Page 1: Advanced Markets enabling Advanced (Smarter Grid ... · – Compressor operates at low load periods; gas turbine serves load as needed – Smoothes out load/supply profile with quick

PJM©2011

Advanced Markets enabling Advanced (Smarter Grid) Technologies in PJM

Chantal HendrzakGeneral Manager, Applied Solutions

PJM InterconnectionJuly 25, 2011

Page 2: Advanced Markets enabling Advanced (Smarter Grid ... · – Compressor operates at low load periods; gas turbine serves load as needed – Smoothes out load/supply profile with quick

PJM©20112

PJM as Part of the Eastern Interconnection

KEY STATISTICSPJM member companies 700+millions of people served 58peak load in megawatts 158,448MWs of generating capacity 180,400miles of transmission lines 61,200GWh of annual energy 794,335generation sources 1,365square miles of territory 211,000area served 13 states + DCInternal/external tie lines 142

• 24% of generation in Eastern Interconnection

• 27% of load in Eastern Interconnection• 19% of transmission assets in

Eastern Interconnection

20% of U.S. GDP produced in PJM

www.pjm.com

As of 6/1/2011

Page 3: Advanced Markets enabling Advanced (Smarter Grid ... · – Compressor operates at low load periods; gas turbine serves load as needed – Smoothes out load/supply profile with quick

PJM©20113

PJMIntegrating

Grids & Markets

1. Keeping the Lights On 2. Fair and Efficient Markets3. Infrastructure for the future

Focus on three things

Page 4: Advanced Markets enabling Advanced (Smarter Grid ... · – Compressor operates at low load periods; gas turbine serves load as needed – Smoothes out load/supply profile with quick

PJM©20114

Smart Grid – Two-way Communications and Control

Generation

Transmission & Sub-transmissionDistribution

Customer

Smart Metering, Demand Response, PHEV, Energy Conservation and Distributed Resources

Substation Automation

Distribution Automation

SCADA and PhasorMeasurements

The Smart Grid is realized by merging data from these areas of automation to achieve a total end-to-end systems view by integrating information technology and operational technology.

Energy Storage

System Operator

Page 5: Advanced Markets enabling Advanced (Smarter Grid ... · – Compressor operates at low load periods; gas turbine serves load as needed – Smoothes out load/supply profile with quick

PJM©20115

Smart Grid Network

System/Market Operator

Page 6: Advanced Markets enabling Advanced (Smarter Grid ... · – Compressor operates at low load periods; gas turbine serves load as needed – Smoothes out load/supply profile with quick

PJM©20116

Innovation Activity

www.pjm.com

Page 7: Advanced Markets enabling Advanced (Smarter Grid ... · – Compressor operates at low load periods; gas turbine serves load as needed – Smoothes out load/supply profile with quick

PJM©20117

Smart Grid Network - Smart Home

• Smart ApplianceEnergy Management

• Smart Charger (PHEV)Storage

• Regulation Signal• Price Signal• Reliability• Load Curtailment

Aggregator

Grid Signal

System/Market Operator

Page 8: Advanced Markets enabling Advanced (Smarter Grid ... · – Compressor operates at low load periods; gas turbine serves load as needed – Smoothes out load/supply profile with quick

PJM©20118

Smart@Car-a connection to the grid

Page 9: Advanced Markets enabling Advanced (Smarter Grid ... · – Compressor operates at low load periods; gas turbine serves load as needed – Smoothes out load/supply profile with quick

PJM©2011

• Mid-Atlantic Grid Interactive Car Consortium (MAGICC) – electric companies, research institutes, and vehicle manufacturers

• Over one year experience with the MAGICC battery electric vehicle responding to the PJM regulation signal

Smart Grid and Plug-in Hybrid Electric Vehicles (PHEVs)

Page 10: Advanced Markets enabling Advanced (Smarter Grid ... · – Compressor operates at low load periods; gas turbine serves load as needed – Smoothes out load/supply profile with quick

PJM©201110

Load in GW

Hour of Day1 3 5 7 9 11 13 15 17 19 21 23

120110100

908060

2040

Economic Dispatch

Smart Grid Network – Alternative Generation Resources

System/Market Operator

Page 11: Advanced Markets enabling Advanced (Smarter Grid ... · – Compressor operates at low load periods; gas turbine serves load as needed – Smoothes out load/supply profile with quick

PJM©201111

43,623

0

5,000

10,000

15,000

20,000

25,000

30,000

35,000

40,000

45,000

50,000

1999 2001 2003 2005 2007 2009 2011 2013 2015 2017

Cum

ulat

ive N

amep

late M

W

In planning 1/4/2011

Why Storage – Wind Generation in PJM

www.pjm.com

If you like wind…

…You have to love Storage

Page 12: Advanced Markets enabling Advanced (Smarter Grid ... · – Compressor operates at low load periods; gas turbine serves load as needed – Smoothes out load/supply profile with quick

PJM©201112

Innovation--What Storage in PJM?

www.pjm.com

Pumped Hydro Compressed Air Flywheels

Stationary Battery Mobile Batteries Water Heaters

Page 13: Advanced Markets enabling Advanced (Smarter Grid ... · – Compressor operates at low load periods; gas turbine serves load as needed – Smoothes out load/supply profile with quick

PJM©201113

Compressed Air Energy Storage and Norton

• CAES – a highly responsive technology:– Combines gas turbine with compressed air– Compressor operates at low load periods; gas turbine serves load as needed– Smoothes out load/supply profile with quick response

• PJM is working with FirstEnergy on Norton CAES

Large size provides significant advantage:• 338 million cubic foot cavern provides great flexibility

(more than 4 times the size of the Pentagon)• Approximately 130,000 MWhs of storage • Longer storage period than typical

pumped hydro• Can add capacity in 150 MW increments,

up to 2,700 MW total• Fully dispatchable by PJM

www.pjm.com

Page 15: Advanced Markets enabling Advanced (Smarter Grid ... · – Compressor operates at low load periods; gas turbine serves load as needed – Smoothes out load/supply profile with quick

PJM©201115

Operational DetailsAltairnano, Inc – Lithium Ion nano titanate battery

• Energy: 300 kWh• Efficiency: 90% round trip

• Power: 1 MW for 15 minutes • Usable Charge Range: 5% - 99%

AES Grid-Scale Energy Storage System

Page 16: Advanced Markets enabling Advanced (Smarter Grid ... · – Compressor operates at low load periods; gas turbine serves load as needed – Smoothes out load/supply profile with quick

PJM©201116

Attributes• Life expectancy ~20 years• No capacity decreases over life. • No overcharge and over-discharge • Rapid charging ─ minutes

Status in PJM Generation Queue –20 MW - Impact Study Underway

Alternative Resources – Flywheels

Page 17: Advanced Markets enabling Advanced (Smarter Grid ... · – Compressor operates at low load periods; gas turbine serves load as needed – Smoothes out load/supply profile with quick

PJM©201117

Fast Regulation: Speed Matters…

A fossil power plant following a regulation command signal

Energy Storage (batteries / flywheels) accurately following a regulation command signal

Energy Storage OutputRegulation Signal

Page 18: Advanced Markets enabling Advanced (Smarter Grid ... · – Compressor operates at low load periods; gas turbine serves load as needed – Smoothes out load/supply profile with quick

PJM©201118

SynchrophasorsMeasuring voltages and currentsOutputting accurately GPS time-stamped voltage and current phasors

1-2 yearsAngle / Frequency MonitoringDisturbance AnalysisVoltage Stability Analysis

3-5 yearsImproved State Estimation (Boundary conditions)Rapid Restoration

The FutureReal-Time ControlEarly Cascade Detection

Wide AreaMeasurement

System

Smart Grid Network – Grid Reliability

System/Market Operator

Transmission TechnologiesHigh Voltage DC (HVDC)FACTS DevicesVariable Frequency Transformer (VFT)Substation AutomationDirect Load Control

Page 19: Advanced Markets enabling Advanced (Smarter Grid ... · – Compressor operates at low load periods; gas turbine serves load as needed – Smoothes out load/supply profile with quick

PJM©201119

Smart Grid Investment Grant – PJM Lead

Proposed Substations for Phasor Measurement Unit Installations

Page 20: Advanced Markets enabling Advanced (Smarter Grid ... · – Compressor operates at low load periods; gas turbine serves load as needed – Smoothes out load/supply profile with quick

PJM©201120

SynchroPhasor Applications

Voltage Stability Monitoring

1-2 years 2-5 years >5 years

Disturbance Analysis

Determination of Accurate Operating Limits

Angle & Frequency Monitoring

Real-time Control of wide-area network

System Restoration

Improve State Estimation

Wide-area monitoring

Model Derivation & Validation

Detection of imminent Cascading

Real-time control of corridors

Dep

loym

ent C

halle

nge

Ready to deployNeeds moderate development

Requires more research

Inter-area Oscillation Detection & Analysis

Page 21: Advanced Markets enabling Advanced (Smarter Grid ... · – Compressor operates at low load periods; gas turbine serves load as needed – Smoothes out load/supply profile with quick

PJM©201121

Baselining Results can be Usedto Establish ‘alerts’ for Operations

6

Baselining study resultsto be used to set limits

Page 22: Advanced Markets enabling Advanced (Smarter Grid ... · – Compressor operates at low load periods; gas turbine serves load as needed – Smoothes out load/supply profile with quick

PJM©201122

Surry Unit 1 MW

At 01:18hr, Surry reported Unit 1 saw a 200MW swing and Unit 2 experienced a 50MW swing. The SOC did not detect the MW swing. The SOC does not monitor the output of generators in a way that a MW swing would be readily apparent

PCS PMU

Page 23: Advanced Markets enabling Advanced (Smarter Grid ... · – Compressor operates at low load periods; gas turbine serves load as needed – Smoothes out load/supply profile with quick

PJM©201123

• Demand Response• Energy Efficiency

System/Market Operator

Smart Grid Network – Energy Services

Page 24: Advanced Markets enabling Advanced (Smarter Grid ... · – Compressor operates at low load periods; gas turbine serves load as needed – Smoothes out load/supply profile with quick

PJM©201124

Demand Resource and Energy Efficiency in the Capacity Market-2013/2014

Page 25: Advanced Markets enabling Advanced (Smarter Grid ... · – Compressor operates at low load periods; gas turbine serves load as needed – Smoothes out load/supply profile with quick

PJM©201125

Demand Resource Participation in Capacity Market

0

2,000

4,000

6,000

8,000

10,000

12,000

2005/2006 2006/2007 2007/2008 2008/2009 2009/2010 2010/2011 2011/2012 2012/2013

RPM, EERPM, DRRPM, ILRALM

RPM Implemented

Prior to RPM Implementation

RPM = Reliability Pricing Model DR = Demand ResponseILR = Interruptible Load for Reliability ALM = Active Load Management

MW

Delivery Year

Page 26: Advanced Markets enabling Advanced (Smarter Grid ... · – Compressor operates at low load periods; gas turbine serves load as needed – Smoothes out load/supply profile with quick

PJM©201126

Second Generation: PJM Demand Side Response Programs

$0

$50

$100

$150

$200

$250

$300

$350

HR1HR2

HR3HR4

HR5HR6

HR7HR8

HR9HR10

HR11HR12

HR13HR14

HR15HR16

HR17HR18

HR19HR20

HR21HR22

HR23HR24

Wholesale Price (Hourly LMP)

Retail Rate

Will an End-Use-Customer reduce consumption when

wholesale prices are high or when PJM initiates

Emergency procedures?

Page 27: Advanced Markets enabling Advanced (Smarter Grid ... · – Compressor operates at low load periods; gas turbine serves load as needed – Smoothes out load/supply profile with quick

PJM©201127www.pjm.com

Page 28: Advanced Markets enabling Advanced (Smarter Grid ... · – Compressor operates at low load periods; gas turbine serves load as needed – Smoothes out load/supply profile with quick

PJM©201128

AC2 Key Accomplishments

Page 29: Advanced Markets enabling Advanced (Smarter Grid ... · – Compressor operates at low load periods; gas turbine serves load as needed – Smoothes out load/supply profile with quick

PJM©20112929

©2008 PJMwww pjm com Document #504371

SCADA, NetworkApplications, AGC

Market MgmtSystem

Dispatch Management Tool

eMKT & eFTR

eMTR

eSuite

Single Sign On

Task Based

Personalization

Customization

Navigation

Security

Common Use

r Int

erfac

eEngy Mgmt

System

AC2 Technology

ESB

TNA MARKETBSCs

SCADA PI OTHERBSCs

CEPEngine

CEPEngine

CEPEngine

COMMON OBJECT MODEL(via Integrated Model Manager)

IEPDATABASE

IEP UI

AC2 New Technologies

User Experience & Visualization(advanced dispatcher UI)

Generation Control Application(multi-interval SCED; adaptive constraint/generator modeling)

Intelligent Event Processor(complex event processing/correlation)