adoption of silicon rubber insulator < experience of getco...

22
Adoption of Silicon Rubber Insulator < Experience of GETCO > 25 th Sept’13

Upload: others

Post on 24-Dec-2019

3 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Adoption of Silicon Rubber Insulator < Experience of GETCO >ieema.org/wp-content/uploads/2015/05/LFE_MR_S_K_NEGI.pdf · from 25mm./kV to 31 mm./kV (for 220 kV SRI –6125 mm

Adoption of Silicon Rubber Insulator < Experience of GETCO >

25th Sept’13

Page 2: Adoption of Silicon Rubber Insulator < Experience of GETCO >ieema.org/wp-content/uploads/2015/05/LFE_MR_S_K_NEGI.pdf · from 25mm./kV to 31 mm./kV (for 220 kV SRI –6125 mm

Cost Comparison

2008-09

2009-10

2010-2011

2011-2012

2012-2013

2013-2014

220 KV, 90KN

String of 14 nos. of Antifog Disc Insulators

8303 7027 7378 8988 8263 9123

SRI 9186 6107 4271 5188 5250 5468

SRI cost vs. AF Disc Insulator string

+10 % -13 % -42 % -42 % -36 % -40 %

220 KV, 120KN

String of 15 nos. of Antifog Disc Insulators

11162 9712 9302 10681 10456 10866

SRI 9598 7142 4610 5634 5488 5660

SRI cost vs. AF Disc Insulator string

-14 % -26 % -50 % -47 % -47 % -48 %

(Figures in Rs.)

Page 3: Adoption of Silicon Rubber Insulator < Experience of GETCO >ieema.org/wp-content/uploads/2015/05/LFE_MR_S_K_NEGI.pdf · from 25mm./kV to 31 mm./kV (for 220 kV SRI –6125 mm

Superiority of SRI over Porcelain Insulator

Sr No.

PARAMETERS SRI PORCELAIN A/F DISC INSULATORS

1 Hydrophobicity More Hydrophobic Less Hydrophobic

2 Recovery of Hydrophobicity

High Nil

3 Performance under industrial and coastal pollution

Better Low

4 Resistance to vandalism High Low

5 Weight Very low High

6 Handling of string Easy Difficult

7 Maintenance Very Low High

8 More Creepage distance with same length

Achievable Not achievable

9 Cost Low High

10 Visual Aesthetic look Conventional look

Page 4: Adoption of Silicon Rubber Insulator < Experience of GETCO >ieema.org/wp-content/uploads/2015/05/LFE_MR_S_K_NEGI.pdf · from 25mm./kV to 31 mm./kV (for 220 kV SRI –6125 mm

LENGTH SELECTION220 kV -120 KN Tension String

INSULATOR LENGTH CREEPAGE Appx. WEIGHT

ANTIFOG DISC INSULATOR STRING

2175 mm. 6450 mm. 26.3 mm/kV

127.5 kgs.

SRI 2175 mm. 7595 mm. 31 mm/kV

15 kgs.

Page 5: Adoption of Silicon Rubber Insulator < Experience of GETCO >ieema.org/wp-content/uploads/2015/05/LFE_MR_S_K_NEGI.pdf · from 25mm./kV to 31 mm./kV (for 220 kV SRI –6125 mm

LENGTH SELECTION220 kV - 90KN Suspension String

INSULATOR LENGTH CREEPAGE Appx. WEIGHT

ANTIFOG DISC INSULATOR STRING

2030 mm. 6020 mm. 24.6 mm/Kv

98 kgs.

SRI 2030 mm. 7595 mm. 31 mm/kV

12 kgs.

Page 6: Adoption of Silicon Rubber Insulator < Experience of GETCO >ieema.org/wp-content/uploads/2015/05/LFE_MR_S_K_NEGI.pdf · from 25mm./kV to 31 mm./kV (for 220 kV SRI –6125 mm

DESIGN CHANGE EVOLUTION

DESIGN CHANGE IMPETUS

Increase of Creepage Distance from 25mm./kV to 31 mm./kV (for 220 kV SRI – 6125 mm. to 7595 mm.)

To improve performance under heavy Industrial and coastal pollution area

Adoption of Injection moulding Avoid multiple interface design

Adoption of plain design Avoid accumulation of dust and pollution in under rib design

End termination crimping with Acoustic method and overlap design at end fitting interface

To predict damage free end fitting crimping and to ensure hermetically sealed end fitting

Page 7: Adoption of Silicon Rubber Insulator < Experience of GETCO >ieema.org/wp-content/uploads/2015/05/LFE_MR_S_K_NEGI.pdf · from 25mm./kV to 31 mm./kV (for 220 kV SRI –6125 mm

Type Test Evolution

ADDITION OF TYPE TEST REFERENCE IMPORTANCE

Multi stress test for 5000 Hrs. IEC 61109 1992-03

Accelerated ageing Test including salt fog, humidity, solar radiation simulation to ensure performance under extreme conditions

Power Arc Test IEC 61467-1997 Simulation of flash over trip out at 10 kA x15 cycles to ensure end fitting interface performance

Grading Device Test GETCO Procedure Simulation of vibrations to check displacement of corona control ring from placement

ELECTRIC FIELD MODELLING (FEM analysis)

*** To derive optimum placement of Corona control ring to reduce stress at Interface

Page 8: Adoption of Silicon Rubber Insulator < Experience of GETCO >ieema.org/wp-content/uploads/2015/05/LFE_MR_S_K_NEGI.pdf · from 25mm./kV to 31 mm./kV (for 220 kV SRI –6125 mm

Analysis of tripping data Navsari Circle

1 Year Before

Replacement

1 Year After

Remark

220 kV Vav – Mota 2 T/T – 1S/F - 1

08.2009 to 10.2009

T/T – 2S/F - 0

TT

SF

220 kV Vav – Ukai 1 T/T – 4S/F – 4

08.2009 to 10.2009

T/T – 0S/F – 0

TT

SF

220 kV Mota – Ukai 2 T/T – 9S/F – 3

08.2009 to 10.2009

T/T – 3S/F – 0 TT

SF

220 kV Ukai (H) – Ukai (Th)-2

T/T – 0S/F – 3

03.2012 to 04.2012

T/T – 0S/F – 0

---- TT

SF

Page 9: Adoption of Silicon Rubber Insulator < Experience of GETCO >ieema.org/wp-content/uploads/2015/05/LFE_MR_S_K_NEGI.pdf · from 25mm./kV to 31 mm./kV (for 220 kV SRI –6125 mm

Analysis of tripping data Bharuch circle

Line Before SRI Replaced After Remark

220 kV Haldarwa -Jambuva

TT - 83.2012

TT - 8 -- TT

SF - 2 SF - 2 -- SF

220 kV Haldarwa -Zagadiya

TT - 23.2012

TT- 1 TT

SF - 1 SF - 0 SF

220 kV Haldarwa -Dahej

TT - 1 04.2010 to 07.2010

TT - 1 -- TT

SF - 0 SF - 1 SF

220 kV Haldarwa -IPCL 1

TT - 2 04.2010 to 07.2010

TT - 3 TT

SF - 3 SF - 2 SF

220 kV Haldarwa -IPCL 2

TT - 7 04.2010 to 07.2010

TT - 4 TT

SF - 1 SF - 4 SF

220 kV Achchaliya - Ukai (H) 1

TT - 7 07.2008 to 11.2009

TT - 0 TT

SF - 19 SF - 1 SF

220 kV Achchaliya - Ukai (H) 2

TT - 3 04.2009 to 06.2012

TT - 0 TT

SF - 1 SF - 0 SF

220 kV Achchaliya - Ukai (Th) 1

TT - 3 12.2009 to 10.2012

TT - 0 TT

SF - 0 SF - 0 SF

Page 10: Adoption of Silicon Rubber Insulator < Experience of GETCO >ieema.org/wp-content/uploads/2015/05/LFE_MR_S_K_NEGI.pdf · from 25mm./kV to 31 mm./kV (for 220 kV SRI –6125 mm

Analysis of tripping data Bharuch circle

Line Before SRI Replaced After Remark

220 kV Achchaliya - Ukai (Th) 2

TT - 312.2009 to 10.2012

TT – 2 TT

SF - 0 SF – 0 -- SF

132 kV Achchaliya -GNFC 1

TT - 607.2011 to 10.2012

TT – 0 TT

SF - 0 SF – 0 -- SF

132 kV Achchaliya -GNFC 2

TT - 307.2006 to 04.2007

TT – 0 TT

SF - 0 SF – 0 -- SF

132 kV Achchaliya Ankleshwar 1

TT - 004.2007 to 04.2010

TT – 1 TT

SF - 2 SF – 0 SF

132 kV Achchaliya Ankleshwar 2

TT - 204.2007 to 04.2010

TT – 1 TT

SF - 0 SF – 0 -- SF

220 kV Kim- ZagadiyaTT - 4

01.2011 to 02.2011TT – 0 TT

SF - 1 SF – 0 SF

220 kV Kim - KosambaTT - 3

01.2011 to 02.2011TT – 6 TT

SF - 4 SF – 0 SF

220 kV Kim - GSEGTT – 2

01.2011 to 02.2011TT – 2 -- TT

SF - 2 SF – 0 SF

220 kV Kim - MoraTT - 5

01.2011 to 02.2011TT – 1 TT

SF - 3 SF – 0 SF

Page 11: Adoption of Silicon Rubber Insulator < Experience of GETCO >ieema.org/wp-content/uploads/2015/05/LFE_MR_S_K_NEGI.pdf · from 25mm./kV to 31 mm./kV (for 220 kV SRI –6125 mm

Analysis of Tripping Data Anjar circle

Line Before SRI Replaced After Remark

220 kV Anjar-Kukma

TT - 13 10/ 2012 to 11/ 2012

TT – 1 TT

SF - 1 SF – 0 SF

220 kV Tappar –Nanikhakhar 2

TT - 10 08/ 2009 to 09/ 2009

TT – 4 TT

SF - 5 SF – 1 SF

220 kV Nakhatrana-Nanikhakhar-1

TT - 0 07/ 2007 to 09/ 2007

TT – 0 -- TT

SF - 8 SF – 0 SF

220 kV Nakhatrana-Nanikhakhar-2

TT - 0

07/ 2010

TT – 0 -- TT

SF - 8 SF – 0 SF

220 kV Shivlakha-Morbi2

TT - 0 07/ 2007 to 07/ 2010

TT – 0 -- TT

SF - 3 SF – 0 SF

Page 12: Adoption of Silicon Rubber Insulator < Experience of GETCO >ieema.org/wp-content/uploads/2015/05/LFE_MR_S_K_NEGI.pdf · from 25mm./kV to 31 mm./kV (for 220 kV SRI –6125 mm

FLASH OVER 66 kV SRI

Page 13: Adoption of Silicon Rubber Insulator < Experience of GETCO >ieema.org/wp-content/uploads/2015/05/LFE_MR_S_K_NEGI.pdf · from 25mm./kV to 31 mm./kV (for 220 kV SRI –6125 mm

FLASH OVER 66 kV SRI

Page 14: Adoption of Silicon Rubber Insulator < Experience of GETCO >ieema.org/wp-content/uploads/2015/05/LFE_MR_S_K_NEGI.pdf · from 25mm./kV to 31 mm./kV (for 220 kV SRI –6125 mm

DAMAGED 66 KV SRI

Page 15: Adoption of Silicon Rubber Insulator < Experience of GETCO >ieema.org/wp-content/uploads/2015/05/LFE_MR_S_K_NEGI.pdf · from 25mm./kV to 31 mm./kV (for 220 kV SRI –6125 mm

FLASH OVER 66 KV SRI

Page 16: Adoption of Silicon Rubber Insulator < Experience of GETCO >ieema.org/wp-content/uploads/2015/05/LFE_MR_S_K_NEGI.pdf · from 25mm./kV to 31 mm./kV (for 220 kV SRI –6125 mm

16Thank you !!!

Page 17: Adoption of Silicon Rubber Insulator < Experience of GETCO >ieema.org/wp-content/uploads/2015/05/LFE_MR_S_K_NEGI.pdf · from 25mm./kV to 31 mm./kV (for 220 kV SRI –6125 mm

PROCUREMENT OF ANTIFOG DISC INSULATOR

YEAR 90 KN 120 KN 160 KN

07-08 77500 21500 0

08-09 39929 17582 6680

09-10 88616 32016 1008

10-11 116886 65854 6630

11-12 23034 51007 1380

12-13 19800 11715 380

TOTAL 365765 199674 16078

Page 18: Adoption of Silicon Rubber Insulator < Experience of GETCO >ieema.org/wp-content/uploads/2015/05/LFE_MR_S_K_NEGI.pdf · from 25mm./kV to 31 mm./kV (for 220 kV SRI –6125 mm

PROCUREMENT OF ANTIFOG DISC INSULATOR

VOLTAGE CLASS (KV) 132 132 220 220 400 400

90 KN 120 KN 90KN 120 KN 120 KN 160 KN

07-08 3700 2500 5700 3150 0 0

08-09 0 0 0 0 0 0

09-10 4126 3346 20917 7427 0 0

10-11 1300 840 4355 3082 5557 6158

11-12 3000 3260 14677 9500 0 0

12-13 2100 800 14450 8772 6929 3638

TOTAL 14226 10746 60099 31931 12486 9796

Page 19: Adoption of Silicon Rubber Insulator < Experience of GETCO >ieema.org/wp-content/uploads/2015/05/LFE_MR_S_K_NEGI.pdf · from 25mm./kV to 31 mm./kV (for 220 kV SRI –6125 mm

END FITTING OVERLAP – PLAIN DESIGN

Page 20: Adoption of Silicon Rubber Insulator < Experience of GETCO >ieema.org/wp-content/uploads/2015/05/LFE_MR_S_K_NEGI.pdf · from 25mm./kV to 31 mm./kV (for 220 kV SRI –6125 mm

COST COMPARISION OF 220 KV, 90 KN SUSPENSION SRI v/s A/F INSULATOR STRING

Rs.

Page 21: Adoption of Silicon Rubber Insulator < Experience of GETCO >ieema.org/wp-content/uploads/2015/05/LFE_MR_S_K_NEGI.pdf · from 25mm./kV to 31 mm./kV (for 220 kV SRI –6125 mm

COST COMPARISION OF 220 KV, 120 KN TENSION SRI V/S A/F INSULATOR STRING

Rs.

Page 22: Adoption of Silicon Rubber Insulator < Experience of GETCO >ieema.org/wp-content/uploads/2015/05/LFE_MR_S_K_NEGI.pdf · from 25mm./kV to 31 mm./kV (for 220 kV SRI –6125 mm

PROCUREMENT OF ANTIFOG DISC INSULATOR STRING

VOLTAGE CLASS (KV) 132 132 220 220 400 400

90 KN 120 KN 90KN 120 KN 120 KN 160 KN

07-08 0 0 684 420 36 0

08-09 0 0 804 684 0 38

09-10 0 0 6 24 0 0

10-11 0 0 0 0 480 276

11-12 0 0 72 60 0 0

12-13 0 0 0 0 0 0

TOTAL 0 0 1566 1188 516 315