in the back row.
For Type 8 fixing, the bracket spacing (X), according to design calculations, is as follows:
Notes: Only Hilti anchors of type HST-R M10 in accordance with European tech-nical approval ETA-98/0001 [12], or equivalent, may be used to fix the brackets to the structure. The requirements of this European technical approval must be adhered to. Concrete quality at least C20/25 (cracked concrete).
The steel support element shall be of Execution Class EXC 2.
Bracket layout (plan view):
Such a design is not a substitute for project-specific design calculations.
4 pcs.Hexagon boltISO 4017 M10x30
Falling direction
Flat steel150x20
Type 8:
Type 8a:Type 8b:
SpacingSpacing
Loading against indicated “falling direction”
Loading in indicated “falling direction”
Number of anchors:
Number of anchors:2 pcs. 4 pcs. 2 pcs. 4 pcs.
Continuous lining with grout, max. thickness = 10 mmor pressure-resistant underlayers
25
www.litefront.com
45
80
x2
Ø11
150
55 40 55
2948
113
3535
LF'15_Statik-Typ9b (1:4)
Ø11
45
LF'16_Statik-Typ9 (1:4)
6
Typ 9:
1401802029
4811
3
190
20
1360
340
max
. 10
X X X 0.25m0.25m
250
6
min
.120
Absturzrichtung
Md ≤ 4.5ISO 4017 M10x30Sechskantschraube4 Stk.
U-StahlDIN 1026 U80
6 80
4 80
vollflächige Unterfütterungmit Vergussmörtel d,max = 10mmoder druckfeste Unterlagen
HST-R M10
Md,K [kNm/m]
AbstandX [mm]
0.8 1'3000.9 1'2601.1 1'0031.3 8701.5 7601.6 7101.7 6701.8 6302.0 5702.2 5102.4 4702.5 4502.6 4302.7 4203.2 3503.3 3404.5 2505.0 ‐
Belastung inAbsturzrichtung
Typ 9a
Md,K [kNm/m]
AbstandX [mm]
0.8 5800.9 5101.1 4201.3 3501.5 3101.6 2901.7 2701.8 2602.0 ‐
Belastung gegenAbsturzrichtung
Typ 9b
LF'15_Statik-Typ1 (1:4)
21
111
78
min
.70
1580
15
24 54
max
.10
min.75
Typ 1:
110
max.10
X X X 0.25m0.25m
110 110
= keine Dübel setzen
21
102
399
Md 2.0
6099
29
15 63 21
Ø11
Winkel-Konsole
vollflächige Unterfütterungoder druckfeste Unterlagen
2x HST-R M10
2x HST-R M10
Detailing of bracket supports
For Type 9 fixing, the bracket spacing (X), according to design calculations, is as follows:
At least two brackets. Two anchors and four bolts per bracket.
Notes: Only Hilti anchors of type HST-R M10 in accordance with European tech-nical approval ETA-98/0001 [12], or equivalent, may be used to fix the brackets to the structure. The requirements of this European technical approval must be adhered to. Concrete quality at least C20/25 (cracked concrete).
The steel support element shall be of Execution Class EXC 2.
Bracket layout (plan view):
Such a design is not a substitute for project-specific design calculations.
Continuous lining with grout, max. thickness = 10 mmor pressure-resistant underlayers
4 pcs.Hexagon boltISO 4017 M10x30
Falling direction
U-channelDIN 1026 U80
Type 9:
Type 9a:Type 9b:
SpacingSpacing
Loading against ind. “falling direction”
Loading in ind. “falling direction”
26
www.litefront.com
Explanation of Declaration of Performance (DoP)
Construction Products Regulation
The Construction Products Regulation ( CPR 305 / 2011 ) came into force on 1st July 2013 and replaced the previous Construction Products Directive.
The most important change was that all products that are subject to a "harmonised European standard" (hEN) or a "European Technical Evaluation" (ETA) must be provided with a "Declaration of Performance" (DoP), which must be made available to the customer.
Consequences for all metal fabricators
The tasks of the manufacturer and the certification body are listed in the following table (from EN 1090-1).
The systems for evaluating and reviewing performance capability are described in the Construction Products Regulation. The standard EN 1090-1 makes reference to System 2+.
"Litefront" balustrades in/on residential buildings are generally manufactured in execution class EXC 1. For all other building types, the balustrades are manufactured in execution class EXC 2.
Consequences for all Litefront suppliers
The “Litefront” supplier (producer) must demonstrate a certified FPC (factory production control) and provide the customer with the Declaration of Performance.
Table ZA.3
Assignment of tasks for evaluation of conformity of structural steel and aluminium components
Content of the tasks
Evaluation of
conformity
Clauses to apply
6.2
6.3
Relevant characteristics
of Table ZA.1
Table 2
Initial inspection of
factory and of FPC
Continuous
surveillance,
assessment and
approval of FPC
Tasks for the
certification
body
Certification of FPC
by a certified body
on the basis of
Relevant parameters
related to the characteristics
of Table ZA.1
6.3 and
Annex B
Tasks
Tasks under the
responsibility
of the
manufacturer
Initial type testing
Relevant parameters related to the
performance characteristics
of Table ZA.1
Factory Production Control
(FPC)
Sampling, testing and inspection at the
factory
27
www.litefront.com
Declaration of Performance
LE/DoP No. 100/CPR/14/01/2016
1. Ident. code of product type: Litefront balustrade
2. Ident no.: ___________________________________________ (project number)
3. Purpose: Balustrade
4. Manufacturer: ___________________________________________ (person bringing the product into circulation) ___________________________________________ (e.g. stamp with address)
___________________________________________
___________________________________________
5. Authorised person: see Manufacturer
6. System for evaluation of performance capability: 2+
7. Harmonised standard: EN 1090-1
8. Design: EN 1990-1999 Structural report 1511427
9. Manufacture: in accordance with component specification and EN 1090-3
10. Execution class: EXC 1 EXC 2
11. Installation: in accordance with Litefront installation instructions (01/2017)
12. FPC certificate: _________________________________________________________________
13. Examining agency: TÜV _________________________________________________________
14. Essential characteristics in acc. with EN 1090-1:
Essential characteristics: Details: - Construction materials Per the standards listed in EN 1090-3 - permitted deviations for
dimensions and shape See component specification - Weldability EN AW 6060 T66 - Fracture toughness NPD - Strength characteristics See design report §8 - Fire performance NPD - Hazardous materials NPD - Impact resistance NPD - Durability NPD (NPD = No Performance Determined)
The manufacturer is solely responsible for the production of this Declaration of Performance.Signed for the manufacturer and on behalf of the manufacturer by:
____________________________________ ____________________________________________________________________Place, date Name and Function
LF'15_Statik-Kantenschutz (1:2)
Ø Ø
LE-Chäschtli
LF'15_Statik-Kantenschutz (1:2)
Ø Ø
LE-Chäschtli
LF'15_Statik-Kantenschutz (1:2)
Ø Ø
LE-Chäschtli
LF'15_Statik-Kantenschutz (1:2)
Ø Ø
LE-Chäschtli
LF'15_Statik-Kantenschutz (1:2)
Ø Ø
LE-Chäschtli
(available as download)
28
www.litefront.com
Si l i k o n
15
15
15
15
Dilatationsstoss "S"
Si l i k o n
15
15
15
15
Dilatationsstoss "S"
Ø8
120
A
B
C12
0
Ø8
Dilatationsstoss
Drainage profile and silicone seals
A seam of silicone sealant (approx. 15x15 mm) must be applied along the bottom of both ends of the drainage profile as shown, before clipping on the drainage profile. This prevents the capillary effect along the grooves.
1. Prepare drainage
If used outdoors*, the glass holding profile must be equipped with a drainage feature.
3 options are available:
A The profile consists of one continuous section which is open at the ends, allowing water to drain off at the ends.
B The profile consists of one continuous section which is closed at the ends by end plates.
Drill drainage holes before installation(1x / section, d=8mm). The drainage profile is clipped on at the end of installation and connected to a PVC hose.
C The profile consists of several sections.
At the end of installation, the drainage profiles are clipped on in the joint area and connected to a PVC hose. Wall connections and profile connections must be in the form of dilatation joints (see page 10).
* If the glass is going to be installed at a later point, the opening of the glass holding profile must be covered to prevent water ingress.
A
B
C
Drainage profile
Installation
Dilatation joint
Dilatation joint "S"
Silicone
Joint between glass:
29
www.litefront.com
X X X 0.25m0.25m110 110
X X X 0.25m0.25m110 110
2a. Mount L- / U-brackets as required onto Litefront profile
The factory-prepared brackets are slid onto the Litefront profile from one end, at the required locations (dimensions A/B) and with the required orientation.
Attention:Since the Litefront profile is asymmetric(one side with fewer grooves), attentionmust be paid to its orientation!
The required number of brackets is dependent on the bracket spacing (“X”), and must be determined in advance.
3. Position and align the construction
Keep the profiles clean and free of damage!
Distribute brackets with required spacing, align profile horizontally and vertically with a spirit level, install anchors.
Please note:The first bracket pair at each end must be centred 250mm from the end of the profile (see illustration).
The brackets of each bracket pair must be offset from each other as shown.
2b. Mount L-brackets (heavy) as required onto Litefront profile
The factory-prepared brackets are slid onto the Litefront profile from one end, at the required locations (dimensions A/B) and with the required orientation.
Important:The THREADED PIN (with stainless steel clamping plate in place) must be SECURELY TIGHTENED BEFORE THE CONSTRUCTION IS POSITIONED AND ALIGNED!
This fixes the bracket securely to the Litefront profile.
Threaded pin M10x16
Installation
30
www.litefront.com
Seife
Seife
Seife
Seife
Installation
5. Stick rubber U-profile to the bottom of the glass
Stick the self-adhesive rubber U-profile along the full length of the lower edge of the glass (firmly press adhesive surfaces onto both sides of the glass).
Important:The glass must be CLEAN AND DRY before the rubber U-profile is stuck to it.
4. Check glass thickness
Before inserting the glass: Measure whether the minimum glass thickness (d -0.5mm) has been adhered to!
Otherwise mask off edge of glass with double sided adhesive tape (d=0.5mm) until required glass thickness has been achieved.
Attention:If the tolerances (-0.5) are not satisfied, stability is not ensured!
6. Insert glass with plastic support pads beneath
Check base of Litefront profile for cleanliness before inserting glass. Two plastic support pads must be inserted beneath each panel. Then the sides of the rubber U-profile on the bottom of the glass are sprayed with a little soapy water and the glass is lowered into position.
Please note:The two plastic support pads must each be centred at a distance of 120 mm from the end of the glass panel, as illustrated.
Support pads:Thickness = 3 mmMax. width = 24 mmRecommended length = 100 mm
Soap
Soap
Two support pads per panel
31
www.litefront.com
48h
13
S iliko
n
S ilikon
48h
13
S iliko
n
S ilikon
7. Align glass with adjusting wedges
Vertically align and temporarily secure glass with 1-2 wedges per side of each panel. A gap of at least 8 mm* must be left at the end of each panel. This gap can be maintained, and tilting of one panel relative to the other can be prevented, by connecting two flat bars (e.g. plastic support pads), tension-free, across the gap as illustrated using a suitable cable tie.
Please note:The adjusting wedges should have an acute angle of approx. 10°.
*Note:Permitted joint width: 8 to 30 mm (according to DIN 18008)
Installation
8a. WET GLAZING: Secure the glass panels
The appropriate filling compound (min. Shore-A hardness 55) is injected along the base of the glass panels at each side, between the adjusting wedges. The wedges must be left in place until the filling compound has hardened sufficiently*.
Please note:The filling compound is injected to a height of approx. 13mm below the top of the Litefront profile, as illustrated.
* HARDENING TIME = 48h (2 days) Complete hardening of the filler after about 1 week.
Version 1: WET GLAZING (8a + 8b)
Note:A silicone seal is also formed between the glass panels, at the bottom (inside the Litefront profile).
This seal must not extend upwards (the visible parts of the panels must not be sealed together)!
8b. WET GLAZING: Insert structure connection sheeting (if any) and apply silicone seals
After removing the adjusting wedges (when safe to do so), and hooking in the structure connection sheeting (if any), apply a silicone seal at both sides of the glass, as shown. The temporary fittings at the joints between panels (flat bars and cable ties, or similar) can then be removed.
Filling
compo
und
The silicone must be compatible with the filling compound.
32
www.litefront.com
LF'15_Montage-18 (1:4)
LF'15_Montage-15 (1:4)
10
!
Seife Seife
LF'15_Montage-19 (1:4)weich
#2
5.5 / 7.5
Seife
LF'15_Montage-17 (1:4)
Absturzrichtung
hart#1
5.3 / 7.3
LF'15_Montage-16 (1:4)
Absturzrichtung
10
!
Seife Seife
LF'15_Montage-19 (1:4)
10
!
Seife Seife
LF'15_Montage-19 (1:4)
10
!
Seife Seife
LF'15_Montage-19 (1:4)
#1
#2
9a. Fall side - Filler rod (hard)
The filler rod (hard) is inserted along the entire length of the glass:
- Filler rod Ø 7.3 for LSG 21 mm- Filler rod Ø 5.3 for LSG 25 mm
The adjusting wedges are carefully removed as the rod is inserted, ensuring that the alignment of the glass is not affected.
Important:It is imperative for the hard filler rodto be placed at the fall side.
9b. Impact side - Filler string (soft)
Then, the filler string (soft) is inserted along the entire length of the glass at the impact side and, using a roll-in tool or a ruler, for example, pushed downwards as far as it will go.
- Filler string Ø 7.5 for LSG 21 mm- Filler string Ø 5.5 for LSG 25 mm
This solution with filler rod/string only in combination with handrail or protective U-profile along top of glass panels (to prevent loss of panel alignment).
Tip:The surfaces can be sprayed with a little soapy water to aid insertion.
Impact side
hard
soft
Impact side
Fall side
Fall side
Note:A silicone seal is also formed between the glass panels, at the bottom (inside the Litefront profile). This seal must not extend upwards (the visible parts of the panels must not be sealed together)!
9c. Insert structure connection sheeting (if any) and rubber seals
The structure connection sheeting (if any) is then inserted and the rubber seals are pressed into position as illustrated.
Where structure connecting sheeting is used, the removable strip is pulled off the rubber seal as shown in 9d.
Installation
Version 2: DRY GLAZINGwith filler rod and filler string (9a - 9d)
Soap
Note:If structure connection sheeting is being hooked onto the Litefront profile as shown, the downturn in the metal sheeting must have a length of 10 mm to suit the shape of the rubber seal (see sketch).
33
www.litefront.com
?
LF'15_Montage-20c (1:2)
Gummi-Abrisslippe
25.5 25.5
LF'15_Montage-20a (1:2)
+0.2- 0.5
+0.2- 0.5
d=
5.3
d=
5.5
Gummidichtung TV für Glas 25 mmohne Blech = mit Gummi-Abrisslippe
Gummidichtung TV für Glas 25 mmmit Blech = ohne Gummi-Abrisslippe
LitefrontProfil "glatt"
21.5
LF'15_Montage-20b (1:2)
+0.2- 0.5 21.5+0.2
- 0.5
d=
7.3
d=
7.5
Gummidichtung TV für Glas 21 mmohne Blech = mit Gummi-Abrisslippe
Gummidichtung TV für Glas 21 mmmit Blech = ohne Gummi-Abrisslippe
LitefrontProfil "glatt"
10
!
Seife Seife
LF'15_Montage-19 (1:4)
10
!
Seife Seife
LF'15_Montage-19 (1:4)
Installation
9d. Rubber seal’s removable strip
Where structure connection sheeting is inserted into the gap, the thickness of the rubber seal must be reduced accordingly.
This can be achieved by stripping off the rubber strip along the inside of the rubber seal, as illustrated.
Removable strip
Rubber seal for 21mm panels:Without sheeting = with removable strip
Rubber seal for 21mm panels:With sheeting = without removable strip
Rubber seal for 25mm panels:Without sheeting = with removable strip
Rubber seal for 25mm panels:With sheeting = without removable strip
34
www.litefront.com
10
!
Seife Seife
LF'15_Montage-19 (1:4)
max. 35
max. 35
max. 35
max. 35
10
!
Seife Seife
LF'15_Montage-23 (1:4)
10
!
Seife Seife
LF'15_Montage-19 (1:4)
10
!
Seife Seife
LF'15_Montage-19 (1:4)
10a. Insert alignment inserts
The alignment inserts are inserted, using the appropriate tool (see sketches), at both sides and along the entire length of the glass (except at adjusting wedges, where a gap of up to 35 mm may be left). The inserts are then gently tapped into place.
The alignment inserts to be used depend on the glass thickness:
- Dry glazing alignment insert for LSG 21 mm- Dry glazing alignment insert for LSG 25 mm
Tip:Cut inserts to size with a metal saw.
10b. Align glass panels in relation to each another
Remove adjusting wedges.
By slightly raising or lowering the alignment inserts using the insertion tool, loss of glass panel alignment can be corrected (± 5 mm for panel height (Gh) = 1 m).
Tip: If an alignment insert falls all the way into the profile, it can be simply brought out again (upwards) using the other, pointed end of theinsertion tool.
Note:A silicone seal is also formed between the glass panels, at the bottom (inside the Litefront profile). This seal must not extend upwards (the visible parts of the panels must not be sealed together)!
10c. Insert structure connection sheeting (if any) and rubber seals
The structure connection sheeting (if any) is then inserted and the rubber seals are pressed into position as illustrated.
Where structure connecting sheeting is used, the removable strip is pulled off the rubber seal as shown in 10d.
Installation
Version 3: DRY GLAZINGwith alignment inserts (10a - 10d)
Cut inserts at glass joint
Note:If structure connection sheeting is being hooked onto the Litefront profile as shown, the downturn in the metal sheeting must have a length of 10 mm to suit the shape of the rubber seal (see sketch).
35
www.litefront.com
?
LF'15_Montage-20c (1:2)
Gummi-Abrisslippe
25.5 25.5
LF'15_Montage-24a (1:2)
+0.2- 0.5
+0.2- 0.5
Gummidichtung TV für Glas 25 mmohne Blech = mit Gummi-Abrisslippe
Gummidichtung TV für Glas 25 mmmit Blech = ohne Gummi-Abrisslippe
LitefrontProfil "glatt"
Ausrichtungs-Einlage TVfür Glas 25mm
21.5
LF'15_Montage-24b (1:2)
+0.2- 0.5 21.5+0.2
- 0.5
Gummidichtung TV für Glas 21 mmohne Blech = mit Gummi-Abrisslippe
Gummidichtung TV für Glas 21 mmmit Blech = ohne Gummi-Abrisslippe
LitefrontProfil "glatt"
Ausrichtungs-Einlage TVfür Glas 21mm
10
!
Seife Seife
LF'15_Montage-19 (1:4)
10
!
Seife Seife
LF'15_Montage-19 (1:4)
Installation
Alignment insert for 21mm panels
10d. Rubber seal’s removable strip
Where structure connection sheeting is inserted into the gap, the thickness of the rubber seal must be reduced accordingly.
This can be achieved by stripping off the rubber strip along the inside of the rubber seal, as illustrated.
Removable strip
Rubber seal for 21mm panels:Without sheeting = with removable strip
Rubber seal for 21mm panels:With sheeting = without removable strip
Rubber seal for 25mm panels:Without sheeting = with removable strip
Rubber seal for 25mm panels:With sheeting = without removable strip
Alignment insert for 25mm panels
36
www.litefront.com
3
Installation
12. Cleaning and care
Clean glass with a soft cloth and a normal glass cleaning solution.
CAUTION: Improper cleaning can cause damage!
- Never use metal blades to clean the panes of glass, even if this is recommended.
- Do not use abrasive or scratching materials.- Never use strongly solvent-containing or abrasive cleaning agents.- Do not use alkalis (bases). - Dirt particles in cloths can scratch the glass.- The use of a high pressure washer is not
suitable for cleaning.
11. Attach handrail or protective strip (if any) to top of glass
Where required, the stainless steel handrail of protective strip can finally be attached to the top of the glass panels.
With handrail profile:
Apply suitable adhesive rubber or a sufficient* quantity of transparent silicone (LSG film-compatible) to the handrail profile, and stick along the top of the glass.
* Depending on country-specific standards / requirements
With protective strip:
The customer-provided protective strip (stainless steel, 1.5 mm thick) is affixed with double-sided adhesive tape directly to the top of the glass panel (clean beforehand).
One protective strip is glued onto each glass panel (not continuous across gaps between panels).
37
www.litefront.com
Litefront_Bestellung (1:4)
Litefront_Bestellung (1:4)
Litefront_Bestellung (1:4)
Litefront_Bestellung (1:4)
Litefront_Bestellung (1:4)
Litefront_Bestellung (1:4)
Litefront_Bestellung (1:4)
LF'15_Bestellung2 (1:4)Litefront - Bestellung / Artikel
Order form
System Art. No. Name Packaging Order:
860032 Litefront profile 1 x 6 m section Raw aluminium 10.3 kg/m ............ section(s)
860315 Litefront profile (smooth) 1 x 6 m section Raw aluminium 9.5 kg/m ............ section(s)
860070 L-bracket 1 packet of 10 pieces Aluminium anodized E6 / EV1 102 x 45 mm, L = 110 mm ................ pack(s)
860339 L-bracket (heavy) 1 piece Aluminium anodized E6 / EV1 160 x 61 mm, L = 110 mm ................... pc(s)
860063 U-bracket 1 packet of 10 pcs Aluminium anodized E6 / EV1 16 x 45 mm, L = 100 mm ................ pack(s)
860049 Rubber U-profile 1 x 6 m roll for 21 mm glass
................... roll(s)
860056 Rubber U-profile 1 x 6 m roll for 25 mm glass
................... roll(s)
860117 End plate (stainless steel) 1 packet of 2 pcs with rubber coating incl. 12 screws ................ pack(s)
860094 Drainage profile (stainless steel) 1 piece with hose connection point Ø16 ................... pc(s)
860100 Hose package 1 packet of: PVC hose (transparent) Internal diameter 16 mm 1 x 3 mroll Hose clips (stainless steel) 2 pieces Wall mounting clips (stainless steel) 6 pieces ................ pack(s) 860162 Installation set, consisting of: 1 packet of: Plastic support pads 20 x 100 x 3mm 30 pieces 20 x 100 x 1mm 20 pieces Adjusting wedges, PVC 30 x 115mm, D=1-18mm 10 pieces Cable ties, 280 x 4.5mm 10 pieces ................ pack(s)
Aluminium alloy = EN AW 6060, T66 (AlMgSi 0.5)38
www.litefront.com
LF'15_Bestellung1 (1:4)Litefront - Bestellung / Artikel
LF'15_Bestellung1 (1:4)Litefront - Bestellung / Artikel
LF'15_Bestellung2 (1:4)Litefront - Bestellung / Artikel
LF'15_Bestellung2 (1:4)Litefront - Bestellung / ArtikelLF'15_Bestellung2 (1:4)
Litefront - Bestellung / Artikel
LF'15_Bestellung2 (1:4)Litefront - Bestellung / Artikel
LF'15_Bestellung2 (1:4)Litefront - Bestellung / Artikel
LF'15_Bestellung3 (1:4)Litefront - Bestellung / Artikel
LF'15_Bestellung3 (1:4)Litefront - Bestellung / Artikel
LF'15_Bestellung3 (1:4)Litefront - Bestellung / Artikel
LF'15_Bestellung3 (1:4)Litefront - Bestellung / Artikel
LF'15_Bestellung3 (1:4)Litefront - Bestellung / Artikel
Order form
System Art. No. Name Packaging Order: 860124 Litefront Filler 1 packet of 12 pcs High Track, 290 ml
............... pack(s)
860148 Litefront Silicone 1 packet of 12 pcs Multiplo Allround black, 310 ml ............... pack(s)
860247 Filler rod (hard) Ø 7.3 1 packet* of 6 pieces x 1 m for 21 mm glass
............... pack(s)
860230 Filler rod (hard) Ø 5.3 1 packet* of 6 pieces x 1 m for 25 mm glass
............... pack(s)
860261 Filler string (soft) Ø 7.5 1 x 6m roll* for 21 mm glass
.................. pc(s)
860254 Filler string (soft) Ø 5.5 1 x 6m roll* for 25 mm glass
.................. pc(s)
860285 Roll-in tool 1 piece for filler string
.................. pc(s)
860377 Dry glazing rubber seal 1 x 12 m roll* for 21 mm glass, black
................. roll(s)
860360 Dry glazing rubber seal 1 x 12 m roll* for 25 mm glass, black
.................. roll(s)
860421 Dry glazing alignment insert 1 packet* of 36 pieces x 0.33 m for 21 mm glass, black
................ pack(s)
860414 Dry glazing alignment insert 1 packet* of 36 pieces x 0.33 m for 25 mm glass, black
................ pack(s)
860438 Insertion tool 1 packet of 2 pcs for dry glazing alignment insert
................ pack(s)
* for 6 metre balustrades39