Air Quality Node Descriptions Highlights: The RS485 are hardened up for overvoltage and power supply crossed over. Display in degrees Fahrenheit or Celsius(connection to Bacnet). The LCD is a bitmap so we can show network connectivity. The user can configure what they want to show on the dis- play: network activiy, baud rate, protocol, etc. You can show a user setpoint so you can use it as a room / setpoint display. RS485/Bacnet MS/TP for direct digital reading on all mod- els Air Quality Node is designed for environment monitoring and controlling in industrial, commercial and other buildings. These transmitters can be used to monitor air quality and temperature in various industrial and commercial settings. Modbus RS485/Bacnet MS/TP for direct digital reading on all models. Specifications Typical Applica- tion Wall mount indoors RS485 ports 1 Power 15-24V +/- 10%, AC or DC, 1 watt typical Operating Temp -30~+60°C, 0-95% non condensing Plastic Housing Flammability rating UL 94V0 file E194560 Display LCD screen, Resolution 0.1°C, 0.1% RH Control Features N/A Analog Output 10v 4-20mA Protocols Bacnet&Modbus TEMP Sensor Type 10K thermistor Range -40~150°C(-60~340°F) Accuracy < ±0.5°C @ 25°C Output 4-20mA, 0-5V or 0-10V, RS 485 Relative Humidity Sensor Type Capacitance polymer Range 0~100% non condensing Accuracy 3% RH (25°C, 20~80% RH) Output 4-20mA, 0-5V or 0-10V, RS 485 AQ Sensor Type TGS2600 Size 80.5 (L)x 80.5(W)x22.4(H)mm AQ-N-LCD AQ-N

Upload: others

Post on 10-Apr-2022

3 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Air Quality Node Descriptions

Air Quality Node

Descriptions

Highlights:• TheRS485arehardenedupforovervoltageandpowersupplycrossedover.• DisplayindegreesFahrenheitorCelsius(connectiontoBacnet).• TheLCDisabitmapsowecanshownetworkconnectivity.• Theusercanconfigurewhattheywanttoshowonthedis-play:networkactiviy,baudrate,protocol,etc.• Youcanshowausersetpointsoyoucanuseitasaroom/setpointdisplay.• RS485/BacnetMS/TPfordirectdigitalreadingonallmod-els

AirQualityNodeisdesignedforenvironmentmonitoringandcontrollinginindustrial,commercialandotherbuildings.Thesetransmitterscanbeusedtomonitorairqualityandtemperatureinvariousindustrialandcommercialsettings.ModbusRS485/BacnetMS/TPfordirectdigitalreadingonallmodels.

SpecificationsTypical Applica-tion

Wallmountindoors

RS485 ports 1Power 15-24V+/-10%,ACorDC,1watttypicalOperating Temp -30~+60°C,0-95%noncondensingPlastic Housing FlammabilityratingUL94V0fileE194560Display LCDscreen,Resolution0.1°C,0.1%RHControl Features N/AAnalog Output10v4-20mAProtocols Bacnet&ModbusTEMP SensorType 10Kthermistor

Range -40~150°C(-60~340°F)Accuracy <±0.5°C@25°COutput 4-20mA,0-5Vor0-10V,RS485

Relative Humidity SensorType CapacitancepolymerRange 0~100%noncondensingAccuracy 3%RH(25°C,20~80%RH)Output 4-20mA,0-5Vor0-10V,RS485

AQ SensorType TGS2600Size 80.5(L)x80.5(W)x22.4(H)mm

AQ-N-LCD

AQ-N

Page 2: Air Quality Node Descriptions

Air Quality Node

Dimension

AQ-N-LCD

AQ-N

Page 3: Air Quality Node Descriptions

Air Quality Node

Backplate Features

Toinsertwiresintothenuscrewterminalsthereisasmalltrickwhichmaynotbeapparenttofolkswhohavenotusedtheseterminalsbefore.Stripthewireabouthalfacentimeterandtwistthestandstogetherifitsstrandedconductor,Gentlypresstheendofasallflatscrewdriverintothewireentryport,insertthewireintotheholewhilemaintainingpressurewiththescrew-driver.Releasethescrewdriverandtheconnectionismade.Tugonthewiretomakesurethere’sgoodcontactthewireshouldnotpullout.

Page 4: Air Quality Node Descriptions

Air Quality Node

Modbus Register List

Address Bytes Register Description

0to3 4 SerialNumber-4bytevalue.Read-only4to5 2 SoftwareVersion–2bytevalue.Read-only6 1 ADDRESS.DefaultModbusdeviceaddress=2547 1 ProductModel.Thisisaread-onlyregisterthatisusedbythemicrocontroller

todeterminetheproduct8 1 HardwareRevision.Thisisaread-onlyregisterthatisusedbythemicrocon-

trollertodeterminethehardwarerev9 1 PICfirmwareversion10 1 PLUG_N_PLAY_ADDRESS,‘plugnplay’address,usedbythenetwork

mastertoresolveaddressconflicts.SeeVCcodeforalgorithms15 1 BaudrateSetting:0=9600bps,1=19200bps,2=38400bps,3=57600bps,4=11

5200bps16 1 FirmwareUpdateRegister,usedtoshowthestatusoffirmwareupdates

17to99 Blank,forfutureuse100 2 adcvalueofco2voltageoutput,notused,readonly101 2 adcvalueoftemperaturevoltageoutput,notused,readonly102 2 adcvalueofhumidityvoltageoutput,notused,readonly103 2 adcvalueofco2currentoutput,notused,readonly104 2 adcvalueoftemperaturecurrentoutput,notused,readonly105 1 adcvalueofhumiditycurrentoutput,notused,readonly106 2 adcvalueofonboardthermistorsensor,readonly107 2 adcvalueofonboardlightsensor,readonly108 2 co2value(ppm).Itwillbecalibratedifwritetoit.109 2 co2calibrationoffset.Usercanchangeittocalibratetheco2ppm.Itwillbe

changedalsoifuserwritethedatatoregisterco2ppm110 1 Deltavalueforeliminatingthepulseppmvalue.Thedefaultvalueis200.111 2 Fitlertimes,maketheppmvaluegosmooth.Thedefaultvalueis5.112 2 Thefairalarmppmsetpointofco2sensor.113 2 Thepooralarmppmsetpointofco2sensor.114 1 co2alarmstatus:

0b'xxxx1xxx':co2poor0b'xxxx01xx':co2fair0b'xxxx001x':co2good

115 1 theversionnumberofhumiditysensor116 2 therelativehumidity117 2 thefrequencyvaluereadfromhumiditysensor,readonly118 1 thenumberofcalibrationpointsofthehumiditysensor119 2 degreecelsiustemperaturevalueofthehumiditysensor120 2 degreefahrenheittemperaturevalueofthehumiditysensor121 2 celsiusdegreetemperaturevalueoftheonboardthermistorsensor

Page 5: Air Quality Node Descriptions

Air Quality Node

Modbus Register List

Address Bytes Register Description

123 2 theoffsetforcalibratingtheonboardthermistorsensor124 1 selectthetemperaturedirecttoanalogoutput:

0:onboardthermistorsensor,defaultsetting1:humiditysensor

125 1 selectthetemperatureunitdirecttoanalogoutput:0:degreecelsius1:degreefahrenheit,defaultsetting

126 2 Lightingvalue,forfeature127 1 analogoutputmode,changeitbysettingthejumper(J20)ontheboard,read

only128 2 theminimumvalueoftemperaturedirectstotheanalogoutput129 2 themaximumvalueoftemperaturedirectstotheanalogoutput130 2 theminimumvalueofhumiditydirectstotheanalogoutput131 2 themaximumvalueofhumiditydirectstotheanalogoutput132 2 theminimumvalueofco2directstotheanalogoutput133 2 themaximumvalueofco2directstotheanalogoutput

e.g.co2output:iftheco2ppmis1000,the(minimumvalue,maximumvalue)=(0,3000),then1.settingJ20toselect0V-10Voutputmode,sotheco2outputisabout((1000ppm/(3000ppm-0ppm))*(10V-0V))+0V=3.3V2.settingJ20toselect0V-5Voutputmode,sotheco2outputisabout((1000ppm/(3000ppm-0ppm))*(5V-0V))+0V=1.65V3.settingJ20toselect4mA-20mAoutputmode,sotheco2outputisabout((1000ppm/(3000ppm-0ppm))*(20mA-4mA))+4mA=9.3mA

184 2 AQvalue

500 1 co2automaticcompensationbackgroundenalbeordisable.0=Disable,1=En-able.

501 2 “BackgroundC02”,defaultis400ppm,minimumis390,maxis500.

502 1 Maximumadjustmentperday”defaultis1ppm,maxis10ppm,minimumis1.

503 1 “Numberofdaystowatchforminimum”,defaultis7days.Maxis30days.Minimumis2days.

505 2 co2backgroundcalibrationoffset.

Page 6: Air Quality Node Descriptions

Air Quality Node

Bacnet Register List

Value ValueandDescription

AV1 SerialNumberLowByteAV2 SerialNumberHighByteAV3 SoftWareVersionAV4 ModbusidAV5 ProductModelAV6 InstanceAV7 StationNumberAV8 BaudRateAV9 UpdateAV10 Protocolswitch.0=MODBUS,1=MSTP.

AV11 Auto/Manual,Analogoutputauto/manualcontrol.Bit1directstotemperatureoutput,0=Auto,1=Manual.

AV12 DewPointAV13 PasswordsAV14 MixingRatio,themassofwateroverthemassofdrygas,[g/kg]AV15 Enthalpyoftheair,[kJ/kg]AV16 SpareAV17 TemperatureOffset

AV18~AV19 SpareAV20 TemperatureFilterAV21 SpareAV22 TemperatureUnitAV23 OutputMode

AV24~AV25 SpareAV26 MinimalRangefortemperatureAV27 MaxiumRangefortemperature

AV28~AV30 SpareAV31 TemperatureSetpointAV32 Spare

AnalogIntput AnalogInputandDescription

AI1 SpareAI2 TemperatureAI3 Spare

AI4 AQ

Page 7: Air Quality Node Descriptions

Air Quality Node

AnalogOutput AnalogOutputandDescription

AO1 SpareAO2 TemperatureAO3 Spare