Series Programmable DC Power Supplies Full-Rack 5kW in 1U Height • Arbitrary Waveform Generator with Auto-Trigger Capability • Programmable Slew-Rate Control (Vout/Iout) • Constant Power Operation • Internal Resistance Programming • Built-In LAN (LXI 1.5), USB, and RS-232/RS-485 Interfaces • Built-In Remote Isolated Analog Interface • Blank Front Panel Option Available • Scalable Power Systems of 10kW and 15kW NEW ! - Lightweight 5kW Output Power in 1U Height - NEW ! ! Advanced Features Built-In ! Innovating Reliable Power www.us.tdk-lambda.com/hp

Upload: others

Post on 28-Dec-2019

14 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Advanced Features Built-Inwescalkorea.com/111/tdk-lambda_catalog/GENESYS_PLUS.pdf4 ™ 5kW SERIES MENU buttons and Active menu LED's Output Control buttons and Status LED's Front Panel

™ Series

Programmable DC Power Supplies

Full-Rack 5kW in 1U Height

• Arbitrary Waveform Generator with Auto-Trigger Capability

• Programmable Slew-Rate Control (Vout/Iout)

• Constant Power Operation • Internal Resistance Programming

• Built-In LAN (LXI 1.5), USB, and RS-232/RS-485 Interfaces

• Built-In Remote Isolated Analog Interface

• Blank Front Panel Option Available

• Scalable Power Systems of 10kW and 15kW

NEW ! - L

ightweight 5kW Output Power in 1U Height - N

EW !

! Advanced Features Built-In !

Innovating Reliable Powerwww.us.tdk-lambda.com/hp

Page 2: Advanced Features Built-Inwescalkorea.com/111/tdk-lambda_catalog/GENESYS_PLUS.pdf4 ™ 5kW SERIES MENU buttons and Active menu LED's Output Control buttons and Status LED's Front Panel

2 ™ 5kW SERIES

Overview:

- The ™ 1U 5kW series of precision DC programmable power supplies represents a new generation platform that brings advanced performance and higher power density to the high reliability TDK-Lambda DC Programmable Power Supply product portfolio.

- This new DC programmable power supply platform offers significant advancements such as a high contrast, wide viewing angle multi-segment front panel LCD display (with user controllable brightness and dimming functions) with five embedded

multi-functional Power Supply Setup menus that address Digital Communication, Protective Functions, Operating Configuration, System Configuration and System Triggering. These Setup menus offer many new adjustable user-selectable functions including Internal Resistance simulation, Constant-Power limit and Slew-Rate control (Output voltage/current). Arbitrary waveform profiles (such as vehicle battery start-up simulation) of up to 100 steps can also be generated and stored in four on-board memory cells and can be recalled and activated via the embedded menus or through any standard Remote Digital communication interface (LAN ( , 1.5), USB or RS-232/RS-485).

- All model functions can be programmed locally via the menu-driven front panel display or remotely using one of the three standard Remote Digital communication interfaces (LAN ( 1.5), USB and RS-232/RS-485) or through the optional IEEE (SCPI-compliant) interface.

- A built-in standard Remote Isolated Analog Program/Monitor & Control Interface (with 600V isolation) is also provided with new functions such as Output control pins (for activation of external devices for polarity reversal/load disconnect), Trigger-

In/Trigger-Out pins (for synchronization), ENABLE control (with user-selectable polarity) and high accuracy Program/

Monitor signals.

- A new Advanced Parallel Master/Slave system, unique to TDK-Lambda, allows for improved multi-unit system performance (Output ripple/noise and dynamic response) where up to four units* can be connected in parallel and automatically configured by detection of the parallel data-link cable connections between units.

- New mechanical options include a Blank Front Panel and a Dust Cover. The Blank Front Panel option is available for applications where the front panel display and controls are not required and only remote interfacing (Digital/Analog) is needed. The Dust Cover is used in dusty air environment applications, snaps in place and has a removable filter (for easy maintenance).

- Models are available from 10V (500A) to 600V (8.5A) with conversion efficiencies up to 92% and options for three-phase AC Input include 208VAC (170~265VAC) or a wide-range 480VAC (342~528VAC), all with built-in active Power-Factor-Correction (0.94 typical).

Key Features:

• High power density: 5kW In 1U height • Light weight: < 16.5lbs (7.5 kg)

• Output Voltage/Current: ten models ranging from 10V/500A to 600V/8.5A (10V, 20V, 30V, 40V, 60V, 80V, 100V, 150V, 300V and 600V)

• Two 3ø AC inputs available: 3ø-208VAC (170~265VAC) and wide-range 3ø-480VAC (342~528VAC)

• Standard Remote Digital Interfaces: LAN ( 1.5), USB and RS-232/RS-485

• Built-in Isolated Analog Programming, Monitoring & Control (600V isolation)

• Arbitrary Waveform Generator with Auto-Triggering

• Output Up/Down Slew-Rate Control (Voltage & Current)

• Constant Power (CP) limit mode • Internal Resistance Simulation

• Control Pins for Output Polarity reversal/Load disconnect

• Scalable Master-Slave Operation with Auto-paralleling (up to four identical units*)

• Certified LabWindows™/CVI, LabVIEW™, and IVI Drivers

• Five Year Warranty

• Worldwide Safety Agency Approvals (EN/UL/cUL 60950-1 Listed)

• CE Marked for LV, EMC and RoHS2 Directives

* Please contact the factory for more than four identical units connected in parallel

2

Page 3: Advanced Features Built-Inwescalkorea.com/111/tdk-lambda_catalog/GENESYS_PLUS.pdf4 ™ 5kW SERIES MENU buttons and Active menu LED's Output Control buttons and Status LED's Front Panel

3™ 5kW SERIES

Front Panel Highlights (Standard Model)

1. Input Power ON/OFF Switch2. Front panel air intake slots (allows zero-stacking of units for flexible rack system integration)3. Product label (identifies model Output voltage and Output current)4. VOLTAGE encoder (with detent) and pushbutton

• Encoder: for adjustment of Voltage setting and navigation of multi-functional setup menus• Pushbutton: accepts Voltage setting value in PREView mode

5. VOLTAGE display (4 digit 16-segment with "V" as fifth digit)• PREView mode: indicates the programmed setting of Output voltage; set with FINE or COARSE ajdustment• Menu Navigation mode: indicates the selected function (eg. PROTection menu: OVP function)

6. CURRENT display (4 digit 16-segment display with "A" as fifth digit)• PREView mode: indicates the programmed setting of Output current; set with FINE or COARSE adjustment• Menu Navigation mode: indicates the selected parameter (eg. - PROTection menu: OVP value)

7. CURRENT encoder (with detent) and pushbutton• Encoder: for adjustment of Current setting and navigation of multi-functional setup menus• Pushutton: accepts Current setting value in PREView mode, selects menu level and sets parameter value

8. OUT button (Output ON/OFF control) with embedded GREEN/RED LED• Lit GREEN when Output is ON; unlit when Output OFF; blinking RED (1/2Hz rate) during FAULT condition

9. Output Control buttons (PREV and FINE) with embedded GREEN status LED's• PREView mode: displays Output voltage/Output current settings; active when GREEN LED is illuminated• FINE mode: high resolution encoder operation; active when GREEN LED is illuminated (otherwise COARSE mode)

10. Setup MENU buttons (PROG, SYST, CONF, PROT, COMM) with embedded GREEN LED's (lit GREEN when active)11. BACK button (to move one step back in an active Setup MENU)

1. Isolated Analog Program, Monitor and Control connector (DB26-female)2. USB Interface connector (Type B)3. RS-232/RS-485-IN (RJ-45 type) for Remote Digital Interface and RS-485 -OUT (RJ-45 type) for Multi-Drop connection4. LAN ( 1.5) Interface connector (RJ-45 type with LAN status indicators)5. Auto-Paralleling Bus connectors (mini I/O type) for connecting Master unit-to-Slave unit and Slave unit-to-Slave unit6. Remote/Local Output voltage sense connector (spring-cage type); Phoenix Contact connector (SPT-THR 1,5/3-H-3, 5 P26)7. DC Output Connection

• Rugged busbars (shown) for models with Vout < 150V (two holes: Vout < 40V, one hole: 60V < Vout < 100V)• Phoneix Contact connector (IPC 5/4-STF-7, 62) for models with Vout > 150V

8. AC Input connector (Three-phase 208VAC/480VAC)• Phoenix Contact connector (Power Combicon PC 5/4-STCL1-7, 62 series) with added strain relief

9. Optional Interface port (IEEE 488.2 Interface)10. Exhaust air slots assure reliable operation when units are zero-stacked11. Functional Ground connection (M4 x 8mm stud)

1

2

3 465

7

Rear Panel Highlights (Standard Model)

1

10

2 3 4 5 6

7

8

9

9 81011

11

Page 4: Advanced Features Built-Inwescalkorea.com/111/tdk-lambda_catalog/GENESYS_PLUS.pdf4 ™ 5kW SERIES MENU buttons and Active menu LED's Output Control buttons and Status LED's Front Panel

4 ™ 5kW SERIES

MENU buttonsand

Active menu LED's

Output Control buttonsand

Status LED's

Front Panel Display MENU/CONTROL buttons:

6543

2

1

1. BACK button: used for moving one step back in an active Setup MENU (PROG, SYST, CONF, PROT, COMM)

2. PROGram MENU button / Indicator• PROGram menu provides SEQUENCER function control, TRIGGER function control and loads a sequence stored in Power

Supply on-board memory3. SYSTem MENU button / Indicator

• Front Panel Lock/Unlock is set by first pressing SYST button followed by pressing the CURRENT encoder• SYSTem menu provides Local/Remote sensing selection, INTERLOCK function control, ENABLE function control, PS_OK

signal control, SAVE/RECALL Power Supply configuration, PROGrammable Signal control, Pre-Load ON/OFF control, Display brightness and dimming control and RESET Power Supply settings

4. CONFiguration MENU button / Indicator• CONFiguration menu provides Power Supply Start mode control (Safe/Auto), Voltage & Current source control, Analog

Program/Monitor range selection, Internal Resistance ON/OFF control and setting, Constant Power limit ON/OFF control and setting and Output Slew-Rate Control function control and settings

5. PROTection MENU button / Indicator• PROTection menu provides Output OVP setting, Output UVL setting, Output UVP function control, FOLDback V/I function

control and OCL ON/OFF control6. COMMunication MENU button / Indicator

• COMMunication menu provides communication interface selection (LAN, USB, RS-232, RS-485, OPT), Power Supply Address selection (0-31), LAN Interface Settings control, Baud rate selection, Communication language selection and Software revision information

7. FINE button / Indicator• Pressing activates the encoder FINE function (GREEN LED lit). Once lit, pressing the FINE button exits back to the main

display (actual Vout/Iout or Output OFF)• FINE button provides Output Voltage/Current Fine or Coarse adjustment control. In FINE mode, VOLTAGE and CURRENT

encoders operate in high-resolution mode. In COARSE mode, Voltage and CURRENT encoders operate in standard resolution (approximately 3 turns for rated Output Voltage/Current)

8. PREView button / Indicator• Pressing activates the PREView function (GREEN LED lit). Once lit, pressing the PREView button exits back to the main

display (actual Vout/Iout or Output OFF). If no button is pressed, the display returns back to the actual Output voltage/Output current after 5 seconds.

• If voltage or current values are changed then the PREView mode displays Output voltage/Output current settings for 15 seconds. After 15 seconds the front panel display returns back to the actual Output voltage/current.

9. OUT button (Output ON/OFF control) with embedded GREEN/RED LED• lluminated GREEN when Output is ON; unlit when Output is OFF; blinking RED (1/2Hz rate) during FAULT condition

NOTE: Pressing any MENU button (PROG, SYST, CONF, PROT or COMM) will activate that menu (GREEN LED lit). Once lit, pressing the same MENU button will exit the MENU (GREEN LED not lit) and go back to the main display (actual Vout/Iout or Output OFF).

78

9

Page 5: Advanced Features Built-Inwescalkorea.com/111/tdk-lambda_catalog/GENESYS_PLUS.pdf4 ™ 5kW SERIES MENU buttons and Active menu LED's Output Control buttons and Status LED's Front Panel

5™ 5kW SERIES

Voltage Display + ‘V’ Symbol(16 Segment)

AUTO-startSAFE-startIndicator

FOLDback Voltage Current

Indicator

Power Supply Power/Address

Indicator

Remote Communication Active RS-232/RS-485, USB, LAN, OPT

(IEEE, etc.)

Current Display + ‘A’ Symbol(16 Segment)

OperationMode

External VoltageProgramming

External CurrentProgramming

LFP (Locked Front Panel) TRIGger System Active

Active Memory Cell (Sequence)

1

1. VOLTAGE display: 4-digit, 16-sement display which normally displays Output voltage, 5th digit is "V" symbol. In PREView mode, the VOLTAGE display shows the programmed setting of the Output voltage. In MENU navigation, the VOLTAGE display indicates the selected MENU function.

2. Operating Mode indicator: CV (Constant-Voltage), CC (Constant-Current) or CP (Constant-Power).3. CURRENT display: 4-digit, 16-sement display which normally displays Output current, 5th digit is "A" symbol. In PREView mode,

the CURRENT display shows the programmed setting of the Output current. In MENU navigation, the CURRENT display indicates the selected MENU parameter.

4. LFP (Locked Front Panel) indicator: Illuminated if Front Panel is Locked (default is Unlocked (not lit)).5. AUTO Re-Start indicator: Illuminated if AUTO Re-Start mode is active.6. SAFE Start indicator: Illuminated if SAFE-Start mode is active (default is SAFE).7. FOLD V/I indicator: FOLD V is illuminated if FOLDback CV protection is active. FOLD I is is illuminated if FOLDback CC

protection is active.8. Power/Address indicator: If Output is ON, the actual Output power is displayed. If Output is OFF, the Power Supply communication

Address is displayed (the Power Supply communication Address is displayed while the COMM menu is active, regardless of the Power Supply Output state)

9. ext V / ext I indicators: ext V is lit if Remote Analog Voltage programming is active. ext I is lit if Remote Analog Current programming is active.

10. REMote indicator: REMOTE digital communication indicator. REMote is active when Power Supply is controlled by LAN, USB, RS-232/RS-485, IEEE or other digital communication interface.

11. RS indicator: Recommended Standard (RS) indicator is illuminated if RS-232 or RS-485 digital communication is selected.12. USB indicator: Universal Serial Bus (USB) indicator is lit if USB communication is selected.13. LAN indicator: Local Area Network (LAN) indicator is lit if LAN communication is selected.14. OPT indicator: OPTional communication interface indicator is lit if selected (eg. optional IEEE interface).15. TRIG indicator: TRIGger indicator is lit if Trigger-In is enabled and initialized.16. Active Memory Cell indicator: displays the Active memory cell. Shows 1, 2, 3 or 4 if a sequence is loaded from that cell; shows

"_" if a sequence is loaded from an external controller; Indicator blinks if a sequence is running.

Front Panel Display Indicators

2 3

4 5 67

8

9 9

10 1112

1314

15

16

Page 6: Advanced Features Built-Inwescalkorea.com/111/tdk-lambda_catalog/GENESYS_PLUS.pdf4 ™ 5kW SERIES MENU buttons and Active menu LED's Output Control buttons and Status LED's Front Panel

6 ™ 5kW SERIES

™ Parallel and Series Configurations

Parallel Operation - Master/Slave:

Auto-paralleling Scalable Master-Slave Operation.Active current sharing allows up to four identical units to be connected.Total actual Output current is programmed, measured and reported by the Master unit.Separate "Parallel Kit" available for 20kW (4 unit) systems allowing easy system setup.

A Blank Front Panel is available for applications where the front panel display and controls are not required and only Remote interfacing (digital/analog) is required.The Blank Front Panel option has all the standard product functions and features without the front panel display.The power supply can be controlled via any rear panel Remote digital interface (LAN, USB, RS-232/RS-485, etc.) or via the Remote Isolated Analog interface.

™ Blank Front Panel

Multi-Drop Remote Programming via Digital Communication InterfaceStandard built-in LAN, USB, RS-232 and RS-485 (or optional IEEE) Digital Interfaces allow "Multi-Drop" control of up to 31 power supplies via the same RS-485 unit-to-unit linking bus.

• First unit is LAN, USB, RS-232, RS-485, etc.• All other units use RS-485 daisy-chain with linking cable

Scalable Power Systems (10kW/15kW)*Factory assembly and test available for 10kW (2 unit) and 15kW (3 unit) systems. Separate "Parallel Kit" available for 20kW (4 unit) systems allowing easy system setup.* Contact the factory for Scalable Power System specifications

GSP 10kW in 2U GSP 15kW in 3U

Standard Units: zero-stacked (up to 4 units)

Standard & Blank Units: zero-stacked (up to 4 units)

Series Operation:

Two units may be connected in series to increase the total Output voltage or to provide a bipolar output (maximum of 600V from any Output terminal to Chassis ground).

LAN, USB, RS-232RS-485, IEE or

other

RS-485 link

RS-485 link

Page 7: Advanced Features Built-Inwescalkorea.com/111/tdk-lambda_catalog/GENESYS_PLUS.pdf4 ™ 5kW SERIES MENU buttons and Active menu LED's Output Control buttons and Status LED's Front Panel

7™ 5kW SERIES

Graphical User Interface

Advanced "Virtual Front Panel" allows for programming and monitoring of unit(s) with or without front panel display

• Control and monitor up to 31 units with "Address" bar• Control and monitor Power Supply functions (Output ON/OFF, Voltage/Current/Power/Resistance settings and more)• Output status, encoder settings and indications• Informative "Parameters" status bar• Front panel SETUP menu control (PROGram, SYSTem, CONFiguration, PROTection and COMMunication)• Individual unit and Global command control• Virtual front panel controls lock• Power Supply settings SAVE and RECALL function

Embedded Menu tabs (STATUS LOG, WAVEFORM PROFILE, V/I GRAPH and ADVANCED) give capabilities for utiilization of advanced features/functions.

• STATUS LOG tab (shown above): Provides capability for data logging including fault and recovery events

• WAVEFORM PROFILE tab: Allows user to create a waveform, display the real-time graph and store/load a waveform sequence

• V/I GRAPH tab: Sets and displays Power Supply operation limits (CV/CC/CP), generates Solar Array operating profiles and calculates DC load resistance

• ADVANCED tab: Adusts front panel display settings (Lock Front Panel, Safe/Auto-Restart and UVP, Local/Remote), active J1 signals (Programmable pins, ILC, ENA), reset Power Supply settings, review Registers and test front

panel display

Page 8: Advanced Features Built-Inwescalkorea.com/111/tdk-lambda_catalog/GENESYS_PLUS.pdf4 ™ 5kW SERIES MENU buttons and Active menu LED's Output Control buttons and Status LED's Front Panel

8 ™ 5kW SERIES

Technical Specifications: Unit with Air Filter Assembly Installed • Derating (enviromental): • Operating Temperature • For all models (except 10V): 0˚C to +40˚C; For 10V model: 0˚C to +30˚C, derate 5A/˚C for 30˚C < Ta < +40˚C • Altitude • For all models (except 10V): derate 2˚C/100m or 2% of load/100m (above 2000m) • For 10V model: derate 1˚C/100m or 2% of load/100m (above 2000m)

Air Filter Assembly Components

Standard Unit (P/N: G-AFK)

• Air Filter Cover (two pieces) • Slide Button #1 (two locations: near AC ON/OFF switch and near left-hand side of front panel display) • Slide Button #2 (one location: right-hand side of front panel display) • Filter foam (two pieces) Blank Front Panel Unit (P/N: GB-AFK)

• Air Filter Cover (one piece) • Slide Button #1 (two locations) • Filter foam (one piece)

• Part Number (for standard unit): G-AFK

• Part Number (for unit with blank front panel): GB-AFK

A front panel air filter assembly is available for dusty air environment applications (see User's Manual) and has removable snap-in covers and locking buttons with removable foam inserts (for easy maintenance).

Front Panel Air Filter Assembly

Filter Foam Technical Specifications

• Material: reticulated polyurethane foam • Thickness: 4.0mm • Porosity: 30ppi • Operating Temperature Range: 0˚C to +60˚C • Storage Temperature Range: -40˚C to +85˚C • Humidity: 95% RH

Page 9: Advanced Features Built-Inwescalkorea.com/111/tdk-lambda_catalog/GENESYS_PLUS.pdf4 ™ 5kW SERIES MENU buttons and Active menu LED's Output Control buttons and Status LED's Front Panel

9™ 5kW SERIES

Power Supply Identification / Accessories

StandardG 10 - 500 - XXX - 3PXXX

Series Name OutputVoltage

OutputCurrent

InterfaceOptions

AC Input Options

(0~10V) (0~500A) IEEE3P208 (Three-Phase 170~265VAC)3P480 (Three-Phase 342~528VAC)

Blank Front Panel

GB 10 - 500 - XXX 3PXXX

(0~10V) (0~500A) IEEE 3P208 (Three-Phase 170~265VAC)3P480 (Three-Phase 342~528VAC)

Scalable Power

System

GSP 10 - 1000 - XXXX 3PXXX

(0~10V) (0~1000A)-10kW

or(0~1500A)-15kW

IEEE 3P208 (Three-Phase 170~265VAC)3P480 (Three-Phase 342~528VAC)

Scalable with

Blank Front Panel

GBSP 10 - 1000 - XXXX 3PXXX

(0~10V) (0~1000A)-10kW

or(0~1500A)-15kW

IEEE 3P208 (Three-Phase 170~265VAC)3P480 (Three-Phase 342~528VAC)

Models (5kW Full-Rack: Standard Model and Blank Front Panel Model)

Model (A)Output Voltage

(VDC)

Output

Current

(ADC)

Output

Power

(kW)

G/GB10-500 0~10 0~500 5.0

G/GB20-250 0~20 0~250 5.0

G/GB30-170 0~30 0~170 5.1

G/GB300-17 0~300 0~17 5.1

G/GB600-8.5 0~600 0~8.5 5.1

Model (B)Output Voltage

(VDC)

Output

Current

(ADC)

Output

Power

(kW)

G/GB40-125 0~40 0~125 5.0

G/GB60-85 0~60 0~85 5.1

G/GB80-65 0~80 0~65 5.2

G/GB100-50 0~100 0~50 5.0

G/GB150-34 0~150 0~34 5.1

Model (A)Output Voltage

(VDC)

OutputCurrent

(ADC)

OutputPower(kW)

GSP/GBSP10-1000 0 ~ 10 0 ~ 1000 10.0

GSP/GBSP10-1500 0 ~ 10 0 ~ 1500 15.0

GSP/GBSP20-500 0 ~ 20 0 ~ 500 10.0

GSP/GBSP20-750 0 ~ 20 0 ~ 750 15.0

GSP/GBSP30-340 0 ~ 30 0 ~ 340 10.2

GSP/GBSP30-510 0 ~ 30 0 ~ 510 15.3

GSP/GBSP300-34 0 ~ 300 0 ~ 34 10.2

GSP/GBSP300-51 0 ~ 300 0 ~ 51 15.3

GSP/GBSP600-17 0 ~ 600 0 ~ 17 10.2

GSP/GBSP600-25.5 0 ~ 600 0 ~ 25.5 15.3

Model (B)Output Voltage

(VDC)

OutputCurrent

(ADC)

OutputPower(kW)

GSP/GBSP40-250 0 ~ 40 0 ~ 250 10.0

GSP/GBSP40-375 0 ~ 40 0 ~ 375 15.0

GSP/GBSP60-170 0 ~ 60 0 ~ 170 10.2

GSP/GBSP60-255 0 ~ 60 0 ~ 255 15.3

GSP/GBSP80-130 0 ~ 80 0 ~ 130 10.4

GSP/GBSP80-195 0 ~ 80 0 ~ 195 15.6

GSP/GBSP100-100 0 ~ 100 0 ~ 100 10.0

GSP/GBSP100-150 0 ~ 100 0 ~ 150 15.0

GSP/GBSP150-68 0 ~ 150 0 ~ 68 10.2

GSP/GBSP150-102 0 ~ 150 0 ~ 102 15.3

Models (Scalable10kW/15kW Full-Rack: Standard Model and Blank Front Model)

Interface Options (Factory installed) P/N

IEEE (488.2) - (option) IEEE

LAN ( 1.5, Class C) - (built-in) -

USB (2.0) - (built-in) -

RS-232/RS-485 - (built-in) -

Isolated Analog Pgm/Mon/Ctrl (600V isolation) - (built-in) -

How - to - Order

Page 10: Advanced Features Built-Inwescalkorea.com/111/tdk-lambda_catalog/GENESYS_PLUS.pdf4 ™ 5kW SERIES MENU buttons and Active menu LED's Output Control buttons and Status LED's Front Panel

10 ™ 5kW SERIES

AccessoriesAccessories are shipped separately (according to order)

2. Multi-Drop Linking cable (included with the power supply)

Daisy-chain up to 31 ™ power supplies.

3. Paralleling cable: Unit-to-Unit (ordered separately)

Mode RS-485 RS-232 RS-232

PC ConnectorCommunication Cable

Power Supply Connector

DB-9FShielded, L = 2m

RJ-45

DB-9FShielded, L = 2m

RJ-45

DB-25FShielded, L = 2m

RJ-45

P/N GEN/485-9 GEN/232-9 GEN/232-25

Mode Power Supply Connector Communication Cable P/N

RS-485 RJ-45 Shielded L=50cm GEN/RJ45

Connectors Cables P/N

2013595-1 (TYCO) Shielded, L = 11cm G/P

1. Serial Communication cable (ordered separately)

RS-232/RS-485 cable is used to connect the power supply to the host controller.

4. Air Filter Kit (ordered separately)

Series P/N Series P/N

Standard Model G-AFK Blank Front Panel Model GB-AFK

Scalable Standard Model (10kW) GSP10-AFK

Scalable Blank Front Panel Model (10kW) GBSP10-AFK

Scalable Standard Model (15kW) GSP15-AFK

Scalable Blank Front Panel Model (15kW) GBSP15-AFK

5. Parallel Kit: 20kW operation (ordered separately)

Series P/N

Standard ModelBlank Front Panel Model

G/P-4U

Page 11: Advanced Features Built-Inwescalkorea.com/111/tdk-lambda_catalog/GENESYS_PLUS.pdf4 ™ 5kW SERIES MENU buttons and Active menu LED's Output Control buttons and Status LED's Front Panel

11™ 5kW SERIES

™ 5000W SERIES - TECHNICAL SPECIFICATIONS

OUTPUT RATING GEN 10-500 20-250 30-170 40-125 60-85 80-65 100-50 150-34 300-17 600-8.51. Rated Output Voltage, (*1) V 10 20 30 40 60 80 100 150 300 6002. Rated Output Current, (*2) A 500 250 170 125 85 65 50 34 17 8.53. Rated Output Power W 5000 5000 5100 5000 5100 5200 5000 5100 5100 5100

INPUT CHARACTERISTICS V 10 20 30 40 60 80 100 150 300 6001. AC Input Voltage/Frequency (3-phase, 3 Wire + Ground, (*4) ---

3-Phase, 208V models: 170~265VAC, 47~63Hz (Covers 200VAC/230VAC range)3-Phase, 480V models: 342~528VAC, 47~63Hz (Covers 380VAC/400VAC/415VAC/440VAC/460VAC/480VAC ranges)

2. Input Current, maximum (100% load)

3-Phase, 208V models:Arms

17.5Arms @ 200VAC, 18.0Arms @ 180VAC3-Phase, 480V models: 9.2A @ 380VAC, 8.3Arms @ 432VAC

3. Power Factor (typical) --- 0.94 @ 200VAC/380VAC, rated Output power4. Efficiency (*5) % 90 91 91 91 91 91 91 91 92 925. Inrush Current (*6) Apk Less than 50Apk6. Phase Imbalance % < 5%

CONSTANT VOLTAGE MODE V 10 20 30 40 60 80 100 150 300 6001. Line Regulation, maximum: +/- 0.01% of Vo(rated), (*7) mV 1 2 3 4 6 8 10 15 30 602. Load Regulation, maximum: +/- 0.01% of Vo(rated)+5mV, (*8) mV 6 7 8 9 11 13 15 20 35 653. Ripple and Noise (p-p, 20MHz), (*9) mV 75 75 75 75 75 80 90 120 200 4804. Ripple (RMS, 5Hz~1MHz), (*9) mV 8 10 12 12 12 15 15 20 60 1005. Temperature Coefficient ppm/°C +/- 50ppm/°C from Vo(rated), following 30 minute warm-up6. Temperature Stability % +/- 0.01% of Vo(rated) over 8hr interval, following 30 minute warm-up (constant AC line, DC load & ambient temperature)7. Warm-Up Drift % Less than +/- 0.05% of Vo(rated) + 2mV over 30 minutes, following Output power on.8. Remote Sense compensation per wire, (*10) V 2 2 5 5 5 5 5 5 5 59. Up-Prog Response Time, (*11) ms 30 30 30 30 50 50 50 50 50 10010. Down Prog Response Time Full-load, (*11) ms 50 50 80 80 80 100 100 100 100 200

No-load, (*12) ms 300 600 800 900 1000 1200 1500 2000 3000 300011. Transient Response Time

msLess than 1ms for models where Vo(rated) < 100V. Less than 2mS for models where Vout(rated) > 100V. Time for Output voltage to recover within 0.5% of Vo(rated) for a load change of 10~90% of Io(rated). Output voltage set-point: 10~100% with local sense.

12. Hold-Up Time (typical) ms 5ms (Ta = 25°C, 208VAC/400VAC/480VAC, all three phases interrupted simultaneously)

CONSTANT CURRENT MODE A 500 250 170 125 85 65 50 34 17 8.51. Line Regulation, maximum: - +/- 0.05% of Io(rated), (*7) mA 250 125 85 62.5 42.5 32.5 25 17.0 8.5 4.252. Load Regulation, maximum: +/- 0.08% of Io(rated), (*13) mA 400 200 136 100.0 68.0 52.0 40 27.2 13.6 6.803. Load Regulation Thermal Drift --- Less than +/- 0.03% of Io(rated) over 30 minutes, following load change4. Ripple (RMS) @ 10% of Vo(rated), (*14) mA 1200 600 300 150 100 70 45 45 15 85. Ripple (RMS, 5Hz ~ 1MHZ) @ Vo(rated) mA 700 300 150 75 50 35 23 23 7.5 46. Temperature Coefficient ppm/°C +/- 70ppm/°C from Io(rated), following 30 minute warm-up7. Temperature Stability % +/- 0.01% of Io(rated) over 8hr interval, following 30 minute warm-up (onstant AC line, DC load & ambient temperature)8. Warm-Up Drift

%10V model: Less than +/-0.2% of Io(rated) over 30 minutes, following Output power on.20V~600V models: Less than +/-0.1% of Io(rated) over 30 minutes, following Output power on.

PROTECTIVE FUNCTIONS V 10 20 30 40 60 80 100 150 300 6001. Output Foldback protection (FOLD)

---

Output shutdown when Power Supply Output changes mode from CV mode (or CP limit mode) to CC mode (FOLD-I) or from CC mode (or CP Limit mode) to CV mode (FOLD-V). Front panel displays FOLD FAULT. User-presetable by front panel or digital communication. Reset by AC Input ON/OFF switch recycle (AUTO-Restart mode), by OUT button, by rear panel Remote Analog control (ENABLE/DISABLE) or by digital communication (OUT ON/OUT 1). Default = OFF.

2. Output Over-Voltage Protection (OVP)---

Output shutdown when Power Supply Output (at sense points) exceeds the OVP setting. Front panel displays OVP FAULT. User-presetable by front panel or digital communication . Reset by AC Input ON/OFF switch recycle in AUTO-Restart mode, by OUT button, by rear panel Remote Analog control or by digital communication.

3. Output OVP Programming Range --- Shall always be > 105% of Output voltage setting. Default setting = 110% ~ 120% of Vo(rated) and is model dependent.

V 0.50~12.00 1.00~24.00 2.00~36.00 2.00~44.10 5.00~66.15 5.00~88.20 5.00~110.20 5.00~165.37 5.00~330.75 5.00~661.504. Output OVP Programming Accuracy --- +/-1% of Vo(rated)5. Output Under Voltage Limit (UVL)

---Prevents from adjusting Vout below the UVL setting (with no Power Supply shutdown). Does not affect rear panel Remote Analog programming.User-presetable by front panel or digital communication.

6. Output UVL Programming Range --- 0% to 95% of Vo(rated) and shall always be less than 95% of Output voltage setting. Default = 0% of Vo(rated).7. Output UVL Programming Accuracy % +/-0.05% of Vo(rated)8. Output Under Voltage Protection (UVP)

---

Prevents Power Supply operation if Vout is below the UVL limit. Output shutdown upon detection of an Output Under-Voltage condition. Front panel displays UVP FAULT User-presetable by front panel or digital communication. Reset by AC input ON/OFF recycle (AUTO-Restart mode), by OUT button, by rear panel Remote Analog control (ENABLE/DISABLE) or by dIgital communication. Default = OFF.

9. Output UVP Programming Accuracy % +/-0.05% of Vo(rated)10. Over Current Limit (OCL) --- Limits Analog current programming to a programmed value (from Io(min) to Io(rated)). Set via front panel or digital communication. Default = OFF.11. OCL Setpoint Range --- Io(min) to Io(rated). Set via front panel or digital communication.12. OCL Setpoint Programming Accuracy --- Same as Digital Programming Accuracy for Iout. Set via front panel or digital communication.13. Over Temperature Protection (OTP)

---Output shutdown if internal temperature exceeds internal limit or locked/stopped fan condition occurs. Front panel displays OTP FAULT.User-selectable: Latched in SAFE mode/Auto-recovery in AUTO-Restart mode.

14. AC Fail---

Output shutdown if AC Input has been shut down or AC input is too low. Front panel displays AC FAULT.User-selectable: Latched in SAFE mode/Auto-recovery in AUTO-Restart mode.

FUNCTIONS AND FEATURES

1. Constant Power Limit---

Limits the Output power to a programmed value (eg. Vrated*Irated). CP Limit programming resolution = 1W (FINE) / 100W (COARSE).Programming via front panel or digital communication. Supports both FOLDback for CV and CC mode. Default = OFF (Setpoint = Rated V/I).

2. Internal Resistance Simulation---

Emulates series resistance (Vout = Vsetting - (Iout*Rseries)). Programming via front panel or digital communication.Resistance range/step: 1~1000mΩ/1mΩ (FINE mode), 100mΩ (COARSE mode). Default: OFF/Setpoint = 1mΩ.

3. Pre-Load Control---

Enables/Disables Output Pre-Load. ON: Pre-Load active when Output is ON, OFF: Disables Pre-Load five (5) seconds after Output transition to OFF state. Programming via digital communication or front panel. Default = ON (when PS Output is ON).

4. Slew-Rate Function Control---

Programmable Output Slew-Rate Rise/Fall. Programming via front panel or digital communication.Programming range: 0.0001~999.99 V/ms (or A/ms). Programming Step = 1V/ms (or A/ms) COARSE, 0.01V/ms (or A/ms) FINE from 100.00V/ms to 999.99V/ms.Default = OFF (999.99V/ms (or A/ms)).

5. Arbitrary Waveform Generation (SEQUENCER)

---

Waveform profiles of up to 100 steps (in steps of 1ms) can be stored in four (4) memory cells. Default = OFF.Activation via front panel PROG menu or digital communication. Activity Indicator (TRIG) and Active memory cell (1-4) visible on front panel display.LIST/WAVE mode: Output value change (in steps/slopes) determined by LIST/WAVE parameters, Output change activated by Input trigger, LIST/WAVE parameters activated by the "Program" subsystem (see User's Manual).

Page 12: Advanced Features Built-Inwescalkorea.com/111/tdk-lambda_catalog/GENESYS_PLUS.pdf4 ™ 5kW SERIES MENU buttons and Active menu LED's Output Control buttons and Status LED's Front Panel

12 ™ 5kW SERIES

™ 5000W SERIES - TECHNICAL SPECIFICATIONSFRONT PANEL

1. Control Functions---

Rotary VOLTAGE encoder for Vout adjustment and MENU function scrolling; pushbutton to accept PREV V setting.Rotary CURRENT encoder for Iout adjustment and MENU parameter scrolling; pushbutton to accept PREV I setting, select MENU level and select parameter.

--- Vout/Iout/Power Limit (CP mode) manual adjust by separate encoders (COARSE and FINE adjustment).

--- OVP/UVL/UVP manual adjust by CURRENT encoder (COARSE and FINE adjustment).

---PROGram functions: Activates the Program/Sequencer menu. Provides Sequencer function control, Trigger function control, and loading/activation of a sequence stored in Power Supply memory.

---SYSTem functions: Front Panel LOCK/UNLOCK, Local/Remote SENSE, ILC, ENA, ENA Polarity, PS-OK Delay, SAVE/RECALL Memory Cell, PIN 1/PIN 2 (On/Off), PRELoad (On/Off), DISPlay (Brightness/Dimming).

---CONFiguration functions: Select SAFE/AUTO-Start mode, V/I Programming (FP/Voltage/Resistive), Programming Range (5V/10V, 5K/10K),Internal Resistance Control, Constant Power Control, Slew-Rate Control (Voltage/Current, Up/Down, Value).

--- PROTection functions: OVP, UVL, UVP, UVP Delay, FOLDback (CV/CC), FOLDback Delay, OCL (ON/OFF).

---COMMunication functions: Interface (RS-232/RS-485/USB/LAN/OPT), Unit Address (0-31), LAN Address (IP, MAC, LAN Reset), BAUD rate, Software LANGuague, Software REVision.

2. Display --- Vout: 4 digits + "V" symbol, Accuracy: +/- 0.05% of Vo(rated) +/-1 count

--- Iout: 4 digits + "A" symbol, Accuracy: +/- 0.2% of Io(rated) +/-1 count

--- Pout: 5 digits + "W" symbol3. Front Panel Button Indications --- Green LED (continuous) built into button: OUTput ON, PREView, FINE, PROGram, SYSTem, PROTection, CONFiguration, COMMunication.

--- Red LED (blinking - 1/2Hz rate) built into OUT button: ALARM/FAULT (FOLD, OVP, UVP, ENA, ILC, AC, OTP)..4. Front Panel Display Indications

---Voltage, Current, Power/Address, CV/CC/CP, External Voltage Pgm, External Current Pgm, LFP (Locked Front Panel) logo, AUTO Re-Start/SAFE-Start, FOLDback V/I, REMote (Digital communication), RS/USB/LAN/OPT(IEEE) communication, TRIGger active, Active Memory Cell (for Waveform Sequencer)

SYSTEM CONFIGURATIONS

1. Parallel Operation, (*18)

---

Up to four identical units in Master/Slave mode using parallel bus cable(s) for up to 20kW Output power. Parallel accessory kit availabe for 20kW system. Master and Slave units automatically detect parallel connection and set their required parameters. Master unit displays the parallel system actual Output current. System acknowledge feature available to prevent unintended parallel system changes.Scalable power systems of 10kW (eg. 10-1000) and 15kW (eg. 10-1500) also available.

2. Series Operation, (*19) --- Up to two identical units (with external diodes) with total Output voltage not to exceed +/-600V potential from Chassis ground.3. Multi-Drop Configuration

---

Up to thirty-one (31) Slave power supplies can be connected in RS-485 Multi-Drop daisy-chain from Master unit.Utilized from all Master unit digital interfaces (LAN, USB, RS-232/RS-485, or OPT (IEEE, etc.)).Uses Master (RS-485 OUT) to Slave (RS-485 IN) and Slave (RS-485 OUT) to Slave (RS-485 IN) connection(s).

4. Daisy-Chain Shutdown Connection---

Power supplies can be connected in Daisy-Chain to synchronize turn-On, turn-Off and FAULT detection/shutdown.Unit with FAULT will display fault (eg. OVP) and Alarm LED blinks RED while all other units display SO FAULT.When all faults are removed, the system recovers according to the Master unit Safe-Start/Auto-Restart setting.

REMOTE ANALOG PROGRAM AND MONITOR (ISOLATED FROM THE OUTPUT )

1. Vout Voltage Programming (VPGM) --- 0~100%, 0~5V or 0~10V, user-selectable. Accuracy and linearity: +/-0.15% of Vo(rated), Isolated (SELV) signal.2. Iout Voltage Programming (IPGM), (*15) --- 0~100%, 0~5V or 0~10V, user-selectable. Accuracy and linearity: +/-0.40% of Io(rated), Isolated (SELV) signal.3. Vout Resistor Programming --- 0~100%, 0~5kohms or 0~10kohms, user-selectable. Accuracy and linearity: +/-0.50% of Vo(rated), Isolated (SELV) signal.4. Iout Resistor Programming, (*15) --- 0~100%, 0~5kohms or 0~10kohms, user-selectable. Accuracy and linearity: +/-0.50% of Io(rated), Isolated (SELV) signal.5. Output Voltage Monitor (V_MON) --- 0~5V or 0~10V, user-selectable. Accuracy: +/-0.50% of Vo(rated), Isolated (SELV) signal.6. Output Current Monitor (I_MON), (*15) --- 0~5V or 0~10V, user-selectable. Accuracy: +/-0.50% of Io(rated), Isolated (SELV) signal.

REMOTE ANALOG SIGNALS AND CONTROLS (ISOLATED FROM THE OUTPUT )

1. Power Supply OK Monitor (PS_OK #1)

---

Power Supply Output Monitor (open-collector output), Isolated (SELV) signalOutput On (or OK): Low, Output Off ( FAULT): High, (Maximum voltage: 30V, Maximum sink current: 10mA)FAULTS include FOLD (V/I), OVP, UVP, ENA (Disable), ILC (Disable) , AC Fail, OTP , Output OFF.

Programmable Delay (OFF-to-ON): 0.000 to 10.000 seconds, 0.001s/0.100s resolution (FINE/COARSE). Default = 0.010s.

2. CV/CC Monitor (CV/CC)---

CV/CC Mode Monitor (open-collector output), Isolated (SELV) signalCC mode: On (Low), CV/CP mode, Output OFF: Off (High), (Maximum voltage: 30V, Maximum sink current: 10mA)

3. LOCAL/REMOTE Select ---Enable/Disable Remote Analog Control (electrical signal or dry-contact), Remote = Analog control, Local = Front Panel/Digital Interface Control.Remote: 0~0.6V or Short, Local: 2~30V or Open, Isolated (SELV) signal

4. LOCAL/REMOTE Monitor---

Remote Analog Pgm Control Monitor (open-collector output), SELV signalRemote: On (Low). Local: Off (High), (Maximum voltage: 30V, Maximum sink current: 10mA)

5. Daisy-IN/SO

---

Used as an Input to Shut-Off (Disable) the Power Supply in Dasiy-Chain Shut-Off application (when connected to the Dasiy-OUT pin of another Power Supply).Active after first Power Supply OFF to ON transition, Activated ONLY when a transition from High to Low is detected, Isolated (SELV) signal.Accepts Voltage (2V ~ 25V (High) = Enable, 0 ~ 0.6V (Low) = Disable) or Dry-Contact (Open = Enable, Closed (Short) = Disable) to Enable or Disable the Power Supply Output (after High to Low transition).

6. Daisy-OUT (PS_OK #2)---

Used as an Output to Shut-Off (Disable) the next Power Supply in Dasiy-Chain Shut-Off application (when connected to Dasiy-IN pin of another Power Supply).Change from OK to FAULT will shut down Daisy-Chain system of units (FAULTS: FOLD, OVP, UVP, ENA (Disable), ILC (Disable), AC Fail, Output OFF, OTP).OK: 5V (typical), FAULT: 0V (typical), (500ohm series resistance to COM), Isolated (SELV) signal

7. ENABLE/DISABLE Control (ENA_IN)---

Enables/Disables the Output (electrical signal or dry-contact)., Isolated (SELV) signalENABLE: 0~0.6V or Short, DISABLE: 2~30V or Open, Default = OFF. User-selectable polarity: NORM or REV, Default = REV

8. INTERLOCK Control (ILC)---

Enables/Disables the Output (electrical signal or dry-contact), Isolated (SELV) signalENABLE: 0~0.6V or Short. DISABLE: 2~30V or Open. Default = OFF

9. PROGrammed Signals (PROG#1, PROG#2)---

Two programmable signals (open-drain output), Isolated (SELV) signals.Output On: High, Output Off: Low, Maximum voltage: 25V, Maximum sink current: 100mA (Shunted by 27V zener diode). Default = Output On (High)

10. TRIGGER IN signal

---

Input Trigger (EXT) - provides the ability to sychronize Sequencer Arbitrary Waveforms, can be used in conjunction with Trigger Delay, Isolated (SELV) signal.Maximum low level Input voltage = 0.8V, Minimum high level Input voltage = 2.5V, Maximum high level Input voltage = 5VPositive Edge trigger: Twidth (Tw) = 10us minimum. Trise (Tr), Tfall (Tf) = 1us maximum, Minimum time delay (Td) between 2 pulses = 1msPROGram MENU setting = EXT

11. TRIGGER OUT signal

---

Output Trigger - trigger signal activated if Power Supply Output state or V/I programming value change, Isolated (SELV) signal.Maximum low level Input voltage = 0.8V, Minimum high level Input voltage = 2.5V, Maximum high level Input voltage = 5VMaximum source current = 16mA, Pulsewidth = 100us minimumPROGram Menu settings = OFF (Trigger OFF), TRIG, and FSTR (TRIG and FSTR change depending on programming mode; See User's Manual), Default = OFF

DIGITAL PROGRAMMING AND READBACK

(LAN, USB, RS-232/RS-485 and IEEE Interface)

V 10 20 30 40 60 80 100 150 300 600I 500 250 170 125 85 65 50 34 17 8.5

1. Vout Programming Accuracy, 0.05% of Vo(rated), (*16) mV 5 10 15 20 30 40 50 75 150 3002. Iout Programming Accuracy --- 0.1% of Io(actual) + 0.2% of Io(rated), (*15)

3. Vout Programming Resolution, 0.002% of Vo(rated) mV 0.2 0.4 0.6 0.8 1.2 1.6 2.0 3.0 6.0 12.0

4. Iout Programming Resolution, 0.002% of Io(rated) mA 10.0 5.0 3.4 2.5 1.7 1.3 1.0 0.68 0.34 0.17

5. Vout Readback Accuracy, 0.05% of Vo(rated) mV 5 10 15 20 30 40 50 75 150 300

6. Iout Readback Accuracy, 0.2% of Io(rated) (*15) A 1.00 0.500 0.340 1.00 0.170 0.130 0.100 0.068 0.034 0.017

7. Vout Readback Resolution, % of Vo(rated) %(mV)

0.011%(1.1)

0.006%(1.2)

0.004%(1.2)

0.003%(1.2)

0.002%(1.2)

0.002%(1.6)

0.011%(11.0)

0.007%(10.5)

0.004%(12.0)

0.002%(12.0)

8. Iout Readback Resolution, % of Io(rated) %(mA)

0.003%((15.0)

0.005%((12.5)

0.006%((10.2)

0.009%(11.25)

0.002%(1.7)

0.002%(1.3)

0.003%((1.5)

0.004%((1.36mV)

0.006%((1.02)

0.002%(0.170)

Page 13: Advanced Features Built-Inwescalkorea.com/111/tdk-lambda_catalog/GENESYS_PLUS.pdf4 ™ 5kW SERIES MENU buttons and Active menu LED's Output Control buttons and Status LED's Front Panel

13™ 5kW SERIES

ENVIRONMENTAL CONDITIONS

1. Operating Temperature---

0°C to +50°C (+32°F to +122°F), 100% load (Vo(rated) / Io(rated))Air Filter Installed: For all models (except 10V) = 0°C to +40°C (+32°F to +104°F), 100% load (Vo(rated) / Io(rated)); For 10V model = 0°C to +30°C (+32°F to +86°F), 100% load (Vo(rated) / Io(rated)), derate 5A/°C for +30°C < Ta < +40°C.

2. Storage Temperature --- -20°C to +85°C (-4°F to 185°F)3. Operating Humidity % 20~90% RH (non-condensating)4. Storage Humidity % 10~95% RH (non-condensating)5. Altitude

---

Operating (Standard/Blank front panel): Rated Load @ Ta = +50°C, up to 6560ft (2000m); Output current derating = 2% of Irated per 328ft (100m) - from 6560ft to 9840ft (2000m to 3000m) or Tambient derating = 1°C per 328 ft (100m) - from 6560ft to 9840ft (2000m to 3000m).Operating (Air Filter): For all models (except 10V) - Rated Load @ Ta = +40°C up to 6,560ft (2000m); Output current derating = 2% of Irated per 328ft (100m) - from 6560ft to 9840ft (2000m to 3000m) or Tambient derating = 2°C per 328 ft (100m) - from 6560ft to 9840ft (2000m to 3000m). For 10V model - Rated Load @ Ta = +30°C up to 6,560ft (2000m); Output current derating = 2% of Irated per 328ft (100m) - from 6560ft to 9840ft (2000m to 3000m) or Tambient derating = 1°C per 328 ft (100m) - from 6560ft to 9840ft (2000m to 3000m).Non-Operating: 40,000ft (12000m)

6. Vibration --- MIL-STD-810G, Method 514.6, Procedure I, Test Condition Annex C - 2.1.3.1, unit is fixed to vibrating surface7. Shock --- Less than 20G, half-sine, 11ms, each axis, unit is unpackaged8. Audible Noise (typical) --- 44dB (no-load), 57dB (rated load); measured 1m from front panel display, Ta = +30°C

MECHANICAL

1. Cooling --- Forced air cooling by internal fans (variable speed) with air flow from front to rear (no side ventilation). Zero-stackableChassis slides or suitable rear support required

2. Weight lbs Less than 16.5 lbs (7.5kg)3. Dimensions (WxHxD) in Width: 16.65 inches (423mm), Height: 1.72 inches (43.6mm), Depth: 17.38 inches (441.5mm); refer to Outline Drawing4. AC Input Connector --- Three-phase 208VAC/480VAC models: Mate = Phoenix Contact Power Combicon PC 5/4-STCL1-7, 62 series with custom strain relief; refer to Outline Drawing

5. DC Output Connectors --- Vout < 40V models: busbar, L = 2.55 inches (64.7mm), two holes (Ø = 10.5mm)40V < Vout < 100V models: busbar, L = 1.58 inches (40.2mm), one hole (Ø = 8.5mm)Vout > 150V models: Phoenix Contact IPC 5/4-STF-7, 62

6. Interface Connectors (LAN, USB, etc.) --- J1 (Remote Analog): DB26-HD female, J2 (USB): Type-B socket, J3 (485 Multi-Drop OUT): 8 pin shielded RJ-45, J4 (232/485 IN): 8 pin shielded RJ-45, J5 (LAN): RJ-45 w/ LAN status indicators, J6 (Parallel: Slave-IN): 8 pin HD shielded jack, J7 (Parallel: Master-OUT): 8 pni HD shielded jack, J8 (Local/Remote Sense): 3 pin spring-cage type, J9 (IEEE): shielded IEEE; see User's Manual for details

SAFETY1. Applicable Standards --- UL60950-1, CSA22.2 No. 60950-1, IEC60950-1, EN60950-12. Interface Classification

---

Vout ≤50V models: Output (+V, -V), J1 (Remote Analog), J2 (USB), J3 (485 Multi-Drop OUT), J4 (232/485 IN), J5 (LAN), J6 (Parallel: Slave-IN),J7 (Parallel: Master/Slave-OUT), J8 (Local/Remote Sense), J9 (IEEE/other option) are SELV.60 ≤ Vout ≤ 600V models: Output (+V, -V), J8 (Local/Remote Sense) are Hazardous; J1 (Remote Analog), J2 (USB), J3 (485 Multi-Drop OUT),J4 (232/485 IN), J5 (LAN), J6 (Parallel: Slave-IN), J7 (Parallel: Master/Slave-OUT), J9 (IEEE/Other option) are SELV.

3. Withstand Voltage (*20)

VDC

10V ≤ Vout ≤ 100V models: Input - Output: 4242VDC for 60s, Input - SELV: 4242VDC for 60s, SELV-Ground: 707VDC for 60s,Output - SELV: 707VDC for 60s, Output - Ground: 707VDC for 60s, Input - Ground: 2835VDC for 60s.150V ≤ Vout ≤ 600V models: Input - Output: 3656VDC for 60s, Input - SELV: 4242VDC for 60s, SELV-Ground: 707VDC for 60s,Output - SELV: 1132VDC for 60s, Output - Ground: 707VDC for 60s, Input - Ground: 2835VDC for 60s.

4. Insulation Resistance Mohms Greater than 100Mohms at Ta = +25°C, 70% RH

EMC1. Applicable Standards --- IEC/EN61204-3, Industrial environment

2.1. Electrostatic Discharge (ESD) --- EN61000-4-2: Air Discharge: 8kV, Contact DIscharge: 4kV2.2. Fast Transient Burst --- EN61000-4-4: Output/Input/Signal - 2kV2.3. Lightning Surge Immunity --- EN61000-4-5: 1kV Line-to-Line, 2kV Line-to-Ground2.4. Conducted Immunity --- EN61000-4-6: 10V2.5. Radiated Immunity --- EN61000-4-3: 10V/m2.6. Magnetic Field Imnunity --- EN61000-4-8: 30A/m2.7. Voltage Dips and Short Interruptions --- IEC/EN61204-3 Table 9, Clause 10-3 (EN61000-4-11)2.8. Voltage Fluctutations and Flicker --- EN61000-3-32.9 Conducted Emmisions --- IEC/EN61204-3 Industrial environment, Annex H Table H.1; FCC Part 15-A, VCCI-A2.10 Radiated Emissions --- IEC/EN61204-3 Industrial environment, Annex H Table H.3 and H4; FCC Part 15-A, VCCI-A

INTERFACES (Digital, Analog, Parallel Operation)1. IEEE (488.2) --- OPTIONAL, 24 position shielded connector (IEEE), J92. LAN (LXI 1.5) --- Standard (LXI 1.5, Class C compliant), RJ-45 type connector with LAN status indicators, J53. USB (2.0) --- Standard (2.0 compliant), with USB Type-B socket, J24. RS-232/RS-485 IN --- Standard, 8 pin female shielded modular jack, J45. RS-485 Multi-Drop OUT --- Standard, 8 pin female shielded modular jack, J36. Remote Isolated Analog Program/Monitor/Control --- Standard, DB26-HD plastic female connector, J17. Parallel-OUT (Master/Slave) --- Standard, 8 pin HD shielded jack, connection to Master/Slave unit (for parallel operation), J78. Parallel-IN (Slave) --- Standard, 8 pin HD shielded jack, connection to Slave unit (for parallel operation), J6

NOTES:

*1: Minimum voltage is guaranteed to maximum 0.1% of rated Output voltage.*2: Minimum current is guaranteed to maximum 0.2% of rated Output current.*3: N/A*4: For cases where conformance to various safety standards (UL, IEC, etc…) is required, to be described as 190-240Vac (50/60Hz) for 3-Phase AC Input.*5: 3-Phase 200VAC models: At 200VAC input voltage, 3-Phase 480VAC: At 380VAC input voltage. With rated output power.*6: Not including EMI filter inrush current (less than 0.2ms).*7: 3-Phase 200VAC models: 170~265VAC, constant load. 3-Phase 480VAC models: 342~528VAC, constant load.*8: From No-Load to Full-Load, constant AC input voltage. Measured at the sensing point using Remote Sense function.*9: For 10V~150V models: Measured with JEITA RC-9131A (1:1) probe. For 300~600V model: Measured with 100:1 probe.*10: The maximum voltage on the power supply terminals must not exceed the rated Output voltage.*11: From 10% to 90% or 90% to 10% of rated Output Voltage, with rated, resistive load.*12: From 90% to 10% of rated Output Voltage.*13: For load voltage change, equal to the unit voltage rating, constant AC input voltage.*14: For 10V model the ripple is measured at 2V and rated Output current. For other models, the ripple is measured at 10% of rated Output voltage. Bandwidth = 5Hz~1MHz. *15: The Constant-Current (CC) programming, readback and monitoring accuracy do not include the "Warm-Up" and "Load Regulation" thermal drift.*16: Measured at the sensing point.*17: N/A*18 Contact Technical Suport for questions about "Parallel" applications and for connecting more than four identical units in parallel.*19 Contact Technical Support for questions about "Series" applications and for connecting more than two identical units in series.*20 Contact Technical Support for questions about Power Supply and System "Withstand Voltage" requirements.

™ 5000W SERIES - TECHNICAL SPECIFICATIONS

Page 14: Advanced Features Built-Inwescalkorea.com/111/tdk-lambda_catalog/GENESYS_PLUS.pdf4 ™ 5kW SERIES MENU buttons and Active menu LED's Output Control buttons and Status LED's Front Panel

14 ™ 5kW SERIES

Outline Drawing ™ 5kW (Standard Model)

Dim

ension / Model

10V-40V60V-100V

L164.7m

mL2

40.2mm

OU

TPUTS

CO

VER

Page 15: Advanced Features Built-Inwescalkorea.com/111/tdk-lambda_catalog/GENESYS_PLUS.pdf4 ™ 5kW SERIES MENU buttons and Active menu LED's Output Control buttons and Status LED's Front Panel

15™ 5kW SERIES

Outline Drawing ™ 5kW (Blank Front Panel Model)

Dim

ension / Model

10V-40V60V-100V

L164.7m

mL2

40.2mm

OU

TPUT

CO

VER

Page 16: Advanced Features Built-Inwescalkorea.com/111/tdk-lambda_catalog/GENESYS_PLUS.pdf4 ™ 5kW SERIES MENU buttons and Active menu LED's Output Control buttons and Status LED's Front Panel

TDK-Lambda CorporationInternational Sales Division,3-9-1, Shibaura, Minato-ku,Tokyo 108-0023, JapanTel: +81-3-6852-7125 Fax: +81-3-6852-7140Web: www.tdk-lambda.com

Wuxi TDK-Lambda Electronics Co. Ltd, Shanghai Office5th Floor Kehui Tower, 1188 Qinzhou Road (North)Xuhui District Shanghai, 200233, P. R. CHINA Tel: +86-21-6485-0777 Fax: +86-21-6485-0666Web: www.cn.tdk-lambda.com

Beijing Branch of Wuxi TDK-Lambda Electronics Co. Ltd.Room 12B11-12B12, Unit 7 Dacheng Square, No. 28Xuanwumenxi Street, Xuanwu District, Beijing, 10053, P. R. CHINA Tel: +86-21-6310-4872 Fax: +86-10-6310-4874Web: www.cn.tdk-lambda.com

Shenzen Branch of Wuxi TDK-Lambda Electronics Co. Ltd.69/F, Ping An Finance Center, 5033 Yitian RoadFutian District, Shenzen, P. R. CHINA Tel: +86-755-83588261 Fax: +86-755-83588260Web: www.cn.tdk-lambda.com

TDK-Lambda Corporation Korea Branch(Seocho-Dong, 8F. Songnam Bldg.) 273, Gangnam-Daero,Seocho-Gu, Seoul 137-862, Republic of Korea 137-862Tel: 82-2-3473-7051, Fax: 82-2-3472-9137Web: www.tdk-lambda.co.kr

TDK-Lambda Malaysia Sdn. Bhd.c/o TDK (Malaysia) Sdn. Bhd.,Lot 709, Nilai Industrial Estate 71800 NilaiNegeri Sembilan, MalaysiaTel: +60-6-799-1130 Fax: +60-6-799-3277Web: www.my.tdk-lambda.com

TDK-Lambda Singapore Pte. Ltd.1008 Toa Payoh North # 06-01/08, #07-01/03Singapore 318996Tel: +65-6251-7211 Fax: +65-6250-9171Web: www.sg.tdk-lambda.com

TDK-Lambda Singapore Pte. Ltd. (India Branch)No.989, 1st Cross, 2nd Floor , 13th Main, HAL 2nd Stage, Bangalore, Karnataka , India – 560 008Tel : +91-80-43550 500, Fax :+91-80-43550 501E-Mail: [email protected], Web: www.in.tdk-lambda.com

TDK-Lambda Ltd. IsraelKibbutz Givat Hashlosha Tel-Aviv 48800, IsraelTel: +972-3-902-4333 Fax: +972-3-902-4777E-Mail: [email protected]: www.tdk-lambda.co.il

TDK-Lambda Americas Inc.405 Essex Rd. Neptune, NJ 07753, USATel: +1-732-922-9300 Fax: +1-732-922-1441E-Mail: [email protected]: www.us.tdk-lambda.com/hp

ACA TMetrix3835 Laird Road, Mississauga, Ontario, L5L 5Y4Tel: +1-800-665-7301 Fax: +1-905-890-1959E-Mail: [email protected]: tmetrix.com

AcMax de Mexico39 Poniente. No. 3515 Piso 5 Col. Las Animas Puebla, Pue. C.P. 72400Tel: 01-800-211-0060 / (222) 891-8484 Fax: 222-264-1445E-Mail: [email protected], Web: www.acmax.mx

Suplitec - Suprimentos Tecnicos LtdaRua Sena Madureira 46531340-000 Belo Hte - MG - Brazil Tel: +55-31-3498 1177E-Mail: [email protected], Web: www.suplitec.com.br

TDK-Lambda UK Ltd.Kingsley Avenue Ilfracombe, Devon EX 34 8ES, United KingdomTel: +44-1271-856666 Fax: +44-1271-864894E-Mail: [email protected]: www.uk.tdk-lambda.com

TDK-Lambda France SAS3 Avenue du Canada, Parc Technopolis - Batiment Sigma91940 Les Ulis - France CS 41077Tel: +33 1 60 12 71 65 Fax: +33 1 60 12 71 66 E-Mail: [email protected], Web: www.fr.tdk-lambda.com

TDK-Lambda Germany GmbHKarl-Bold-Strasse 40D-77855 Achern, GermanyTel: +49-7841-666-0 Fax: +49-7841-500-0E-Mail: [email protected] Web: www.de.tdk-lambda.com

TDK-Lambda ItalyTDK-Lambda France Sas Succursale ItalianaVia dei Lavoratori 128/130IT 20092 Cinisello Balsamo, Milano, ItalyTel: +39-02-6129-3863 Fax: +39-02-6129-0900E-Mail: [email protected]: www.it.tdk-lambda.com

DK-Lambda Germany GmbHKarl-Bold-Strasse 40D-77855 Achern, GermanyTel: +49-7841-666-0 Fax: +49-7841-500-0E-Mail: [email protected]: www.de.tdk-lambda.com

USA

CANADA

MEXICO

BRAZIL

UK IRELAND

FRANCE NETHERLANDS SPAIN

GERMANY AUSTRIA SWITZERLAND

ITALY

JAPAN

CHINA

KOREA

MALAYSIA

SINGAPORE PHILIPPINES THAILAND

RUSSIAISRAEL

INDIA

TDK Logo is a trademark or registered trademark of TDK Corporation© Copyright 2018 TDK-Lambda Americas Inc.

SCANDINAVIA BALTICS

P/N

: 93-

538-

101

Rev

A-U

SATDK-Lambda Americas Inc.

Programmable & High Voltage405 Essex Road, Neptune, NJ 07753 USATel: +1.732.922.9300; Fax: +1.732.922.1441www.us.tdk-lambda.com/hp