Air Circuit Breakers
www.sigmaelektrik.com
Do not risk your safety!
www.sigmaelektrik.com
33
IntroductionSFA and SDA series air circuit breaker is suitable for the circuit of AC 50Hz/60Hz with rated service voltage 400V, 690V and rated service current up to 4000A. It is mainly used to distribute electric energy and protect circuits and electric equipment against over-load, under-voltage, short-circuit and single-phase earthing fault. With intelligentized and selective protection functions, the breaker can improve the reliability of power supply, and avoid unnucessary power failure. The breaker is applicable for power stations, foctories, mines (for 690V) and modernhigh-buildings, especially for the distribution system of intelligentized building.
Main FeaturesAccording to the mounting: fixed and draw-outAccording to the poles: three poles, four polesAccording to the operation ways: motor and manuel
Operation ConditionsAmbient air temperature
a) Maximum not exceed +40°Cb) Minumum not lower than -5°Cc) 24h average value not exceed +35°C
Note: Ambient air temperature is -10°C or -25°C and users should declare to manufacturer when put the order; ambient working condition is between -25°C and +40°C. User should negotiate with manufacturer.
Elevation ≤ 2000M
Atmosphere condition: relative humidity is not exceeding 50% at the maximum ambient temperature of +40°C With lower temperature, higher humidity would be permitted, but the lowest average tempature in a month not exceeding +25°C during the moistest month, and the maximum monthly average relative humidity not exceeding 90% in that month,and giving consideration to the dews on the goods surface, which would appear due to temparature change.
ACBAir Circuit BreakersACBACB
ACBACB
www.sigmaelektrik.com
34
Technical Specifications
Type SDA 2000/ SFA 2000 SDA 3200/ SFA 3200 SDA 4000/ SFA 4000Kind Of Assembly Drawout/Fixed Drawout/Fixed Drawout/Fixed
No Of Poles 3-4 3-4 3-4
Electrical Specifications
Rated Current at 40°C A 1600,2000 2500,3200 4000
Rated Voltage Ue V AC 415 415 415
Rated Insulation Voltage Ui V 750 750 1000
Rated Impulse Withstand Voltage Uimp kV 8 8 8
Rated Short-circuit Breaking Capacity
Rated Ultimate Short-circuit Breaking Capacity Icu kA690 V AC 50 65 65
415 V AC 80 100 100
Rated Service Short-circuit Breaking Capacity Ics kA690 V AC 40 50 50
415 V AC 50 65 65
Category A,B A,B A,B
Pollution degree 3 3 3
Electrical life ope. 415 V 1000 500 500
Mechanical life ope. 10000 5000 5000
Tripping Unit Electronic Electronic Electronic
Long-time delay current Ir A (0,4-1)xIn (0,4-1)xIn (0,4-1)xIn
Action time at 1.5xIn Tr sn15,20,25,30,40,5060, 80,100,120,160200, 240,320,480
15,20,25,30,40,50,60, 80,100,120,160,
200, 240,320,480
15,20,25,30,40,50,60, 80,100,120,160,
200, 240,320,480
Short-Time Delay Current Im A (0,4-15)xIn (0,4-15)xIn (0,4-15)xIn
Short-Time Delay Time sn0,1-0,2-0,3-0,4-0,5-
0,6-0,7-0,8-0,9-1-OFF0,1-0,2-0,3-0,4-0,5-
0,6-0,7-0,8-0,9-1-OFF0,1-0,2-0,3-0,4-0,5-0,6-
0,7-0,8-0,9-1-OFF
Instantaneous Current Ii A In...50 kA +OFF In...50 kA +OFF In...50 kA +OFF
Earth Fault Current Ie A (0,2-0,8)xIn+OFF (0,2-0,8)xIn+OFF (0,2-0,8)xIn.OFF
Ambient Temp.
Max. Operatioanal Ambient Temperature °C From -25 to +70 From -25 to +70 From -25 to +70
Max. Storage Temperature °C From -40 to +80 From -40 to +80 From -40 to +80
Dimensions
W mm 335/318 395/378 510
H mm 432/402 432/402 432
D mm 501/322 421/322 487
Weight kg 74/45 95/53 119/73
Accessories
Shunt Trip coil ( 230 V AC) On Request On Request On Request
Undervoltage Coil (230 V AC) On Request On Request On Request
Closing Coil ( 230 V AC) On Request On Request On Request
Aux. Contact ( 2NO+2NC) Standard Standard Standard
Motor Operator ( 230 V AC) On Request On Request On Request
Mechanical Interlock On Request On Request On Request
ACMIDPAVACB ACBAir Circuit Breakers Air Circuit Breakers
www.sigmaelektrik.com
35
Current ratingsRange(Ir1)
Error Current Actions Time Time Error
(0.4~1)In ±10%
≤1.05Ir1 <2h Non-trip
˃1.30Ir1 <1h trip
1.51 Ir1 (setting time) 15 30 60 120 240 480 ±10%2.0Ir1 8.4 16.9 33.7 67.5 135 270 ±10%
Current ratingsRange(Ir2)
Error Current Actions Time Time Error
(1~15)Ir1+OFF (OFF Position) ±10%
≤0.9Ir2 Non-trip
˃1.10Ir2 Delayed-trip
Time setting (ts) 0.1 0.2 0.3 0.4 ±15%Returnable Time 0.06 014 0.23 0.35 ±15%
Current ratingsRange(Ir4)
Error Current Actions Time Time Error
(0.2~0.8)In+OFF (OFF Position)
(NA1-2000,min160A)±10%
≤0.9Ir2 Non-tripping
˃1.10Ir2 Tripping
Setting time (Tg) 0.1 0.2 0.3 0.4 ±15%Returnable time 0.06 014 0.23 0.35 ±15%
Phase N Overload and Over-Current Characteristic
Overload long time-delay protection
Short-circuit short-delay protection
Short-circuit instantaneous protection
Single phase earth fault protection technical data:
100% or 50% (Applicable to 3p+N or 4P)
Current Ratings Range(Ir3) Error Current Action Characteristic1.0 In~50A/75kA/100A
+OFF (OFF Position)± 15%
≤0.85lr3 Non-trip
˃1.15lr3 trip
Intelligent Controller Functions
ACMIDPAVACB ACBAir Circuit Breakers Air Circuit Breakers
www.sigmaelektrik.com
36
30 40 50 60 70 80 100.2 .3 .4 .5 .6 .8 1 2 3 4 5 6 8 10 20 x ln
t (a)
kA
10000
5000
2000
1000
500
200
100
50
20
10
5
2
1
0.5
0.2
0.1
0.05
0.02
0.01
Ir1=(0. 4~1)In
Tr=(15~480)s
I2toff
Ir2=(I.0~I5)Irl
0.4s
0.3s
0.2s
0.1s
Ir3=1.0In~50kA/75kA/100kA
Time-Current Characteristics Curves
1000
500
100
50
20
10
5
2
1
0.5
0.2
0.1
0.05
0.02
0.01
Ir4=(0.2~0.8)In
xln
t(s)
.05 .06 .08 .1 .2 .3 .4 .5 .6 .8 1 2 3 4 5 6 8 10 20 30
0.4s
0.3s
0.2s
0.1s
0.4s
0.3s
0.2s
0.1s
Over-current protection characteristic curve
Earth fault protection characteristic curve
The earth fault protection has definite time-delay characteristic with the failure delayed time no less than the definite time-delay time setting
ACMIDPAVACB ACBAir Circuit Breakers Air Circuit Breakers
www.sigmaelektrik.com
37
Control Circuit
MainCircuit Asistant Switch
DF
Q F X M
DF
SB1
SB1
SB3
SA
26864
0 0
2
AC380VAC220VVorking powersupply
1
(-)(+)
U1 (+) U2 (-)
3/46/8
28
259753 27 29 31 33 35 36 38 39 41 42 44 45 47
30 32 34 37 40 43 46
power supply
offStored energy
main circuit
power supply
*DC220V DC110V
Processing
Unit
Intelligent Controller
closeAllident
Sb1 shurt button (prepared by user)
Sb2 under-vottage button (prepared by user)
SB3 swich-on button (prepared by user)
DF auxiliary contect
F shurt relaase
SA motor microphonic
X swich-on electric magnet
M stored energy motor
XT wiring terminal
Q under-voltage release or under-voltage delay release
O always-open contact
O signal lamp (prepared by user)
ACMIDPAVACB ACBAir Circuit Breakers Air Circuit Breakers
www.sigmaelektrik.com
38
Control Circuit
Examples
The busbars should be suitably adjusted to ensure the connection points are positioned on the terminals before the bolts are inserted B the connections are held by the supporter which is fixed to the framework of the swich board, in this way the circuit breaker terminals do not have to support its weight C. (This support should be placed close to the terminals).
Correct clamping of busbars depends on the tightening torques used for the nuts and bolts,etc Over-tightening may have the same consequences as under-tightening.
For connecting busbars to the circuit breaker, the tightening torques to be used are shown in the table below.These values are for use with copper busbars and steel nuts and bolts, class 8.8.
Preferred tightening torque for NA1's tightening componets
Type Of Screw Application Preferred Tightening TorqueM4 Screws For Secondary Terminals 11 Nm
M10 Installing Bolts Of Air Circuit Breaker 45 NmM12 Connection Terminals 50 Nm
B BC
5
1
1 breaker terminal
2 busbar
3 bolt
4 washer
5 nut
2 3 4
ACMIDPAVACB ACBAir Circuit Breakers Air Circuit Breakers
www.sigmaelektrik.com
39
Recommendation for user's connecting bus-bar
Note: The specifications in the table is obtanied as the ambient tempature of air circuit breaker is 40°C, with open installations; this is in compliance with the specication of copper busbars adopted under the heating conditions regulated in IEC/EN60947-2.
Connected Position Test Position Disconnected Position Drawout Position
Making the secondary circuit power, the motor-driven mechanims can store energy automatically until hearing the click and energy stored ''indicating on the panel. Otherwise press the storage handle for 6 times until hearing the click and the indicator display energy stored'' And the closing operation can be realized either by closing electromagnet or manuel button.
Both main circuit and 1. control circuit are connected.
Normal application 2. conditions
The main circuit is 1. disconnected and the control circuit is connected.
Test application 2. conditions.
Neither the main circuit nor the control circuit is connected.
Main body is out of the drawer seat.
In (A) 1600 2000 2000 2500 3200 4000
BusbarThickness(mm) 10 10 8 10 10 10
Width (mm) 80 80 100 100 100 100Number 2 2 2 2 4 4
ACMIDPAVACB ACBAir Circuit Breakers Air Circuit Breakers
www.sigmaelektrik.com
40
3 vertical installed circuit breaker with lever interlock. If two breakers interlock, it only needs remove the above breaker.
50
40
160
50
40
153
163
166
Base
Base Of Circuit Breaker
900
900
45
100
52 60
52 60
65
160
2m max
R≥120 mm
Horizontal Interlock
Vertical Interlock
Mechanical Interlocking between 2 or 3 Air Circuit Breakers
ACMIDPAVACB ACBAir Circuit Breakers Air Circuit Breakers
www.sigmaelektrik.com
41
ACMIDPAVACB ACBAir Circuit Breakers Air Circuit Breakers
378
352
400
258
2113211
1111
290
402
112
a55
150
318
292
340
11
258
13
50 150
290
112
55a
335
402
Dimensions
SFA 2000 (1600 A, 2000 A)
SFA 3200 (2500 A , 3200 A)
In A a mm
1600 15
2000 20
www.sigmaelektrik.com
42
205
487
533
175 97
9230
112
510
550352
258
425
432
37
307
70
4xM12
400
150362
8xMS
311
267
404
2
300
342.2
25
8.5
269
311.
2
340
12
150
Terminal Connection (mm)Terminal Connection (mm) Panel Front Cut out (mm)
140
14050
20
103
33 175
440
14
11
2-11x17
197.5 197.5
Terminal Connection (mm) Panel Front Cut out (mm)
Panel Front Cut Out (mm)
SFA 4000 ( 4000 A )
Connection Terminals
28
95 95
42
6013
17
5086
16115 11532
16
9xM12
ACMIDPAVACB ACBAir Circuit Breakers Air Circuit Breakers
www.sigmaelektrik.com
43
ACMIDPAVACB ACBAir Circuit Breakers Air Circuit Breakers
Type No order Rated Current Break. Cap Release pack boxof poles code In (A) Icu (kA) pcs pcs
SFA-2000 3 SFA 1600 640-1600 80 Electronic 1 1SFA-2000 3 SFA 2000 1200-2000 80 Electronic 1 1SFA-3200 3 SFA 2500 1000-2500 80 Electronic 1 1SFA-3200 3 SFA 3200 1280-3200 80 Electronic 1 1SFA-4000 3 SFA 4000 1600-4000 80 Electronic 1 1
Type No order Rated Current Break. Cap Release pack boxof poles code In (A) Icu (kA) pcs pcs
SFA-2000 3 SDA 1600 640-1600 80 Electronic 1 1SFA-2000 3 SDA 2000 1200-2000 80 Electronic 1 1SFA-3200 3 SDA 2500 1000-2500 80 Electronic 1 1SFA-3200 3 SDA 3200 1280-3200 80 Electronic 1 1SFA-4000 3 SDA 4000 1600-4000 80 Electronic 1 1
TypeCode
OrderCode Description Spec. Pack
pcsBox pcs
SADG SADG Undervoltage Coil 220 V AC 1 1SAAB SAAB Shunt Trip Coil 220 V AC 1 1SAKB SAKB Closing Coil 220 V AC 1 1SAMM SAMM Motor Operator 220 V AC 1 1SAYK SAYK Aux. Contact 2NO+NC 1 1SAMK SAMK Mechanical Interlock 1 1
OrderingFixed Type ACB's
Drawable Type ACB's