FLOOR STANDING TYPE DUCT TYPE COOLING ONLY 50Hz AIR COOLED PACKAGED AIR CONDITIONERS Suitable for factories PCTPSG1812Aaprv All rights reserved AK c Specifications, designs and other content appearing in this brochure are current as of September 2018 but subject to change without notice. 1. Air conditioners should not be installed in areas where corrosive gases, such as acid gas or alkaline gas, are produced. 2. If the outdoor unit is to be installed close to the sea shore, direct exposure to the sea breeze should be avoided. If you need to install the outdoor unit close to the sea shore, contact your local distributor. Cautions on product corrosion Ask a qualified installer or contractor to install this product. Do not try to install the product yourself. Improper installation can result in water or refrigerant leakage, electrical shock, fire or explosion. Use only those parts and accessories supplied or specified by Daikin. Ask a qualified installer or contractor to install those parts and accessories. Use of unauthorised parts and accessories or improper installation of parts and accessories can result in water or refrigerant leakage, electrical shock, fire or explosion. Read the user's manual carefully before using this product. The user's manual provides important safety instructions and warnings. Be sure to follow these instructions and warnings. If you have any enquiries, please contact your local importer, distributor and/or retailer. IE3 MOTOR VERSION DUCT CONNECTION TYPE DIRECT AIR BLOW TYPE FVPGR10-20NY1G (IE3 Motor) FVGR05-10NV1 DUCT TYPE FDR05-20NY1G (IE3 Motor) FLOOR STANDING TYPE

Upload: others

Post on 24-Mar-2020

66 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: AIR COOLED PACKAGED AIR CONDITIONERS Cooled... · the outdoor unit. (Applies to all outdoor units) (Applies to RUR05N/06N) AIR COOLED PACKAGED AIR CONDITIONERS Previous 20HP outdoor

FLOOR STANDING TYPEDUCT TYPE

COOLING ONLY 50Hz

AIR COOLED PACKAGEDAIR CONDITIONERS

Suitable for

factories

PCTPSG1812Aaprv

All rights reservedAK

c

Specifications, designs and other content appearing in this brochure are current as of September 2018 but subject to change without notice.

1. Air conditioners should not be installed in areas where corrosive gases, such as acid gas or alkaline gas, are produced.2. If the outdoor unit is to be installed close to the sea shore, direct exposure to the sea breeze should be avoided. If you need to install the outdoor unit close to the sea shore, contact your local distributor.

Cautions on product corrosion

Ask a qualified installer or contractor to install this product. Do not try to install the product yourself. Improper installation can result in water or refrigerant leakage, electrical shock, fire or explosion.

Use only those parts and accessories supplied or specified by Daikin. Ask a qualified installer or contractor to install those parts and accessories. Use of unauthorised parts and accessories or improper installation of parts and accessories can result in water or refrigerant leakage, electrical shock, fire or explosion.

Read the user's manual carefully before using this product. The user's manual provides important safety instructions and warnings. Be sure to follow these instructions and warnings.

If you have any enquiries, please contact your local importer, distributor and/or retailer.

IE3 MOTOR VERSION

DUCT CONNECTION TYPEDIRECT AIR BLOW TYPEFVPGR10-20NY1G (IE3 Motor)FVGR05-10NV1

DUCT TYPEFDR05-20NY1G (IE3 Motor)

FLOOR STANDING TYPE

Page 2: AIR COOLED PACKAGED AIR CONDITIONERS Cooled... · the outdoor unit. (Applies to all outdoor units) (Applies to RUR05N/06N) AIR COOLED PACKAGED AIR CONDITIONERS Previous 20HP outdoor

DUCT CONNECTION TYPE

DUCT TYPEAir blow via connected ducts

Comfortable air conditioning of the entire factory by connecting a blow duct at the top of the indoor unit.

Note: Ducts to be procured locally.

Nice, cool air in the factory or in the cafeteria

HFC R-410A Line Upfor Factories and Offices

HFC R-410A Line Upfor Factories and Offices

Even when selecting air conditioners, a new model featuring R-410A could

be the perfect step in promoting your corporate image.

Even when selecting air conditioners, a new model featuring HFC R-410A

refrigerant could be the perfect step in promoting your corporate image.

We have entered an era in which being recognized as an environmentally

responsible corporate citizen has taken utmost importance.

We have entered an era in which being recognized as an environmentally

responsible corporate citizen has taken utmost importance.

Product Line Up

1 2

DIRECT AIR BLOW TYPE

Direct air blow from indoor unit with plenum

Comfortable factory air conditioning using multiple indoor units installed in accordance with the space. Installation is next to walls, so units will not affect the factory layout even if the changes are made.

FLOOR STANDING TYPE Cooling only

Cooling only

50Hz

50,000

14.760,000

17.6100,000

29.380,000

23.5160,000

46.9120,000

35.2180,000

52.8200,000

12,600 15,100 25,20020,200 40,30030,200 45,400 50,400

58.65 10 13 1886 15 20

kWCapacity 1, 2

Btu/hkcal/h

RUR10NY1RUR08NY1RUR05NY1 RUR06NY1

RUR10NY1 RUR13NY1 RUR15NY1 RUR18NY1 RUR20NY1

HP

Outdoor unit

Indoor unit

Outdoor unit

Indoor unit

OUTDOOR UNIT

1Rated cooling capacities are based on the following conditions: Return air temp., 27°CDB, 19.5°CWB; outdoor temp. 35°CDB. Equiv. refrigeration piping, 5 m (horizontal). 2Capacity includes indoor fan motor heat.

Note :

Dimensions Page 14,15

DUCT TYPE 50Hz

50,000

14.760,000

17.6100,000

29.3120,000

35.2180,000

52.880,000

23.5160,000

46.9200,000

58.65 10 13 1886 15 20

kWCapacity 1, 2

Btu/hkcal/h

DUCT TYPE

RUR10NY1 RUR13NY1 RUR15NY1 RUR18NY1 RUR20NY1RUR08NY1RUR05NY1 RUR06NY1

HP

Outdoor unit

Indoor unit

OUTDOOR UNIT

Specifications Page 6Dimensions Page 12,13

Dimensions Page 14,15

12,600 15,100 25,20020,200 40,30030,200 45,400 50,400

FVGR08NV1FVGR05NV1 FVGR06NV1

FDR10NY1G FDR13NY1G FDR15NY1G FDR18NY1G FDR20NY1GFDR08NY1GFDR05NY1G FDR06NY1G

FVGR10NV1

FVPGR10NY1G FVPGR13NY1G FVPGR15NY1G FVPGR18NY1G FVPGR20NY1G

DIRECT AIR BLOW TYPE

DUCT CONNECTION TYPE

FLO

OR

STA

ND

ING

TY

PE

Specifications Page 5Dimensions Page 10

Specifications Page 5Dimensions Page 11

Page 3: AIR COOLED PACKAGED AIR CONDITIONERS Cooled... · the outdoor unit. (Applies to all outdoor units) (Applies to RUR05N/06N) AIR COOLED PACKAGED AIR CONDITIONERS Previous 20HP outdoor

3 4

DurabilityHeat exchange fins provided with anti-corrosion treatmentTo achieve increased durability by improved resistance to salt corrosion and atmospheric pollution, coated PE fins (with special acryl pretreatment) are used for the heat exchanger of the outdoor unit.

(Applies to all outdoor units)

(Applies to RUR05N/06N)

AIR COOLED PACKAGED AIR CONDITIONERS

Previous 20HP outdoor unit

Installation space is saved thanks to a more compact outdoor unit. This also makes it easier to install.

Space savings

RUG10AUY1 X 2RUR20NY1

(20HP)

2,560mm690mm

1,240mm765mm

space savedcompared to

previous model

53%

Refrigerant pre charged for up to 7.5 metres

Design flexibilityDesigned for long refrigerant piping. 50 m maximum length and 30 m maximum level difference to cover medium- and large-scale building needs.

Outdoor unit roof installation possible for plenty of leeway.

Allowable refrigerant pipe length and level difference

Max. leveldifference

Pre-charged 1 Max. length

30 m7.5 m 50 m(Equivalent length 70 m)

Note: 1Additional refrigerant charging is required if the refrigerant pipe is longer than the indicated length.

4-direction piping affords more freedom of layoutPiping can be run from the front, bottom, right or rear surface according to how the unit is installed.

In case of RUR08–20N, piping can be drawn out in two directions-front, and under side.

Max. length

Max. level difference

RUR05NY1-20NY1

Easy operationDigital remote control comes standard with indoor unit.

Enhanced varieties of factory modification and optional accesories

Standard model

Factory modification

Auto restart

Floor Standing Type

Fac

tory

Mod

ifica

ion

DuctConnection

Type

Duct Type

Modify wiring for central control adapter kit (DTA107A55) installation

Discharge grill plenum chamber

Side discharge grillon discharge plenum chamber

Front suction high efficiency filter chamber

Suction grill for front suction high efficiency filter chamber

Front suction base flange for front suction high efficiency filter chamber

Rear suction

Drain pump

Remote sensor(Thermistor for suction air)

Central control adaptor kit (external terminal for ON/OFF , abnormal)1 DTA107A55

Opt

ion

BRC1C62LCD remote controller2

DCS601C51intelligent Touch Controller2

DCS302CA61Central remote controller2

DCS301B61Unified ON/OFF controller3

DST301BA61Schedule timer3

KRCS01-1BRemote sensor (thermistor for suction air)3

BRC1NU64Remote controller

Note: 1Wiring modification is needed on floor stand model to connect with central control ADP kit.2Need to use central control adapter kit for option connection.3Central control adapter kit and LCD remote controller is necessary for option connection.

Equipped with scroll compressor for quiet operation

Smooth running, low vibration, low operating sound.

Quiet Operation

Outdoor unitSound level

59 dB

380V 415V

RUR05NY1

59 dB

60 dB

60 dBRUR06NY1

Reliability, long life and premium efficiency motor

Reduce energy consumption, CO2 emissions and the impact of industrial operations on the environment.

For FVPGR10-20NY1GFDR5-20NY1G

IE3 Fan Motor

Temperature setting is possible by button operation. The set temperature is conveniently displayed on the LED.

1453

6789

210

1

2

3

5

6

7

89

Note.1

Note.1

4

1 Power

3 Temperature setting

2 Temperature scale

4 Mode setting

5 Next setting

6 Fan indicator lamp

7 Cool indicator lamp

9 Compressor 1 indicator lamp

10 Temperature sensor

8 Compressor 2 indicator lamp

1 On/Off button

3 Temp. setting up

2 Fan button

4 Temp. setting down

5 Mode button

6 LED display

7 Compressor operation lamp.

8 Fan operation lamp.

9 Cool operation lamp.

Note.1 It cannot be used for FVPGR10–20NY1G

(Standard accessory)Floor standing type

(optional accessory)Duct type

DUCT CONNECTION TYPE

FLOOR STANDING TYPEDIRECT AIR BLOW TYPE

DUCT TYPE

RUR10NY1FDR10NY1G

RUR10NY1FVGR10NV1

RUR10NY1FVPGR10NY1G

Direct Air Blow

Page 4: AIR COOLED PACKAGED AIR CONDITIONERS Cooled... · the outdoor unit. (Applies to all outdoor units) (Applies to RUR05N/06N) AIR COOLED PACKAGED AIR CONDITIONERS Previous 20HP outdoor

RUR05NY1

14.750,000

17.6 23.5

RUR06NY1 RUR08NY1

461,620

541,910

682,400

450X900X85074 81 97

Belt drive9

RUR10NY1

29.360,000 80,000 100,000

12,600 15,100 20,200 25,200

782,750

500X1,330X850108

450X1,130X850 500X1,130X850

92 105 203

2.5 (Charged for 7.5 m) 3.5 (Charged for 7.5 m) 4.5 (Charged for 7.5 m)

Hermetically sealed scroll type

206

6.0 (Charged for 7.5 m)

1,345X900X320 1,680X930X765

4.5 4.5 6.7 9.0

FDR05NY1G FDR06NY1G FDR08NY1G FDR10NY1G

Belt drive

Hermetically sealed scroll type

35.2 46.9

RUR13NY1 RUR15NY1

1364,800

625X1,620X850169

RUR18NY1

52.8 58.6

RUR20NY1

1665,860

625X1,980X850196

120,000 160,000 180,000 200,00030,200 40,300 45,400 50,400

243 319

4.5 (Charged for 7.5 m) 8.0 (Charged for 7.5 m)

322 3291,680X1,240X765

5.0+5.0 6.7+6.7 7.5+7.5 9.0+9.0

FDR13NY1G FDR15NY1G FDR18NY1G FDR20NY1G

Note : 1Rated cooling capacities are based on the following conditions : Return air temp., 27°CDB, 19.5°CWB; outdoor temp. 35°CDB. Equiv. refrigeration piping, 5 m (horizontal). 2Anechoic chamber conversion value, measured according to JIS parameters and criteria. During operation these values are somewhat higher owing to ambient conditions.3Capacity includes indoor fan motor heat.

lvory White

Ivory white Hermetically sealed scroll type

9.0

29.3100,000

802,830

1,740X1,170X510155

6.0 (Charged for 7.5 m)

46.9160,000

4,240120

208

Cooling capacity 1, 3 kWBtu/hkcal/h

Indoorunit

Sound level 2 dBAExt. Static Pressure mmH2O 15

Belt DriveDrive

Refrigerant charge (R-410A) kg

Machine weight kgOperation range °CWB

Air flow rate (H) m3/mincfm

Outdoorunit

Colour

Dimensions (HXWXD)

Colour

mm

Power supply 380–415 V, 50 Hz, 3 Phase, 4 Wires

kWMotor outputCompressor Type

10HP

RUR10NY1

15HP

RUR15NY1ModelName

Indoor unitOutdoor unit

Fan

5 6

POLYOL ESTER3.3 5.0

13HP

RUR13NY1

LChargeRefrigerantoil

Model

5.5 6.4 8.9 11.3kW

14.8 17.7 21.2 24.8

Starting currentPower factor

9.25 10.76 15.16 19.2Running current A

86.2 86.2 85.1 85.3%70.0 78.2 115.5 129.5A

kW

Starting currentPower factor

Running current A

%A

25.15 29.97 36.0 42.0

85.3 85.6 85.3 85.5118.0 130.3 143.4 146.3Starting current

Power factor

Running current A

30,200

35.2120,000

1,870X1,170X720

4.5 (Charged for 7.5 m)

11.3 17.6

61 62 63 6362

19.2 30.024.9

% 85.3 85.185.4A 129.5 130.3118.0

6.58.0 (Charged for 7.5 m)

FVPGR10NY1G FVPGR15NY1GFVPGR13NY1G

5.0+5.0 6.7+6.7

Sound level 2 dBA 61 6262380V

14 to 25

DUCT CONNECTION TYPE

FLOOR STANDING TYPE

25,200 40,300kWPower consumption 1 14.7

50,400

58.6200,000

5,720162

259

RUR20NY1

20HP18HP

RUR18NY1

45,400

52.8180,000

41.635.8

85.385.0146.3143.4

1,870X1,470X720

FVPGR20NY1G FVPGR18NY1G

7.5+7.5 9.0+9.0

63 63

24.521.0

DUCT TYPE

Cooling capacity 1, 3 kWBtu/hkcal/h

°CDB

°CWBOperation range

ModelName

Indoor unitOutdoor unit

Dimensions (HXWXD) mmSound level (H) 2 dB(A)

Refrigerant charge (R-410A) kg

Dimensions (HXWXD) mmMachine weight kg

Piping connections

mmmm

mm

kg

Airflow rate (H)

Fan External static pressureDriving system

m3/mincfm

mmH2O

Outdoorunit

mm

Operation range

Max. interunit piping length mm

Machine weight

Indoorunit

Colour

Max. installation level difference

Colour

Power supply

kWMotor outputCompressor Type

Galvanized steel

Ivory white

3050 (equivalent length 70 m)

380–415 V, 50 Hz, 3 Phase, 4 Wires

13HP 15HP 18HP 20HP

o/ 12.7(Brazing) o/ 15.9(Brazing)o/ 28.6(Brazing)

o/ 12.7(Flare)o/ 28.6(Brazing)

o/ 34.9(Brazing)

o/ 15.9(Flare)o/ 34.9(Brazing)

5HP 6HP 8HP 10HP

Cooling capacity 1, 3 kWBtu/hkcal/h

Power consumption 1

Power consumption 1

°CDB

°CWBOperation range

ModelName

Indoor unitOutdoor unit

Dimensions (HXWXD) mmSound level (H) 2 dB(A)

Refrigerant charge (R-410A) kg

Dimensions (HXWXD) mmMachine weight kg

Piping connections

mmLiquidmmGas

LiquidGas

mm

Indoor unit

Outdoor unit

LiquidGas

LiquidGas

Indoor unit

Outdoor unit

kg

Airflow rate (H)

Fan External static pressureDriving system

m3/mincfm

mmH2O

Outdoorunit

mm

Operation range

Max. interunit piping length mm

Machine weight

Indoorunit

Colour

Max. installation level difference

Colour

Power supply

kWMotor outputCompressor Type

Ivory white

3050 (equivalent length 70 m)

380–415 V, 50 Hz, 3 Phase, 4 Wires

o/ 9.5(Flare)

o/ 9.5(Brazing) o/ 12.7(Brazing)o/ 19.1(Brazing) o/ 22.2(Brazing) o/ 28.6(Brazing)

o/ 12.7(Flare)o/ 22.2(Brazing) o/ 28.6(Brazing)o/ 19.1(Flare)

Note : 1Rated cooling capacities are based on the following conditions : Suction temp., 27°CDB, 19.5°CWB ; outdoor temp. 35°CDB. Equiv. refrigeration piping, 5 m (horizontal). 2Anechoic chamber conversion value, measured according to JIS parameters and criteria. During operation these values are somewhat higher owing to ambient conditions.3Capacity includes indoor fan motor heat.

Galvanized steel

Sound level 2 dBA 59 60 6159dBA

L380V415V 60 61 6260

Sound level 2 dBAL

61 63 63625.0 6.5 6.56.5

6058

dBA380V415V 62 64 6463

mm ----------o/ 26.0 (Hole) Drain

mmDrain

mm PS 1B Internal threadDrain

mm ----------Drain

RefrigerantPiping

mmIndoor unit mm

Outdoor unit

mmLiquid Gas

Liquid Gas

mm

mmmm

1,680X930X765206 243 319

1,680X1,240X765

3050 (equivalent length 70 m)

Dimensions (HXWXD) mmMachine weight kgOperation range °CDB

Max. installation level differenceMax. interunit piping length m

m

o/ 12.7 (Brazing)o/ 28.6 (Brazing)

o/ 12.7 (Flare)o/ 28.6 (Brazing)

PS 1B Internal thread

----------

o/ 15.9 (Brazing)o/ 34.9 (Brazing)

o/ 15.9 (Flare)o/ 34.9 (Brazing)

21 to 46322 329

Drain

Drain

DAPHNE FVC68D1.4 1.8

POLYOL ESTERCharge

Refrigerantoil

Model3.3 3.3

49 51 53

POLYOL ESTERCharge

Refrigerantoil

Model

14 to 25

10

21 to 46

14 to 25

15

21 to 46

PS 3/4B Internal thread

lvory White

14 to 25Ivory white

Hermetically sealed scroll type4.5

RUR10NY1

5HP

12,600

14.7

RUR05NY1

50,000

421,480

421,480

1,870X750X51090 90

2.5 (Charged for 7.5 m)

8HP

20,200

23.5

RUR08NY1

80,000

1,91054

1,870X950X510107

4.5 (Charged for 7.5 m)

10HP

25,200

29.3100,000

2,830

59/54/50 59/54/50 60/56/51 61/57/52

80

1,870X1,170X510143

6.0 (Charged for 7.5 m)

Cooling capacity 1, 3 kWBtu/hkcal/h

kWPower consumption 1

ModelName

Indoorunit

Indoor unitOutdoor unit

Sound level (H/M/L) 2 dBADirect Drive 3 SpeedDrive

Refrigerant charge (R-410A) kgSound level 2 dBA

Machine weight kgOperation range °CWB

Air flow rate (H) m3/mincfm

Outdoorunit

Colour

Dimensions (HXWXD)

Colour

mm

Power supply 380–415 V, 50 Hz, 3 Phase, 4 Wires

kWMotor outputCompressor Type

POLYOL ESTERDAPHNE FVC68D1.4 1.8 3.3LCharge

Refrigerantoil

Model

Fan

6HP

RUR06NY1

15,1005.5 8.6 11.26.4

Starting currentPower factor

17.660,000

1,870X750X510

9.0 10.5 14.0 18.2Running current A72.7 80.9 118.2 135.0A88.0 87.8 88.4 88.3%

3.5 (Charged for 7.5 m)59 60 6159380V

FVGR05NV1 FVGR08NV1 FVGR10NV1FVGR06NV1

4.5 6.7 9.0

DIRECT AIR BLOW TYPE

21 to 46

1,345X900X32092 105 203 206

1,680X930X765

3050 (equivalent length 70 m)

Dimensions (HXWXD) mmMachine weight kgOperation range °CDB

RefrigerantPiping

mmIndoor unit

Max. installation level difference

mm

Outdoor unit

mmLiquid Gas

Liquid Gas

mmMax. interunit piping length m

m

o/ 9.5 (Brazing)o/ 19.1 (Brazing)

o/ 9.5 (Flare)o/ 19.1 (Flare)

o/ 12.7 (Brazing)o/ 22.2 (Brazing) o/ 28.6 (Brazing)

o/ 12.7 (Flare)o/ 22.2 (Brazing) o/ 28.6 (Brazing)

mmmm

PS 1B Internal thread

----------o/ 26.0 (Hole)

Drain

Drain

Page 5: AIR COOLED PACKAGED AIR CONDITIONERS Cooled... · the outdoor unit. (Applies to all outdoor units) (Applies to RUR05N/06N) AIR COOLED PACKAGED AIR CONDITIONERS Previous 20HP outdoor

7 8

FVPGR10NY1G FVPGR13NY1GFVPGR15NY1G

Upper limit of ESP(standard ESP)

UPPER : FAN PULLEYLOWER : MOTOR PULLEY

UPPER : FAN PULLEYLOWER : MOTOR PULLEY

Upper limit of ESP(standard ESP)

Ext

erna

l sta

tic p

ress

ure

35

30

25

20

15

10

5

0

1400rpm1214rpm

1100rpm

1000rpm

900rpm

1300rpm

1200rpm

800rpm

1181rpm

1100rpm

1000rpm

900rpm

800rpm

900rpm

1000rpm

350

300

250

200

150

100

50

0

50500

450

400

350

300

250

200

150

100

50

0

45

40

35

30

25

20

15

10

5

0

68

138 142 146 150 154 158 162 166 170 174 179

70 72 74 76 78 80 82 84 86 88 90 92 94 96

1A-PD1571A-PD150

1A-PD1571A-PD140

1B-PD1801B-PD145

1B-PD1801B-PD138

1B-PD1801B-PD132

1B-PD1801B-PD125

1B-PD1801B-PD118

1A-PD1571A-PD132

1A-PD1571A-PD125

1A-PD1571A-PD117

1A-PD1571A-PD112

1A-PD1571A-PD109

2B-PD2142B-PD160

2B-PD2142B-PD155

2B-PD2142B-PD150

2B-PD2142B-PD134

2B-PD2142B-PD125

2B-PD2142B-PD118

1A-PD1571A-PD95

1A-PD1571A-PD85

FVPGR18NY1GFVPGR20NY1G

DUCT CONNECTION TYPEFLOOR STANDING TYPE DUCT TYPE

75 81

A125-24

1300rpm

1100rpm

79 82

A150-24

1000rpm

35350

1400rpm

900rpm

A132-24

1200rpm

A116-24

73

100

7463

250

150

65

300

67

30

25

5

20

15

10

06961

0

50

200

71

A160-24

A112-24

A106-24

A140-24

90

900rpm

A106-24 A112-24

35

1200rpm

A140-24

86

A116-24

88

A132-24

A150-24

1000rpm

92 94

1100rpm

1300rpm

350

A125-24

20

10

30

15

25

5

0 07876

50

100

8074

200

84

150

72

250

82

300

70

2B-180-28

2B-180-28

350

2B-160-28

199196

1200rpm

186

1000rpm

1100rpm

2B-186-28

300

200

150

162

250

170

10010

0

20

15

5

25

30

174154

50

0158 166150 178164

800rpm

900rpm

2B-167-28

182

35

190

2B-225-30

2B-250-30

2B-250-30

2B-250-30

2B-250-30

A90-19

A98-19

A118-19

A106-19

51

A112-19

1000rpm

800rpm

55

900rpm

63

1200rpm

59

1100rpm

150

250

100

57

50

610

20

0

25

5

10

15

5349

200

64

A95-19

3D117525A

3D117527A

3D117526A

25

20

5

15

0

10

A112-19

A125-19

A106-19

800rpm

51

250

52

1100rpm

900rpm

43

100

A95-19

54440

46 48

50

50

200

45

1000rpm

49

1200rpm

4742

A118-19

53 55

150

41

A98-19

A90-19

1391350

150

151127

20

0

10

30

25

15

5

123

50

200

131

250

100

147143

300

155

B200-28

B170-28

350

B160-28

163159

35

B186-28

B224-28

B177-28

FDR08NY1G FDR10NY1G

FDR13NY1GFDR15NY1G

FDR18NY1GFDR20NY1G

FDR05NY1G FDR06NY1G

Fan Performance

SDR4150061

SDR4150063

SDR4150062

(mmH2O) (Pa)

Air flow (m³/min)

Upper limit of ESP(standard ESP)

UPPER : FAN PULLEYLOWER : MOTOR PULLEY

Ext

erna

l sta

tic p

ress

ure

(mmH2O) (Pa)

Air flow (m³/min)

Air flow (m³/min)

Air flow (m³/min)

Ext

erna

l sta

tic p

ress

ure

Ext

erna

l sta

tic p

ress

ure

35

30

25

20

15

10

5

0

350

300

250

200

150

100

50

0102 105 108 111 114 117 120 123 126 129

(mmH2O) (Pa)

(mmH2O) (Pa)

1181rpm

1100rpm

1000rpm

900rpm

800rpm

50500

450

400

350

300

250

200

150

100

50

0

45

40

35

30

25

20

15

10

5

0138 142 146 150 154 158 162 166 170 174 179

2B-PD2142B-PD160

2B-PD2142B-PD155

2B-PD2142B-PD150

2B-PD2142B-PD134

2B-PD2142B-PD125

2B-PD2142B-PD118

Upper limit of ESP(standard ESP)

2 ) ( )

Air flow (m³/min)³

Upper limit of ESP(standard ESP)

Air flow (m³/min) Air flow (m³/min)

Ext

erna

l sta

tic p

ress

ure

Ext

erna

l sta

tic p

ress

ure

(mmH2O) (Pa)(mmH2O) (Pa)

Upper limit of ESP(standard ESP)

Air flow (m³/min)

Ext

erna

l sta

tic p

ress

ure

Air flow (m³/min)

Ext

erna

l sta

tic p

ress

ure

(mmH2O) (Pa) (mmH2O) (Pa)

Upper limit of ESP(standard ESP)

Upper limit of ESP(standard ESP)

Upper limit of ESP(standard ESP)

Air flow (m³/min)

Ext

erna

l sta

tic p

ress

ure

(mmH2O) (Pa)

Upper limit of ESP(standard ESP)

1200rpm

1000rpm

800rpm

1100rpm

900rpm

5

0

5

5

0

A112-1

A125-19

A106-1

800rpm

51

250

52

1100rpm

900rpm

43

100

A95-19

54440

46 48

50

50

200

45

1000rpm

49

1200rpm

4742

A118-1

53 55

150

41

A98-19

A90-19

H2O) (Pa)

Upper limit of ESP(standard ESP)

A90-19

A98-19

A118-1

A106-1

51

A112-1

1000rpm

800rpm

55

900rpm

63

1200rpm

59

1100rpm

150

250

100

57

50

610

20

0

25

5

10

15

5349

200

64

A95-19Ext

erna

l sta

tic p

ress

ure

Upper limit of ESP(standard ESP)

75 81

A125-24

1300rpm

1100rpm

79 82

A150-24

1000rpm

3501400rpm

900rpm

A132-24

1200rpm

A116-24

73

100

7463

250

150

65

300

67 69610

50

200

71

A160-24

A112-24

A106-24

A140-24

Air flow (m³/min)³

2O) (Pa)

Upper limit of ESP(standard ESP)

90

900rpm

A106-24 A112-24

5

1200rpm

A140-24

86

A116-24

88

A132-24

A150-24

1000rpm

92 94

1100rpm

1300rpm

350

A125-24

0

0

0

5

5

5

0 07876

50

100

8074

200

84

150

72

250

82

300

70

Air flow (m³/min)³

H2O) (Pa)

Upper limit of ESP(standard ESP)

1391350

150

151127

0

0

0

0

5

5

5

123

50

200

131

250

100

147143

300

155

B200-28

B170-28

350

B160-28

163159

5

B186-28

B224 28

B177-28

H2O) (Pa)

Upper limit of ESP(standard ESP)

1200rpm

1000rpm

800rpm

1100rpm

900rpm

2B-180-2

2B-180-

350

2B-160

199196

1200rpm

186

1000rpm

1100rpm

2B-186-2

300

200

150

162

250

170

1000

0

0

5

5

5

0

174154

50

0158 166150 178164

800rpm

900rpm

2B-167

182

5

190

2B-225-3

2B-250-

2B-250

2B-250-3

2B-250

Air flow (m³/min)³

2 ) ( )

Upper limit of ESP(standard ESP)

Page 6: AIR COOLED PACKAGED AIR CONDITIONERS Cooled... · the outdoor unit. (Applies to all outdoor units) (Applies to RUR05N/06N) AIR COOLED PACKAGED AIR CONDITIONERS Previous 20HP outdoor

9 10

Wiring and Piping

DUCT TYPE

FDR05N/06NY1GRUR05N/06NY1

FDR08N/10NY1GRUR08N/10NY1

FDR13N/15N/18N/20NY1GRUR13N/15N/18N/20NY1

FVPGR10NY1GRUR10NY1

Power

Refrigerant piping

(Liquid, Gas)

Wiring

GroundGround

Power

FVPGR13N/15N/18N/20NY1GRUR13N/15N/18N/20NY1

Power

Refrigerant piping

(Liquid, Gas)

Wiring

Ground Ground

Power

FVGR08N/10NV1RUR08N/10NY1

Refrigerant piping

(Liquid, Gas)

Wiring

Ground

Power

Ground

FVGR05N/06NV1RUR05N/06NY1

Refrigerant piping

(Liquid, Gas)

Wiring

Ground

Power

Ground

DIRECT AIR BLOW TYPEFLOOR STANDING TYPE

DUCT CONNECTION TYPE

RemoteController

Power

Refrigerant piping

(Liquid, Gas)

Wiring

Ground

Ground

Power

RemoteController

Power

Refrigerant piping

(Liquid, Gas)

Wiring

Ground

Ground

Power Power

Refrigerant piping

(Liquid, Gas)

Wiring

Ground

Ground

Power

RemoteController

DIMENSIONS (Unit: mm)

950

750

A B C

720 o/ 9.5

920 o/ 12.7

D

o/ 19.1

750 720 o/ 9.5 o/ 19.1

o/ 22.2

Liquid pipe conn. (C) C1220T brazing Gas pipe conn. (D) C1220T brazing Upper drain outlet (PS 1B Internal thread) Power supply & control wire intake Digital remote controller

12345

510

1870

325

740

370

330

250

100

100

70

1870

35

510

1

2

34

1140

50150

474

5

1170

1170

510

1870

325

740

370

330

250

100

100

70

1870

35

510

A

1

2

34

B

50150

474

5

A

SDR3150151CSDR3150152BSDR3150153C

SDR3150154C

Liquid pipe conn. (ø 12.7) C1220T brazing Gas pipe conn. (ø 28.6) C1220T brazing Upper drain outlet (PS 1B Internal thread) Power supply & control wire intake Digital remote controller

12345

DIRECT AIR BLOW TYPEFLOOR STANDING TYPE

FVGR05NV1FVGR06NV1FVGR08NV1

FVGR10NV1

FVGR05NV1

FVGR08NV1

FVGR06NV1

Page 7: AIR COOLED PACKAGED AIR CONDITIONERS Cooled... · the outdoor unit. (Applies to all outdoor units) (Applies to RUR05N/06N) AIR COOLED PACKAGED AIR CONDITIONERS Previous 20HP outdoor

DUCT TYPE

11 12

Liquid pipe connection (ø 9.5) Gas pipe connection (ø 19.1)Drain pipe connection (PS 3/4B Internal thread)

Earth terminal Power supplySuspension bracket

123456

Liquid pipe connection (ø 9.5) Gas pipe connection (ø 19.1)Drain pipe connection (PS 3/4B Internal thread)

Earth terminal Power supplySuspension bracket

123456

850

756

1200 or more

90 85

46

148

99

9 9

35

735

4XP.

150=

600

4XP.

150=

600

735

900

950

1000

99

50

800

or m

ore

266

5058

63

261

75

150

58

266

50

418

45015

0

35

Service Space

2-M4 Burring holes(Both sides) 2-M4 Burring holes

(Both sides)

6

3

3

452

13

99

50

3

3850 3535

Service Space

6-M4Burring holes

6-M4Burring holes

(Both sides) (Both sides)

92-M4 Burring holes(Both sides) 2-M4 Burring holes

(Both sides)

1200 or more

90 8546

148

9

967

5XP

.180

=90

0

800

or m

ore

266

5015

058

63

261

75

5XP

.180

=90

096

7

1130

1180

1230

9 9

756

266

5815

0

5041

845

0

2

6

5 4

13

3D062899C

3D062900C

FDR05NY1G

FDR06NY1G

DIMENSIONS (Unit: mm)

DUCT CONNECTION TYPE

SDR3150177SDR3150178SDR3150179

SDR3150176

140

1147

1170

1170

1187

510

177

334216

571

1670

1740

470

724

70

325

5051

0

39029

2

146334

31 52

290

250

290

390

25040

1

2

34

50

150

250

100

100

5

50

1800

915

325

H 70

5260

251

0

F

720

A

1870

G

720

C

E

B D33

J

1

2

34

50

150

250

100

100

5

Liquid pipe conn. (ø 12.7) C1220T brazing Gas pipe conn. (ø 28.6) C1220T brazing Upper drain outlet (PS 1B Internal thread) Power supply & control wire intake Digital remote controller

12345

Liquid pipe conn. ( K ) C1220T brazing Gas pipe conn. ( L ) C1220T brazing Upper drain outlet (PS 1B Internal thread) Power supply & control wire intake Digital remote controller

12345

FVPGR13NY1GFVPGR15NY1GFVPGR18NY1GFVPGR20NY1G

FVPGR10NY1G

1470

1170

A B K

477 o/ 15.9

558 o/ 15.9

C

398

474

D

295

438

E

344

407

F

1187

1487

G

1170

1470

J

205

1170 477 o/ 12.7398 295 344 1187 1170 205

237

1470 558 o/ 15.9474 438 407 1487 1470

H

1147

1447

1147

1447 237

FVPGR15NY1G

FVPGR13NY1G

FVPGR20NY1G

FVPGR18NY1G

Page 8: AIR COOLED PACKAGED AIR CONDITIONERS Cooled... · the outdoor unit. (Applies to all outdoor units) (Applies to RUR05N/06N) AIR COOLED PACKAGED AIR CONDITIONERS Previous 20HP outdoor

13 14

Gas pipe connectionLiquid pipe connectionService port (in the unit)

Grounding terminal M5 (in switch box)

Refrigerant piping intakePower supply wiring intakeControl wiring intakeDrain pipe connection

1

2

3

4

5

6

7

8

8

30

2

55

6

61350

620

5

140

89

71

30

4

117

53

16

89

6

5

67

95

16

54

13

84

102

70

54

140

41

7

55

223

19

145

900

9595

58

(345

355)

48

96

1345

60

30

45 376

52

75

Hole for anchorbolt 4-M12

410

435

142

320

19

1

24

3

191

5

80

3D063042A

RUR05NY1RUR06NY1

67

1570

C

163

177

160 67

133

70

792

746

1680

577

163

738

393

4516

0

DETAIL FOR FRONT SIDE

DETAIL FOR BOTTOM SIDE

163

930

176

123

64

234

224

B

224

64

393

176

765

215

577

22.5-mm-Oblong holes4-15

178

661

A

129

100

(Pitch of foundation bolt holes) (Foundation bolt hole)

(Pitc

h of

foun

datio

n bo

lt ho

les)

737

722

4

3

6

8

5

4

1

2

1

2

710

9

(knock-out hole)

(knock-out hole)

(knock-out hole)

(knock-out hole)(knock-out hole)

Liquid pipe connection portGas pipe connection portGrounding terminalPower cord routing hole (side)Power cord routing hole (front)Power cord routing hole (front)Power cord routing hole (bottom)Wire routing hole (front)Pipe routing hole (front)Pipe routing hole (bottom)

1

2

3

4

5

6

7

8

9

10

12.7 Flare connection

(D) Brazing connectionLiquid pipe

2.Gas pipe

Notes)1.Detail For Front Side And Detail For Bottom Side Indicate The Dimensions After Fixing The Attached Piping.

RUR08NY1RUR10NY1

3D062886B3D062887B

69

A B

75

16

22

D

22.2

28.6

RUR08NY1

RUR10NY1

C

165

171

DIMENSIONS (Unit: mm)

OUTDOOR UNIT

Liquid pipe connection (ø 12.7) Gas pipe connection (G)Drain pipe connection (PS 3/4B Internal thread)

Earth terminal Power supplySuspension bracket

123

456

3D062901C3D062902C

3D062912C3D062913C3D062914C

A B E FDC5-M4

Burring holes

6-M4Burring holes5XP.180=9001076 1380 14301330

4XP.180=720876 1180 1230

G

ø28.6

ø22.21130

(Both sides) (Both sides)

2-M4 Burring holes(Both sides)

2-M4 Burring holes(Both sides)

1200 or more

Service Space

800

or m

ore

CB D F G H

1402 16209XP.150=1350 1750 1770 24

E

1710

1762 198011XP.150=1650 2110 2220 542070

A

10- o/ 3.1 holes

1402 16209XP.150=1350 1750 1770 24171010- o/ 3.1 holes

12- o/ 3.1 holes

Notes: 1Prepared holes for M4 tapping screw.

Evaporator air inlet connectionEvaporator air outlet connectionLiquid pipe connection (J)Gas pipe connection (K)Drain pipe connection (PS 1B Internal thread)

Earth terminal Power supply intakeThe holes for anchor bolts

12345

678

600100

7- o/ 3.1 holes*1

4- o/ 3.1 holes*1

*1

(Upward and downward)

(Both sides)3- o/ 3.1 holes*1

(Both sides)

A

10

50 or more

Supporting plate

(Commercially available)

(Upward and downward)

Service Space

Service Space

55

55

3XP

.150

=450

2XP.

150=

300

544

625

4538

257

22.5

349

61

476.

5 72.5

6XP.

150=

900

B C D E F G

H 172

800

or m

ore

800

or m

ore

100

or m

ore

50 or more Supporting plate

(Commercially available)

100

or m

ore

1045

205 80 205 80

10

85035

500 or more

763805 10

10

35

6

7

6

7

85

5

12

J K

ø12.7 ø28.6

ø15.9 ø34.9

ø15.9 ø34.9

39

10 10

398506

3

3

3 2

45155

63

311

160

294

468

A B AB C ED50

0

10050 50

294

160

67 67

47

10

79

10

46

1

99 58

732

F F

FDR08NY1G / 10NY1G

FDR13NY1G / 15NY1G / 18NY1G / 20NY1G

[FDR08NY1G] [FDR10NY1G]

FDR08NY1G

FDR10NY1G

[FDR13NY1G][FDR15NY1G]

[FDR18NY1G][FDR20NY1G]

FDR13NY1G

FDR15NY1G

FDR18NY1GFDR20NY1G

43

Page 9: AIR COOLED PACKAGED AIR CONDITIONERS Cooled... · the outdoor unit. (Applies to all outdoor units) (Applies to RUR05N/06N) AIR COOLED PACKAGED AIR CONDITIONERS Previous 20HP outdoor

15 16

100 or more

900 or more

100 or more

500 or more

Service Area

Space required for indoor unit installation (Unit: mm)

FVPGR10NY1GFVPGR13NY1GFVPGR15NY1GFVPGR18NY1GFVPGR20NY1G

100 or more

900 or more

100 or more

500 or more

Service Area

FVGR05NV1FVGR06NV1FVGR08NV1FVGR10NV1

FDR13NY1GFDR15NY1GFDR18NY1GFDR20NY1G

FDR05NY1GFDR06NY1GFDR08NY1GFDR10NY1G

DIMENSIONS (Unit: mm)

DETAIL FOR FRONT SIDE

DETAIL FOR BOTTOM SIDE

22.5-mm-Oblong holes4-15(Pitch of foundation bolt holes) (Foundation bolt hole)

(Pitc

h of

foun

datio

n bo

lt ho

les)

(knock-out hole)

(knock-out hole)

(knock-out hole)

(knock-out hole)

(knock-out hole)

Liquid pipe connection portGas pipe connection portGrounding terminalPower cord routing hole (side)Power cord routing hole (front)Power cord routing hole (front)Power cord routing hole (bottom)Wire routing hole (front)Pipe routing hole (front)Pipe routing hole (bottom)

1

2

3

4

5

6

7

8

9

10

(C) Flare connection

(B) Brazing connectionLiquid pipe

2.Gas pipe

Notes)1.Detail For Front Side And Detail For Bottom Side Indicate The Dimensions After Fixing The Attached Piping.

171

1056

1049

67

224

70

177

765

64

100

163

393

1680

123

577

1240

133

160

234

1570

48

163

64

176

972

A

67 163

176

224

45

577

1102

178

160

213

129

737

722

393

4

9

3

1

2

1

2

64

8

5

710

22

A

24

28.6

B

34.9

12.7

C

15.9

RUR13NY1

RUR15NY1RUR18NY1RUR20NY1

3D062890B3D062891B

RUR13NY1RUR15NY1RUR18NY1RUR20NY1

1200 or more

800 or more

800 or more

800 or more

800 or more

230or more

When installing the switch box, the suspension bolt should be 230 mm or more away from the unit (so that maintenance can easily be carried out the switch box).

230or more

When installing the switch box, the suspension bolt should be 230 mm or more away from the unit (so that maintenance can easily be carried out the switch box).

Provide enough clearance between the unit and the surrounding walls to prevent contact.

A o

r m

ore

A 570520

FDR05-06 type

Model

FDR08-10 type

Drain pan

Ceiling surface

Return air filer(commerciallyavailable)

Ceiling surface

Supporting plate (commercially avaliable)

Return air filter(commercially avaliable)

720

or m

ore

60 o

r m

ore

Provide enough clearance between the unit and the surrounding walls to prevent contact.

Page 10: AIR COOLED PACKAGED AIR CONDITIONERS Cooled... · the outdoor unit. (Applies to all outdoor units) (Applies to RUR05N/06N) AIR COOLED PACKAGED AIR CONDITIONERS Previous 20HP outdoor

Space required for outdoor unit installation (Unit: mm)

For single unit installation

For RUR08NY1/10NY1/13NY1/15NY1/18NY1/20NY1

10 or more

10 or more

10 or more

10 or more

10 or more

300 or more

300 or more

20 or more

20 or more

10 or more

50 or more

50 or more

50 or more

50 or more

50 or more

50 or more

500 or more

500 or more

500 or more

500 or more

300 or more

300 or more

200 or more

100 or more

100 or more

100 or more

100 or more 100 or more

Pattern 1

Pattern 2

Pattern 3

1500

mm

h2

500

mm

h1

If more units are to be installed than are catered for in the above patterns your layout should take account of the possibility of short circuits.

Notes:1Heights of walls in case of Patterns 1 and 2:

Installation space to be shown in this drawing is based on the cooling operation at 35 degrees outdoor air temperature. When the design outdoor air temperature exceeds 35 degrees or the load exceeds maximum ability because of much generation load of heat in all outdoor unit,take the suction side space more broadly than the space to be shown in this drawing.

2If the above wall heights are exceeded then h2/2 and h1/2 should be added to the front and suction side service spaces respectively as shown in the figure on the right.

3When installing the units most appropriate pattern should be selected from those shown above in order to obtain the best fit in the space available always bearing in mind the need to leave enough space for a person to pass between units and wall and for the air to circulate freely.

4The units should be installed to leave sufficient space at the front for the on site refrigerant piping work to be carried out comfortably.

Front : 1500 mmSuction side : 500 mmSide : Height unrestricted.

Wall height unrestricted

Front

Front

Front

Front

Front SuctionSide

Unit : mm

Front

Front

Front10 or more

10 or more

10 or more

10 or more

20 or more

300 or more

20 or more

50 or more 50

or more

50 or more

50 or more

500 or more

600 or more

500 or more

500 or more

100 or more

100 or more

100 or more

Pattern 1

Pattern 2

Front

Front

Front

Front

10 or more

10 or more20 or more 20 or more

50 or more

50 or more

500 or more

500 or more

300 or more

300 or more

200 or more

400 or more 400 or more

100 or more

100 or more 100 or more

Pattern 1

Pattern 2

Pattern 3 Wall height unrestricted

Front

Front

Front

For installation in rows

For centralized group layout

(Please refer to engineering databook for other installation patterns.)

17 18

For RUR05NY1/06NY1

300 or more

1000 or more

200 or more

100 or more

100 or more100 or more

100 or more

1000 or more

100 or more

500 or less

1000

or m

ore

500 or more

150 or more

150 or more 150 or more

500 or less

1000

or m

ore

300 or more

1000 or more

200 or more

500 or less

1000

or m

ore

500 or less

500 or more

1000

or m

ore

500 or less

1000 or more

1000

or m

ore

When there is an obstruction on the inlet side

When the obstruction on the outlet side is higher than the unit itself (There is no limit to the height of the obstruction on the outlet side.)

For other patterns, please refer to engineering databook.

When there are obstructions on both the inlet and outlet sides

When there is an obstruction on the outlet side

When there are obstructions on the inlet side and both lateral sides

2. For series installation (more than two units)

When there are obstructions on both sides

Pattern 1

When the overhead space is open

1. For single unit installation

When there is an obstruction only on the inlet side

When there is an obstruction in the overhead space

When the overhead space is open

When there are obstructions on both sides

When there is an obstruction in the overhead space

When there is an obstruction on the inlet side

When there are obstructions on the inlet side and both lateral sides

2. For series installation (more than two units)

1. For single unit installation

1. For single unit installation

When the overhead space is open

2. For series installation (more than two units)

1. For single unit installation

2. For series installation (more than two units)

1. For single unit installation

2. For series installation (more than two units)

An obstruction in the overhead space

An obstruction in the overhead space

An obstruction in the overhead space

An obstruction in the overhead space

An obstruction in the overhead space

H

L

500 or more 100 or more

1000 or more300 or m

ore

L H

L H

L H