after the seminar…. firestop plan review and inspection · outline how fire containment in...

66
2/13/2017 1 Firestop Plan Review and Inspection ICC Preferred Provider Course No. 10471 IFC Firestop 108 – Firestop inspection and plan review 0.7 CEUs After the seminar…. Please take our seminar feedback survey: https://www.surveymonkey.com/r/FirestopSeminar2 016 (only 3-4 mins!) You can scan the QR code to take you to the survey Indicate if you would like to receive a seminar certificate Firestop Inspection Training 5 Learning Objectives 1. Outline how fire containment in construction is achieved 2. List the code requirements for firestopping 3. Explain how firestopping materials are tested and to what standards 4. Show why a system approach to firestopping is required 5. Determine when the installation techniques meet applicable standards and code requirements 6. Understand the 2012 IBC requirements for firestop Special Inspection 6 Seminar agenda What is firestopping, and why is it required? Code Requirements Firestop System Fire Testing Penetration Firestop Systems Membrane penetration firestop systems Joint Systems Perimeter Fire Containment Systems Duct Enclosure systems Understanding the UL Directories Firestop installation options Engineering judgments Special inspection and special inspectors Recognizing firestop installation problems Plan review and inspection process recommendations Notable changes in IBC 2009, 12, 15 IFC-Recommended firestop inspection techniques 7 THE BASICS SPECIFIC APPLICATIONS DOCUMENTS !!! AS OF 2012 IBC INSPECTION TIPS Understanding the Concept of Balanced Fire Protection 8 Balanced Fire Protection An integrated system of fire and smoke protection elements in the construction environment composed of detection, suppression and containment features designed to provide an acceptable level of protection for people and property 9

Upload: others

Post on 16-Feb-2021

7 views

Category:

Documents


1 download

TRANSCRIPT

  • 2/13/2017

    1

    Firestop Plan Review and Inspection

    ICC Preferred Provider Course No. 10471IFC Firestop 108 –

    Firestop inspection and plan review0.7 CEUs

    After the seminar….• Please take our seminar feedback survey:https://www.surveymonkey.com/r/FirestopSeminar2016(only 3-4 mins!)

    You can scan the QR code totake you to the survey

    Indicate if you would like toreceive a seminar certificate

    Firestop Inspection Training 5

    Learning Objectives

    1. Outline how fire containment in construction isachieved

    2. List the code requirements for firestopping3. Explain how firestopping materials are tested

    and to what standards4. Show why a system approach to firestopping

    is required5. Determine when the installation techniques

    meet applicable standards and coderequirements

    6. Understand the 2012 IBC requirements forfirestop Special Inspection

    6

    Seminar agenda• What is firestopping, and why is it required?• Code Requirements• Firestop System Fire Testing• Penetration Firestop Systems• Membrane penetration firestop systems• Joint Systems• Perimeter Fire Containment Systems• Duct Enclosure systems• Understanding the UL Directories• Firestop installation options• Engineering judgments• Special inspection and special inspectors• Recognizing firestop installation problems• Plan review and inspection process

    recommendations• Notable changes in IBC 2009, 12, 15• IFC-Recommended firestop inspection techniques

    7

    THE BASICS

    SPECIFICAPPLICATIONS

    DOCUMENTS

    !!! AS OF 2012 IBC

    INSPECTIONTIPS

    Understanding the Concept ofBalanced Fire Protection

    8

    Balanced Fire Protection

    • An integrated system of fire and smokeprotection elements in the constructionenvironment composed of detection,suppression and containment featuresdesigned to provide an acceptable level ofprotection for people and property

    9

  • 2/13/2017

    2

    10

    Fire Protection Triad

    Containment

    DetectionSuppression

    What is the Function of aBalanced Fire Protection Design?• Detectors are used to activate fire alarms and notify

    building occupants and emergency responders• Sprinklers are designed to control small and medium

    fires and to prevent fire spread beyond the typical watersupply design area of about 1,500 ft2

    • Compartmentation mitigates the spread of more severebut less frequent fires by limiting building areas,subdividing building with fire resistance ratedconstruction, based on hourly ratings

    11

    • Requires features that limit spread of fire and productsof combustion:

    – Sprinkler systems and other suppression systems (control)– Fire rated horizontal and wall assemblies– Smoke barriers– Opening protection: doors, windows, shutters in paths of

    egress– Occupant egress requirements– Smoke management systems– Fire detection and alarm systems– Limitations on interior finishes and hazardous materials– Limited heights and areas– Fire rated tenant separations– Structural protection

    12

    IBC Balanced fire protectionfeatures

    13

    Finding The RightBalance

    ActiveProtection(Sprinklersand Alarms)

    PassiveProtection

    (Fire-resistiveAssemblies)

    Smoke & Toxic Gases

    14

    What is the Leading Killer in Fires?

    15

    Visibility: 47% of survivors caught in a fire could not see more than 12feet

    3/4 of all fire deaths are caused bysmoke inhalation.

    Approximately 57% of people killed in fires are not in the room ofthe fire’s origin

    Source: Hall, Jr. John R. NFPA Fire Analysis & Research, Quincy, MA. “Burns, Toxic Gases, and other Hazards”.

    Smoke travels 120-420 feet per minute under fire conditions

    Source: NFPA Fire Protection Handbook, 18th Ed. Table 1-1P. Pg.1-15.

    Source: NFPA Fire Protection Handbook, 18th Ed. Table 8-1P. Pg. 8-17.

    Source: Estimate based upon ceiling jet velocity calculations for typical ceiling heights and heat release rates.

    Fire Statistics – Why We MustContain Smoke and Toxic Gases

  • 2/13/2017

    3

    Containment In Construction

    • Fire-resistance-rated assemblies– Fire Walls– Fire Barriers– Fire Partitions– Smoke Barriers– Horizontal Assemblies

    • Through- and Membrane-Penetrations• Fire-resistant joint systems (i.e. construction joints

    and perimeter joints)• Opening protection (i.e. fire-rated doors and windows)• Air ducts and air transfer openings (i.e. dampers)

    17

    Containment in Construction

    Firestopping: IBC Definition•An assemblage consisting of a fire-resistance-rated floor,floor/ceiling, or wall assembly,+•one or more penetrating items passing through thebreaches in both sides of the assembly+•the materials or devices, or both, installed to resist thespread of fire through the assembly for a prescribed periodof time.

    Compare and contrast• Firestopping• Fireblocking• Draftstopping

    20

    1980 MGM Grand Hotel84 Died – 679 Injured

    Due to Smoke Propagation(Prior to Firestop Requirements)

    May 2001 - Taipei Office BuildingFire started on 3rd Floor

    Spread and jumped to 26th Floor(Unauthorized removal of fire walls and lack of

    perimeter barrier firestopping hampered firecontainment)

    Large loss fires with inadequate compartmentation

  • 2/13/2017

    4

    Fire occurred on the 12th floor extendingto 16th floor (62 story high-rise):– “The lack of firestopping between the floor

    slabs and the skin permitted the fire tospread from floor to floor through thisspace. Fire was observed spreadingthrough this area even before the glassand mullions failed.”

    – “The fire extended upward by…non-firestopped openings between the floorslab and the skin.”

    – “The vertical spread was also throughpoke-through, pipe recesses, and utilityshafts.”

    – “The automatic sprinkler system wasdrained and building fire pumps shut off attime of fire.”Source: Chapman, Elmer F. “High-Rise: An Analysis,” FireEngineering”, August 1988.

    First Interstate Bank BuildingLos Angeles, 1988

    Fire occurred in the 5th floor electricalroom:

    – “Fire and smoke spread beyond therooms involved due to a number ofunprotected horizontal and verticalopenings.”

    – “Based upon the NFPA’s investigationand analysis of this fire, the followingare considered significant contributingfactors to the loss of property in thisincident:

    • Unprotected vertical and horizontalpenetrations. These openingsallowed smoke to spread frombeyond the electrical room and intothe occupied areas.”

    Source: NFPA Fire InvestigationSummary: “High Rise Fire RockefellerCenter”

    Rockefeller CentreNew York, 1996

    Why is Firestopping Required?

    • Mandated by the Codes

    • Life safety and propertyprotection

    • Provide time for first responders toperform their duties

    • Compartmentalize andprevent spread of flameand smoke through astructure during a fire

    Where do the IBC (and NFPA 101)required firestopping?

    Containment In Construction

    Through-Penetrations

    Containment In ConstructionMembrane-Penetrations

    Containment In Construction

  • 2/13/2017

    5

    Construction Joints

    Containment In ConstructionPerimeter Containment

    Containment In Construction

    Firestopping needed in manyApplications

    Graphics – STI

    Seminar agenda• What is firestopping, and why is it required?• Code Requirements• Firestop System Fire Testing• Penetration Firestop Systems• Membrane penetration firestop systems• Joint Systems• Perimeter Fire Containment Systems• Duct Enclosure systems• Understanding the UL Directories• Firestop installation options• Engineering judgments• Special inspection and special inspectors• Recognizing firestop installation problems• Plan review and inspection process

    recommendations• Notable changes in IBC 2009, 12, 15• IFC-Recommended firestop inspection techniques

    31

    THE BASICS

    SPECIFICAPPLICATIONS

    DOCUMENTS

    !!! AS OF 2012 IBC

    INSPECTIONTIPS

    Code Requirements - Firestopping–International Building Code – Chapter 7

    •New Construction–International Fire Code – Chapter 7

    •Existing Buildings–NFPA 101 – Chapter 8

    •Health Care

    Code Requirements – FirestoppingMinimum requirements for New Construction & Maintenance

  • 2/13/2017

    6

    FIRESTOP PROCESS• Design/specification• Plan Review• Installation• Inspection• Maintenance

    34

    • Code provisions provide clear direction for inclusion information onthe plans.107.2.1 - Information on Construction Documents shall be ofsufficient clarity to indicate the location, nature and extent of thework proposed and show in detail that it will conform to theprovisions of this codes

    107.3.4.1-Deferred submittals. Deferral of any submittal items shallhave the prior approval of the building official. The registered designprofessional in responsible charge shall list the deferred submittals onthe construction documents for review by the building official.Documents for deferred submittal items shall be submitted to theregistered design professional … who shall review them and forwardthem to the building official … indicating they … have been reviewedand found to be in general conformance to the design of the building.The deferred submittal items shall not be installed until the deferredsubmittal documents have been approved by the building official.

    Submittals

    Firestop Code Requirements - IBC

    • 110.3.6 Protection of joints and penetrations in fire-resistance-rated assemblies, smoke barriers and smoke partitions shall notbe concealed from view until inspected and approved.

    Inspection

    Firestop Code Requirements - IBC Firestop Code Requirements - IBCThrough-Penetrations

    • Sections 714.3.1.2: Through-Penetrations of Vertical AssembliesThrough penetrations shall be protected by an approved penetrationfirestop system installed as tested in accordance with ASTM E 814 or UL1479 with a minimum positive pressure differential of 0.01 inch (2.49 Pa)of water and shall have an F rating of not less than the required fireresistance rating of the wall penetrated.

    Firestop Code Requirements - IBCThrough-Penetrations

    • Sections 714.4.1.2: Through-Penetrations of Horizontal AssembliesThrough penetrations shall be protected by an approved penetration firestopsystem installed as tested in accordance with ASTM E 814 or UL 1479 with aminimum positive pressure differential of 0.01 inch (2.49 Pa) of water and shallhave The system shall have an F rating/T rating of not less than 1 hour but notless than the required rating of the floor penetrated.

    Exceptions to T-Rating only:1. Floor penetrations contained and located within the cavity of a wall2. Floor penetrations by floor drains, tub drains or shower drainscontained and located within the concealed space of a horizontalassembly3. Max 4-inch diameter penetrations directly into metal-enclosedelectrical power switchgear.

    • Sections 714.3.2: Membrane PenetrationsMembrane Penetrations shall comply with Section 714.3.1. Where walls or

    partitions are required to have a fire-resistance rating, recessed fixtures shallbe installed such that the required fire-resistance will not be reduced.

    – Code Summary:• Membrane penetrations are firestopped at

    the wall membrane or surface, the sameas through penetrations

    Membrane Penetrations

    Firestop Code Requirements - IBC

  • 2/13/2017

    7

    • Section 715.1: Fire Resistive Joint Systems“Joints installed in or between fire-resistance rated walls, floor orfloor/ceiling assemblies and roofs or roof/ceiling assemblies shall beprotected by an approved fire-resistant joint system designed to resistthe passage of fire for a time period not less than the required fire-resistance rating of the wall, floor or roof in or between which the systemis Installed.”

    Exceptions: Several specific exemptions exist e.g. walls permitted tohave unprotected openings, floors within malls, etc..

    Joints

    Firestop Code Requirements - IBCPerimeter Barriers

    Firestop Code Requirements - IBC

    715.4 Exterior curtain wall/floor intersection. Where fire resistance-rated floor or floor/ceiling assemblies are required, voids created at theintersection of the exterior curtain wall assemblies and such floorassemblies shall be sealed with an approved system to prevent theinterior spread of fire. Such systems shall be securely installed andtested in accordance with ASTM E 2307 to provide an F rating for a timeperiod not less than the fire-resistance rating of the floor assembly.Height and fire-resistance requirements for curtain wall spandrels shallcomply with Section 705.8.5.Exception…..

    Perimeter barriers:Floor-to-ceiling glass

    PRESENTATION TITLE 42

    715.4 Exterior curtain wall/floor intersectionException: Voids created at the intersection of the exterior curtain wallassemblies and such floor assemblies where the vision glass extends tothe finished floor level shall be permitted to be sealed with an approvedmaterial to prevent the interior spread of fire. Such material shall besecurely installed and capable of preventing the passage of flame andhot gases sufficient to ignite cotton waste where subjected to ASTM E119 time-temperature fire conditions under a minimum positivepressure differential of 0.01 inch (0.254 mm) of water column (2.5 Pa)for the time period at least equal to not less than the fire-resistancerating of the floor assembly.

    PRESENTATION TITLE 43

    Firestop Code Requirements - IBC2012: 715.4.1 Exterior curtain wall/nonfire-resistance-ratedfloor assembly intersections. Voids created at the intersectionof exterior curtain wall assemblies and nonfire-resistance-ratedfloor or floor/ceiling assemblies shall be sealed with an approvedmaterial or system to retard the interior spread of fire and hotgases between stories.

    2015: 715.4.2 Exterior curtain wall/vertical fire barrierintersections. Voids created at the intersection of nonfire-resistance-rated exterior curtain wall assemblies and fire barriersshall be filled. An approved material or system shall be used tofill the void and shall be securely installed in or on theintersection for its entire length so as not to dislodge, loosen orotherwise impair its ability to accommodate expected buildingmovements and to retard the passage of fire and hot gases.

    • 1705.17 Fire-resistant penetrations and joints. In high-risebuildings or in buildings assigned to Risk Category III or IVin accordance with Section 1604.5, special inspections forthrough-penetrations, membrane penetration firestops,fire-

    resistant joint systems, and perimeter fire barrier systemsthat are tested and listed

    • ASTM standards required in 1705.17 for inspection procedures(E2174-04 and E2393-04)

    Special InspectionsFirestop Code Requirements

    • Fire codes govern the fire safety requirementsof buildings throughout their lifespan

    – International Fire Code

    Inspection during life of a building

    Firestop Code Requirements –Fire Codes

  • 2/13/2017

    8

    – 703.1 Maintenance. The required fire-resistancerating of fire-resistance-rated construction (includingwalls, firestops, shaft enclosures, partitions, smokebarriers, floors, fire-resistive coatings and sprayedfire-resistant materials applied to structural membersand fire-resistant joint systems) shall be maintained.

    – 2009: Such elements shall be visually inspected bythe owner annually and properly repaired, restored orreplaced when damaged, altered, breached orpenetrated.

    – 2015: Records of inspections and repairs shall bemaintained.

    Inspection during life of a buildingInternational Fire Code (IFC)

    International Building CodeTest Standards

    IBC

    ThroughPenetration

    ASTM E814UL 1479

    JointsUL 2079

    ASTM E1966

    PerimeterBarriers ASTM E2307

    Code Requirements - IBC

    IFC Video• “CLOSE ENOUGH IS NOT GOOD ENOUGH”: A

    Demonstration of Proper vs. Improper Firestopping

    http://www.youtube.com/c/FirestopOrg

    48

    Questions / Discussion

    Seminar agenda• What is firestopping, and why is it required?• Code Requirements• Firestop System Fire Testing• Penetration Firestop Systems• Membrane penetration firestop systems• Joint Systems• Perimeter Fire Containment Systems• Duct Enclosure systems• Understanding the UL Directories• Firestop installation options• Engineering judgments• Special inspection and special inspectors• Recognizing firestop installation problems• Plan review and inspection process

    recommendations• Notable changes in IBC 2009, 12, 15• IFC-Recommended firestop inspection techniques

    50

    THE BASICS

    SPECIFICAPPLICATIONS

    DOCUMENTS

    !!! AS OF 2012 IBC

    INSPECTIONTIPS

    How Firestopping is Tested

  • 2/13/2017

    9

    Underwriters Laboratories Inc.

    FM Global (Factory Mutual)

    Intertek Testing Services (ITS)

    Southwest Research Institute

    Third Party Testing Labs

    American Society of Testing and Materials (ASTM)

    Underwriters Laboratories Inc. (UL)

    Labs Test to Standards

    Through-Penetration TestBefore

    ASTM E119 TIME -TEMPERATURE CURVE Through-Penetration Test

    During

    Through-Penetration TestAfter

    Hose Stream Test

  • 2/13/2017

    10

    Example of Successful TestingConstruction - 4” PVC Through Drywall

    Firestopping - Intumescent Device & Sealant

    Before After

    Through-Penetration Systems

    Main Criteria:– F-Rating: Condition of Acceptance:

    • Prohibits flame passage

    • Hose stream (no projections of water through gaps)

    – T-Rating: Max. temp. rise of 325°F above ambient on

    the non-fireside

    Head of Wall Joint

    Fire Resistive Joint Testing

    Floor to Floor Joint

    ASTM E1399: Cyclic Movementand Measuring Min.& Max. JointWidths of Architectural JointSystems

    Cycling RequirementsClass Movement Min. Cycles FrequencyI Thermal 500 1 cycle / min.II Wind Sway 500 10 cycle / min.III Seismic 100 30 cycle / min.IV Combined 100 30 cycle /min.& 400 10 cycle / min

    Before After Fire Exposure

  • 2/13/2017

    11

    Hosestream Hosestream Failure

    Questions / Discussion Seminar agenda• What is firestopping, and why is it required?• Code Requirements• Firestop System Fire Testing• Penetration Firestop Systems• Membrane penetration firestop systems• Joint Systems• Perimeter Fire Containment Systems• Duct Enclosure systems• Understanding the UL Directories• Firestop installation options• Engineering judgments• Special inspection and special inspectors• Recognizing firestop installation problems• Plan review and inspection process

    recommendations• Notable changes in IBC 2009, 12, 15• IFC-Recommended firestop inspection techniques

    67

    THE BASICS

    SPECIFICAPPLICATIONS

    DOCUMENTS

    !!! AS OF 2012 IBC

    INSPECTIONTIPS

    Penetration Firestop Systems

    68

    Penetration Firestop Systems

    Consists of:• Assembly being penetrated• Penetrating item• Fill, void or cavity materials (firestopping

    materials)

    69

  • 2/13/2017

    12

    Three Components ofPenetrations

    71

    Codes & Standards

    Code RequirementsIBC 714.3 (wall assemblies)

    IBC 714.4 (Horizontal assemblies)

    • 714.3.1, 714.4.1 – Through penetration shall beprotected by one of the following:– As tested as part of the entire wall assembly– As tested to ANSI/UL 1479 / ASTM E 814

    • 714.3.1.2 – When tested to ANSI/UL 1479 orASTM E 814, systems shall have F Ratingequal to rating of wall penetrated

    • 714.4.1.2 - …shall have an F rating and a Trating of not less than 1 hour but not less thanthe required rating of the floor penetrated.”

    72

    Code Requirements WallAssemblies Cont.

    • 714.3.2 – Membrane penetration shall beprotected as follows:– As specified in 713.3.1 (i.e. through

    penetrations)– Recessed fixtures shall be installed so as not

    to reduce the required fire resistance– Specific rules for outlet boxes…

    73

    Code Requirements SmokeBarriers

    • 714.5 – Penetrations in smoke barriersshall have an L Rating at ambient and400 °F per UL2079– Max 5.0 CFM / sq ft of opening, or– Max cumulative leakage of 50 cfm for all

    penetrations within any 100 square feet ofwall or floor area

    74

    Sprinkler PipeConsiderations

  • 2/13/2017

    13

    • NFPA 13 Annular Space Limitations– If Pipe < 3.5” then annular = 1”– If pipe > 3.5” then annular = 2”

    • Pipe Movement– Seismic Movement– Water-Hammer from Testing

    76

    Metallic Sprinkler Pipe Penetrations:

    Sprinkler Pipe Considerations Ratings

    • F - Flame Occurrence• T - Heat Transmission• L - Leakage• W - Water Leakage (Optional)

    77

    Conditions of AcceptanceF Rating

    • Passage of Flame• Hose Stream

    78

    L (Air Leakage) Ratings

    • L Rating methodology added to ANSI/UL1479 in 1993

    • Leakage determined at 0.3 in. WC• Tested at Ambient and 400°F• Results published in either CFM/Device

    or CFM per sq ft

    79

    Conditions of AcceptanceTo obtain T-Rating

    • No Passage of Flame• Not to exceed 325°F Temperature Rise• Code-mandated only for some floor

    penetrations

    80

    IBC – T Rating

    81

  • 2/13/2017

    14

    IBC – T Rating• Required for

    – through-penetrations of horizontal assemblies (with exceptions)– membrane penetrations by non-electrical boxes

    T-rating never required by code for wall through-penetrations

    • Methods for achieving a T Rating include:– Wrap metallic pipe with mineral wool or ceramic

    insulation– A listed device around metallic pipe that will cool pipe

    during a fire

    82

    IBC – T Rating (Exceptions)

    83

    Exceptions to floor penetration T-Rating:1. Floor penetrations contained and located within thecavity of a wall2. Floor penetrations by floor drains, tub drains orshower drains contained and located within theconcealed space of a horizontal assembly (IBC 2012)3. Max 4-inch diameter penetrations directly into metal-enclosed electrical power switchgear. (IBC 2015)

    Annular Space

    Typical Annular Space

    85

    1.Centered

    2. Off-Centered

    3. PointContact

    4. ContinuousContact

    Sealant depth & locationmust be verified

    5/8” called for inListed System

    < 5/8” installed in thefield

    TOP VIEWSIDE VIEW

    Crown Bead at Point Contact

  • 2/13/2017

    15

    Intumescence = Expansion with heat Pen

    etra

    ting

    Item

    Untooled sealant on the surfacewill likely fail

    Poor SealantFootprint

    Properly recessed and tooledsealant will expand inward as

    designed.

    Improved SealantFootprint

    Pene

    tratin

    g Ite

    m

    Properly Tooled Penetrations

    • The Firestop sealant mustbe well bonded topenetrating item andsurrounding wall or floor

    • Should always inspectboth sides

    91

    • Intumescent sealant expands and fills the void• The intumescent expands inwards to crush/collapse pipe

    Steel Collars and IntumescentWrap Strips

    STI Graphic

    • Intumescent Putties– Hand moldable intumescent “putties

    Firestop Putties

  • 2/13/2017

    16

    Verify that a PenetrationFirestop System matches the

    applicationEvery tested and listed system has its own uniqueallowances, limits, requirements:-Hourly fire rating-Type of barrier-Type of penetrant-Min/Max Hole size-Firestop product

    94

    Where Can I Find The MostCurrent Listings?

    Hard Copy

    CD-ROM

    Online

    Identifying a matching firestopsystem

    • What type of building assembly is requiring firestopping?– Floor or Wall

    • What type of material is the building assembly– Concrete, CMU, Gypsum, Wood Frame

    • What is the penetrating item(s)?– Metallic, Nonmetallic, Cables, Insulated, Construction Joints, etc.

    • What are the specific descriptions regarding thepenetrants?– Diameter, quantity, type of plastic, type & thickness of insulation,

    etc.• What is the hourly rating you are looking for?

    – F Rating, T Rating• Are there any special considerations?

    – Movement, Environmental exposure• Are there any special considerations?

    – Movement, Environmental exposure

    SYSTEM No. C-AJ-1379

    F Ratings – 3 HrT Ratings – 0 Hr

    1A. Floor or Wall Assembly – Min 4-1/2 in. thick reinforced normal weight (150 pcf) concrete.Wall may also be constructed of any UL classified Concrete Blocks*. Max diam of opening is26-1/2 in.

    See Concrete Blocks (CAZT) category in the Fire Resistance Rating Directory for namesof manufacturers.

    1B. Metallic Sleeve (optional) – Nom 16 in. (or smaller), Schedule 10 (or heavier) steel pipesleeve, cast or grouted into floor or wall assembly.

    2. Through Penetrants – One metallic pipe or tubing to be installed concentrically oreccentrically into opening such that the annular space between the pipe and the periphery of theopening is min 0 in. (point of contact) to max 2-1/2 in. Pipe to be firmly supported on both sides ofopening. The following types and sizes of pipes may be used:

    (a) Nom. 24 in. diam (or smaller) Schedule 30 (or heavier) steel or iron pipe.(b) Nom. 4 in. diam (or smaller) electrical metallic tubing.

    3. Packing Material – Mineral wool insulation of min 4 pcf firmly pressed into opening as apermanent form. Insulation material to be recessed by min depth of 1/2 in. from top surface offloor or both surfaces of wall.

    4. Fill, Void, or Cavity Materials* – Caulk – Min 1/2 in. thickness of fill material appliedwithin the annulus, flush with top surface of floor or both surfaces of wall. A min 1/4 in. crown ofthe caulking material shall be applied around the entire circumference of the pipe at the level ofthe floor surface or both wall surfaces.

    W. R. GRACE & CO. – CONN. – FlameSafe® FS900+

    * Bearing the UL Classification Marking.

    Company ABC – SuperDuper Sealant

    For the Contractor

    98

    UL Systems serve two roles:

    1) Evidence of compliance

    2) A set of build-instructions

    For the Building / Fire Official

    99

    UL Systems serve two roles:

    1) Evidence of compliance

    2) Document by which to inspect

  • 2/13/2017

    17

    100

  • 2/13/2017

    18

    Through Penetration FirestopSystems

    • Each firestop system contains specificconstruction features

    • Many firestop systems contain variousoptions and various ratings

    • Must be followed exactly for rating toapply

    110

    • Floor or wallconstruction type andthickness

    • Size and shape ofopening

    • Size and type ofpenetrating item(s)

    • Percent fill of cables• Annular space• Rating requirement• Firestopping materials

    111

    Factors Affecting Penetrations

  • 2/13/2017

    19

    Summary: Inspection of Penetrations

    • Firestop system must be installed inaccordance with the tested and listedsystem

    • Rating of the system must match therequired rating of assembly beingpenetrated

    • Penetrating item and opening size mustmatch the tested and listed system

    112

    Inspection of Penetrations Cont.

    • Where required, packing material must beinstalled per the tested and listed system

    • Required firestopping material must beinstalled per the tested and listed system

    • Understand some sealants may shrink wheninstalled and the amount of shrinkage maybe in the listing(difference between wet thickness in listing,and dry thickness measured later on)

    113

    Questions / Discussion Seminar agenda• What is firestopping, and why is it required?• Code Requirements• Firestop System Fire Testing• Penetration Firestop Systems• Membrane penetration firestop systems• Joint Systems• Perimeter Fire Containment Systems• Duct Enclosure systems• Understanding the UL Directories• Firestop installation options• Engineering judgments• Special inspection and special inspectors• Recognizing firestop installation problems• Plan review and inspection process

    recommendations• Notable changes in IBC 2009, 12, 15• IFC-Recommended firestop inspection techniques

    115

    THE BASICS

    SPECIFICAPPLICATIONS

    DOCUMENTS

    !!! AS OF 2012 IBC

    INSPECTIONTIPS

    Electrical Membrane Penetrations

    116 117

    Codes & Standards

  • 2/13/2017

    20

    Code RequirementsWall Assemblies

    Membrane Penetrations• 714.3.2 of the IBC• Installed such that the required fire

    resistance will not be reduced:– Metallic boxes installed per limits in IBC– Nonmetallic boxes installed as tested and

    listed

    118

    Metallic ElectricalOutlet Boxes in Walls

    • Metallic boxes installed per code– Maximum 16 sq in. outlet box– Maximum 100 sq in. of opening on each side

    of wall per 100 sq ft of wall area– Maximum 1/8 in. annular space between wall

    membrane and box– Boxes on opposite sides of wall need to be

    either separated horizontally by minimum 24in. or protected by some type of heat barrier

    119

    Metallic Electrical Boxes in Wallwith Less than 24 in. Spacing

    120

    Electrical Boxes

    Non-CompliantNon-Compliant

    Metallic Electrical Boxes in Wallwith Minimum 24 in. Spacing

    121

    24 in. Min

    Electrical Boxes

    Metallic Electrical Boxes in WallsCont.

    • Installation not complying with code limits(16 sq in, max 100 sq in/100 sq ft) shallbe installed as tested and listed

    122

    Metallic ElectricalOutlet Boxes

    • 2015: Metallic boxes installed in up to 2 hrrated walls can– Exceed 16 sq in. outlet box– Exceed 100 sq in. of opening per 100 sq ft of

    ceiling area• provided such penetrating items are

    protected by listed putty pads or otherlisted materials and methods, andinstalled in accordance with the listing.

    123

  • 2/13/2017

    21

    Utility Boxes

    • Other, non-electrical boxes Are Permittedthat:– are protected with a tested penetration firestop

    system, and– have an F and T rating equal to the required fire-

    resistance rating of the wall penetrated, and– are installed in accordance with their listing.

    • Listed non-electrical boxes exist withinherent (listed) fire rating

    124

    Metallic Electrical Boxes inStaggered Stud Walls

    Protection required despite spacing

    125

    Electrical Boxes

    Putty Pads, Insert Pads or Gaskets(CLIV / QCSN), or other methods

    Nonmetallic ElectricalOutlet Boxes in Walls

    • Nonmetallic boxes installed as tested andlisted

    • Maximum 1/8 in. annular space betweenwall membrane and box

    • Boxes on opposite sides of wall need tobe either separated as specified in theirlisting or protected by some type of heatbarrier

    127

    Listed Nonmetallic ElectricalBoxes in Wall with Minimum 24 in.

    Spacing

    128

    24 in. Min

    Electrical Boxes

    Listed Nonmetallic ElectricalBoxes in Wall at Reduced Spacing

    Per Listing

    129

    Electrical Boxes

  • 2/13/2017

    22

    Listed Nonmetallic ElectricalBoxes in

    Staggered Stud Walls Per Listing

    130

    Electrical Boxes

    Putty Pads, Insert Pads or Gaskets(CLIV / QCSN), or other methods

    Recessed electrical boxes in walls:summary• 4 possible challenges

    – Boxes on opposite sides of wall too close(24 inch rule)• Putty pads a solution• 2009 IBC requires stud cavities to be

    “individual noncommunicating stud cavities” for 24 inchseparation to be acceptable

    – Boxes too big(> 16 sq. in.)

    • Putty pads a solution for boxes up to tested size limit(see CLIV listings)

    – Too many boxes in one small area(> 100 sq. in. per 100 sq ft of wall)

    • IBC 2015 allows “listed materials and methods” when thislimit exceeded; putty pads commonly accepted

    – Non-metallic outlet boxes• Must use a specially tested/listed plastic box, within listing

    limits (may require a putty pad)

    Metallic ElectricalOutlet Boxes in Ceilings

    • Metallic boxes installed per code– Maximum 16 sq in. outlet box– Maximum 100 sq in. of opening per 100 sq ft of

    ceiling area– Maximum 1/8 in. annular space between ceiling

    membrane and box• Installation not complying with these

    prescriptive requirements shall be protected bytested and listed solutions

    Nonmetallic ElectricalOutlet Boxes in Ceilings

    • Nonmetallic boxes installed as tested andlisted

    • Maximum 1/8 in. annular space betweenceiling membrane and box

    Questions / Discussion Seminar agenda• What is firestopping, and why is it required?• Code Requirements• Firestop System Fire Testing• Penetration Firestop Systems• Membrane penetration firestop systems• Joint Systems• Perimeter Fire Containment Systems• Duct Enclosure systems• Understanding the UL Directories• Firestop installation options• Engineering judgments• Special inspection and special inspectors• Recognizing firestop installation problems• Plan review and inspection process

    recommendations• Notable changes in IBC 2009, 12, 15• IFC-Recommended firestop inspection techniques

    135

    THE BASICS

    SPECIFICAPPLICATIONS

    DOCUMENTS

    !!! AS OF 2012 IBC

    INSPECTIONTIPS

  • 2/13/2017

    23

    Joint Systems Codes & Standards

    IBC - Definition

    IBC Definition of JOINT• The opening in or between adjacent

    assemblies that is created due to buildingtolerances, or is designed to allowindependent movement of the building inany plane caused by thermal, seismic,wind or any other loading.

    138

    Building Code RequirementsFire Resistive Joints

    139

    Section 715.1: Fire Resistive Joint Systems

    •“Joints installed in or between fire-resistance rated walls, floor orfloor/ceiling assemblies and roofs or roof/ceiling assemblies shall beprotected by an approved fire-resistant joint system designed toresist the passage of fire for a time period not less than the requiredfire-resistance rating of the wall, floor or roof in or between which thesystem is Installed.”

    Exceptions: Several specific exemptions exist e.g. wallspermitted to have unprotected openings, floors within malls, etc..

    Building Code RequirementsIBC – Joints in Smoke Barriers

    • must be designed and constructed to restrictthe movement of smoke.

    • rating used: L Rating– measurement of air leakage rate through a fire

    resistive joint system or penetration.• 715.6 - Joints in smoke barriers shall have an L

    Rating not in excess of 5 cfm / lineal ft ofopening

    140

    Building Code Requirements IBC– Joints

    • 715.2 - Fire-resistant joint systems shall besecurely installed in or on the joint for its entirelength so as not to dislodge, loosen orotherwise impair its ability to accommodateexpected building movements and to resist thepassage of fire and hot gasses

    • 715.3 - Joints shall be tested to ANSI/UL 2079or ASTM E 1966”

    141

  • 2/13/2017

    24

    Forces Which Induce Movement

    142

    Thermal

    Wind Sway

    Seismic

    Load

    Types of Joint Systems

    • Floor-to-Floor (Expansion Joint)• Floor-to-Wall (Edge of Slab)• Head-of-Wall (Top of Wall)• Wall-to-Wall (Vertical Control Joint)• Bottom of Wall

    143

    Categories of Fire-ResistiveJoint systems

    • Sealant Systems (Caulks)• Sprayed /Elastomeric Membranes

    (Sprays)• Mechanical Joints

    144

    • Nominal Joint Width• Assembly Rating• Movement• Extension• Compression• Percent (%) Extension / Compression• Mineral Wool Compression• Sealant Depth

    Construction Joint Terminology

    145

    146

    GypsumBoard

    Roof orFloor Deck

    Deep Leg Track

    Elastomeric Caulkor Spray

    Typical Head of Wall Joint SystemWith

    Nominal Joint Width

    Mineral Wool

    1”

    Steel Stud

    147

    Elastomeric Caulkor Spray

    Mineral Wool

    1/2”

    GypsumBoard

    Steel Stud

    Load

    Roof orFloor Deck

    Deep Leg Track

    Typical Head of Wall Joint System

  • 2/13/2017

    25

    148

    Typical Head of Wall Joint System

    Elastomeric Caulkor Spray

    Mineral Wool

    1-1/2”

    Steel Stud

    Roof orFloor Deck

    Deep Leg TrackLoad

    GypsumBoard

    149

    Flutes are stuffedwith mineral wool orspeed plugs per UL

    system. Remaining joint isstuffed with

    mineral wool orspeed strips per UL

    system.

    Firestop sealant isapplied to both sides

    of wall per ULsystem.

    Head-of-Wall Spray Application

    Cyclic Movement BetweenMinimum

    & Maximum Joint Widths

    153

    Where Can I Find The MostCurrent Listings?

    Hard Copy

    CD-ROM

    Online

    Evaluating a Fire-Resistive JointSystem

    1. What type of buildingassemblies form the joint?

    – Floor/Floor, Floor/Wall,Wall/Wall, Top of Wall/Ceiling

    2. What materials are theassemblies constructedfrom?

    – Concrete, CMU, Gypsum3. What is the required hourly

    rating?– Assembly rating (1 – 4 hour)

    4. What is the width of the joint(inches)?

    5. How much movement isrequired?

    – Must accommodate buildingmovement (% of joint size)

    6. Are there any specialconsiderations?

    – Unique construction condition,environmental exposure

  • 2/13/2017

    26

    UL Nomenclature

    Navigating the UL Directory:

    JOINT SYSTEMS (XHBN)

    First Two Alpha Characters identify the typeof joint system:

    FF = Floor-to-FloorWW = Wall-to-WallFW = Floor-to-WallHW = Head-of-Wall

    157

    HW – D – 0060 Navigating the UL Directory:

    JOINT SYSTEMS (XHBN)

    Third Alpha Character identifies themovement capabilities of the system:

    D = Dynamic (movement capabilities)S = Static (no movement capabilities)

    UL Nomenclature Cont.

    158

    HW – D – 0060

    Navigating the UL Directory:

    JOINT SYSTEMS (XHBN)

    First Numeric Character identifies the nominal width ofthe linear opening:

    0000 – 0999 = < 2 in.1000 – 1999 = > 2 in. and < 6 in.2000 – 2999 = > 6 in. and < 12 in.3000 – 3999 = > 12 in. and < 24 in.4000 – 4999 = > 24 in.

    UL Nomenclature Cont.

    159

    HW – D – 0060 Navigating the UL Directory:

    JOINT SYSTEMS (XHBN)

    Second Through Fourth Numeric Charactersidentify the individual system number

    UL Nomenclature Cont.

    160

    HW – D – 0060

    Joint Systems

    161 162

    Typical Floor-to-Floor System

  • 2/13/2017

    27

    163

    Typical Floor-to-Wall System

    164

    Typical Wall-to-Wall System

    Plan Review of Joint Systems

    • What type of joint is being protected?• What is the required hourly rating?• What is the width of the joint (nominal

    installed width)?• How much movement is required?• Is an L Rating required?• Is submitted system consistent with the

    above requirements?

    165

    Recommended Joint SystemCorrection Notice

    • Deflection is required to be installed with an approvedjoint system per Section 715 of the IBC. Theassemblies need to be designed to allow joints tocompress and extend with movement of structure whilemaintaining the fire-rating of the assemblies.

    • Please clarify building deflection by listing theMaximum and Minimum building deflectionmovements to determine movementcapabilities of assembly and identify listedassemblies for all joint systems.

    166

    Inspection of Joint Systems

    • What type of building assemblies formthe joint (type and thickness)?

    • What materials are the assembliesconstructed from?

    • Are there any special considerations?(EJ’s)

    167

    Joint Inspection Process

    • Inspect joint systems during framing inspection• Contractor to provide you with the UL listed

    assembly as shown / approved on the plans• Confirm all joint systems will accommodate

    required movement• For Mechanical Joints observe the ceiling

    runner for the UL label located on the side ofthe runner

    168

  • 2/13/2017

    28

    Joint Systems - Summary

    • Provide tested and listed systems thatincludes joint movement at Plan Reviewor before field inspection

    • Joints must accommodate expectedbuilding movement

    • Inspect some joint systems duringframing inspection

    169

    Questions / Discussion

    Seminar agenda• What is firestopping, and why is it required?• Code Requirements• Firestop System Fire Testing• Penetration Firestop Systems• Membrane penetration firestop systems• Joint Systems• Perimeter Fire Containment Systems• Duct Enclosure systems• Understanding the UL Directories• Firestop installation options• Engineering judgments• Special inspection and special inspectors• Recognizing firestop installation problems• Plan review and inspection process

    recommendations• Notable changes in IBC 2009, 12, 15• IFC-Recommended firestop inspection techniques

    171

    THE BASICS

    SPECIFICAPPLICATIONS

    DOCUMENTS

    !!! AS OF 2012 IBC

    INSPECTIONTIPS

    Perimeter FireContainment Systems

    PATHS OF FIREPROPAGATION

    173

    What is a Curtain Wall?

    An exterior building wallwhich carries no roof orfloor loads and consists ofmetal, glass or stone or anycombination there ofsupported by a metal frame.

    • Summerland, Isle of Man, British Isles. Fire spreadthrough safing slot. 50 people killed.

    • Hilton Hotel, Las Vegas, NV. Fire spread from 8th to 13thfloor in 25 minutes. 8 fatalities.

    • First Interstate Bank, Los Angeles, CA. Flames spreadfrom 13th to 16th floor via perimeter joint. One death.

    • One Meridian Plaza, Philadelphia, PA. Fire spread from22nd to 30th floor through unprotected openings includingslab edge.

    Unsealed or Improperly sealedperimeter joints cost lives andhuge liability losses…

  • 2/13/2017

    29

    Extending the Rated Floorto the curtain wall...

    The perimeter joint must be sealed with anapproved material or system that extends

    this rating to the exterior wall surface

    Mandated by code!

    Common Terminology

    177

    Aluminum Transom Vision Glass

    Spandrel: Glass,

    Aluminum or ……

    Aluminum Mullion

    How do the codes address theprotection at the perimeter?

    Preventing interior fire spread

    • Sections 715.4• Exterior curtain wall/floor intersection. Void at

    edge of rated floor shall be sealed with anapproved system, shall be securely installedand Tested to ASTM E 2307 for time periodequal to rating of floor

    179

    Preventing exterior fire spread

    • 705.8.5 – Vertical Separation of Openings -requires unprotected openings in exterior wallsnot separated horizontally by 5 ft to be:– Separated 3 ft minimum vertically by 1 hr wall,

    or– Separated 30 in. minimum horizontally by 1 hr

    flame barrier– These requirements waived if building is

    sprinklered and/or three stories of less• Protects against “leap-frog” fire spread

    180

  • 2/13/2017

    30

    Code Requirements Cont.

    • 715.4.5 – Where section 705.8.5 doesnot apply, the requirements of section715.4 shall still apply

    • Protect perimeter void or joint

    181

    Elements of PerimeterFire Containment Systems

    • Floor Assembly• Curtain Wall Assembly• Safing Materials• Attachment methods• Sealants

    182

    183

    Time – Temperature Curve

    Temp

    (°F)

    Time (Hr)

    1050 ° F (6min) glass fiberinsulation melts

    184

    Time – Temperature Curve

    Temp

    (°F)

    Time (Hr)

    1220 ° F (9min)aluminum melts

    ASTM E2307

    Standard Test Method forDetermining Fire Resistance ofPerimeter Fire Barriers Using

    Intermediate-Scale, Multi-StoryTest Apparatus

    CurtainWall TestAssembly

    Pre-Burn

    Transom above floor

    Transom below floor

    Mechanical attachmentssupporting insulation

    Mineral wool insulation atspandrel area

    Mullions

  • 2/13/2017

    31

    ASTM E2307 TestingHas Defined howPerimeter Joints

    Should Be Built…

    188

    Factors AffectingPerimeter Joint Performance

    Floor and/or wallconstruction type andthickness

    Joint width Movement requirements Rating requirement Firestopping materials

    189

    4 Compression Fit Safing

    Mechanically Attached3

    Protect Mullions5

    Reinforcement Member1

    2 Mineral Wool Insulation

    Smoke Barrier6

    1

    3

    4

    5 6

    2

    Curtain Wall Fire ContainmentSix Basic Design Principles

    190

    Typical Curtain Wall SystemCont.

    Mechanical attachmentsare used to hold the curtain wallinsulation (not shown) in placeand are attached to the verticalmullions. Theses come in manyforms such as hangers, stick pins,steel angles, as well as otherforms.

    191

    Reinforcement member or backerbar set 2” below top of slab tosupport curtain wall insulationfrom bowing due to compressionof Safing insulation.Can be a T-bar, hat channel, steelangle, as well as others. Must bemechanically attached tomullions.

    Typical Curtain Wall System Cont.

    Reinforcement Member

    MechanicallyAttached (screw)

    Minimum 2 in. thick, 8 pcf densitymineral wool faced on one sidewith aluminum foil scrim. Curtainwall insulation tightly fittedbetween framing members andmechanically attached to mullionsand transoms.

    Typical Curtain Wall System Cont.

  • 2/13/2017

    32

    193

    4 in. thick, 4 pcf density mineralwool installed with the fibersorientated vertically. Mineral woolto be compressed 25% to 33% inthe thickness dimension, andinstalled flush with the top of thefloor slab.

    Example. An 8 in. joint requires 10¾” of mineral wool safing withinthe joint.

    Typical Curtain Wall System Cont.

    Wrong !

    Correct

    Typical Curtain Wall System Cont.• To allow for movement between the slab and wall

    mineral wool must be inserted perpendicular to thejoint and compressed to the proper %

    STI Graphic

    195

    Min. 1/8 in. wet thickness sprayapplied over mineral wooloverlapping onto concrete floorand curtain wall assembly. Seelisted system for correct overlapand spray applied thickness

    Typical Curtain Wall System Cont.

    196

    Typically - 8 in. wide x 2 in. thick, 8pcf density mineral wool faced onone side with aluminum foil scrim.Framing covers are to be centeredover each vertical framing memberand mechanically secured to thecurtain wall insulation.

    Typical Curtain Wall System Cont.

    197

    CompletedInstallation!

    Typical Curtain Wall System Cont.

    Evaluating a Perimeter JointSystem

  • 2/13/2017

    33

    1. What is the composition of theexterior wall?

    – Concrete panel, Spandrel Glass,Aluminum Panel, Brick Veneer,etc.

    2. What supports the exteriorwall?

    – Steel stud, aluminum mullions,etc.

    3. What is the required hourlyrating?

    – F rating (1 – 2 hour)4. What is the joint width

    (inches)?– Measured from edge of slab to

    nearest point of curtain wall5. How much movement is

    required?– Must accommodate building

    movement (% of joint size)6. Are there any special

    considerations?– Unique construction condition,

    environmental exposure

    UL Nomenclature

    Navigating the UL Directory:

    PERIMETER FIRE CONTAINMENT SYSTEMS(XHDG)

    First Two Alpha Characters identify the typeof system:

    CW = Curtain Wall

    200

    CW – D – 2005

    Navigating the UL Directory:

    PERIMETER FIRE CONTAINMENT SYSTEMS(XHDG)

    Third Alpha Character identifies themovement capabilities of the system:

    D = Dynamic (movement capabilities)S = Static (no movement capabilities)

    UL Nomenclature Cont.

    201

    CW – D – 2005 Navigating the UL Directory:

    PERIMETER FIRE CONTAINMENT SYSTEMS(XHDG)

    First Numeric Character identifies the nominalwidth of the linear opening:

    0000 – 0999 = < 2 in.1000 – 1999 = > 2 in. and < 6 in.2000 – 2999 = > 6 in. and < 12 in.

    UL Nomenclature Cont.

    202

    CW – D – 2005

    Question: Why aren’t floor-to-wall (FW) systems acceptable forcurtain walls?

    Answer: Floor-to-wall systems test fire resistance between arated floor and rated wall tested per ASTM E1966.

    CW systems are specific perimeter tests between arated floor and non-rated curtain wall using theIntermediate Scale Multi-story Apparatus (ISMA) perASTM E2307.

    Design Questions… Additional DesignQuestions…

    Question: Are curtain wall joints static or dynamic?

    Answer: This area is referred to as a slot. The word joint suggestsmovement. Experts tend to agree that a small amount ofmovement occurs within the slot area. It is up to theStructural Engineer to determine the level of movementrequired for the project.Some wall designs are subject to a small amount ofvertical shear or horizontal sway and some systemsincorporate these values.

  • 2/13/2017

    34

    Additional DesignQuestions…

    Question: What if our design isn’t a perfect match for asystem?

    Answer: We strongly suggest specifying tested systems.However, real world designs are seldom a perfectmatch!Manufacturers or Engineers can provide anengineering judgment if a listed system is availablethat is reasonably close in construction

    1. Provide Backing/Reinforcement Member atSafing Line

    2. Mechanically Attached Curtain Wall Insulation

    4. Protect Aluminum Mullions

    3. Compression-fit Safing Insulation - as required per tested assemblyInstall Safing Impaling Clips - as required per tested assembly

    5. For “Smoke Containment” - Add Firestop Coating

    Perimeter Fire Containment

    Basic Design Criteria

    Inspection ofPerimeter Fire Containment Systems

    • Inspected at rough inspection• Does the size of joint fit within the guidelines

    of the tested assembly?• Was the firestopping material/sealant

    installed to minimum depth (thickness) andinstalled with the correct overlap onto boththe insulation and the concrete floor?

    207

    Inspection of Perimeter FireContainment cont.

    •Is the installed mineral wool of the correct densityspecified in listing?•Was the mineral wool installed to the correctcompression and according to the correct orientation?

    Questions / Discussion Seminar agenda• What is firestopping, and why is it required?• Code Requirements• Firestop System Fire Testing• Penetration Firestop Systems• Membrane penetration firestop systems• Joint Systems• Perimeter Fire Containment Systems• Duct Enclosure systems• Understanding the UL Directories• Firestop installation options• Engineering judgments• Special inspection and special inspectors• Recognizing firestop installation problems• Plan review and inspection process

    recommendations• Notable changes in IBC 2009, 12, 15• IFC-Recommended firestop inspection techniques

    210

    THE BASICS

    SPECIFICAPPLICATIONS

    DOCUMENTS

    !!! AS OF 2012 IBC

    INSPECTIONTIPS

  • 2/13/2017

    35

    Fire Resistive Duct andDuct Enclosure Systems

    Fire Resistive Duct andDuct Enclosures

    • Why are certain ducts, cable trays, pipes,electrical enclosures required to be enclosed infire resistive construction?

    Fire Resistive Duct andDuct Enclosures

    • In 2002, an estimated 7,100restaurant structure fires wereresponsible for 108 civilian fireinjuries and $116 million inproperty loss.

    • Approximately 64% of restaurantstructure fires were caused bycooking

    • Cooking materials (grease, oil)were the most frequent items firstignited

    • Statistics from the 2004 Article,“Restaurant Fires” by US FireAdministration. www.usfa.dhs.gov

    Fire Resistive DuctsAnd Duct Enclosures

    • What are fire resistive ducts and ductenclosures?

    Traditional Drywall ShaftEnclosure

    •Utilized “Type X” Drywall

    •Utilizes Listed Shaft-WallDesigns

    •Follow manufacturersinstructions for horizontalassemblies

    Fire Resistive Duct Enclosures

    Alternatives* to traditional shaftenclosure construction include:•Flexible Duct Wrap Enclosure Systems

    •Board type Enclosure Systems

    •Fire Rated Ductwork (enclosure built-in)

    •Factory Built Duct with enclosuresystem built-in (pre-insulated)

    *Alternative systems must be tested andlaboratory listed to the requirements ofthe applicable building code.

    Fire Resistive Ductsand Duct Enclosures

  • 2/13/2017

    36

    Field Applied, Flexible DuctWrap Enclosure Systems

    • Offer design flexibility and spacesavings vs. traditional shaftenclosures

    • Offer Zero clearance between theduct and the duct wrap

    • Offer Zero clearance between theoutside of the duct wrap andcombustible construction

    • Offer a margin of safety with hightemperature fibers rated forextended exposure at/above1800F

    • Offer a system tested specificallyfor the application

    • Grease Ducts

    • Stairwell Pressurization Ducts by design

    • Hazardous Exhaust Ducts

    • Dryer Exhaust Ducts

    • Laundry and Refuse Chutes

    In the absence of dampers, ducts need to eitherbe “Fire Resistive Ducts” or protected by“Fire Resistive Duct Enclosures”

    Building Codes & EngineeringPractice prohibit the use ofdampers in many ducts

    Smoke and Fire Dampers maynot work properly if firestopping

    is installed The Three Elementsof Life Safety

    SUPPRESSIONCOMPARTMENTALIZATION

    DETECTION(1) Contain potential internal fires that

    might occur in ducts conveyinghazardous / flammable materials (suchas grease).

    (2) Protect the stability and integrity of theduct when exposed to external fire

    (3) Prevent the ignition of combustiblematerials inside the duct (grease)when exposed to an external fire.

    (4) Prevent heat from ignitingcombustibles in adjacentcompartments

    Fire Resistive Ducts andDuct Enclosure Systems are

    used to:

    Code Requirements

    222

    Since 2006 IMC requires shaft enclosure for greaseducts that penetrate fire rated construction.

    506.3.10 Grease duct enclosure. A grease duct serving a Type I hoodthat penetrates a ceiling, wall or floor shall be enclosed from thepoint of penetration to the outlet terminal [ ] Ducts shall beenclosed in accordance with the International Building Coderequirements for shaft construction. [ ] Clearance from the duct tothe interior surface of enclosures of combustible constructionshall be not less than 18 inches (457 mm). Clearance from theduct to the interior surface of enclosures of noncombustibleconstruction or gypsum wall board attached to noncombustiblestructures shall be not less than 6 inches (152 mm). The ductenclosure shall serve a single grease exhaust duct system andshall not contain any other ducts, piping, wiring or systems.

  • 2/13/2017

    37

    223

    IMC allows systems tested to ASTM E 2336 asan alternative to “Shaft” construction.

    506.3.10 Grease duct enclosure. - Exceptions:1. The shaft enclosure provisions of this section shall not berequired where a duct penetration is protected with athrough-penetration firestop system classified in accordancewith ASTM E 814 and having an "F" and "T“ rating equal tothe fire-resistance rating of the assembly being penetratedand where the surface of the duct is continuously covered onall sides from the point at which the duct penetrates a ceiling,a wall or floor to the outlet terminal with a classified andlabeled material, system, method of construction or productspecifically evaluated for such purpose, in accordance withASTM E 2336. Exposed duct wrap systems shall beprotected where subject to physical damage.

    224

    NFPA 96 – Requires listing per ASTM E 2336 for fieldapplied grease duct enclosure materials.

    4.3 Field-Applied and Factory-Built Grease Duct Enclosures.4.3.1 Field-applied grease duct enclosures shall be protected with

    a through-penetration firestop system classified inaccordance with ASTM E 814 or UL 1479 having an “F” and“T” rating equal to the fire resistance rating of the assemblybeing penetrated.

    4.3.1.1 The surface of the field fabricated grease duct shall becontinuously covered on all sides from the point at which theduct enclosure penetrates a ceiling, wall, or floor to the outletterminal.

    4.3.1.2 The field-applied grease duct shall be listed in accordancewith ASTM E 2336, and installed in accordance with themanufacturer’s instructions and the listing requirements.

    225

    IBC requires that Hazardous Production Materialshave ventilation. HPM ducts that penetrate firerated floors must be in a “shaft”.

    415.8.2.6 Ventilation. Mechanical exhaust ventilation [ ] shall beprovided throughout the portions of the fabrication area where HPM[Hazardous Production Materials] are used or stored. The exhaustair duct system of one fabrication area shall not connect to anotherduct system outside that fabrication area within the building.

    A ventilation system shall be provided to capture and exhaust gases,fumes and vapors at workstations. [ ]

    Exhaust ducts penetrating occupancy separations shall be contained in ashaft of equivalent fire-resistance-rated construction. Exhaust ductsshall not penetrate fire walls.

    Fire dampers shall not be installed in exhaust ducts.

    Testing RequirementsField Applied Grease Duct Enclosure Systems

    •ASTM E 2336•ASTM E 84 or UL 723•ASTM E 814 or UL1479

    Factory Built Grease Duct Enclosure Systems•ASTM E 2336 or UL 2221•ASTM E 814 or UL 1479•UL 1978•ASTM E 84 or UL 723

    Shaft Alternatives for HVAC Duct Enclosure Systems•ISO 6944•ASTM E2816•ASTM E 814 or UL 1479•ASTM E 84 or UL 723

    227

    ASTM E 2336 is modeled directly from ICC-ES Acceptance Criteria 101 (AC101) firstpublished in 1994.

    ASTM E 2336 requires compliance to 5 fire tests:1. Section 4.1.1 requires non-combustibility to ASTM E 1362. Section 4.1.2 requires a 2 Hour ASTM E 119 Wall Panel Test3. Section 4.1.3 requires a durability test modeled after ASTM C 5184. Section 4.1.4 requires an internal grease duct fire test to demonstrateperformance during long term exposure to service conditions (500°F for 4 hours),and exposure to a standardized internal grease fire (2000°F for 30 minutes)5. Section 4.1.5 requires a fire engulfment test run to the ASTM E 119 fire curve,which tests the capability of the duct and enclosure system to resist externalfires, tests the integrity of the enclosure fastening system, and tests the throughpenetration performance of the system per ASTM E 814.

    What is ASTM E 2336? HVAC Duct EnclosureFull Engulfment per ISO 6944

    ISO 834 Fire Curve (Similar to ASTM E-119 )

    • Stability – does the duct collapse

    • Integrity – are opening created in theduct

    • Insulation (Similar to ASTM E 814)

    Duct A requires negative pressure on a ductwithout openings to the furnace

    Duct B requires negative pressure on a ductwith openings to the furnace

  • 2/13/2017

    38

    Duct InspectionsWas the Sealant applied Before

    sheet metal flanges wereinstalled?

    Questions / Discussion

    Seminar agenda• What is firestopping, and why is it required?• Code Requirements• Firestop System Fire Testing• Penetration Firestop Systems• Membrane penetration firestop systems• Joint Systems• Perimeter Fire Containment Systems• Duct Enclosure systems• Understanding the UL Directories• Firestop installation options• Engineering judgments• Special inspection and special inspectors• Recognizing firestop installation problems• Plan review and inspection process

    recommendations• Notable changes in IBC 2009, 12, 15• IFC-Recommended firestop inspection techniques

    231

    THE BASICS

    SPECIFICAPPLICATIONS

    DOCUMENTS

    !!! AS OF 2012 IBC

    INSPECTIONTIPS

    Understanding the UL Directories

    Hard Copy

    CD-ROM

    Online

  • 2/13/2017

    39

    Fire Resistance Directory(printed volumes)

    • Volume 1 – Columns, Beams,Floor/Ceilings, Roof/Ceilings and Walls

    • Volumes 2A & 2B – Joint Systems,Perimeter Fire Containment Systems,and Through-Penetration FirestopSystems

    • Volume 3 – Dampers, Fire Doors, DoorFrames and Glazing

    235

    Organization UnderEach Product Area

    • Guide Information• Designs, Systems or Assemblies• Product Categories (indexed by

    manufacturer’s names)

    236

    “Guide Information” for each class ofproducts

    • Available online and print• General installation and specification rules

    applicable to all systems listed in that Class• Equipment, materials or systems included in the

    Category• Intended use, restrictions or supplemental

    information that apply• Standard(s) used to evaluate products under the

    Category• Listing or Classification Mark information for the

    Category

    237

    Examples of Guide Informationfor penetration firestop Systems

    (Listing category XHEZ)• General Description of a Firestop System• Standard• Description of Ratings• Permitted Substitutions• Specifications of Penetrating Items• Support of Penetrating Items• Angle of Penetration• Description of Numbering System

    238

    Existing Systems

    There are thousands of Tested and ListedSystems:

    Each one belongs to a particular manufacturerAnd are tested ONLY for a particular product(s)

    Different manufacturers’ products may never besubstituted into a design where it is notspecified.

    • UL Approved No Such Thing (Only AHJapproves products/systems)

    • UL Classified Lab has used the countryrequirements to evaluate the productfor specific hazards or properties

    • UL Listed Passes the standard test and isin the lab’s directory

  • 2/13/2017

    40

    Questions / Discussion Seminar agenda• What is firestopping, and why is it required?• Code Requirements• Firestop System Fire Testing• Penetration Firestop Systems• Membrane penetration firestop systems• Joint Systems• Perimeter Fire Containment Systems• Duct Enclosure systems• Understanding the UL Directories• Firestop installation options• Engineering judgments• Special inspection and special inspectors• Recognizing firestop installation problems• Plan review and inspection process

    recommendations• Notable changes in IBC 2009, 12, 15• IFC-Recommended firestop inspection techniques

    242

    THE BASICS

    SPECIFICAPPLICATIONS

    DOCUMENTS

    !!! AS OF 2012 IBC

    INSPECTIONTIPS

    FIRESTOP INSTALLATIONALTERNATIVES

    243

    FIRESTOP INSTALLATION

    • All Trades – “Person who pokes hole, fillshole”

    • Multiple Contracts – To FirestopContractors or Subs

    • Single Source Firestop Contractor

    244

    Programs that certify a company has the knowledge andquality control procedures to properly install firestopping Min. 2 years in firestop installation business Designated Responsible Individual (DRI) is formally

    tested by FM or UL at regular intervals Documented and archived record keeping system for

    all installations Must have an approved Quality Control Manual

    Firestop Systems and Assemblies Training

    FM 4991 Approved or UL CertifiedContractor

    If Require an FM4991 or

    UL Certified Contractor

    Experience – References

    Education with Firestopsystems

    Certified or Accredited bymanufacturers

    Insurance

    Licensed and bonded

  • 2/13/2017

    41

    Firestop ContractorsInternational Association

    Contractors specializing in installation offirestop systems

    Understand firestopping requirements acrossall areas of construction

    Committed to providing consistent, high-quality installations

    Active in the advancement of the firestoppingindustry

    Questions / Discussion

    Seminar agenda• What is firestopping, and why is it required?• Code Requirements• Firestop System Fire Testing• Penetration Firestop Systems• Membrane penetration firestop systems• Joint Systems• Perimeter Fire Containment Systems• Duct Enclosure systems• Understanding the UL Directories• Firestop installation options• Engineering judgments• Special inspection and special inspectors• Recognizing firestop installation problems• Plan review and inspection process

    recommendations• Notable changes in IBC 2009, 12, 15• IFC-Recommended firestop inspection techniques

    249

    THE BASICS

    SPECIFICAPPLICATIONS

    DOCUMENTS

    !!! AS OF 2012 IBC

    INSPECTIONTIPS

    ENGINEERING JUDGMENTS

    250

    • What are they?• When are they acceptable?• When are they not appropriate?• What are the guidelines?

    Engineering Judgments: Engineering Judgments

    • An Engineering Judgment is a letter or report issued bysome knowledgeable party which evaluates theconstruction of some site-specific application whichdeviates from a tested design, system or assembly andconcludes with a judgment of the applicable rating ofthat assembly

    • Engineering Judgments are commonly called EJ’s.

    252

  • 2/13/2017

    42

    IBC References JustifyingEngineering Judgments

    • IBC 104.11 Alternative materials, designand methods of construction andequipment

    • IBC 703.2 Fire-resistance ratings• IBC 703.3 Alternative methods for

    determining fire resistance

    253

    Engineering Judgments Cont.

    • Most often applied to fire resistive construction

    • Applications for an Engineering Judgment– Design and system concept where multiple

    components, some listed and some unlisted, areused to field construct the finished assembly (e.g.wall)

    – Typically products are not required to be listed bycode

    • Contractor or architect initiates process

    254

    Engineering Judgments Cont.

    • Engineering Judgment letter issued, summarizingconstruction and making conclusion on applicablerating

    • AHJ makes decision on validity of EngineeringJudgment letter and if approved, inspects constructionfor consistency with letter

    255

    Who IssuesEngineering Judgments?

    – Manufacturer– Fire protection engineer– Professional engineer– Testing laboratory

    • Must be acceptable to the Building Official or the AHJ

    256

    When are they acceptable?

    – When tested systems do not exist.– When modifying the application is unrealistic.– When existing test data supports the

    interpolation.– When the author has experience with the

    performance of the system and knowledge of theconditions.

    – When an illustration is provided to aid ininstallation.

    – When issued only for a specific jobsite

    Important Points of anEngineering Judgment

    • No guidance from the International Code Council or thevarious I-Codes

    • No guidance from UL

    • Best documents available are from the InternationalFirestop Council (IFC)www.firestop.org/engineering-judgment-guidelines.html

    258

  • 2/13/2017

    43

    IFC Guidelines

    • Two Documents– Recommended IFC Guidelines for Evaluating

    Firestop Systems in Engineering Judgments(EJs)• Covers firestops, joint systems and grease/air

    duct assemblies– Recommended IFC Guidelines for Evaluating

    Firestop Systems in Engineering Judgments(EJs) – Perimeter Fire Barrier Systems• Covers perimeter fire barriers systems (a.k.a.

    perimeter fire containment systems or perimeterjoints)

    259

    – According to the InternationalFirestop Council “listed firestopsystems can be broadened withinthe context of their originally testedand rated conditions through thecareful and restricted application ofaccepted engineering principles andfire protection testing guidelines.”

    IFC Engineering JudgementsGuidelines

    General Discussion

    • Should field inspectors approve EngineeringJudgments?

    • Is it appropriate to accept an Engineering Judgment ifthere are other tested listed systems?

    • Other Names for Engineering Judgments (Certificate ofCompliance)

    261

    Questions / Discussion

    Seminar agenda• What is firestopping, and why is it required?• Code Requirements• Firestop System Fire Testing• Penetration Firestop Systems• Membrane penetration firestop systems• Joint Systems• Perimeter Fire Containment Systems• Duct Enclosure systems• Understanding the UL Directories• Firestop installation options• Engineering judgments• Special inspection and special inspectors• Recognizing firestop installation problems• Plan review and inspection process

    recommendations• Notable changes in IBC 2009, 12, 15• IFC-Recommended firestop inspection techniques

    263

    THE BASICS

    SPECIFICAPPLICATIONS

    DOCUMENTS

    !!! AS OF 2012 IBC

    INSPECTIONTIPS

    FIRESTOP SPECIAL INSPECTIONS(IBC CHAPTER 17)

    264

  • 2/13/2017

    44

    3rd party inspections mandatory as of 2012 IBC

    Chapter 17: Special inspections and tests

    1705.16 Fire-resistant penetrations and joints. In high-rise buildings or inbuildings assigned to Risk Category III or IV in accordance with Section1604.5, special inspections for through-penetrations, membrane penetrationfirestops, fire- resistant joint systems, and perimeter fire barrier systems thatare tested and listed in accordance with Sections 714.3.1.2, 714.4.1.2, 715.3and 715.4 shall be in accordance with Section1705.16.1 or 1705.16.2.

    High-rise: A building with an occupied floor located more than 75 feet (22860 mm) above the lowest level of fire department vehicle access.

    Risk category III buildings IBC 1604.5 Buildings and other structures that represent a substantial hazard to

    human life in the event of failure, including but not limited to:

    public assembly > 300 occupants. elementary school, secondary school or day care > 250 occupants adult education > 500 occupants Group I-2 > 50 occupants, no surgery or emergency Group I-3 (prisons, jails) > 5,000 occupants Power-generating stations, water treatment facilities for potable water,

    waste water treatment facilities and other public utility facilities notincluded in Risk Category IV.

    Buildings/structures not included in Risk Category IV containingquantities of toxic or explosive materials that exceed certain thresholdsand hazardous to public if released

    Risk category IV buildings IBC 1604.5

    Buildings and other structures designated as essential facilities, including butnot limited to: Group I-2 occupancies having surgery or emergency treatment Fire, rescue, ambulance and police stations and emergency vehicle

    garages. Designated earthquake, hurricane or other emergency shelters. Designated emergency preparedness, communications and operations

    centers and other facilities required for emergency response. Power-generating stations and other public utility facilities required as

    emergency backup facilities for Risk Category IV structures. Aviation control towers, air traffic control centers and emergency aircraft

    hangars. Buildings and other structures having critical national defense functions. Water storage facilities and pump structures required to maintain water

    pressure for fire suppression. Buildings and other structures containing quantities of highly toxic materials

    that exceed certain thresholds and pose a threat to public if released

    General inspection requirements

    1703.1.1 Independence. An approved agency shall be objective, competentand independent from the contractor responsible for the work beinginspected. The agency shall also disclose possible conflicts of interest sothat objectivity can be confirmed.

    1703.1.3 Personnel. An approved agency shall employ experiencedpersonnel educated in conducting, supervising and evaluating tests and/orinspections.

    General inspection requirements: Who pays?

    1704.2 Special inspections. Where application is made for construction asdescribed in this section, the owner or the registered design professional inresponsible charge acting as the owner’s agent shall employ one or moreapproved agencies to perform inspections during construction on the typesof work listed under Section 1705. These inspections are in addition to theinspections identified in Section 110.

    General inspection requirements:Inspector qualifications

    1704.2.1 Special inspector qualifications.The special inspector shall provide written documentation to the buildingofficial demonstrating his or her competence and relevant experience ortraining. Experience or training shall be considered relevant when thedocumented experience or training is related in complexity to the sametype of special inspection activities for projects of similar complexity andmaterial qualities. These qualifications are in addition to qualificationsspecified in other sections of this code.The registered design professional in responsible charge and engineersof record involved in the design of the project are permitted to act as theapproved agency and their personnel are permitted to act as the specialinspector for the work designed by them, provided they qualify as specialinspectors.

  • 2/13/2017

    45

    How is the inspection conducted?

    1705.16.1 Penetration firestops. Inspections of penetration firestop systemsthat are tested and listed in accordance with Sections 714.3.1.2 and714.4.1.2 shall be conducted by an approved inspection agency inaccordance with ASTM E 2174.

    1705.16.2 Fire-resistant joint systems. Inspection of fire-resistant jointsystems that are tested and listed in accordance with Sections 715.3 and715.4 shall be conducted by an approved inspection agency in accordancewith ASTM E 2393.

    The special inspection process

    Statistical sampling Verify materials prior to installation Verify against listed systems and/or EJs Verify that ALL firestops installed

    ASTM E2174: Standard Practice for On-Site Inspection of Installed Fire Stops For each “type” of firestop being installed:

    Witness 10% of Installations, orDestructive Testing on 2% of Installations

    ASTM E2393, Standard Practice for On-Site Inspection of Installed FireResistive Joint Systems and Perimeter Fire Barriers For each “type” of fire resistive joint system being installed:

    Witness 5% of linear feet being installed, orDestructive (or disassembly) testing on 1 ft. per every 500 ft.

    If non-compliance identified

    One non-compliant:one full additional inspection of that type

    10% non-compliance of one type:inspection halted, installer re-inspects own work

    Non-compliant firestop must be repaired/replaced E2174/E2393: no guidance on what is an acceptable non-

    compliance percentage

    ASTM E2174/E2393: Inspector Requirements Acceptable to AHJ Qualifications: Meet the criteria in ASTM E699

    (Construction Quality assurance agencies), OR Min. 2 years construction inspection experience and credentials

    acceptable to Authorizing Authority, OR Quality assurance agency accredited by AHJ

    (e.g. IAS AC291 – Special Inspection Agencies) No conflicts of interest Completely independent of installer, contractor, manufacturer, or

    supplier of any material Not a competitor to those above Inspector to submit notarized statement indicating compliance

    Must not interfere or direct ASTM standard being developed for inspector qualifications

    How do you decide if a proposed special inspectoris acceptable?

    275

    ASTM E 2174 and ASTM E 2393Reporting/Inspection Forms

    • Inspection Date• Inspectors Name• Project• Reference No.• Firestop type per Inspection• Quantity of Firestop type on Project• Quantity Inspected (the day of Inspection)• Total Quantity Inspected to Date• Locations of Inspected Firestop• Deficiency (if non-compliant )

    276

    ASTM E 2174 and ASTM E 2393Final Report

    Report should contain:• Cover Page• Name and Address of Inspector• Name and Address of each firestop Installer, as well as the

    prime contractor• Name and Address of the AA• Name and Address of the AHJ• Executive Summary outlining verification method used to

    ascertain compliance• Notarized written statement of Conflict of Interest• Summary of contain percentages of deficiencies• All daily inspection reports

  • 2/13/2017

    46

    EDUCATION FOR THIRD-PARTYFIRESTOP INSPECTORS:IFC INSPECTOR TRAINING

    Firestop special inspection training can befound at www.firestop.org/inspection

    IFC Education Program Overview

    Typical 1-day class is insufficient for a special inspector Comprehensive study material from multiple authoritative sources Only firestop inspector exam developed and written by 3rd Party Firestop Inspectors Manufacturers that develop the technology and test the firestop

    systems Scientists and engineers experienced in firestop technology

    All reading curriculum relevant to firestop inspectors Online curriculum at no cost*

    * ASTM inspection standards must be purchased from ASTM

    IFC Education Program Overview (con’t)

    Reading list of linked documents and videos Optional online exam (test.com) Free practice test

    Passing the exam =certificate of achievement Space to record hands-on product training

    from 4 IFC-member firestop manufacturers AHJs:

    Ask inspectors for their IFC educationprogram certificate!

    Verifying whether someone has passed theIFC inspector exam www.firestop.org/certificate-holders Premier certificate holders:

    additional hands-on product training

    Intertek IQP ProgramQualified Firestop Inspector

    282

  • 2/13/2017

    47

    IQP

    • Intertek• Qualified• Personnel

    283

    IQP Differentiator

    Industry Experience

    Formalized Training

    Required Retesting

    Regular Quality Audits

    Inspector Network

    Backing of Intertek

    • AssociationTrained

    • ExperiencedInspector/Installer

    284

    IQP Programs

    Fire

    Doo

    r Ins

    pect

    ors

    Rac

    eway

    Inst

    alle

    rs

    Fiel

    d In

    spec

    tors

    ATI P

    rogr

    ams

    Asso

    ciat

    ion

    Prog

    ram

    s

    Inte

    rtek

    Prog

    ram

    s

    The IQP Programis an umbrellaprogram toencapsulate allpersonnelprograms underone name to helpbring unity to themarket and toAHJs, facilitymanagers, buildingowners, etc.

    285

    IQP Differentiated: Firestop Inspectors

    IQP Firestop Inspector

    IFC Certificated

    Experienced Personnel

    286

    Questions?

    Registration•Chris [email protected]

    http://www.intertek.com/IQP/firestop-inspector/

    287

    Understanding IFCinspector training elements

    PRESENTATION TITLE 288

    Mandated by OSHPDfor firestop inspectorsin existing construction

    Mandated by OSHPDfor firestop inspectorsin new construction

  • 2/13/2017

    48

    Special Inspection Agency accreditationIAS AC291 International Accreditation Service, Inc.

    “ACCREDITATION CRITERIA FOR SPECIAL INSPECTION AGENCIES” Accreditation of company, not of individual inspectors Requires one employee to have passed UL or FM exam for firestop

    contractors Potential conflict with ASTM E2174/E2393 conflict of interest mandates6.2.2 Conflicts of Interest:6.2.2.1 The contract inspector shall be completely independent of, and divested from,the installer, contractor, manufacturer, or supplier of any material being inspected.6.2.2.2 The contract inspector shall not be a competitor of the installer, contractor,manufacturer, or supplier of any material being inspected. As of Nov. 2015, agencies accredited AC291 for firestop inspection: 2 in New York (without UL/FM exams) 1 in Auburn, WA 2 in Dubai

    Special inspections summary

    2012 IBC makes firestop special inspection mandatory for high-risesand Risk Category III and IV buildings

    Approved agency shall be objective, competent and independent Special inspector shall provide written documentation to the

    building official demonstrating his or her competence and relevantexperience or training

    Property owner pays for the inspection Inspection per ASTM E2173, E2393 IFC program provides both education and needed written

    documentation

    Seminar agenda• What is firestopping, and why is it required?• Code Requirements• Firestop System Fire Testing• Penetration Firestop Systems• Membrane penetration firestop systems• Joint Systems• Perimeter Fire Containment Systems• Duct Enclosure systems• Understanding the UL Directories• Firestop installation options• Engineering judgments• Special inspection and special inspectors• Recognizing firestop installation problems• Plan review and inspection process

    recommendations• Notable changes in IBC 2009, 12, 15• IFC-Recommended firestop inspection techniques

    291

    THE BASICS

    SPECIFICAPPLICATIONS

    DOCUMENTS

    !!! AS OF 2012 IBC

    INSPECTIONTIPS

    RECOGNIZING FIRESTOPINSTALLATION PROBLEMS

    292

    This is what code calls for… And this is what you often receive !!!

  • 2/13/2017

    49

    Firestopping in the Real World

    • Firestop system details are hardly ever on plans• Code Officials generally do not ask for copies of approved firestop

    systems• Tested/Listed systems rarely installed correctly• Joints are generally not inspected during the framing inspection

    and installed to provide movement• Engineering judgments are being used when there are tested and

    listed systems available• Firestopping considered beneath contractors• Most users are untrained• No Licensed firestop contractors

    295Discussion: how can each of these be solved?

    FREQUENTLY ASKED QUESTIONS

    296

    ARE ALL FIRESTOP SEALANTS EQUAL?

    • NO. Each manufacturer’s material has its own uniqueproperties and functions when applied in a firestop systemdesign.

    • Similar firestop products cannot be used interchangeably

    • Each firestop system must be judged on its own merits andwithin the parameters of each manufacturer’s system specificdesign

    Frequently Asked Questions?

    IS MINERAL WOOL 1-HOUR RATED?

    • NO. Mineral wool is a component of many firestop systemsbut is normally used in conjunction with sealants or coatings

    • Mineral wool alone does not pass the hose stream test

    • Mineral wool alone will not provide a smoke seal

    Frequently Asked Questions?

    Frequently Asked Questions?

    WHAT IS THE FIRE RATING FOR YOUR CAULK?

    • Firestopping products do not have a fire rating (e.g. 1” ofcaulk does not equate to a 1 hr rating, etc.)

    • The assembly in which it is installed has the fire rating

    • The thousands of different firestop systems each detailingthe required parameters and building components

    Are firestop caulksrequired to be RED?

    Answer: There is NO building code requirementanywhere that mandates product color. However, mostmanufacturers deliberately use colors that stand out tofacilitate inspection and different colors to distinguishbetween products.

    RedRed BlackBlackGrayGrayGreenGreen

  • 2/13/2017

    50

    Answer: Fire safing, orpacking an opening withmineral wool is certainlybetter than nothing, but isnot a firestop. Using onlymineral wool does notprovide a smoke seal, doesnot address combustiblepenetrants and cannotwithstand the shock fromthe hose stream.

    Is safing insulationan adequate firestop?

    Fire blocking or safing with wool

    FICTION: Polyurethane foamis a firestop.

    FACT: Polyurethane foams, frequently used as draft stops,burn vigorously and are not generally not acceptablefirestopping materials. Some are UL Classified for surfaceflammability only, but typically are not fire resistant.

    Polyurethane FoamPolyurethane Foam

    Improper Firestop Installations:what it should not look like

    303 304

    Improper Firestop Installations

    305

    Improper Firestop Installations

    306

    Improper Firestop Installations

  • 2/13/2017

    51

    307

    Improper Firestop Installations

    308

    Improper Firestop Installations

    309

    Improper Firestop Installations

    310

    Improper Firestop Installations

    311

    Improper Firestop Installations Improper Firestop Installations

    312

  • 2/13/2017

    52

    313

    Improper Firestop Installations

    314

    Improper Firestop Installations

    315

    Improper Firestop Installations

    316

    Improper Firestop Installations

    317

    Improper Firestop Installations

    318

    Improper Firestop Installations

  • 2/13/2017

    53

    319

    Improper Firestop Installations Improper Firestop Installations

    320

    Improper Firestop Installations

    321

    Improper Firestop Installations

    322

    323

    Improper Firestop Installations

    324

    Improper Firestop Installations

  • 2/13/2017

    54

    Correct Firestop Installations

    325 326

    Correct Firestop Installations

    Correct Firestop Installations

    327 328

    Correct Firestop Installations

    329

    Correct Firestop Installations Correct: First Floor - Undersideof Joint

    330

  • 2/13/2017

    55

    Correct: Second Floor – Top ofJoint

    331 332

    Correct Firestop Installations

    Correct Firestop Installations

    333 334

    Correct Firestop Installations

    335

    Correct Firestop Installations

    336

    Correct Firestop Installations

  • 2/13/2017

    56

    Correct Firestop Installations

    337

    Correct Firestop Installations

    338

    Common Misinstalled Conditions

    1. Frame studs around beam or joist

    2. Tightly compress mineral wool belowand on sides of beam/joist

    3. Spray coating over mineral wooloverlapping wall and fireproofing

    Beam penetrating gypsum wall assembly – the right way!

    There are no UL designs that permit this !!!

    1. Gypsum wallboard cut to the shape of the beam or joist.2. Mineral wool inserted to the depth of drywall sheet3. Firestop coating sprayed over mineral wool with little overlap on

    fireproofing and wall

    Beam penetrating gypsum wall assembly – Field practice

    Common Misinstalled Conditions

    Common Misinstalled Conditions

    • Typically firestopped over the 5/8” wallboard only

    • Space above 1” liner board inside the J runner must also be protected