advances in digital protection of power transformer
TRANSCRIPT
Advances in Digital Protection of Power Transformer
Synopsis
of
Research work undertaken for the award of Ph. D. degree
in
Electrical Engineering
by
Ashesh Mukeshbhai Shah
159997109001
under supervision of
Dr. Rajeshkumar M. Patel (Supervisor)
And
Dr. Bhaveshkumar R. Bhalja (Co-Supervisor)
GUJARAT TECHNOLOGICAL UNIVERSITY
AHMEDABAD
[December - 2020]
CONTENTS
1. Abstract .............................................................................................................................. 1
2. State of the art of research topic ........................................................................................ 2
2.1 Harmonic Restraint Method ......................................................................................... 2
2.2 Transformer Model Based Algorithms ........................................................................ 3
2.3 Current Waveform Identification Based Schemes ....................................................... 4
3. Definition of the problem .................................................................................................. 4
4. Objective and Scope of work ............................................................................................. 5
5. Original contribution by the thesis ..................................................................................... 6
5.1 S-transform and Support Vector Machine based method ............................................ 6
5.2 Superimposed of differential currents based method ................................................... 7
5.3 Sequence component of differential current based method ......................................... 7
5.4 Quartile of differential current based method .............................................................. 8
6. Methodology of Research, Results / Comparisons ............................................................ 8
7. Achievements with respect to objectives ......................................................................... 14
8. Conclusion ....................................................................................................................... 14
9. List of publications .......................................................................................................... 15
10. References ...................................................................................................................... 15
1
1. Abstract
The differential protection is primary protection for power transformers since long time, that
is based on a comparison of the primary and secondary winding currents. These currents are
in proportion under healthy operating conditions of power transformer and deviate from the
predetermined criteria in case of abnormal condition such as internal fault. However, the
stability of the differential protection endangers when the transformer is energized.
Additionally, the differential relay must remain inoperative for other non-internal fault
conditions of power transformer such as over-excitation, Current Transformer (CT)
saturation due to external faults, sympathetic inrush and recovery inrush. Simultaneously, a
high sensitivity to detect low value turn-to-turn type internal fault has also been required by
differential protection.
Conventionally, harmonic restraint percentage differential protection scheme is used for
power transformer protection. According to the said scheme, the differential protection
restrains the relay operation depending on the content of second harmonic component and,
sometimes, the fifth harmonic component in order to avoid unnecessary tripping against non-
internal fault condition. However, it is difficult to achieve proper discrimination between
internal fault and non-internal fault situations in modern power transformers. Now-a-days,
most of the power transformer manufacturers utilise improved magnetic material due to
which harmonic components has been considerably reduced. On the contrary, the operation
of the above schemes may be delayed/ inhibited in case of external fault on the adjacent long
transmission line due to capacitance effect and also at the time of energisation of transformer
with an internal fault. Moreover, internal faults appear near to the end of the winding or
neutral of the winding in case of star connection, turn-to-turn faults and interwinding faults
are also a challenge for researchers and engineers, since these types of internal faults are not
easy to detect properly with the percentage differential restraining protection scheme of
power transformer. It is, therefore, necessary to develop a new improved technique for
differential protection of the power transformer in order to discriminate internal faults and
other abnormal operating conditions of the power transformer.
Thus, in order to overcome the above mentioned shortcoming of the differential protection
of power transformer, a research work has carried out to develop more robust and accurate
digital differential transformer protection scheme. Moreover, in the proposed research,
2
efforts have been made to present differential protection schemes which should not be
dependent on second harmonic components of differential currents. Further, effective
solutions have been proposed that can identify low valued turn-to-turn faults, interwinding
faults and internal fault while energizing transformer. At the same time, the proposed
methods have been shown to work under stable conditions during the disturbing events such
as magnetizing inrush, over-excitation and CT saturation during external faults.
2. State of the art of research topic
In power transformer differential protection, several techniques have been proposed in the
literature to discriminate between internal faults and non-internal fault operating conditions
such as magnetizing inrush current, over-excitation and external faults during current
transformer saturation. Initially, in order to avoid the tripping operation of differential relay
during non-internal fault operating conditions, differential relays have been utilized slow
speed induction type relays or desensitized for few cycles after switching on the power
transformer. However, differential protection becomes insensitive in case of internal fault
during energization of transformer. Hence, in order to solve the said setback, the other
methods have been proposed to improve the differential relay operation in terms of
sensitivity, selectivity and speed. These methods are primarily classified on the basis of (i)
harmonic restraint methods (ii) transformer model based algorithms and (iii) current
waveform identification based schemes.
2.1 Harmonic Restraint Method
The harmonic restraint method is widely adopted for high rating transformer protection. This
is based upon the investigation of harmonic contents of the magnetizing inrush and over-
excitation currents. In case of internal fault conditions, the differential current is sinusoidal
in nature. However, during magnetizing inrush and over-excitation conditions, this current
contains harmonics which distorts the differential current waveform. Henceforth, the
differential protection of power transformer is based on extracting the fundamental
component (1st), second harmonic component (2nd), and sometimes fifth harmonic
component (5th) of differential current. The ratio of the 2nd harmonic component to
fundamental component is found and compared with a predefined threshold value to
discriminate between magnetizing inrush and internal fault conditions. Moreover, the
proportion of the 5th harmonic component into fundamental frequency component is being
3
compared with a predefined threshold value in order to distinguish between internal fault
and over-excitation state. In order to extract fundamental and higher order harmonic contents
from the differential current, various filters, transforms and mathematical functions have
been utilized. The filtered harmonic components are utilized to restrain or operate the
differential relay. Normally, 15% restrain setting in differential current is adjusted to restrict
the operation during magnetizing inrush. It shows that if second harmonic content in
differential current is greater than or equal to 15% of the fundamental frequency component,
the relay restrains the operation of differential protection of the power transformer.
Though, number of methods have been proposed to extract fundamental frequency and
harmonic components of the differential current signal, second harmonic restraint method
by means of traditional Fast Fourier Transform (FFT) in discrete form is most widely used
technique in the current set-up for power transformer differential protection. However, the
weak performance of FFT has been found during electromagnetic transients and impulsive
conditions. It has also been noted in various literatures that the second harmonic component
may be generated during internal faults in power transformer due to CT saturation and
distributive capacitance of long transmission line to which transformer is connected. In these
situations, the magnitude of second harmonic component during an internal fault may be
nearer or greater than that found in the magnetizing current. On contrary, the second
harmonic components in the magnetizing current likely to be small in modern power
transformer due to improvement in design and core material of modern power transformer.
Hence, the conventional harmonic restraint criteria for differential protection of power
transformer may not be fulfilled to discriminate between internal faults and magnetizing
inrush currents/over-excitation conditions. Thus, the new improved technique for
differential protection of power transformer is required to distinguish between internal fault
and above mentioned abnormal operating conditions of the power transformer.
2.2 Transformer Model Based Algorithms
Digital algorithms have also been proposed based on transformer model which do not utilize
harmonic components of differential current to differentiate internal faults and magnetizing
inrush. These approaches include flux restraints and variations, equivalent circuit
parameters, compensated current, two terminal network and inductance of transformer based
methods. These methods based on transformer model are highly dependent on transformer
parameters. However, it becomes necessary to determine equivalent parameters
4
experimentally, as these parameters are not always available from the manufacturer. In
addition, accurate values of transformer parameters are challenging to attain using complex
electromagnetic relations of transformer model. Additionally, few methods based on
transformer parameters utilize transformer winding currents for relay operation. Though, it
is difficult to measure winding currents in case of delta connected windings as terminals are
generally not taken out from the transformer tank. Furthermore, boosting costs of protective
system of differential protection due to prerequisite of special type of sensors like search
coils, quintuplet set on printed circuit board and additional potential transformer are the main
drawbacks of the transformer model based techniques.
2.3 Current Waveform Identification Based Schemes
Current waveform identification based digital relaying techniques have been proposed in
recent literatures to increase sensitivity, reliability and speed of digital relays. These methods
have been established depending on fuzzy logic, artificial neural network, machine learning,
power differential, wavelet and other transforms and sequence components of differential
currents. Moreover, digital differential protection of power transformer has been also
developed using principal component analysis, mathematical morphology, orthogonal
polynomials and statistical tools.
These advanced current waveform identification techniques for the power transformer
protection have utilized properties of power transformer and percentage differential
characteristic. Further, the system response involves the measurement of various electrical
parameters such as voltage, current, frequency, phase angle, energy and active power.
Moreover, the variation in the rate of change of these parameters with respect to the time as
well as with respect to other parameters has been also examined for the identification of
internal fault situations. Afterwards, the patterns of measurements and variations have been
fed to waveform identification based methods to obtain discrimination accuracy between
internal fault and non-internal fault conditions. However, these developed methods still
suffer from standardization, universal threshold, sensitivity towards noise and computational
complexity.
3. Definition of the problem
The techniques, which are reported in preceding section, is representing a substitute or
advancement in the existing power transformer differential protection schemes. However,
5
no novel approach seems to have reached a practical point so far, and the second harmonic
component restraining technique using Discrete Fourier Transform (DFT) is widely utilized
for power transformer protection. It has been observed that the saturation of current
transformer due to external fault on adjoining long transmission line connected with
transformer may develop second harmonic component during internal faults of power
transformer. In these cases, the magnitude of second harmonic component in internal fault
has been found out as high as that of magnetizing current. On the other hand, the
improvement of the core material in modern power transformer has reduced the second
harmonic component. Thus, the conventional harmonic restraint based differential relay may
not be applicable to distinguish internal faults and magnetizing inrush currents. Moreover,
internal faults appear near to the end of the winding or neutral of the winding in case of star
connection, turn-to-turn faults and interwinding faults are also a challenge for researchers
and engineers, since these types of internal faults are not easy to detect properly with the
percentage differential restraining protection scheme of power transformer. Furthermore, the
conventional percentage differential protection combined with harmonic restraint scheme
may fail and affect the relaying operation in several operating conditions of power
transformer, such as sympathetic inrush and recovery inrush. In addition, this protection
approach has shown significant decrease in sensitivity in case of CT saturation conditions
and simultaneous internal fault while energizing transformer.
4. Objective and Scope of work
The main objective of the thesis is to design and develop effective protection schemes for
accurate discrimination of internal fault and magnetizing inrush conditions of the power
transformer. Moreover, the proposed schemes should be able to detect the low value turn-
to-turn faults as well as interwinding faults. On the other hand, the developed scheme should
also remain stable against other abnormal operating conditions such as various types of
magnetizing inrushes (sympathetic inrush and recovery inrush), over-excitation situation and
CT saturation condition due to external faults. Thus, keeping in the view of research gaps,
the following objectives have been set for the proposed research work:
To develop a new digital relaying algorithm for transformer differential protection;
this should discriminate between magnetizing inrush and internal fault currents.
6
To achieve discrimination between magnetizing inrush and internal faults; and
capable to detect minor faults like turn-to-turn and remain stable against over-
excitation and magnetizing inrushes situations such as switching on inrush including
residual magnetism, sympathetic inrush and recovery inrush.
To design self-decision making and fast digital/numerical transformer differential
protection scheme that should capable to operate or block the operating signal in
unseen situation of power system variation due to residual flux, fault inception angle
(in case of faults) or switching angle (in case of magnetizing inrush and over-
excitation), CT parameters, source impedances and loading condition of power
transformer as well as different rating and connection of power transformers.
The current state of the art and the existing gaps provides tremendous opportunities for
further development of intelligent digital/numerical protection for power transformer, many
of which are subjects of modern research.
5. Original contribution by the thesis
The primary objective of the thesis is to design and develop effective transformer protection
strategies for the identification of internal faults. These methods recognize different types of
internal fault such as winding faults, turn-to-turn faults and interwinding faults successfully
and remain stable against magnetizing inrushes (switching on inrush including residual flux,
recovery inrush and sympathetic inrush), over-excitation conditions as well as CT saturation
during external fault. The main contribution of this research has been listed as follows.
5.1 S-transform and Support Vector Machine based method
Recently, with the advent of Artificial Intelligent (AI) technology, Support Vector Machine
(SVM) has emerged as an outperforming classifier. Using this classifier, a combined S-
transform and SVM based method has been presented to distinguish between internal faults
and other disturbances. In order to evaluate the classification of the different operating
conditions of the power transformer, the power system network is modelled using PSCAD /
EMTDC simulation software and differential currents have been achieved. Obtained
differential currents have been utilized in S-transform to extract the correct feature for
classification of internal faults with non-internal faults. To perform the classification, the
Radial Basis Function (RBF) kernel of SVM has been used to train the dataset. The optimal
7
RBF parameters, attained from the five-fold cross-validation process, have been utilized to
testing dataset to obtain the discrimination accuracy of the internal fault classification.
Compared to the existing technique, the proposed combined S-transform and SVM based
scheme has provided better accuracy of the internal fault classification.
5.2 Superimposed of differential currents based method
Digital differential protection algorithm has been proposed for power transformer protection
based on the extraction of positive and negative sequence components from superimposed
differential currents. Initially, different types of internal faults, magnetizing inrush and over-
excitation conditions have been generated to obtain differential currents by modelling the
power transformer of the power transmission system using the PSCAD/EMTDC software
package. Subsequently, the fundamental frequency positive and negative sequence
components have been extracted from the superimposed differential currents using the
Modified Discrete Fourier Transform (MDFT). Such sequence components have been used
to determine the Internal Fault Detection Factor (IFDF) that can differentiate internal faults
from non-internal faults. The proposed method has also been tested for CT saturation,
specific power transformer connection & rating, CT error and change of tap position. Later,
the reliability of the proposed scheme has been evaluated using internal fault and
magnetizing inrush data collected from the actual field. At the end, a comparative study of
the proposed scheme with recent approaches and conventional techniques has been
conducted. The assessment of the proposed method for diversified cases indicates a high
degree of reliability for internal faults and greater stability during other disturbances.
5.3 Sequence component of differential current based method
A novel method based on sequence components of differential currents has been presented
for distinguishing between internal fault and magnetizing inrush of a power transformer. In
this method, the Internal Fault Detection (IFD) ratio has been calculated from the differential
currents of the power transformer to identify internal faults. Initially, more than 1600
simulation cases have been carried out to produce differential current waveforms for the
different operating conditions of the power transformer. The simulation has been performed
using 3-phase power transformer modelling using the PSCAD / EMTDC software package.
Subsequently, MDFT algorithm has been used to extract fundamental frequency positive and
negative sequence components from differential currents. As a result, using these sequence
8
component values, IFD threshold value has been identified which can effectively
discriminate internal (LG, LL, and turn-to-turn) faults from magnetizing inrushes such as
residual and sympathetic inrushes. In addition, this method also remains stable against over-
excitation and CT saturation during external fault events. A comparative assessment with
the recently developed method had also been carried out to indicate the effectiveness of the
proposed method.
5.4 Quartile of differential current based method
Due to the unavailability of negative sequence components during symmetrical internal
faults (which are very rare to occur in transformers), Superimposed and Sequence
components based differential current algorithms may not able to detect internal fault in case
of Triple Line and Triple Line-to-Ground faults. In order to overcome this limitation, a
quartile of differential current based method has been proposed for the protection of the
power transformer. In this method, the Fault Detection Ratio (FDR) has been computed to
detect internal fault from quartiles of the differential current. The threshold value of the FDR
has been determined from the mathematical models of internal fault, magnetizing inrush and
over-excitation conditions, and further, validated with the help of the simulation dataset
(generated using PSCAD/EMTDC software) for the different operating conditions of the
power transformer. The proposed method has been successfully assessed for all types of
internal faults, including large value symmetrical internal fault currents to low value turn-
to-turn fault currents. In addition, the proposed method has been performed reliably against
the different connection and rating of the transformer, real-time field data from the substation
and noise. In the end, the comparative assessment of the proposed method with conventional
differential protection and the recently developed & existing method reveals superior
performance in terms of sensitivity, reliability and speed.
6. Methodology of Research, Results / Comparisons
The research plan had been designed thoroughly and the study has been carried out on the
following points.
Literature Survey.
Collection of data.
Simulation of different conditions for power transformer differential protection
scheme using PSCAD/EMTDC environment.
9
Development of Hypothesis.
Testing of Hypothesis.
Publications.
The results of the proposed methods in thesis in terms of identification of various power
transformer conditions have been depicted as follows:
S-transform and Support Vector Machine based method
In the proposed scheme, internal and non-internal fault conditions have been simulated to
generate the training and testing dataset using PSCAD/EMTDC software package. Total
12864 cases have been generated for different types of internal faults, various types of
magnetizing inrushes, over-excitation, external fault and normal operating conditions of
power transformer. In order to obtain fault classification accuracy, two features viz.
maximum magnitude of frequency components and standard deviation of the phase contour
of differential currents have been derived with the help of S-transform. Afterwards, SVM
technique has been employed in MATLAB environment by means of Lib-SVM toolbox. Out
of the total 12864 cases, 6432 cases (i.e. 50% of total cases) have been selected for training
dataset comprising different system and fault parameters. For testing and validation of the
proposed technique, remaining 6432 cases have been preferred. Thus, for the total test cases,
the fault discrimination accuracy (η) has been calculated using (1),
𝜂 = 𝑁𝑢𝑚𝑏𝑒𝑟 𝑜𝑓 𝑐𝑜𝑟𝑟𝑒𝑐𝑡 𝑡𝑒𝑠𝑡 𝑐𝑎𝑠𝑒𝑠
𝑇𝑜𝑡𝑎𝑙 𝑛𝑢𝑚𝑏𝑒𝑟 𝑜𝑓 𝑡𝑒𝑠𝑡 𝑐𝑎𝑠𝑒𝑠 (6432) × 100% (1)
Once training cases have been identified among all simulated cases, the next step is to train
SVM with the most optimum parametric settings. Using researcher’s experience in
various literature, it has been found that the RBF kernel function is the most valuable and
best choice for fault detection and classification algorithms. In order to achieve the optimum
values of the parameters (cost parameter (C) and free parameter (γ)) of the RBF kernel,
fivefold cross validation has been implemented by altering the values of these two
parameters to avoid over-fitting models on training data. It has been perceived that the
highest cross validation accuracy of 99.78% has been retrieved for C = 103 and γ = 10-3 and
hence, it has been chosen for training the SVM. Utilizing these parameters for SVM training,
the overall performance of the proposed scheme for a total 6432 test cases of internal fault
and non-internal fault has been presented in Table 1.
10
Table 1: Different operating conditions which identify using proposed methods
Faults/
Abnormalities
Number
of test
cases
Number
of cases
identified
correctly
Number of
cases not
identified
correctly
η
(%)
Total Internal faults 3240 3201 39 98.80
Total Non-Internal faults 3192 3099 93 97.09
Overall accuracy 6432 6300 132 97.95
It has been observed from Table 1 that the proposed scheme is capable of correctly
distinguishing internal faults with 98.80% accuracy, while non-internal faults with 97.09%,
thus the overall accuracy has been obtained as 97.95%. Furthermore, a comparative
assessment with the existing scheme reveals that the proposed scheme shows more superior
results compared to the existing scheme.
Superimposed of differential currents based method
In this method, different types of internal faults, magnetizing inrush and over-excitation
conditions have been generated, initially, to obtain differential currents by modelling the
power transformer of the power transmission system using the PSCAD/EMTDC software
package. Subsequently, the fundamental frequency positive and negative sequence
components have been extracted from the superimposed differential currents using MDFT.
Such sequence components have been used to determine the Internal Fault Detection Factor
(IFDF) that can differentiate internal faults from non-internal faults. In the proposed method,
if the value of IFDF is greater than threshold value (in this case, threshold is 1.0) for a definite
time (here, it is 5 ms) then internal fault in the transformer is said to be detected and the
proposed method initiates a trip command. On the contrary, if IFDF is less than threshold
value then the proposed scheme remains stable. The simulation results of the proposed
scheme have been shown for internal fault and magnetising inrush conditions as follows. As
shown in Fig. 1 (a), a solid LG fault (on phase-a) has been simulated at 50% of winding from
the terminal of HV side of the power transformer at 30˚ fault inception angle. Fig. 1 (b)
shows the calculated IFDF by the proposed scheme. As observed from Fig. 1 (b) that the
value of IFDF remains above the threshold for more than a quarter cycle (5 ms) after the
inception of fault. Hence, the suggested scheme is capable to detect such type of an internal
fault within half a cycle after the occurrence of fault. Moreover, the proposed scheme has
been also evaluated for the interwinding and turn-to-turn faults and results indicates that the
proposed method is capable to identify these types of internal faults.
11
Fig. 1 Response of LG fault (a) differential current, (b) IFDF; Response during magnetizing inrush (c)
differential current (d) IFDF
In order to assure stability of the proposed scheme, the residual inrush has been simulated at
0˚ incident angle of the voltage source during no-load condition. The simulation results in
terms of magnitude of residual inrush current and IFDF are shown in Fig. 1 (c) and (d),
respectively. It is to be noted from Fig. 1 (d) that the value of IFDF remains well below the
threshold.
Furthermore, the proposed method remains stable for the different types of magnetizing
inrushes, over-excitation and CT saturation due to external fault conditions. At the same
time, the proposed technique is equally applicable to an entirely different rating and type of
power transformer connection. Subsequently, the performance of the proposed technique has
also been evaluated using internal fault and magnetizing inrush data recorded in the actual
field. Finally, the assessment of the proposed technique has also been carried out with the
recently established techniques.
Sequence component of differential current based method
In this method, the Internal Fault Detection (IFD) ratio has been calculated from the
differential currents of the power transformer to identify internal faults. To correctly
differentiate internal fault from other operating condition of power transformer, the
computed IFD is equated with the predetermined threshold (in this case, it is 7.0). If the
calculated IFD is larger than predetermined threshold value, then it is to be said that an
internal fault in the power transformer is existed and trip command has been commenced.
Conversely, if IFD value is smaller than predetermined threshold then the proposed method
12
prevents tripping. The simulation results of the proposed scheme have been shown for turn-
to-turn type internal fault and over-excitation conditions as follows.
Fig. 2 (a) shows waveform of turn-to-turn internal fault on phase ‘b’ of primary winding
with 0.5% shorted turns at 0˚ fault impedance angle. It has been found from Fig. 2 (b) that
value of IFD raises above the threshold after the beginning of fault. Hence, it could be said
that the proposed method is competent to recognize turn-to-turn type internal fault
accurately. Furthermore, performance of presented method has also been verified against
over-excitation condition of power transformer. In case of over-excitation condition, a
simulation test has with rise in voltage value by 10% and reducing system frequency by 2%
Hz with 0° switching angle has been evaluated. The simulated differential current waveform
for over-excitation and corresponding value of IFD are revealed in Fig. 2 (c). It has been
perceived from Fig. 2 (d) that IFD prevails value lower than threshold and henceforth, kept
away the undesirable tripping. Further, the simulation results show that the proposed scheme
is sensitive to detect different types of internal faults, while improves stability during non-
internal fault conditions. At last, a comparative analysis with recently developed technique
provides the capability of the proposed method.
Fig. 2 Response of turn-to-turn fault (a) differential current, (b) IFD; Response during over-excitation
(c) differential current (d) IFD
Quartile of differential current based method
In the proposed method, the Fault Detection Ratio (FDR) has been computed from quartiles
of the differential current to detect internal fault of power transformer. The threshold value
13
(4% in this case) of the FDR has been determined from the mathematical models of internal
fault, magnetizing inrush and over-excitation conditions, and further, validated with the help
of the simulation dataset (generated using PSCAD/EMTDC software) for the different
operating conditions of the power transformer. The simulation results of the proposed
scheme have been shown for internal fault and magnetising inrush conditions as follows.
Waveforms of the differential currents and FDR for all phases, during a LG fault at 95% of
winding from the terminal with 0° FIA on HV side, are shown in Fig. 3 (a) and (b),
respectively. It is noted from Fig. 3 (b) that the value of FDR for phases ‘a’ and ‘b’ increases
from 0% to around 8% within a cycle after the inception of fault. Thus, it is observed from
the aforementioned internal fault case that the proposed algorithm detects an internal fault
condition when the value of FDR crosses the threshold for any of the three phases. Further,
the proposed scheme equally provides the reliable operation during turn-to-turn and
interwinding faults in noise condition too.
Fig. 3 Differential currents (a) and (c) and FDRs (b) and (d) during LG fault and magnetizing inrush,
respectively
Waveform of differential currents and FDRs during transformer energization at no load with
0° switching angle are shown in Fig. 3 (c) and (d), respectively. It is observed from Fig. 3
(d) that the values of FDR stay well below the threshold. Further, the proposed scheme
remains stable for various types of inrushes, over-excitation and CT saturation conditions.
Simultaneously, it provides equally promising results to the different rating and winding
connection of the power transformer. In addition, verification of its performance on actual
14
field data (containing faulty transformer energization and magnetizing inrush condition)
reveals its correctness in detecting internal faults and immunity from nuisance trip during
non-internal faults. Finally, the comparative assessment of the proposed technique in terms
of coverage of different types of internal faults, stability during external disturbances,
average relay operation time and the sampling frequency requirement demonstrates its
advantages compared to other existing methods.
7. Achievements with respect to objectives
The main objective of the thesis is to design and develop effective transformer protection
strategies that identify different internal faults and endure stable operation during all types
of magnetizing inrushes, over-excitation and CT saturation during external fault conditions.
All proposed methods have been able to fulfil above mentioned objective in terms of high
discrimination accuracy and capability to identify various abnormal conditions. Moreover,
the proposed methods have provided equally promising results for different rating and
connection of transformer that points out the applicability of the proposed methods on
generalized form. Furthermore, the superimposed and quartile of differential currents based
methods have been successfully evaluated on real field data of power transformer which
indicates the proposed methods are capable to provide alternative approach for the power
transformer protection.
8. Conclusion
The work has begun with the aim of developing new differential protection schemes capable
of addressing the challenges and issues associated with conventional differential protection
techniques and providing a more reliable protection solution for the differential protection
of power transformers. The work has been focused on the development of efficient
techniques for distinguishing between internal faults and other disturbances, such as
magnetizing inrush, over-excitation and CT saturation due to external faults. Further, these
methods should recognize different types of internal fault such as winding faults, turn-to-
turn faults and interwinding faults. In this context, four different algorithms for differential
protection of the power transformer have been developed based on the classification of
internal and non-internal faults, the superimposed of differential currents, the sequence
components of differential currents and the quartile of differential current. These developed
15
techniques are fast, reliable and stable for the differential protection of the power
transformer. In this way, the objective of the work has been achieved to a large extent.
9. List of publications
Published Journal Papers:
1. A. M. Shah, B. R. Bhalja and R. M. Patel, "New protection scheme for power
transformer based on superimposed differential current," in IET Generation,
Transmission & Distribution, vol. 12, no. 14, pp. 3587-3595, Aug. 2018.
2. A. M. Shah et al., "Quartile Based Differential Protection of Power Transformer," in
IEEE Transactions on Power Delivery, vol. 35, no. 5, pp. 2447-2458, Oct. 2020.
Published Conference Papers:
1. A. M. Shah, B. R. Bhalja and R. M. Patel, "Power transformer differential protection
using S-transform and Support Vector Machine," 2016 National Power Systems
Conference (NPSC), Bhubaneswar, 2016, pp. 1-6.
2. A. M. Shah, B. R. Bhalja, R. M. Patel and Y. M. Makwana, "The Sequence
Components based Identification of Internal Fault in Power Transformer," 2019
IEEE 16th India Council International Conference (INDICON), Rajkot, India, 2019,
pp. 1-4.
10. References
[1] S. H. Horowitz and A. G. Phadke, Power System Relaying, Third Ed. John Wiley &
Sons Ltd, 2008.
[2] J. L. Blackburn and T. J. Domin, Protective Relaying: Principles and Applications,
Third Ed. Taylor & Francis Group, 2007.
[3] P. M. Anderson, Power System Protection. Wiley - IEEE Press, 1998.
[4] B. R. Bhalja, R. P. Maheshwari, and N. G. Chothani, Protection and Switchgear,
Second Ed. Oxford University Press, 2018.
[5] IEEE Guide for Protecting Power Transformers. IEEE Standard C37. 91-2008
(Revision of IEEE Std. C37.91-2000).
[6] ABB Inc. Limited, Transformer protection RET670 Version 2.1 ANSI: Application
manual. 2019.
[7] R. Hamilton, “Analysis of Transformer Inrush Current and Comparison of Harmonic
Restraint Methods in Transformer Protection,” IEEE Trans. Ind. Appl., vol. 49, no. 4,
pp. 1890–1899, Jul. 2013.
[8] G. W. McKenna, “Theory and Application of Transformer Differential Protection,”
Trans. Am. Inst. Electr. Eng., vol. 69, no. 2, pp. 1197–1202, Jan. 1950.
16
[9] C. D. Hayward, “Harmonic-current-restrained relays for transformer differential
protection,” Electr. Eng., vol. 60, no. 6, pp. 377–382, Jun. 1941.
[10] R. L. Sharp and W. E. Glassburn, “A Transformer Differential Relay with Second-
Harmonic Restraint,” Trans. Am. Inst. Electr. Eng. Part III Power Appar. Syst., vol.
77, no. 3, pp. 913–918, Apr. 1958.
[11] M. A. Rahman and B. Jeyasurya, “A state-of-the-art review of transformer protection
algorithms,” IEEE Trans. Power Deliv., vol. 3, no. 2, pp. 534–544, Apr. 1988.
[12] J. Sykes and I. Morrison, “A Proposed Method of Harmonic Restraint Differential
Protecting of Transformers by Digital Computer,” IEEE Trans. Power Appar. Syst.,
vol. PAS-91, no. 3, pp. 1266–1272, May 1972.
[13] T. S. Sidhu and M. S. Sachdev, “Online identification of magnetizing inrush and
internal faults in three-phase transformers,” IEEE Trans. Power Deliv., vol. 7, no. 4,
pp. 1885–1891, 1992.
[14] A. J. Degens, “Algorithm for a digital transformer differential protection based on a
least-squares curve-fitting,” IEE Proc. C Gener. Transm. Distrib., vol. 128, no. 3, p.
155, 1981.
[15] M. A. Rahman, P. K. Dash, and E. R. Downton, “Digital Protection of Power
Transformer Based on Weighted Least Square Algorithm,” IEEE Trans. Power Appar.
Syst., vol. PAS-101, no. 11, pp. 4204–4210, Nov. 1982.
[16] B. Jeyasurya and M. Rahman, “Application of Walsh Functions for Microprocessor-
Based Transformer Protection,” IEEE Trans. Electromagn. Compat., vol. EMC-27,
no. 4, pp. 221–225, Nov. 1985.
[17] D. B. Fakruddin, K. Parthasarathy, L. Jenkins, and B. W. Hogg, “Application of Haar
functions for transmission line and transformer differential protection,” Int. J. Electr.
Power Energy Syst., vol. 6, no. 3, pp. 169–180, Jul. 1984.
[18] A. Phadke and J. Thorp, “A New Computer-Based Flux-Restrained Current-
Differential Relay for Power Transformer Protection,” IEEE Trans. Power Appar.
Syst., vol. PAS-102, no. 11, pp. 3624–3629, Nov. 1983.
[19] Y. C. Kang, B. E. Lee, S. H. Kang, and P. A. Crossley, “Transformer protection based
on the increment of flux linkages,” IEE Proc. - Gener. Transm. Distrib., vol. 151, no.
4, p. 548, 2004.
[20] K. Inagaki et al., “Digital protection method for power transformers based on an
equivalent circuit composed of inverse inductance,” IEEE Trans. Power Deliv., vol. 3,
no. 4, pp. 1501–1510, 1988.
[21] G. Baoming, A. T. DeAlmeida, Z. Qionglin, and W. Xiangheng, “An Equivalent
Instantaneous Inductance-Based Technique for Discrimination Between Inrush
Current and Internal Faults in Power Transformers,” IEEE Trans. Power Deliv., vol.
20, no. 4, pp. 2473–2482, Oct. 2005.
[22] Y. C. Kang, E. S. Jin, S. H. Kang, and P. A. Crossley, “Compensated-current
differential relay for protection of transformers,” IEE Proc. - Gener. Transm. Distrib.,
vol. 151, no. 3, p. 281, 2004.
[23] J. Ma, Z. Wang, Q. Yang, and Y. Liu, “A Two Terminal Network-Based Method for
Discrimination Between Internal Faults and Inrush Currents,” IEEE Trans. Power
Deliv., vol. 25, no. 3, pp. 1599–1605, Jul. 2010.
[24] F. Haghjoo and M. Mostafaei, “Flux-based turn-to-turn fault protection for power
transformers,” IET Gener. Transm. Distrib., vol. 10, no. 5, pp. 1154–1163, Apr. 2016.
17
[25] F. Haghjoo, M. Mostafaei, and H. Mohammadi, “A New Leakage Flux-Based
Technique for Turn-to-Turn Fault Protection and Faulty Region Identification in
Transformers,” IEEE Trans. Power Deliv., vol. 33, no. 2, pp. 671–679, Apr. 2018.
[26] F. Naseri, Z. Kazemi, M. M. Arefi, and E. Farjah, “Fast Discrimination of Transformer
Magnetizing Current From Internal Faults: An Extended Kalman Filter-Based
Approach,” IEEE Trans. Power Deliv., vol. 33, no. 1, pp. 110–118, Feb. 2018.
[27] B. Kasztenny, E. Rosolowski, M. M. Saha, and B. Hillstrom, “A self-organizing fuzzy
logic based protective relay-an application to power transformer protection,” IEEE
Trans. Power Deliv., vol. 12, no. 3, pp. 1119–1127, Jul. 1997.
[28] Myong-Chul Shin, Chul-Won Park, and Jong-Hyung Kim, “Fuzzy logic-based
relaying for large power transformer protection,” IEEE Trans. Power Deliv., vol. 18,
no. 3, pp. 718–724, Jul. 2003.
[29] D. Barbosa, U. C. Netto, D. V. Coury, and M. Oleskovicz, “Power Transformer
Differential Protection Based on Clarke’s Transform and Fuzzy Systems,” IEEE
Trans. Power Deliv., vol. 26, no. 2, pp. 1212–1220, Apr. 2011.
[30] D. Bejmert, W. Rebizant, and L. Schiel, “Transformer differential protection with
fuzzy logic based inrush stabilization,” Int. J. Electr. Power Energy Syst., vol. 63, pp.
51–63, Dec. 2014.
[31] L. G. Perez, A. J. Flechsig, J. L. Meador, and Z. Obradovic, “Training an artificial
neural network to discriminate between magnetizing inrush and internal faults,” IEEE
Trans. Power Deliv., vol. 9, no. 1, pp. 434–441, 1994.
[32] J. Pihler, B. Grcar, and D. Dolinar, “Improved operation of power transformer
protection using artificial neural network,” IEEE Trans. Power Deliv., vol. 12, no. 3,
pp. 1128–1136, Jul. 1997.
[33] A. L. Orille-Fernandez, N. K. I. Ghonaim, and J. A. Valencia, “A FIRANN as a
differential relay for three phase power transformer protection,” IEEE Trans. Power
Deliv., vol. 16, no. 2, pp. 215–218, Apr. 2001.
[34] M. Tripathy, R. P. Maheshwari, and H. K. Verma, “Power Transformer Differential
Protection Based On Optimal Probabilistic Neural Network,” IEEE Trans. Power
Deliv., vol. 25, no. 1, pp. 102–112, Jan. 2010.
[35] H. Balaga, N. Gupta, and D. N. Vishwakarma, “GA trained parallel hidden layered
ANN based differential protection of three phase power transformer,” Int. J. Electr.
Power Energy Syst., vol. 67, pp. 286–297, May 2015.
[36] S. Afrasiabi, M. Afrasiabi, B. Parang, and M. Mohammadi, “Integration of
Accelerated Deep Neural Network Into Power Transformer Differential Protection,”
IEEE Trans. Ind. Informatics, vol. 16, no. 2, pp. 865–876, Feb. 2020.
[37] K. Yabe, “Power differential method for discrimination between fault and magnetizing
inrush current in transformers,” IEEE Trans. Power Deliv., vol. 12, no. 3, pp. 1109–
1118, Jul. 1997.
[38] A. Hooshyar, M. Sanaye-Pasand, S. Afsharnia, M. Davarpanah, and B. M. Ebrahimi,
“Time-Domain Analysis of Differential Power Signal to Detect Magnetizing Inrush in
Power Transformers,” IEEE Trans. Power Deliv., vol. 27, no. 3, pp. 1394–1404, Jul.
2012.
[39] O. A. S. Youssef, “A wavelet-based technique for discrimination between faults and
magnetizing inrush currents in transformers,” IEEE Trans. Power Deliv., vol. 18, no.
1, pp. 170–176, Jan. 2003.
18
[40] M. M. Eissa, “A Novel Digital Directional Transformer Protection Technique Based
on Wavelet Packet,” IEEE Trans. Power Deliv., vol. 20, no. 3, pp. 1830–1836, Jul.
2005.
[41] J. Faiz and S. Lotfi-Fard, “A Novel Wavelet-Based Algorithm for Discrimination of
Internal Faults From Magnetizing Inrush Currents in Power Transformers,” IEEE
Trans. Power Deliv., vol. 21, no. 4, pp. 1989–1996, Oct. 2006.
[42] R. P. Medeiros, F. B. Costa, and K. M. Silva, “Power Transformer Differential
Protection Using the Boundary Discrete Wavelet Transform,” IEEE Trans. Power
Deliv., vol. 31, no. 5, pp. 2083–2095, Oct. 2016.
[43] J. P. Marques, C. Lazaro, A. P. Morais, and G. Cardoso, “A reliable setting-free
technique for power transformer protection based on wavelet transform,” Electr.
Power Syst. Res., vol. 162, no. April, pp. 161–168, Sep. 2018.
[44] R. P. Medeiros and F. B. Costa, “A Wavelet-Based Transformer Differential
Protection: Internal Fault Detection During Inrush Conditions,” IEEE Trans. Power
Deliv., vol. 33, no. 6, pp. 2965–2977, Dec. 2018.
[45] S. A. Saleh, B. Scaplen, and M. A. Rahman, “A New Implementation Method of
Wavelet-Packet-Transform Differential Protection for Power Transformers,” IEEE
Trans. Ind. Appl., vol. 47, no. 2, pp. 1003–1012, Mar. 2011.
[46] S. A. Saleh, A. Aktaibi, R. Ahshan, and M. A. Rahman, “The Development of a d–q
Axis WPT-Based Digital Protection for Power Transformers,” IEEE Trans. Power
Deliv., vol. 27, no. 4, pp. 2255–2269, Oct. 2012.
[47] A. Aktaibi, M. A. Rahman, and A. M. Razali, “An Experimental Implementation of
the dq-Axis Wavelet Packet Transform Hybrid Technique for Three-Phase Power
Transformer Protection,” IEEE Trans. Ind. Appl., vol. 50, no. 4, pp. 2919–2927, Jul.
2014.
[48] W. Wang, L. Yan, T. Jin, H. Liu, F. Hu, and D. Wu, “Inrush current method of
transformer based on wavelet packet and neural network,” J. Eng., vol. 2019, no. 16,
pp. 1257–1260, Mar. 2019.
[49] D. Guillén, H. Esponda, E. Vázquez, and G. Idárraga-Ospina, “Algorithm for
transformer differential protection based on wavelet correlation modes,” IET Gener.
Transm. Distrib., vol. 10, no. 12, pp. 2871–2879, Sep. 2016.
[50] S. R. Samantaray, B. K. Panigrahi, P. K. Dash, and G. Panda, “Power transformer
protection using S-transform with complex window and pattern recognition
approach,” IET Gener. Transm. Distrib., vol. 1, no. 2, p. 278, 2007.
[51] A. Ashrafian, M. Rostami, and G. B. Gharehpetian, “Hyperbolic S-transform-based
method for classification of external faults, incipient faults, inrush currents and internal
faults in power transformers,” IET Gener. Transm. Distrib., vol. 6, no. 10, pp. 940–
950, 2012.
[52] A. M. Shah and B. R. Bhalja, “Discrimination Between Internal Faults and Other
Disturbances in Transformer Using the Support Vector Machine-Based Protection
Scheme,” IEEE Trans. Power Deliv., vol. 28, no. 3, pp. 1508–1515, Jul. 2013.
[53] S. R. Samantaray and P. K. Dash, “Decision Tree based discrimination between inrush
currents and internal faults in power transformer,” Int. J. Electr. Power Energy Syst.,
vol. 33, no. 4, pp. 1043–1048, May 2011.
[54] S. Karagol and O. Ozgonenel, “Power transformer protection based on decision tree
approach,” IET Electr. Power Appl., vol. 8, no. 7, pp. 251–256, Aug. 2014.
19
[55] A. M. Shah and B. R. Bhalja, “Fault discrimination scheme for power transformer
using random forest technique,” IET Gener. Transm. Distrib., vol. 10, no. 6, pp. 1431–
1439, Apr. 2016.
[56] A. Ashrafian, B. Vahidi, and M. Mirsalim, “Time–time-transform application to fault
diagnosis of power transformers,” IET Gener. Transm. Distrib., vol. 8, no. 6, pp. 1156–
1167, Jun. 2014.
[57] S. Kumar Murugan, S. P. Simon, P. S. R. Nayak, K. Sundareswaran, and N. P. Padhy,
“Power transformer protection using chirplet transform,” IET Gener. Transm. Distrib.,
vol. 10, no. 10, pp. 2520–2530, Jul. 2016.
[58] S. kumar Murugan, S. P. Simon, K. Sundareswaran, P. S. R. Nayak, and N. P. Padhy,
“An Empirical Fourier Transform-Based Power Transformer Differential Protection,”
IEEE Trans. Power Deliv., vol. 32, no. 1, pp. 209–218, Feb. 2017.
[59] D. Zacharias and R. Gokaraju, “Prototype of a Negative-Sequence Turn-to-Turn Fault
Detection Scheme for Transformers,” IEEE Trans. Power Deliv., vol. 31, no. 1, pp.
122–129, Feb. 2016.
[60] E. Vazquez, I. I. Mijares, O. L. Chacon, and A. Conde, “Transformer Differential
Protection Using Principal Component Analysis,” IEEE Trans. Power Deliv., vol. 23,
no. 1, pp. 67–72, Jan. 2008.
[61] Z. Lu, W. H. Tang, T. Y. Ji, and Q. H. Wu, “A Morphological Scheme for Inrush
Identification in Transformer Protection,” IEEE Trans. Power Deliv., vol. 24, no. 2,
pp. 560–568, Apr. 2009.
[62] Q. Wu, T. Ji, M. Li, and W. Wu, “Using mathematical morphology to discriminate
between internal fault and inrush current of transformers,” IET Gener. Transm.
Distrib., vol. 10, no. 1, pp. 73–80, Jan. 2016.
[63] B. Khalkhali and J. Sadeh, “Transformer Differential Protection by Online Core
Modeling and Orthogonal Polynomials,” IEEE Trans. Power Deliv., vol. 30, no. 5, pp.
2146–2153, Oct. 2015.
[64] A. Ashrafian, M. Mirsalim, and M. A. S. Masoum, “Application of a Recursive Phasor
Estimation Method for Adaptive Fault Component Based Differential Protection of
Power Transformers,” IEEE Trans. Ind. Informatics, vol. 13, no. 3, pp. 1381–1392,
Jun. 2017.
[65] Y. N. Batista, H. E. P. de Souza, F. de Assis dos Santos Neves, and R. F. D. Filho, “A
GDSC-Based Technique to Distinguish Transformer Magnetizing From Fault
Currents,” IEEE Trans. Power Deliv., vol. 33, no. 2, pp. 589–599, Apr. 2018.
[66] L. M. Peres and K. M. Silva, “Power transformer protection using an instantaneous-
current-value negative sequence differential element,” Int. J. Electr. Power Energy
Syst., vol. 108, no. December 2018, pp. 96–106, Jun. 2019.
[67] N. Farzin, M. Vakilian, and E. Hajipour, “Transformer Turn-to-Turn Fault Protection
Based on Fault-Related Incremental Currents,” IEEE Trans. Power Deliv., vol. 34, no.
2, pp. 700–709, Apr. 2019.
[68] H. Samet, T. Ghanbari, and M. Ahmadi, “Discrimination of internal fault from
magnetising inrush current in power transformers based on sine-wave least-squares
curve fitting method,” IET Sci. Meas. Technol., vol. 9, no. 1, pp. 73–84, Jan. 2015.
[69] L. M. R. Oliveira and A. J. M. Cardoso, “Extended Park’s vector approach-based
differential protection of three-phase power transformers,” IET Electr. Power Appl.,
vol. 6, no. 8, p. 463, 2012.
20
[70] H. Dashti and M. Sanaye-Pasand, “Power Transformer Protection Using a Multiregion
Adaptive Differential Relay,” IEEE Trans. Power Deliv., vol. 29, no. 2, pp. 777–785,
Apr. 2014.
[71] X. Lin, J. Lu, R. Zhang, N. Tong, O. S. Adio, and Z. Li, “Internal fault fast
identification criterion based on superimposed component comparison for power
transformer,” Int. J. Electr. Power Energy Syst., vol. 73, pp. 491–497, Dec. 2015.
[72] A. A. A. Etumi and F. J. Anayi, “The Application of Correlation Technique in
Detecting Internal and External Faults in Three-Phase Transformer and Saturation of
Current Transformer,” IEEE Trans. Power Deliv., vol. 31, no. 5, pp. 2131–2139, Oct.
2016.
[73] A. Sahebi and H. Samet, “Efficient method for discrimination between inrush current
and internal faults in power transformers based on the non-saturation zone,” IET
Gener. Transm. Distrib., vol. 11, no. 6, pp. 1486–1493, Apr. 2017.
[74] E. Ali, A. Helal, H. Desouki, K. Shebl, S. Abdelkader, and O. P. Malik, “Power
transformer differential protection using current and voltage ratios,” Electr. Power
Syst. Res., vol. 154, pp. 140–150, Jan. 2018.
[75] L. L. Zhang, Q. H. Wu, T. Y. Ji, and A. Q. Zhang, “Identification of inrush currents in
power transformers based on higher-order statistics,” Electr. Power Syst. Res., vol.
146, pp. 161–169, May 2017.
[76] H. Esponda, E. Vázquez, M. A. Andrade, D. Guillén, and B. K. Johnson, “Extended
second central moment approach to detect turn-to-turn faults in power transformers,”
IET Electr. Power Appl., vol. 13, no. 6, pp. 766–775, Jun. 2019.
[77] M. Tajdinian, M. Allahbakhshi, A. Bagheri, H. Samet, P. Dehghanian, and O. Parkash
Malik, “An enhanced sub-cycle statistical algorithm for inrush and fault currents
classification in differential protection schemes,” Int. J. Electr. Power Energy Syst.,
vol. 119, no. September 2019, p. 105939, Jul. 2020.
[78] H. Weng, S. Wang, X. Lin, Z. Li, and J. Huang, “A novel criterion applicable to
transformer differential protection based on waveform sinusoidal similarity
identification,” Int. J. Electr. Power Energy Syst., vol. 105, no. July 2018, pp. 305–
314, Feb. 2019.
[79] H. Weng, S. Wang, Y. Wan, X. Lin, Z. Li, and J. Huang, “Discrete Fréchet distance
algorithm based criterion of transformer differential protection with the immunity to
saturation of current transformer,” Int. J. Electr. Power Energy Syst., vol. 115, no. July
2019, pp. 1–9, Feb. 2020.