BSVQ100-250P8 EEDEN11-200 Air Conditioners Individual branch selector for VRV® heat recovery (Individual BS box) Technical Data

Upload: dinhtram

Post on 22-Mar-2018

218 views

Category:

Documents


3 download

TRANSCRIPT

Page 1: Air Conditioners Technical · PDF file · 2017-02-20Air Conditioners Individual branch ... Dimensions Unit HeightxWidthxDepth mm 207x388x326 ... 4 - 2 Centre of gravity BSVQ100,160PV1

BSVQ100-250P8

E E D E N 1 1 - 2 0 0

Air Conditioners

I ndiv idual branch se lec tor for VR V® heat recover y ( I ndiv idual BS box)

Technical Data

Page 2: Air Conditioners Technical · PDF file · 2017-02-20Air Conditioners Individual branch ... Dimensions Unit HeightxWidthxDepth mm 207x388x326 ... 4 - 2 Centre of gravity BSVQ100,160PV1

BSVQ100-250P8

E E D E N 1 1 - 2 0 0

Air Conditioners

I ndiv idual branch se lec tor for VR V® heat recover y ( I ndiv idual BS box)

Technical Data

Page 3: Air Conditioners Technical · PDF file · 2017-02-20Air Conditioners Individual branch ... Dimensions Unit HeightxWidthxDepth mm 207x388x326 ... 4 - 2 Centre of gravity BSVQ100,160PV1

• Accessories • Individual branch selector for VRV® heat recovery 1

• Individual branch selector for VRV® heat recovery • BSVQ-P8

TABLE OF CONTENTSBSVQ-P8

1 Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2

Technical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2

Electrical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2

2 Safety device settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3

3 Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3

4 Dimensional drawing & centre of gravity . . . . . . . . . . . . . . . . . . . . . . . . 4

Dimensional drawing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4

Centre of gravity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6

5 Piping diagram. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7

6 Wiring diagram. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8

Wiring diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8

7 Sound data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9

Sound pressure spectrum . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9

Page 4: Air Conditioners Technical · PDF file · 2017-02-20Air Conditioners Individual branch ... Dimensions Unit HeightxWidthxDepth mm 207x388x326 ... 4 - 2 Centre of gravity BSVQ100,160PV1

• Individual branch selector for VRV® heat recovery • BSVQ-P8

• Accessories • Individual branch selector for VRV® heat recovery2

1 Specifications

Outdoor uni Accessories BSVQ-P8 Individual

Standard Accessories : Insulation pipe cover;

Standard Accessories : Attached piping;

Standard Accessories : Clamps;

Standard Accessories : Installation manual;

Notes

(1) In case of connection with a 20~50 type indoor unit, match to the size of the field pipe using the attached pipe. Connection between the attached pipe and the field pipe must be brazed.

(2) Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits.

(3) Maximum allowable voltage range variation between phases is 2%.

(4) MCA/MFA: MCA = 1.25 x FLA

(5) MFA ≤ 4 x FLA

(6) Next lower standard fuse rating minimum 15A

(7) Select wire size based on the value of MCA

(8) Instead of a fuse, use a circuit breaker

(9) In case of connecting with indoor unit capacity index between 150 and 160, match to the size of the field pipe using the attached pipe. Connection between the attached pipe and the field pipe must be brazed.

(10)In case of connecting with a 200 type indoor unit or capacity index more than 160 and less than 200, match to the size of the field pipe using the attached pipe. Connection between the attached pipe and the field pipe must be brazed.

1-1 Technical Specifications BSVQ100P8V1B BSVQ160P8V1B BSVQ250P8V1B

Power input Cooling Nom. kW 0.005

Heating Nom. kW 0.005

Casing Material Galvanised steel plate Galvanised steel

Dimensions Unit HeightxWidthxDepth mm 207x388x326

Weight Unit kg 12 15

Piping connections Outdoor unit Liquid Type Brazing connection

OD mm 9.5

Gas Type Brazing connection

OD mm 15.9 15.9 (1) 22.2

Discharge gas Type Brazing connection

OD mm 12.7 12.7 (1) 19.1

Indoor unit Liquid Type Brazing connection

OD mm 9.5 (1) 9.5

Gas Type Brazing connection

OD mm 15.9 (1) 22.2

Sound absorbing thermal insulation Foamed polyurethane, frame resisting needle felt

1-2 Electrical Specifications BSVQ100P8V1B BSVQ160P8V1B BSVQ250P8V1B

Power supply Phase 1~

Frequency Hz 50

Voltage V 220-240

Voltage range Min. % -10

Max. % 10

Total circuit Minimum circuit amps (MCA) A 0.1

Maximum fuse amps (MFA) A 15

Page 5: Air Conditioners Technical · PDF file · 2017-02-20Air Conditioners Individual branch ... Dimensions Unit HeightxWidthxDepth mm 207x388x326 ... 4 - 2 Centre of gravity BSVQ100,160PV1

• Accessories • Individual branch selector for VRV® heat recovery 3

• Individual branch selector for VRV® heat recovery • BSVQ-P8

2 Safety device settings

3 Options

BSVQ-P8

4D057956B

ModelSafety devices

PC board fuse

BSVQ100PV1 250V 3.15A

BSVQ160PV1 250V 3.15A

BSVQ250PV1 250V 3.15A

BSVQ36PVJU 250V 3.15A

BSVQ60PVJU 250V 3.15A

BSVQ96PVJU 250V 3.15A

BSVQ-P8

4TW31159-1A

NOTE

1 All options are kits.

2 Only available for standard BSVQ boxes (not possible for central BSV4Q).

Allows to reduce operating sound of BSVQ-box (requires 1 sound kit per BSVQ-box).

OPTION LIST

No Item BSVQ100P BSVQ160P BSVQ250P

1 PCB for multi tenant DTA114A61

2 Sound reduction for BSVQ box EKBSVQLNP (see note 2)

Page 6: Air Conditioners Technical · PDF file · 2017-02-20Air Conditioners Individual branch ... Dimensions Unit HeightxWidthxDepth mm 207x388x326 ... 4 - 2 Centre of gravity BSVQ100,160PV1

• Individual branch selector for VRV® heat recovery • BSVQ-P8

• Accessories • Individual branch selector for VRV® heat recovery4

4 Dimensional drawing & centre of gravity

4 - 1 Dimensional drawingBSVQ100PV1

3D056011

NOTES

1 Electric box can also be fixed on the other side of the unit.

2 Be sure to install an inspection door at electric box side.

3 Attached pipe is only used in case of connecting with a 20~50

class indoor unit.

4 Small sound of refrigerant will be made, which may be

disturbing.

Do not install it at the place such as bedroom under roof.

Nr Name Description

1 Suction gas pipe connection port ø15.9mm brazing connection

2 HP/LP gas pipe connection port ø12.7mm brazing connection

3 Liquid pipe connection port ø9.5mm brazing connection

4 Gas pipe connection port ø15.9mm brazing connection

5 Liquid pipe connection port ø9.5mm brazing connection

6 Electric box (note 1.)

7 Suspension brackets M8 ~M10

8 Grounding terminal M4

9 Attached pipe (1) (Note. 3) ø12.7mm brazing connection

10 Attached pipe (2) (Note. 3) ø6.4mm brazing connection

(Sus

pens

ion

bolt

pitc

h)

250 or more

(Suspension bolt pitch)

(Servicing space)

Servicing space

300 or more

(Servicing space)

Inspection door

(Note 2.)

Location of unit’s name plate - - - right side of electric box

65 orm

ore

(Ser

vicin

gsp

ace)

(Ser

vici

ng s

pace

)

250 or more

(Servicing space)(Ser

vici

ngsp

ace)

50 o

rm

ore

(In case of use attached pipe)

BSVQ160PV1

3D058004

NOTES

1 Electric box can also be fixed on the other side of the unit.

2 Be sure to install an inspection door at electric box side.

3 Attached pipe is only used in case of connecting with indoor unit

capacity index 150 or more and 160 or less.

4 Small sound of refrigerant will be made, which may be

disturbing.

Do not install it at the place such as bedroom under roof.

Nr Name Description

1 Suction gas pipe connection port ø15.9mm brazing connection

2 HP/LP gas pipe connection port ø12.7mm brazing connection

3 Liquid pipe connection port ø9.5mm brazing connection

4 Gas pipe connection port ø15.9mm brazing connection

5 Liquid pipe connection port ø9.5mm brazing connection

6 Electric box (note 1.)

7 Suspension brackets M8 ~M10

8 Grounding terminal M4

9 Attached pipe (1) (Note. 3) ø19.1mm brazing connection

10 Attached pipe (2) (Note. 3) ø15.9mm brazing connection

(Sus

pens

ion

bolt

pitc

h)

250 or more

(Suspension bolt pitch)

(Servicing space)

Servicing space

Inspection door

(Note 2.)

Location of unit’s name plate - - - right side of electric box

250 or more

(Servicing space)

65 or

mor

e(S

ervi

cing

sp

ace)

350 or more

(Servicing space)

350 or more

(Servicing space)

(In case of use Attached pipe)

(Sus

pens

ion

bolt

pitc

h)

50 orm

ore

(Ser

vici

ng

spac

e)

(Note 1.)

Page 7: Air Conditioners Technical · PDF file · 2017-02-20Air Conditioners Individual branch ... Dimensions Unit HeightxWidthxDepth mm 207x388x326 ... 4 - 2 Centre of gravity BSVQ100,160PV1

• Accessories • Individual branch selector for VRV® heat recovery 5

• Individual branch selector for VRV® heat recovery • BSVQ-P8

4 Dimensional drawing & centre of gravity

4 - 1 Dimensional drawingBSVQ250PV1

3D056012A

NOTES

1 Electric box can also be fixed on the other side of the unit.

2 Be sure to install a inspection door at electric box side.

3 Attached pipe (1) and attached pipe (2) is used in case of

connecting with indoor capacity index more than 160 and less

than 200 In case of connecting one indoor unit of 200 type, only

gas pipe connection port need Attached pipe (1).

4 Small sound will be made when changing over the motor

operated valve, which may be disturbing. Do not install it at the

place such as bedroom under roof.

Nr Name Description

1 Suction gas pipe connection port ø22.2mm brazing connection

2 HP/LP gas pipe connection port ø19.1mm brazing connection

3 Liquid pipe connection port ø9.5mm brazing connection

4 Gas pipe connection port ø22.2mm brazing connection

5 Liquid pipe connection port ø9.5mm brazing connection

6 Electric box (note 1.)

7 Suspension brackets M8 ~M10

8 Grounding terminal M4

9 Attached pipe (1) (Note. 3) ø19.1mm brazing connection

10 Attached pipe (2) (Note. 3) ø15.9mm brazing connection

(Sus

pens

ion

bolt

pitc

h)

300 or more

(Suspension bolt pitch)

(Servicing space)

Servicing space

Inspection door(Note 2.)

Location of unit’s name plate - - - right side of electric box

300 or more

(Servicing space)

65 orm

ore

(Ser

vici

ng

spac

e)

400 or more

(Servicing space)

400 or more

(Servicing space)

(In case of use Attached pipe)

(Ser

vici

ng s

pace

)

50 orm

ore

(Ser

vici

ng

spac

e)

(Note 1.)

Page 8: Air Conditioners Technical · PDF file · 2017-02-20Air Conditioners Individual branch ... Dimensions Unit HeightxWidthxDepth mm 207x388x326 ... 4 - 2 Centre of gravity BSVQ100,160PV1

• Individual branch selector for VRV® heat recovery • BSVQ-P8

• Accessories • Individual branch selector for VRV® heat recovery6

4 Dimensional drawing & centre of gravity

4 - 2 Centre of gravity

BSVQ100,160PV1

3D058131

In case of the electrical box on the other side of the unitIn case of the electrical box on the standard side of the unit

BSVQ250PV1

3D058132

In case of the electrical box on the other side of the unitIn case of the electrical box on the standard side of the unit

Page 9: Air Conditioners Technical · PDF file · 2017-02-20Air Conditioners Individual branch ... Dimensions Unit HeightxWidthxDepth mm 207x388x326 ... 4 - 2 Centre of gravity BSVQ100,160PV1

• Accessories • Individual branch selector for VRV® heat recovery 7

• Individual branch selector for VRV® heat recovery • BSVQ-P8

5 Piping diagram

BSVQ-P8

4D057985B

Double pipe heat exchanger

Filter

Electric Expansion Valve

(EVL)

Filter

Filter

Liquid pipe connection port

Electric Expansion Valve

(EVLS)

Electric Expansion Valve

(EVH)

Electric Expansion Valve

(EVHS)

Capillary tube

HP/LP gas pipe connection port

Filter

Suction gas pipe connection port

Electric Expansion Valve

(EVSC)

Gas pipe connection port

Liquid pipe connection port

Page 10: Air Conditioners Technical · PDF file · 2017-02-20Air Conditioners Individual branch ... Dimensions Unit HeightxWidthxDepth mm 207x388x326 ... 4 - 2 Centre of gravity BSVQ100,160PV1

• Individual branch selector for VRV® heat recovery • BSVQ-P8

• Accessories • Individual branch selector for VRV® heat recovery8

6 Wiring diagram

6 - 1 Wiring diagramBSVQ-P8B

3TW31796-1

NOTES

1 This wiring diagram applies to the BS unit only.

2 When using the COOL/HEAT selector (optional accessory), connect it to terminals A, B and C on X2M.

3 As for wiring to the IN/D unit (F1) - (F2) and OUT/D unit (F1)-(F2) on X1M (A1P), refer to the installation manual.

4 Use copper conductors only.

5 Dip switch (DS1-2) initial settings are as follows.

For using dip switch (DS1-2), refer to the installation manual or to the ‘service label’ on de el.compo.box cover.

A1P Printed circuit board X1M Terminal strip (power) Y5E Electronical expansion valve (main suction)DS1, DS2 Dip switch X1M (A1P) Terminal strip (control) Z1C Noise filter (ferrite core)

F1U Fuse (T, 3.15A, 250V) X2M Terminal strip (C/H selector)

F2U Field fuse Y1E Electronical expansion valve (sub cool) Connector for optional partsHAP Light emitting diode (service monitor green) Y2E Electronical expansion valve (sub discharge) X2A Connector (wiring external control adapter for outdoor)

PS Switching power supply Y3E Electronical expansion valve (sub suction) X38A Connector (adapter for multi tenant)

Q1DI Earth leak detector Y4E Electronical expansion valve (main discharge)

: Terminal strip L : Live Colors: BLU Blue

: Connector N : Neutral RED Red

: Terminal

: Field wiring

: Protective earth (screw)

Indoor unit

~ 50 Hz220 -240 V

Outdoor unit

To IN/D unit To OUT/D unit

F1 F2 F1 F2

Note 5

Note 2

BS unit top

BSVQ100PBSVQ160PBSVQ250P

ON

OFF

ON

OFF

ON

OFF

ON

OFF

ON

OFF

BSVQ100PBSVQ100P BSVQ160P BSVQ250P

Page 11: Air Conditioners Technical · PDF file · 2017-02-20Air Conditioners Individual branch ... Dimensions Unit HeightxWidthxDepth mm 207x388x326 ... 4 - 2 Centre of gravity BSVQ100,160PV1

• Accessories • Individual branch selector for VRV® heat recovery 9

• Individual branch selector for VRV® heat recovery • BSVQ-P8

7 Sound data

7 - 1 Sound pressure spectrum

4D058945

NOTE

1 Over All (dB):(B, G, N is already rectified)

2 Operating conditions:

• Power source: 220-240V 50Hz• Standard condition (JIS)

3 Measuring place: Anechoic chamber.

4 Operation noise differs with operation and ambient conditions.

5 In case of other unit operating in the same system, operating sound will be generated, ever if indoor unit connected to BS unit is stopped.

6 Location of microphone.

Oct

ave

band

sou

nd p

ress

ure

leve

l d

B(0

dB=0

.000

2μba

r)

Octave band center frequency (Hz)

Approximate threshold hearing for continuous noise

BVSQ100P8

Operating sound

Stoppage sound

(note 5)

Scale Operation sound

Stoppagesound

A 42 32

C 49 40

1,5m

4D058953

NOTE

1 Over All (dB):(B, G, N is already rectified)

2 Operating conditions:

• Power source: 220-240V 50Hz• Standard condition (JIS)

3 Measuring place: Anechoic chamber.

4 Operation noise differs with operation and ambient conditions.

5 In case of other unit operating in the same system, operating sound will be generated, ever if indoor unit connected to BS unit is stopped.

6 Location of microphone.

Oct

ave

band

sou

nd p

ress

ure

leve

l d

B(0

dB=0

.000

2μba

r)

Octave band center frequency (Hz)

Approximate threshold hearing for continuous noise

BVSQ160P8

Operating sound

Stoppage sound(note 5)

Scale Operation sound

Stoppagesound

A 43 32

C 49 40

1,5m

4D058946

NOTE

1 Over All (dB):(B, G, N is already rectified)

2 Operating conditions:

• Power source: 220-240V 50Hz• Standard condition (JIS)

3 Measuring place: Anechoic chamber.

4 Operation noise differs with operation and ambient conditions.

5 In case of other unit operating in the same system, operating sound will be generated, ever if indoor unit connected to BS unit is stopped.

6 Location of microphone.

Oct

ave

band

sou

nd p

ress

ure

leve

l d

B(0

dB=0

.000

2μba

r)

Octave band center frequency (Hz)

Approximate threshold hearing for continuous noise

BVSQ250P8

Operating sound

Stoppage sound(note 5)

Scale Operation sound

Stoppagesound

A 44 34

C 49 39

1,5m

Page 12: Air Conditioners Technical · PDF file · 2017-02-20Air Conditioners Individual branch ... Dimensions Unit HeightxWidthxDepth mm 207x388x326 ... 4 - 2 Centre of gravity BSVQ100,160PV1

Naamloze Vennootschap - Zandvoordestraat 300, B-8400 Oostende - Belgium - www.daikin.eu - BE 0412 120 336 - RPR Oostende EE

DE

N1

1-2

00

• 0

1/1

1 •

Co

py

rig

ht

Da

ikin

Th

e p

rese

nt

pu

blic

ati

on

su

pe

rse

de

s E

ED

EN

10

-20

0

Pre

par

ed

in B

elg

ium

by

Lan

no

o (

ww

w.la

nn

oo

pri

nt.

be

), a

com

pan

y w

ho

se c

on

cern

for

the

en

viro

nm

en

t is

se

t in

th

e E

MA

S an

d IS

O 1

40

01

sys

tem

s.

Re

spo

nsi

ble

Ed

ito

r: D

aik

in E

uro

pe

N.V

., Z

an

dv

oo

rde

stra

at

30

0,

B-8

40

0 O

ost

en

de

ÉEEDEN10-200kËÍ

Daikin products are distributed by:

Daikin’s unique position as a manufacturer of air

conditioning equipment, compressors and refrigerants

has led to its close involvement in environmental issues.

For several years Daikin has had the intention to become

a leader in the provision of products that have limited

impact on the environment. This challenge demands the

eco design and development of a wide range of products

and an energy management system, resulting in energy

conservation and a reduction of waste.

VRV® products are not within the scope of the Eurovent

certification programme.

The present publication is drawn up by way of information only and does not constitute an offer binding

upon Daikin Europe N.V.. Daikin Europe N.V. has compiled the content of this publication to the best of its

knowledge. No express or implied warranty is given for the completeness, accuracy, reliability or fitness for

particular purpose of its content and the products and services presented therein. Specifications are subject

to change without prior notice. Daikin Europe N.V. explicitly rejects any liability for any direct or indirect

damage, in the broadest sense, arising from or related to the use and/or interpretation of this publication. All

content is copyrighted by Daikin Europe N.V..