10
© 2021 MacroAir Technologies Toll Free: 866 668 3247 Fax: 909 890 2313 www.macroairfans.com Rev. 210525 Item # Description Qty 30-90308-00 Digital Remote Assembly (Standard) 30-04006-00 Controller 4 30-04007-00 Controller 4 + Temperature Sensor 30-04030-00 Controller 30 30-10012-00 AirLynk - BacNet 30-04030-02 Dual Control Enabled Controller 30 (requires AirLynk-BacNet) Item # Options Qty 60-50143-00 Rapid Mount Commercial with I-beam Hardware Kit (up to 5ft drop length) (Standard) 60-50142-00 AVD Universal Mount with I-beam Hardware Kit 60-40049-00 Glulam Hardware Kit Item # Diameter Qty 60-20006-00 6 ft / 1.83 m 60-20008-00 8 ft / 2.44 m 60-20010-00 10 ft / 3.05 m 60-20012-00 12 ft / 3.66 m Item # Options Qty M370-0025-MA AVD 370 Power Unit, 3/4 HP Equivalent AirVolution-D 370 Note: Custom drop lengths greater than 5 ft require guy wires Ultra Efficient, PMAC Direct Drive motor Revolutionary integrated drive/mount/enclosure system* Clearcoat anodized blades Forward, reverse, variable speed Rated for indoor and outdoor use*** Capable of Building Automation Integration (with AirLynk upgrade) and fire alarm Digital wall controller with fault code access STANDARD FEATURES STEP 1: POWER UNIT STEP 2: FAN BLADE DIAMETER STEP 4: MOUNTING * Patent Pending - U.S. Provisional Application No. 63/157,965 ** Pending UL 507 *** Fan unit only STEP 5: CONTROLS The next generation of air movement is here and engineered for maximum performance with peak efficiency. Ideal for ceiling heights as low as 12 feet, the AirVolution-D 370 commercial ceiling fan is the perfect airflow solution for cooling your smaller spaces. A sleek design and custom color options add to its appeal, making these fans the most attractive ceiling fans on the market. 24" [.609m] 26.5" [.673m] ILLUSTRATION SHOWN WITH STANDARD DROP LENGTH ** Item # Diameter Qty 30-05005-00 100-120V Single Phase, 50/60Hz 31-21010-00 208-240V Single Phase, 50/60Hz STEP 3: VOLTAGE

Upload: others

Post on 01-Oct-2021

1 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: AirVolution-D 370

Rev. Date 040218 © 2018 MacroAir Technologies Toll Free: 866 668 3247 Fax: 909 890 2313 www.macroairfans.com 20© 2021 MacroAir Technologies Toll Free: 866 668 3247 Fax: 909 890 2313 www.macroairfans.com Rev. 210525

Item # Description Qty

30-90308-00 Digital Remote Assembly (Standard)

30-04006-00 Controller 4

30-04007-00 Controller 4 + Temperature Sensor

30-04030-00 Controller 30

30-10012-00 AirLynk - BacNet

30-04030-02 Dual Control Enabled Controller 30 (requires AirLynk-BacNet)

Item # Options Qty

60-50143-00 Rapid Mount Commercial with I-beam Hardware Kit (up to 5ft drop length) (Standard)

60-50142-00 AVD Universal Mount with I-beam Hardware Kit

60-40049-00 Glulam Hardware Kit

Item # Diameter Qty

60-20006-00 6 ft / 1.83 m

60-20008-00 8 ft / 2.44 m

60-20010-00 10 ft / 3.05 m

60-20012-00 12 ft / 3.66 m

Item # Options Qty

M370-0025-MA AVD 370 Power Unit, 3/4 HP Equivalent

AirVolution-D 370

Note: Custom drop lengths greater than 5 ft require guy wires

• Ultra Efficient, PMAC Direct Drive motor• Revolutionary integrated drive/mount/enclosure system*• Clearcoat anodized blades• Forward, reverse, variable speed • Rated for indoor and outdoor use***• Capable of Building Automation Integration (with AirLynk

upgrade) and fire alarm• Digital wall controller with fault code access

STANDARD FEATURES

STEP 1: POWER UNIT

STEP 2: FAN BLADE DIAMETER

STEP 4: MOUNTING

* Patent Pending - U.S. Provisional Application No. 63/157,965

** Pending UL 507

*** Fan unit only

STEP 5: CONTROLS

The next generation of air movement is here and engineered for maximum performance with peak efficiency. Ideal for ceiling heights as low as 12 feet, the AirVolution-D 370 commercial ceiling fan is the perfect airflow solution for cooling your smaller spaces. A sleek design and custom color options add to its appeal, making these fans the most attractive ceiling fans on the market.

24" [.609m]

26.5" [.673m]

ILLUSTRATION SHOWN WITHSTANDARD DROP LENGTH

**

Item # Diameter Qty

30-05005-00 100-120V Single Phase, 50/60Hz

31-21010-00 208-240V Single Phase, 50/60Hz

STEP 3: VOLTAGE

Page 2: AirVolution-D 370

Rev. Date 040218 © 2018 MacroAir Technologies Toll Free: 866 668 3247 Fax: 909 890 2313 www.macroairfans.com 21© 2021 MacroAir Technologies Toll Free: 866 668 3247 Fax: 909 890 2313 www.macroairfans.com Rev. 210525

AirVolution-D 370

Item # Length (ft/in) Length (m) Qty

5x-D01in-02 1 ft* 0.30 m

5x-D0200-02 2 ft (Standard) 0.61 m

5x-D0300-02 3 ft 0.91 m

5x-D0400-02 4 ft 1.22 m

5x-D0500-02 5 ft 1.52 m

5x-D0600-02 6 ft 1.83 m

5x-D0700-02 7 ft 2.13 m

5x-D0800-02 8 ft 2.44 m

5x-D0900-02 9 ft 2.74 m

5x-D1000-02 10 ft 3.05 m

5x-Dftin-02** Customization fee

STEP 5: STOCK DROP LENGTHS

OPTIONAL: POWDER COATING

yy = ft, fan diameter

For powder coating colors, please refer to Appendix A.

Item # Diameter Estimated Lead Time Qty

60-20006-02 6 ft / 1.83 m 15 business days

60-20008-02 8 ft / 2.44 m 15 business days

60-20010-02 10 ft / 3.05 m 15 business days

60-20012-02 12 ft / 3.66 m 15 business days

Special Finishes

60-201yy-00(Light Oak Wood Grain)

All Diameters --

Mounting hardware & drop length

All Diameters 15 business days

Hub Cover All Diameters 15 business days

Item # Description Qty

10-60200-00 AVD Fuse Disconnect Switch*

ADDITIONAL OPTIONS

DROP LENGTH is the distance from fan mounting point to the blades.

AirVolution-D fans can only be connected with a single-piece of custom length drop tube.

Measure the distance from the fan’s mounting point down to the desired fan blade position and provide this information with the fan order to receive the correct custom drop length. Guy wires kits are provided and required in all situations where a drop length of greater than 5 feet.

For custom drop lengths, order a length

longer and MacroAir will cut it down to

the requested length. Estimated lead

time is 10 business days.

x = 0 for Rapid Mount Commercial, or 1 for AVD Universal Mount

ft = length in feet (i.e. 04 for 4 feet, 10 for 10 feet)in = length in inches (i.e. 05 for 5 inches, 10 for 10 inches) *1 ft is the shortest allowed drop length for AVD-370. Lengths shorter than the standard drop lengthare not recommended and will not work for some fan diameters. Consult MacroAir for more details.To order custom Drop Length or length greater than 10 ft, please call MacroAir.

Do you have a custom color in mind? Custom powder coating is available for all our blades, mounts and drop lengths.

*IEC Compliance requires a fused disconnect switch. If you order a disconnect for your AVD 370 fan, you will still need to provide the appropriate fuse. Recommended fuses are listed on the subsequent page.

Page 3: AirVolution-D 370

Rev. Date 040218 © 2018 MacroAir Technologies Toll Free: 866 668 3247 Fax: 909 890 2313 www.macroairfans.com 22© 2021 MacroAir Technologies Toll Free: 866 668 3247 Fax: 909 890 2313 www.macroairfans.com Rev. 210525

BASIC SPECIFICATIONS

AIRFOIL DIAMETER 6ft 8ft 10ft 12ft

Airfoil Style 4.5” Extruded Anodized Aluminum Airfoil

Number of Airfoils 6

PERFORMANCE

Max Speed 164 RPM 140 RPM 94 RPM 65 RPM

Recommended Spacing*28 ft

[8.5 m]36 ft

[11 m]40 ft

[12.2 m]48 ft

[14.6 m]

Max Affected Area1,400 ft2

[130 m2]2,400 ft2

[223 m2]3,200 ft2

[297 m2]4,000 ft2

[371 m2]

Sound Level dBA at Max Speed** 45 55 56 48

HANGING REQUIREMENTS

Hanging Weight71 lbs

[32.21 kg]79 lbs

[35.83 kg]86 lbs

[39.01 kg]93 lbs

[42.18 kg]

Max Torque4 ft-lb[5 Nm]

13 ft-lb[18 Nm]

20 ft-lb[27 Nm]

19 ft-lb[26 Nm]

Max Thrust in Reverse2 lbs

[0.9 kg]4 lbs

[1.8 kg]6 lbs

[2.7 kg]7 lbs

[3.2 kg]

MOTOR AND DRIVE TRAIN

Motor Type Gearless Direct Drive

Equivalent Horsepower Rating 3/4 HP

Operating Temp Range 16°F [-10C°] - 122 F° [50C°]

MAX AMP DRAW / RECOMMENDED FUSE

110 VAC Single Phase*** 5A / 7.5A 8A / 12A 9A / 15A 7A / 10A

208 VAC Single Phase 2.36A / 5A 4A / 7.5A 4.2A / 7.5A 3.4A / 5A

POWER AND CONTROLS

Power Source Low Single Phase 110-120 VAC 50/60 Hz / Single Phase 208-240 VAC 50/60 Hz

Control Options Digital Touchpad, MacroAir Controller 30, AirLynk - BacNet

INSTALLATION

Mounting Hardware Rapid Mount Commercial

Drop LengthIn addition to the standard drop length supplied, optional drop lengths are available in 1ft increments; total drop lengths

5ft and greater require Universal Mounting Hardware with guy wires

RATINGS AND COMPLIANCE

Fire and Sprinkler NFPA Compliant

Outdoor Rating**** Rated for outdoor use

Certifications UL 507 Pending

*For spacing between fan units based on the dimensions of a specific space please refer to https://macroairfans.com/airviz.

**Sound testing taken with the sensor 5 ft above the ground and 20 ft from the center of the fan at 20 ft high.

***Preliminary Test Results

****Applicable to the fan unit only, does not include controller and accessories.

AirVolution-D 370

Page 4: AirVolution-D 370

Rev. Date 040218 © 2018 MacroAir Technologies Toll Free: 866 668 3247 Fax: 909 890 2313 www.macroairfans.com 27© 2021 MacroAir Technologies Toll Free: 866 668 3247 Fax: 909 890 2313 www.macroairfans.com Rev. 210525

MacroAir Controllers - Digital Remote

Note: Only one type of controller can be used when selecting Controller 4, Digital Remote Assembly or Analog Remote Assembly. AirLynk (BacNet) can be used as a stand alone, or paired with a Dual Control Enabled Controller 30 (see Dual Control page) or with Local Override Remotes for some fan models (see Local Override page)

• Standard on all MacroAir fan models (Except AirLegacy)

• Simple and intuitive control

• Easy ground-level troubleshooting and diagnostics

Features Digital Touchpad Remote

Item # 30-90308-00

# Fans Controlled 1 fan

Display 2.8 TFT

Resolution 240x320x16 pixels

Backlight life time 20,000 hours

Backlight brightness 160 cd/m2

Shock IEC 60068-2-27

Vibration IEC 60068-2-6

Rating (front) IP 40 / NEMA 1

Weight (incl. enclosure) 375 g

Communication Protocol RS 485

Power Supply 24V from fan

Size (incl. enclosure) 91.2 x 135.5 x42.0

Operating Temperature -4o to 158oF / -20o to +70oC

Storage Temperature -22o to 176oF / -30o to +80oC

Page 5: AirVolution-D 370

Rev. Date 040218 © 2018 MacroAir Technologies Toll Free: 866 668 3247 Fax: 909 890 2313 www.macroairfans.com 28© 2021 MacroAir Technologies Toll Free: 866 668 3247 Fax: 909 890 2313 www.macroairfans.com Rev. 210525

• Available upgrade for all MacroAir fan models (Except

AirLegacy)

• Control up to 4 fans from a single point

• Control fans individually, independent of speed &

direction

• Simple and intuitive control

• Temperature sensor (optional upgrade) starts and stops

the fan(s)

Features Controller 4 Controller 4 with temperature sensor

Item # 30-04006-00 30-04007-00

# Fans Controlled Up to 4 fans, individually

Display 2.8 TFT

Resolution 240x320x16 pixels

Backlight life time 20,000 hours

Backlight brightness 160 cd/m2

Shock IEC 60068-2-27

Vibration IEC 60068-2-6

Rating (front) IP 40 / NEMA 1

Weight (incl. enclosure) 375 g

Communication Protocol RS 485

Power Supply 24V from fan

Size (incl. enclosure) 91.2 x 135.5 x42.0

Operating Temperature -4o to 158oF / -20o to +70oC

Storage Temperature -22o to 176oF / -30o to +80oC

MacroAir Controllers - Controller 4

Note: Only one type of controller can be used when selecting Controller 4, Digital Remote Assembly or Analog Remote Assembly. AirLynk (BacNet) can be used as a stand alone, or paired with a Dual Control Enabled Controller 30 (see Dual Control page) or with Local Override Remotes for some fan models (see Local Override page)

Page 6: AirVolution-D 370

Rev. Date 040218 © 2018 MacroAir Technologies Toll Free: 866 668 3247 Fax: 909 890 2313 www.macroairfans.com 29© 2021 MacroAir Technologies Toll Free: 866 668 3247 Fax: 909 890 2313 www.macroairfans.com Rev. 210525

MacroAir Controllers - Controller 30

Features Controller 30

Item # 30-04030-00

# Fans Controlled 30 fans

Display 10.1” (16:9), TFT-LCD with LED backlight

Resolution 1024x600 pixels

Backlight life time 50000 hours

Backlight brightness 500 cd/m2

Shock 15g, half-sine, 11ms according to IEC60068-2-27

Vibration 1g, according to IEC 60068-2-6, Test Fc

Sealing front IP65, NEMA 4X/ 12 and UL Type 4X/ 12

Sealing back (excl. enclosure) IP20

Weight (incl. enclosure) 10 lb / 4.5 kg

Communication Protocol MODBUS RS485

Ethernet Port 2x100 Mbit

USB Port 2

Power Supply 110-240 V

Size (incl. enclosure) 10.7 x 13.0 x 3.7 in (W x H x D) / 272 x 330 x 84 mm (W x H x D)

Operating Temperature 14o to 140oF / -10o to +60oC

Storage Temperature -4o to 158oF / -20o to +70oC

Languages English, Spanish, French, Malay

• Available upgrade for all MacroAir fan models

(except AirLegacy)

• Provides a single point for individual or group fan

control

• Enables run time, scheduling, grouping, and fan

naming

• Secure remote login to controller via smart device

or computer

• Optional auto mode available with AirEffect

• Password protection capabilities for scheduling,

naming, and temperature/humidity (with upgrade

to AirEffect)

STANDARD FEATURES

Note: Only one type of controller can be used when selecting Controller 4, Digital Remote Assembly or Analog Remote Assembly. AirLynk (BacNet) can be used as a stand alone, or paired with a Dual Control Enabled Controller 30 (see Dual Control page) or with Local Override Remotes for some fan models (see Local Override page)

Page 7: AirVolution-D 370

Rev. Date 040218 © 2018 MacroAir Technologies Toll Free: 866 668 3247 Fax: 909 890 2313 www.macroairfans.com 30© 2021 MacroAir Technologies Toll Free: 866 668 3247 Fax: 909 890 2313 www.macroairfans.com Rev. 210525

AirEffect Temperature Control

Features AirEffect (up to 4 zones)

Item # 30-04009-00

Number of Sensors 2 (1 floor & 1 ceiling)

Measured temperatures -40 through +125 °C (±2 to ±4 %)

Measured humidity 0 through 100% RH (±2 to ±4 %)

Communication Protocol MODBUS RS485

• Senses and maintains desired room temperature

• Measurers temperature and humidity at two points (ceiling & floor)

• Calculates heat index through temperature and humidity calculations

• Runs fans in reverse or forward direction in response to heat index

• Compatible with all fans (except AirLegacy)

• Independent, external sensors allow the controllers to be mounted in a different room than the fans and sensors

AirEffect (only available with Controller 30) is an optional control system that senses and automatically maintains a desired room

temperature. AirEffect gages the heat index by measuring the temperature and humidity at the ceiling and floor. To achieve the

desired temperature, AirEffect takes the heat index and calculates the fan’s ideal operating speed and direction and runs the fans

accordingly. Simply setup AirEffect to the desired temperature range and enjoy a consistently comfortable environment.

STANDARD FEATURES

*Controller not included

Page 8: AirVolution-D 370

Rev. Date 040218 © 2018 MacroAir Technologies Toll Free: 866 668 3247 Fax: 909 890 2313 www.macroairfans.com 31© 2021 MacroAir Technologies Toll Free: 866 668 3247 Fax: 909 890 2313 www.macroairfans.com Rev. 210525

Gives the ability to control your fans through BACnet® (MS/TP or IP) and LonWorks®.

BACnet and LonWorks are both protocols used to automate or manage buildings systems (commonly called a BMS or BAS). Our fans use MODBUS to communicate and the correct use of AirLynk, MacroAir’s interface, will allow the integration of our fans intoa BMS/BAS. A BMS/BAS enables you to run the fans in conjunction with your HVAC system to help save energy costs.

Our proven solution is AirLynk, an external, high-performance building automation multi-protocol interface that is pre configuredto communicate between any MacroAir fan and various building automation protocols including: BACnet®MS/TP, BACnet/IP, Modbus TCP/IP, and LonWorks®.

Successful integration of any MacroAir fan with a BMS/BAS is dependent upon following these guidelines:

• Identify the BMS and its protocol before the purchase order is placed. This allows the fans to be pre programmed, dramatically reducing installation errors and integration time.

• Strictly adhere to the included installation manual to eliminate issues that will occur from wrong types of wire, improper wire terminations or wire routing.

• We highly recommend engaging our Controls Engineers to visit the site for fan start-up to ensure a smooth and successful integration. Our experience has found that many installers are unfamiliar with the subtle but critical differences between BMS systems, interfaces, fan models, connection methods and best practices. For a nominal fee plus travel expenses, one of our Controls Engineers can be on site to ensure a smooth and successful start-up. For more information about this service, please inquire with our Technical Services Department.

To Order BMS enabled fans and AirLynk please do the following:

• Identify the BMS network• Discuss your network with MacroAir’s Control Engineers• Order one AirLynk to connect up to 30 fans

AirLynk BMS Integration

Item # Description

30-10012-00 AirLynk - BACnet, (Works on all Fan Lines, except AirLegacy), Up to 30 Fans per AirLynk

30-10011-00 AirLynk - LonWorks, (Works on all Fan Lines, except AirLegacy), Up to 30 Fans per AirLynk

30-90315-00 Local Override Remote (each fan) for BMS (Works on all Fan Lines, except AirLegacy and AVD 370)

30-04030-02 Dual Control Enabled Controller 30 (Works on all Fan Lines, except AirLegacy) Up to 30 Fans per AirLynk

10-80632-00 Repeater (required for some older model fans; contact your sales rep for details)

Note: Only one type of controller can be used when selecting Controller 4, Digital Remote Assembly or Analog Remote Assembly. AirLynk (BacNet) can be used as a stand alone, or paired with a Dual Control Enabled Controller 30 (see Dual Control page) or with Local Override Remotes for some fan models (see Local Override page)

AirLynk BMS Integration

Page 9: AirVolution-D 370

Rev. Date 040218 © 2018 MacroAir Technologies Toll Free: 866 668 3247 Fax: 909 890 2313 www.macroairfans.com 33© 2021 MacroAir Technologies Toll Free: 866 668 3247 Fax: 909 890 2313 www.macroairfans.com Rev. 210525

• Seemless integration of a building management

system and local fan network

• Fans take last known command, be it from

the BMS, the Dual Control enabled Network

Controller 30 screen(s), or VNC enabled smart

devices

• Provides a single point of local control of up to 30

fans

• Enables grouping and fan naming

• Password protection capabilities for operation,

naming, and grouping

• Requires AirLynk (BacNet) and Dual Control

Enabled Controller 30*

STANDARD FEATURES

Dual Control for BMS Integration

*AirEffect is not compatible with Dual Control. Temperature monitoring by BMS can regulate fan operation.

Page 10: AirVolution-D 370

Rev. Date 040218 © 2018 MacroAir Technologies Toll Free: 866 668 3247 Fax: 909 890 2313 www.macroairfans.com 37© 2021 MacroAir Technologies Toll Free: 866 668 3247 Fax: 909 890 2313 www.macroairfans.com Rev. 210525

Fan Placement & Clearance

© 2017 MacroAir Technologies Toll Free: 866 668 3247 Fax: 909 890 2313 www.macroairfans.com 6

Rev. Date 050917

HVAC Diffuserwith airflow UNDER fan

HVAC Diffuserwith airflow ABOVE fan

Fan Placement & Clearance

space from diffuser

space from diffuser

at least 1.5 x diameter away from intake/discharge

at least 2 x diameter away from intake/discharge

spacing between fans

space from wall

at least 1.5 x diameter away from the wall

at least 3 x diameter of the fans apart

© 2015 MacroAir Technologies Toll Free: 866 668 3247 Fax: 909 890 2313 www.macroairfans.com Rev. 090315

BA

Fluorescent LightLight

Ambient light

Light

General Notes:

Dimension "A": The smaller the distance between the light and the blade, the higher concentration and frequency of shuttering. So the greater distance "A" is from the fan blade, the less the shuttering effect.

Dimension "B": The closer the light is located to the center of the fan, the higher the frequency of shuttering.

Ambient light: Another variable increasing the shuttering effect is the amount of ambient light available. The more lights, the less the effect. As shown, the more overlapping patterns the less shuttering/strobing. The type of light can also influence the effect. For example, a domed light is more sensitive than a fluorescent tube.

Summary: Variables that affect strobing are (1) blade to light height, (2) the fan center to light dimension, and (3) the amount of ambient light within the space. To minimize theSummary: Variables that affect strobing are (1) blade to light height, (2) the fan center to light dimension, and (3) the amount of ambient light within the space. To minimize thepossible negative effects of strobing, follow all MacroAir installation instructions including clearance requirements.

LIGHT SHUTTERING/STROBING WITH HVLS FAN SYSTEMS